Download Attachment

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Voltage optimisation wikipedia , lookup

Ground (electricity) wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Mains electricity wikipedia , lookup

Electrical substation wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Portable appliance testing wikipedia , lookup

Transcript
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
16878 – Gas Insulated Switchgear Equipment
Table of Contents
16878.1 General ....................................................................................................................................... 2
16878.1.1 Scope of Supply ................................................................................................................... 2
16878.1.1.1 Contractor’s Services. .................................................................................................. 4
16878.1.2 Items Furnished by Others and Interfaces........................................................................... 4
16878.1.3 Performance and Design Requirements .............................................................................. 5
16878.1.4 Codes and Standards .......................................................................................................... 5
16878.1.5 Technical Attachments......................................................................................................... 7
16878.1.6 Supplemental Specifications ................................................................................................ 8
D100.6 Building Code and Site Conditions ...................................................................................... 8
D200 Design Ambients ..................................................................................................................... 8
E100 Wiring Methods, Cable, and Raceway .................................................................................... 8
E520 Terminal Blocks and Fuse Holders ....................................................................................... 13
16878.1.7 GIS Equipment Ratings and Service Conditions ............................................................... 17
16878.1.8 Specific Equipment Requirements ..................................................................................... 19
16878.1.9 Circuit Breakers ................................................................................................................. 20
16878.1.10 Disconnect and Grounding Switches ............................................................................... 21
16878.1.11 Gas System ..................................................................................................................... 22
16878.1.12 Current Transformers ....................................................................................................... 24
16878.1.13 Inductive Voltage Transformers ....................................................................................... 24
16878.1.14 Metal-Enclosed Surge Arresters ...................................................................................... 25
16878.1.15 SF6 Gas-to-Air Bushings .................................................................................................. 25
16878.1.16 GIS to Cable Connections ............................................................................................... 25
16878.1.17 Local Control Cabinets..................................................................................................... 25
16878.1.18 Audible Noise ................................................................................................................... 27
16878.1.19 Ladders, Platforms, Stairs, and Walkways ...................................................................... 27
16878.1.20 Special Tool Requirements .............................................................................................. 28
16878.1.21 Factory Testing ................................................................................................................ 28
16878.1.22 Studies ............................................................................................................................. 28
16878.1.23 Final Exhibits .................................................................................................................... 29
16878.1.24 Training ............................................................................................................................ 29
16878.1.24.1 GIS Application Theory - Overall Introduction .......................................................... 29
16878.1.24.2 Equipment Principles of Operation ........................................................................... 29
16878.1.24.3 Assembly .................................................................................................................. 30
16878.1.24.4 Testing ...................................................................................................................... 30
16878.1.24.5 SF6 Gas .................................................................................................................... 30
16878.1.25 Videos and Photographs.................................................................................................. 31
16878.1.26 Tests ................................................................................................................................ 31
16878.1.27 Gas Leak Detector ........................................................................................................... 33
16878.1.28 Gas Handling Equipment ................................................................................................. 33
16878.1.29 Shipment .......................................................................................................................... 34
16878.1.30 Packaging ........................................................................................................................ 34
16878.1.31 Spare Parts ...................................................................................................................... 35
16878.2 Erection, Site Testing, and Commissioning Specifications ............................................... 35
16878.2.1 General .............................................................................................................................. 35
16878.2.2 Equipment Erection ............................................................................................................ 36
16878.2.3 Miscellaneous Material ...................................................................................................... 36
16878.2.4 Equipment Protection ......................................................................................................... 36
16878.2.5 Cleaning ............................................................................................................................. 36
16878.2.6 Maintenance Tools ............................................................................................................. 36
16878.2.7 Contractor’s Inspection and Supervision ........................................................................... 37
16878.2.8 Testing ............................................................................................................................... 37
16878.2.9 Commissioning .................................................................................................................. 41
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 1 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
16878.1 General
16878.1.1 Scope of Supply
The Contractor shall design, manufacture, test, ship, deliver, offload, assemble, gas fill, field test, assist
SMUD during commissioning, and guarantee all equipment, material, and services for a complete GIS
facility as shown on the drawings included in Section 16878.1.5.
The GIS shall consist of circuit breakers, disconnect switches, maintenance grounding switches, high
speed grounding switches, voltage transformers (VTs), current transformers (CTs), surge arresters,
buses, local control cabinets (LCCs), cable sealing ends (CSE), elbows, expansion bellows, controls,
low voltage cables for control, protection and monitoring of the GIS equipment systems, gas density
monitors, platforms, surge arresters, special tools (including leak detection and gas handling
equipment), and SF6 gas for initial filling.
The Contractor shall provide the following:
The complete GIS equipment with associated circuit breakers, disconnect and
grounding switches, CTs, and VTs.
All metal-enclosed bus for interconnecting various switchgear assemblies, including
flexible joints to ensure service continuity during thermal cycling and vibration.
All necessary fixed permanent supports, platforms, stairways, and walkways, including
fasteners to foundation. This includes all required steel supports for the gas insulated
bus (GIB) up to the defined termination point. Final design of platforms and walkways
shall be acceptable to SMUD.
All auxiliary equipment for emergency control and local supervision, including
interlocks; operating mechanisms; and control, monitoring and protective devices,
installed in suitable cabinets.
All LCCs with respective mimic buses, internal wiring, and terminations.
All wiring of devices and terminations internal to the GIS and all shielded control cables
(and associated raceways), above foundation, between the GIS equipment and the GIS
LCCs. Wiring between the GIS equipment terminals and the LCC shall be with
dedicated factory prefabricated cables with modular plugs and receptacles (only for the
device end, terminate the LCC end with lugs/terminal blocks). Raceways and conduits
shall be installed so as not to present a safety hazard or impediment to personnel
servicing the equipment.
Ground buses and grounding connection pads for connection to the station ground grid.
The grounding design shall meet IEEE/IEC requirements.
Gas density monitors (with alarm contacts), pressure relief devices, and gas filling
connections.
New gaskets, sealant, and desiccant for permanent sealing of all field assembled joints
and all access covers removed during assembly. No gaskets are to be reused for any
permanent seal broken or disturbed in the field. If pressure relief devices are rupture
disks or other self-destructive devices, then at least six spare discs and associated
gaskets are to be provided. Rupture disks and gaskets are also to be included as part
of normal replacement parts stock.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 2 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
Initial filling (plus 5 percent as spare) of SF 6 gas and any fluids, greases, etc., as
required.
Any other equipment that is not specifically noted herein but that is necessary for
trouble-free operation, installation, and maintenance of the GIS.
GIS Contractor to provide all, personal, equipment, facilities, and competent
engineering/supervisory staff required to for assembly, installation and training SMUD's
personnel during the installation of the GIS at site.
All high voltage and low voltage test equipment, materials, and testing personnel
required, including transportation to and from the jobsite, to fully test the GIS and
accessories at site to certify the equipment ready for energization done by contactor.
Any special tools, lifting devices, cover plates, and gas manifolds necessary for
erection. All such materials, required for maintenance purposes, will be retained by
SMUD to be turned over to SMUD.
External surface preparation and coating. The Contractor shall include detailed coating
information in the proposal, and a minimum of 4 liters of touchup coating shall also be
provided after the Contractor has completed the work and left at the site.
Anchor bolts and/or other embedded steel/materials, if part of foundation pouring,
required by the GIS Contractor for providing a level mounting surface for the GIS
equipment and for mitigating ground potential rises around the GIS.
The Contractor shall include in the proposal documents any costs associated with
providing recommendations for grounding the GIS to mitigate step and touch potentials
during normal operation and fault interruption conditions.
All provisions necessary to mitigate very fast transients (VFTs) in the GIS during
switching operations.
Equipment identification nameplates for each main GIS component and operating
device must be delivered and installed with the equipment.
Equipment rating nameplates for each main GIS component and operating device must
be delivered and installed with the equipment.
Complete design documentation for GIS equipment including but not limited to physical
drawings, schematics and wiring diagrams.
Training for SMUD’s operation and maintenance personnel.
An insulation coordination study shall be performed to verify the location and number of
air-insulated switchgear (AIS) surge arresters for protection of the GIS equipment,
interconnected underground cable circuit insulation systems, and other equipment.
The Contractor shall include in the proposal a listing of the information needed to
perform the insulation coordination study, the breakout of the cost of the study, and the
estimated time to perform the study. The Contractor shall also include in the proposal
(should the study results indicate GIS metal-enclosed surge arresters are required at
the underground cable circuit terminations) the physical ramifications of adding GIS
metal- enclosed type surge arresters into the arrangement as far as change in overall
GIS equipment footprint inside the GIS Building.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 3 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
The grounding and bonding design shall be prepared and all enclosure bonding
provisions shall be included to mitigate induced currents in the GIS. The Contractor
shall include specific recommendations for grounding the GIS to mitigate step and
touch potentials, as well as mitigating VFTs and induced sheath currents.
The short-time current withstand ratings of all equipment and components comprising
the equipment shall be coordinated.
Drawings and calculations for SMUD's review and approval indicating the Contractor's
grounding and bonding requirements for the GIS equipment.
Drawings for SMUD's review and approval indicating the Contractor's raceway design
for the cabling internal to the GIS equipment and cable design between the GIS
equipment and the LCCs.
Drawings indicating the Contractor's proposed LCC design and layout.
Calculations and a report documenting the technical aspects of VT ferroresonance
suppression for the GIS station.
16878.1.1.1 Contractor’s Services.
The Contractor's services shall be in accordance with the following:
Contractor shall be responsible for all aspects of furnish and install (F&I) process, the completed GIS
system shall be warranted against all defects or failures resulting from faulty design, manufacturing,
workmanship, installation and testing.
Duration of the Contractor's services shall be based on project needs.
The Contractor shall provide field-experienced (minimum of 5 years experience) and certified (by the
Contractor) technicians in the quantity required to perform installation/erection work for the GIS and
accessories. The Contractor's technicians shall be on the site at all times during the GIS and
accessories installation.
16878.1.2 Items Furnished by Others and Interfaces
Items furnished by others and not in this scope of supply include the following:
Permanent building completed by the date for receipt of the GIS equipment.
Permanent building services, e.g., ventilation, lighting, and hoisting equipment
(maintenance crane), completed by the date for receipt of the GIS equipment.
Concrete foundations for indoor GIS equipment.
Air-insulated substation and transmission system equipment (AIS) outside the GIS.
Underground cable circuits connecting to the GIS.
Below grade station ground grid and ground connections of adequate length to connect
the GIS equipment to the station ground grid.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 4 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
DC power and other station service equipment such as panelboards and associated
raceway.
AC auxiliary power and other station service equipment such as panelboards, safety
switches, and associated raceway.
DC batteries and battery chargers.
Supervisory control and data acquisition (SCADA) remote terminal unit (RTU)
equipment.
Raceway and wiring from the Contractor-furnished equipment to equipment that is
provided by others.
Protective relaying and control systems.
16878.1.3 Performance and Design Requirements
Performance and design requirements are as follows:
All equipment and material shall be prefabricated, factory assembled, tested, and shipped in the largest
practical assemblies. All equipment ratings shall be equal to or greater than the GIS standards (IEEE
C37.122/IEC 62271-200) for this class of equipment except where specifically noted otherwise.
Assembled equipment shall be capable of withstanding electrical, mechanical, and thermal ratings of
the specified system. All joints and connections shall be able to withstand the forces of expansion,
vibration, contraction, and specified seismic requirements without deformation, malfunction, or leakage.
Equipment shall be capable of withstanding the specified environmental conditions.
Optimized arrangements are required to reduce installation time, provide ease of operation, minimize
maintenance and repair costs, and facilitate future additions as described in these specifications. The
space or area limitations for the GIS are shown on the drawings included with these specifications.
Final arrangement shall be as approved by SMUD.
Optimized arrangements shall permit full opening of each manhole, cover, and door. Sufficient space
and access areas shall be provided to permit the removal and reinstallation of each internal and
external equipment and component. The access areas around the equipment shall accommodate the
use of overhead cranes, maintenance fixtures, jigs, and any other required test and maintenance
equipment. All gauges, viewports, and gas fill points shall be located so as to be readily
accessible/viewable by maintenance personnel.
16878.1.4 Codes and Standards
GIS equipment and work performed under these specifications shall be done in accordance with the
following codes and standards:
ANSI (US) C2, National Electric Safety Code.
ASTM (US) D2472, Specification for Sulfur Hexafluoride.
IEC 60044-1, Instrument transformers – Part 1: Current transformers (latest edition
including amendments)
IEC 60050 (all parts), International Electrotechnical Vocabulary.
IEC 60060, High Voltage Test Techniques.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 5 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
IEC 60068-2-11, Basic environmental testing procedures – Part 2-11: Tests – test Ka:
Salt mist
IEC 60071 (parts 1 and 2), Insulation Coordination.
IEC 60137, Insulated bushings for alternating voltages above 1000V.
IEC 60270, High-voltage test techniques – Partial discharge measurements
IEC 60376, Specification of technical grade sulfur hexafluoride (SF6) for use in
electrical equipment.
IEC 60480, Guidelines for the checking and treatment of sulfur hexafluoride (SF 6) taken
from electrical equipment and specification for its re-use.
IEC 61462, Composite hollow insulators – pressurized and unpressurized insulators for
use in electrical equipment with rated voltage greater than 1000V – Definitions, test
methods, acceptance criteria, and design recommendations.
IEC TS 61639, Direction connection between power transformers and gas-insulated
metal-enclosed switchgear for rated voltages of 72.5kV and above.
IEC 61869-1, Instrument transformers – Part 1: General requirements
IEC 61869-3, Instrument transformers – Part 3: Additional requirements for inductive
voltage transformers.
IEC 62155, Hollow pressurized and unpressurized ceramic and glass insulators for use
in electrical equipment with rated voltages greater than 1000V.
IEC 62271-1, High-voltage switchgear and controlgear – Part 1: Common
specifications.
IEC 62271-100, High-voltage switchgear and controlgear – Part 100: Alternatingcurrent circuit-breakers.
IEC 62271-102, High-voltage switchgear and controlgear – Part 102: Alternatingcurrent disconnectors and earthing switches.
IEC 62271-200, High-voltage switchgear and controlgear – Part 200: AC metalenclosed switchgear and controlgear for rated voltages above 1kV and up to and
including 52kV.
IEC 62271-203, High-voltage switchgear and controlgear – Part 203: Gas-insulated
metal-enclosed switchgear rated for voltages above 52kV.
IEC 62271-209, High-voltage switchgear and controlgear – Part 209: Cable
connections for gas-insulated metal-enclosed switchgear for rated voltages above 52
kV – Fluid-filled and extruded insulation cables – Fluid-filled and dry-type cableterminations
IEC TR 62271-303, High-voltage switchgear and controlgear – Part 303: Use and
handling of sulfur hexafluoride (SF6).
IEEE 80, Guide for Safety in AC Substation Grounding.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 6 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
IEEE C37.04, IEEE Standard Rating Structure for AC High-Voltage Circuit Breakers Rated
on a Symmetrical Basis.
IEEE C37.06, IEEE Standard for AC High-Voltage Circuit Breakers Rated on a
Symmetrical Current Basis—Preferred Ratings and Required Capabilities for Voltages
above 1000V.
IEEE C37.017, Bushings for High-Voltage [over 1000 V (ac)] Circuit Breakers and GasInsulated Switchgear
IEEE C37.122, High Voltage Gas-Insulated Substations Rated Above 52 kV
IEEE C37.122.1, Guide for Gas-Insulated Substations Rated Above 52 kV.
IEEE C37.122.2, Guide for the Application of Gas-Insulated Substations 1 kV to 52 kV
IEEE C37.122.3, Guide for Sulphur Hexafluoride (SF6) Gas Handling for High-Voltage
(over 1000 Vac) Equipment
IEEE C57.19.01, Performance Characteristics and Dimensions for Outdoor Apparatus
Bushings.
IEEE Std C57.13, IEEE Standard Requirements for Instrument Transformers.
ISO 3231, Paints and varnished – Determinating of resistance to humid atmospheres
containing sulfur dioxide.
National Electrical Manufacturers Association (NEMA) CC 1, Electric Power
Connectors for Substations.
National Fire Protection Association (NFPA) (US) 70 (NEC), National Electrical Code.
16878.1.5 Technical Attachments
The following attachments accompany these specifications in either paper or electronic format. The
information contained in these documents constitutes requirements under the defined Scope of Work:
Document
Number/Description
Title
Revision
STG-A1C-D001
Architectural Sub Level Floor (EL -10’-0”)
B
STG-A1C-D002
Architectural Level Floor (EL 4’-0”)
B
STG-A1C-D003
Architectural Level Floor (34’-4”)
B
STG-A2H-D001
Architectural Section (Sheet 1)
A
STG-A2H-D002
Architectural Section (Sheet 2)
A
STG-E1B-D001
One Line Station Switching
D
STG-E1B-D002, D003,
D004, D005
Functional One Line 115kV Station Control &
Relay
A
SS1009
Districts Equipment Wiring Requirements
5
SS0001 (W001)
Drawings and Technical Data
9
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 7 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
Document
Number/Description
Title
Revision
S001
Field Engineering Services Requirements
1
16878.1.6 Supplemental Specifications
Technical supplemental specifications that are applicable to the work required shall be incorporated in
equipment design by Contractor.
D100.6 Building Code and Site Conditions
Table D100-2 Building Code and Site Conditions
General Design Data:
Building Code
N/A
Occupancy Category
N/A
Ft (Finished Grade Elevations)
See 16878.1.5
Wind Design Data: per ASCE 7
N/A
Seismic Design Data:
Seismic design zone
IEEE 693 high
D200 Design Ambients
Area Specific Design. The general design ambient air conditions shall be used unless area specific or
equipment specific conditions are indicated below:
Table D200-1 General Ambient Air Conditions
Temperature, °C
Relative Humidity, %
Area
Minimum
Maximum
Minimum
Maximum
General Outdoor Area
-30
39.5
44
100
E100 Wiring Methods, Cable, and Raceway
E100.1 General Requirements
In general, all devices furnished under these specifications and requiring electrical connections shall be
designed for wiring into electrical enclosures with terminal blocks. Terminal blocks shall be furnished
for conductors requiring connection to circuits external to the specified equipment, for internal circuits
crossing shipping splits, and where equipment parts replacement and maintenance will be facilitated.
Splices in wiring will not be acceptable.
Banding of the cable to the structure or equipment will not be permitted.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 8 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
Unless otherwise specified, all spare contacts on all electrical devices, including (but not limited to)
each control switch, auxiliary relay, control relay, and lockout relay, shall be wired out to terminal
blocks.
All wiring exiting an enclosure shall be from terminal blocks and not from other devices in the enclosure.
Auxiliary equipment including terminal blocks, auxiliary relays, or contactors shall be readily accessible.
Auxiliary equipment shall be located in compartments, enclosures or junction boxes in such an
arrangement that service personnel will have direct access to the equipment without removal of
barriers, cover plates, or wiring.
Terminal blocks (GE EB-25) for external connections shall be grouped in the LCC for easy accessibility,
unrestricted by interference from structural members and instruments. Sufficient space shall be
provided on each side of each terminal block to allow an orderly arrangement of all wiring to be
terminated on the block.
Terminal blocks shall not be mounted in compartments containing uninsulated conductors operating at
voltages above 1000 volts.
Current transformer leads shall be terminated on shorting type terminal blocks (GE EB-27)
For safety reasons, the current transformer shall be grounded but the grounding shall occur only at the
shorting terminal blocks.
All electrical cables shall be conservatively selected for the electrical and environmental conditions of
the installations and shall be of the best construction for the service where unusual service conditions
are encountered. Proper temperature application cable shall be used throughout. All electrical power
and control conductors shall be Class B, stranded copper conductors, 14 AWG or larger, voltage
transformer conductors shall be 12 AWG or larger, and current transformer conductors shall be 10
AWG or larger.
Electrical cables shall not include PVC. Shielded control cable shall be required.
Control conductors 8 AWG (10 mm 2) and smaller shall be terminated with compression ring tongue type
lugs properly sized for the conductor and the terminal. Terminal connectors for connecting to screw
terminals shall be pre-insulated ring type terminal connectors. The terminal connectors shall be
constructed of copper and shall be tin-plated. The interior surface of the connector wire barrel shall be
serrated, and the exterior surface of the connector wire barrel shall be furnished with crimp guides.
Except for internal wiring of factory prewired electronic system cabinets, crimping ferrules with plastic
insulating sleeves shall be provided on all stranded control conductors that are to be terminated to
compression Type IEC terminal blocks. Conductors for current transformer circuits shall be terminated
with uninsulated compression ring type terminal connectors. (see SMUD wiring Standard SS1009)
Pre-insulated ring type terminal connectors with solid barrel (shank) shall be used on all control circuits.
Pre-insulated terminal connectors shall include a vinyl sleeve, color coded to indicate conductor size.
Pre-insulated terminal connectors shall include a metallic support sleeve bonded to the vinyl insulating
sleeve, designed to grip the conductor insulation.
Enclosure internal wiring shall utilize stranded copper conductors with flame retardant, cross-linked
polyethylene or flame retardant, ethylene-propylene rubber insulation rated 600 volts and shall meet the
requirements of UL (US) 44 for Types SIS and XHHW. The cables shall also meet the UL (US) 44 VW1 flame test.
General service power and control cables, integral to the equipment furnished, but not internal wiring of
control cabinets or panels, shall be rated for the maximum service voltage, but not less than 600 volts.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 9 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
Single conductor cables shall have ethylene-propylene rubber insulation with a chlorosulfonated
polyethylene (Hypalon®) jacket. Multiconductor cables shall have flame retardant, cross-linked
polyethylene conductor insulation and an overall chlorosulfonated polyethylene (Hypalon®) jacket or
equal insulation system.
Silicone rubber insulated cable with braided glass jacket or fluorinated ethylene-propylene insulated
cable shall be used where ambient conditions cause conductor operating temperatures to exceed the
temperature ratings of the general service cable insulation specified.
Each terminal block, terminal, conductor, relay, breaker, fuse block, and other auxiliary devices shall be
permanently labeled to coincide with the identification indicated on the drawings. All terminals provided
for termination of external circuits shall be identified by inscribing terminal designations acceptable to
SMUD on the terminal block white marking strips with permanent black ink. All internal wiring
terminations shall be identified by printing on conductor identification sleeves. A conductor
identification sleeve shall be provided on each end of each internal conductor. Each sleeve
shall be marked with the opposite end destination identification using permanent black ink.
Conductor identification shall be permanent, unaffected by age, heat, or solvents and not easily
dislodged. Adhesive labels are not acceptable.
The arrangement of connections on terminal blocks shall be acceptable to SMUD.
All connections requiring disconnect plug and receptacle type devices shall be provided with factory
terminated conductors on each plug and receptacle. Plugs and receptacles shall be factory wired into
junction boxes containing terminal blocks for external connections. All conductors on the disconnect
portion of plug-receptacle assemblies shall be in a common jacket. The plug-receptacle assemblies
shall have provisions for locking the devices together.
All temporary wiring installed in the factory for equipment testing shall be removed prior to shipment of
the equipment.
Reference to NEC means the codes and standards as defined by the USA National Electrical Code,
ANSI/NFPA 70.
All shielded control, relay, power, or instrument cable overall shield shall be bonded at ONE end of the
cable by a cable shield connector. The cable shield shall be bonded to the grounding system by a
green #12AWG conductor. Acceptable shield connector bonding clips shall be 3M, Cat. #4460-D.
E100.2 Equipment Safety Grounding (Earthing)
All electrical equipment that is part of an integral shipping unit or assembly shall be furnished with a
bare copper grounding pad. The pad shall be suitable for field connection to the station ground grid by
SMUD.
Isolated logic system or single-point ground connections required for proper operation of electronic
equipment shall be insulated from the equipment safety ground. Such connections will be extended,
using insulated cable, to a single termination point suitable for field connections to the appropriate
ground system by SMUD.
Electrical equipment requiring grounding provisions shall include all enclosures containing electrical
connections or bare conductors with the exception of control devices, such as solenoids, pressure
switches, and limit switches, unless such devices require grounding for proper operation.
The raceway system shall not be used as a ground conductor except for itself. All metal conduits
containing power circuits shall be provided with grounding type bushings and shall be wired together
inside enclosures and connected internally to the enclosure grounding pad or grounding bus with bare
copper conductor. The grounding bushing ground conductor shall be sized in accordance with NEC or
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 10 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
other internationally recognized standard but shall not be less than 8 AWG (10 mm2) bare copper
conductor.
E100.3 Electrical Interconnections
All electrical interconnections between devices, panels, and boxes shall use one of the following wiring
methods as specified on the table at the end of this section:
NonShielded Cable. Non-shielded cable which is continuously supported and
protected by conduit or installed in cable tray.
Shielded Cable. Shielded cable which is continuously supported and protected by
conduit or installed in cable tray.
The installation of the cable and raceway system shall meet the requirements of NEC or other
internationally recognized standard.
E100.4 Cable
Unless otherwise specified on the table at the end of this section, both nonarmored and armored cable
shall meet the following minimum requirements:
Stranded copper conductors.
Flame retardant cross-linked polyethylene (FRXLPE) or ethylene propylene rubber
(FREPR) on power and control cables.
General service power and control cables, integral to the equipment furnished but not
internal wiring of control cabinets or panels, shall be rated for the maximum service
voltage but not less than 600 volts.
Unless otherwise specified on the table at the end of this section, fiber optic and
communication cable shall meet the following minimum requirements.
Fiber Optic Cable
Multimode/Singlemode
Duplex fiber
Minimum buffer thickness of 900um
Minimum OD of 2.0 mm
Jacket shall be OFNR rated and RoHS compliant
Jacket color shall be Orange for Multimode and Yellow for Singlemode
Multimode fiber shall be 62.5/125 graded index type
Singlemode fiber shall be 9/125 graded index type
Communications Cable
Ethernet
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 11 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
Category 5E, shielded
4-pair stranded, 26AWG
Must meet ANSI/TIA/EIA-568-B latest revision
Jacket shall be plenum rated
E100.5 Conduit
All conduit interconnections between devices, panels, boxes, and fittings shall be rigid metal conduit
which conforms to NEMA C80.1 and UL 6 and shall be constructed of aluminum. All conduit
connections shall be of the threaded type, and all conduit, couplings, and fittings shall be aluminum.
Liquidtight flexible metal conduit may be used as long as the length does not exceed 3 feet (1 meter).
All conduit which enters the top of an enclosure shall enter through raintight steel or malleable iron hubs
or threaded openings.
All liquidtight flexible metal conduit shall be constructed of continuously interlocked rust resistant metal
core. Conduit shall be coated with sunlight resistant thermoplastic jacket. The conduit shall also resist
heat, oil, and chemical breakdown and shall be UL listed. Liquidtight flexible conduit shall be Sealtite®
Type EF or SMUD approved equal.
One exterior locknut, one interior locknut, and one bushing shall be provided at the termination of each
rigid metal conduit not terminated in a hub. Locknuts shall be designed to securely bond the conduit to
the box or cabinet when tightened. Locknuts shall be constructed to mitigate loosening by vibration.
Grounding type insulated bushings with insulating inserts in metal housings shall be provided on all
conduits not terminated in hubs and couplings. Bushings shall be galvanized.
All conduit fittings shall conform to the requirements of UL 514. All liquidtight flexible metal conduit
fittings shall be galvanized steel or malleable iron with insulated throat (Appleton Type STN, STB, or
SMUD approved equal) and shall be UL listed.
All conduit runs shall be rigidly supported at intervals not exceeding 10 feet. Each conduit shall be
supported within 12 inches of junction boxes and fittings.
Conduit shall be securely fastened to all boxes and cabinets. Threads on metallic conduit shall project
through the wall of the box to allow the bushing to butt against the end of the conduit. The locknuts
both inside and outside shall then be tightened sufficiently to bond the conduit securely to the box.
The raceway system provided for all interconnecting wiring shall be acceptable to SMUD.
E100.6 Terminations
The capacities of conduit entrances and terminal enclosures for terminating SMUD's cable shall be
coordinated with SMUD. Final sizes shall be acceptable to SMUD.
The following criteria apply to wiring methods, cable, and raceway specified herein:
Wiring Methods, Cable, and Raceway
Electrical Interconnections Between
Electrical Enclosures, Devices, or Lighting
Source: 16878, (2016), v.1.0
Nonarmored cable routed in tray and/or conduit
Armored cable routed in tray
Armored cable for lighting routed
Gas Insulated Switchgear Equipment
Page 12 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
Wiring Methods, Cable, and Raceway
Thermocouple Cable Insulation Color Coding
per thermocouple type
Cable - Additional Requirements
600 volt power and control cable shall supply power
to loads at 480 VAC and 125 VDC or less. 600 volt
power and control cable shall have FR-EPR or FRXLPE insulation with flame-retardant jacket.
Instrument cable shall be twisted shielded pairs or
triads with 300 volt class insulation (minimum). This
cable shall have XLPE insulation with flame retardant
jacket (minimum). Single and multiple pairs shall
have an overall shield. Multiple pairs shall also have
pairs shielded.
Switchboard and panel wire shall be multi-stranded
XLPE insulated for 600 volts.
E520 Terminal Blocks and Fuse Holders
E520.1 General
In general, manufacturer standard terminal blocks will be accepted provided they meet the
requirements of this specification and quality levels equivalent to the manufacturer's terminal blocks
listed in the table at the end of this section. Self-stripping terminal blocks, multiple deck (step type)
terminal blocks, and angled terminal blocks will not be acceptable. Screw type terminals suitable for
ring lug termination shall be furnished for all current transformer secondary lead connections shorting
terminal block.
Each terminal block shall be provided with a unique identifier. All terminal points shall have provisions
to be uniquely identified on the terminal block white marking strip and, where permitted by the safety
codes and standards, shall be without covers. Spare points shall be provided with blank strips that can
be field marked with a permanent ink marking pen. Spare (unused) terminals shall be furnished evenly
distributed on the terminal blocks for circuit modifications. No fewer than two spare unused terminals
shall be furnished for every ten terminals used.
Terminal blocks shall be manufactured from materials that will not support combustion. Terminal blocks
shall meet the Inflammability Class V0 rating in accordance with UL 94. All terminal blocks, except
internal terminal blocks in factory prewired electronic systems cabinets and terminal blocks for
thermocouple extension wire, shall be rated for 600 volts or greater. No more than two conductors shall
be terminated at one connection point. For terminal blocks interfacing with SMUD's field cabling, one
side of the terminal block shall be used by the equipment manufacturer for factory wiring and the other
side of the terminal block shall be reserved for SMUD's field cabling terminations.
E520.2 Not Used
E520.3 Strap Screw Terminal Blocks
Strap screw terminal blocks shall be of heavy-duty construction capable of terminating a conductor from
16 AWG (1.5 mm2) to 10 AWG (6 mm 2). The point-to-point spacing shall not be less than 0.375 inch
(9.5 mm).
E520.4 Power Terminal Blocks
Power terminal blocks shall be used for conductors 8 AWG (10 mm 2) and larger.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 13 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
E520.5 Not Used
E520.6 Fuse Holders for Power Circuits
When fuses rated from 1 to 30 amperes at 250 volts maximum are required, the fuse holders shall be
suitable for 30 amperes, 250 volts, Class H cartridge fuses. The fuse holders shall be in accordance
with ANSI/UL 521, shall have a withstand rating of 10,000 rms symmetrical amperes, and shall have
reinforced fuse contact clips. (BUSSMANN CH14)
The fuse bases shall be molded phenolic, polyester, or other plastic having a Flammability Rating of V0 when tested in accordance with UL 94. Porcelain is not acceptable materials for fuse holder bases.
The following criteria shall apply to terminal blocks and fuse holders:
Terminal Blocks and Fuse Holders
Applications
Acceptable
Termination
Methods
FeedThrough
General Purpose
Shorting
Power
Terminal
Block Type
Acceptable
Construction
Acceptable
Manufacturers
Strap Screw,
Manufacturer's
Standard
SMUD-Approved Equal
Current
Transformer
Strap Screw
Grouped Block,
Bolted
GE EB-25 or SMUDApproved Equal
600 Volt Power
(8 AWG through
4/0 AWG [10 mm2
through 95 mm2])
Screw,
Compression,
Stud
Grouped Block,
Bolted
GE EB-27 or SMUDApproved Equal
E530.1 Electrical Indicating Instruments
All annunciators devices shall be designed for flush mounting.
E530.2 Control Relays
General service auxiliary relays shall be ABB, Siemens, GE, Allen-Bradley Bulletin 700 Type P,
Schneider, Potter Brumfield, Agastat, Square D or SMUD approved equal. Where current carrying
requirements exceed the capacity of the general service auxiliary relays, auxiliary relays shall be ABB,
Siemens, GE, Allen-Bradley Bulletin 700 Type PK, General Electric or SMUD approved equal.
Timing relays for general service where the delay period is 1 minute or less shall be either pneumatic or
solid-state. Timing relays for critical service shall be solid-state. Timing relays shall be Agastat Series
7000, ABB, Siemens, GE or SMUD approved equal.
If the manufacturer proposes the use of auxiliary or timing relays other than the ones listed above,
technical data sheets for the proposed relays shall be submitted for approval by SMUD.
Unless otherwise specified, DC relays that interface with SMUD's control system shall have a diode
surge suppressor installed across the relay coil.
E530.3 Electrical Switches
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 14 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
Control switches shall be 600 volt, 20 ampere, multistage, rotary type. Unless otherwise specified,
switches shall have black, fixed, modern, pistol grip type handles and engraved black plastic
escutcheon plates with targets.
Push buttons and selector switches shall be heavy-duty oiltight.
E530.4 Indicating Lights
Indicating lights in the LCC shall be heavy-duty oiltight and shall permit light changing from the front.
Luminous output shall be suitable for the location and ambient lighting conditions. Unless otherwise
specified, LED type indicators are preferred on panels.
E530.5 Contacts
Contact ratings for all electrical accessory devices shall be suitable for interface with SMUD's control
system. SMUD's control system interrogation voltages will range up to 230 volts ac and 125 volts DC.
All contacts that interface with SMUD's control system shall be electrically "dry." Solid-state switches or
triac outputs are not acceptable for contacts that interface with SMUD's electronic equipment.
Alarm contacts shall consist of one normally open and one normally closed contact "Form C."
All contacts shall be rated a minimum 1.0 ampere make or break at 125 volts DC.
E530.6 Fuses and Circuit Breaker
Fuses shall be provided with ampere ratings sized for the application. Circuit breakers required for all
equipment electrical systems (TRIP, CLOSE, ETC)
E530.7 Colors of Indicating Devices and Actuators
Coding of indicating devices and switch actuators (push button, knob, selector switch, or handle) shall
be subject to SMUD review. If words or recognized abbreviations are required to describe the function
of the indicating device or actuator, the language used shall be English. Indicating lights shall be
energized when the condition described in the following table exists, and shall be de-energized when
the condition does not exist.
E530 Electrical Accessory Devices - Supplemental Requirements
Colors of Indicating Devices
Color
Meaning
Explanation
Examples
Green
Equipment de-energized;
process stopped
Normal off condition
requiring no action by
the operator
Motor stopped; valve
(damper) closed; breaker
open, contactor deenergized
Red
Equipment energized;
process normal
Normal running
condition requiring no
action by the operator
Motor running; valve
(damper) open; breaker
closed, contactor
energized; process within
normal limits;
cabinet/panel power
available
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 15 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
Colors of Indicating Devices
Color
Meaning
Explanation
Examples
Orange
Equipment abnormality;
process abnormality
Abnormal condition
requiring monitoring
and/or fault by the
operator
Motor trip; breaker trip,
contactor trip; tripping by a
protective device or
interlock; electrical lockout
relay tripped; position
change from normal;
pressure or temperature
beyond normal limits;
overload
Orange Flashing
Emergency
Dangerous condition
requiring immediate
action by the operator
Pressure or temperature
beyond safe limits; loss of
critical process
Blue
Mandatory
Indication of a
condition which
requires action by the
operator
Instruction to enter a
value; paralleled electrical
power sources to bus
causing bus rating to be
exceeded
White
Permissive
Normal condition;
General information;
electrical lockout relay
reset
Healthy condition;
Equipment start
permissive;
equipment protective
relay reset
Colors of Actuators
Color
Meaning
Examples
Red
Emergency
Emergency-stop/off
Black
Normal stop/off
Normal stop; open breaker,
contactor de-energized
Black
Normal start/on
Normal start; closed breaker,
energize contactor
Electrical Switches
Application
Description
Manufacturer/Style
Breaker Control Switches
Control Switches
Control Panel LCC
Electroswitch
#88PD907LA / #88PB907LA
Push Buttons and
Selector Switches
LCC
ABB, Siemens, GE, Electroswitch
SMUD Approved Equal
Toggle Switches
Control Panel
ABB, Siemens, GE, Electroswitch
SMUD Approved Equal
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 16 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
Fuses and Fuse Blocks
Application
Manufacturer/Style
Slow Blow Fuses
SMUD Approved Equal
Bussman/NON
Fast Acting Fuses
SMUD Approved Equal
Bussman/NON
Extremely Fast Acting Fuses
SMUD Approved Equal
Bussman/NON
16878.1.7 GIS Equipment Ratings and Service Conditions
The GIS equipment shall be provided with the specified ratings, considering the electrical and
environmental service conditions listed below:
Service Conditions
Enclosure
Enclosed in a building
Site Conditions
See Section 16878.1.5
Ratings
GIS
Rated maximum voltage , kV
145 kV rms
Rated insulation level – basic impulse level (BIL)
(across the isolating distance), kV minimum peak
value
650 kV
Rated low frequency phase-to-ground withstand
voltage, kV rms
275 kV
Rated frequency, Hz
60 Hz
Rated minimum current, main buses, A
2000 A
Rated minimum current, cross buses, and bus
taps, A
2000 A
Rated short-time withstand current, kA rms
40 kA
Rated withstand current, kA peak
104 kA
Rated duration of short circuit, seconds (minimum)
3 seconds
Circuit Breakers
Rated maximum voltage, kV
145 kV
Rated maximum interrupting time, cycles
Three on a 60 Hz
Rated minimum current, all breakers, A
2000 A
Rated short-circuit breaking current, kA rms
40 kA
Rated closing and latching current, kA peak
104 kA
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 17 of 43
STG-GIS
SMUD STATION G GIS
Rated operating sequence
Duty Cycle: O-t1-CO-t2-CO
where t1 = 0.3 second,
and t2 = 3 minutes
Rated capacitive switching currents
IEC 62271-100 Table 9
Number of mechanical operations
10,000 (minimum)
Number of trip coils
Two
Final
01/31/2017
Disconnect Switches
Rated minimum current, all disconnect switches, A
2000 A
Rated short-time withstand current, kA
100 kA
Rated peak withstand current, kA peak
141 kA
Rated duration of short circuit, seconds
3 seconds
Mechanical endurance
1,000 cycles (minimum)
Grounding Switches
Rated minimum current, all grounding switches, A
2000 A
Rated short-time withstand current, kA
40 kA
Rated peak withstand current, kA
60 kA
Rated short-circuit making current (high speed
grounding switch only), kA
40 kA
Electrical endurance (high speed grounding switch
only)
E1 (Two minimum full fault closing operations,
before inspection/contact replacement)
Rated duration of short circuit, seconds
3 seconds
Mechanical endurance
1,000 cycles (minimum)
Current Transformers
Ratio, rated primary current, A
Five lead, multi-ratio (IEEE C57.13 Table 8),
2000 A
Rated secondary current, A
5A
Rated continuous thermal secondary current, A
10 A (RF = 2.0)
Rated 1 second thermal equivalent primary
current, kA
63 kA
Relay accuracy class
C800 (IEEE C57.13)
Voltage Transformers
Application
Three-phase, phase-to-ground in an effectively
grounded system
Rated primary voltage, line-to-ground, kV
66.4kV Ground Y (Max Operating Voltage 69.0
kV)
Rated secondary voltages, V
115V and 66.4 V (two secondary windings, two
taps in each winding)
Rated output, VA
400 volt-amperes (VA) (minimum), each winding
Accuracy class and burden
IEEE C57.13, 0.3 at W, X, Y, Z, ZZ
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 18 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
Metal-Enclosed Surge Arresters
Type
Metal oxide varistor (MOV), station class
Application
Metal-enclosed, phase-to-ground in an effectively
grounded system
Maximum continuous operating voltage (MCOV)
rating, kV
76 kV
Rated frequency, Hz
60 Hz
A discharge counter and leakage current monitoring system shall be provided for each surge arrester.
16878.1.8 Specific Equipment Requirements
The GIS electrical configuration (line and bus layout), and equipment rating/features shall be in
accordance with the drawings listed in Article 16878.1.5.
Disconnect switches shall be gang and motor-operated, and capable of interrupting the charging
current of the connected GIS bus and associated components.
Maintenance grounding switches shall be gang and motor-operated.
High-speed grounding switches shall be gang and motor charged spring-operated.
High-speed grounding switches shall be capable of handling the charging currents associated with the
GIS bus, high voltage overhead transmission lines, and high voltage underground cable termination
lines. High-speed grounding switches shall be capable of accidentally closing in on an energized bus
without damage to the switch or the enclosure.
Each disconnect switch, maintenance grounding switch, and high-speed grounding switch shall be
equipped with mechanism-actuated auxiliary switches for indication of the contact position.
Visual inspection means shall be provided to observe disconnect switch, maintenance grounding switch
and high-speed grounding switch contact positions. A mechanically connected external position
indicator shall be provided for each switch.
Electrical interlocks shall be furnished to prevent incorrect sequential operation or equipment
malfunction that might result in equipment damage or personnel injury. Electrical interlock schemes
shall provide the interlock function upon loss of the control power.
Mechanical blocking devices (not interlocks) shall be provided to block (disable) operation of all
disconnect switches and grounding switches. Provisions for pad-locking shall be provided on each
blocking device and disconnect switch.
Proper grounding for mitigating overvoltages during disconnect switch or circuit breaker operation shall
be included. Ground pads (NEMA 2 hole) for connection to SMUD's grounding system shall be
stainless steel, unless otherwise approved by SMUD.
Heaters shall be installed in control cabinets and equipment housings to avoid condensation.
High voltage conductors shall be made of aluminum tubing suitable for the specified current and voltage
ratings. The enclosure shall be aluminum. Adjoining enclosures shall be bolted together, and
connected to ground.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 19 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
The GIS equipment shall be designed to prevent mechanical failure and withstand pressure buildup if
the breaker fails to interrupt full rated fault current. The use of a rupture disk as a pressure relief device
is acceptable. Each SF6 gas-filled enclosure shall be in complete compliance with the requirements of
established national pressure vessel code standard requirements. The Contractor shall identify in the
proposal the methodology for calculating the thickness and construction of the enclosures and the
applicable pressure vessel code standards.
Pressure relief devices shall be provided with a shield and shall be vented to provide a safe
environment for personnel, and for equipment, during operation. The bursting pressure of the relief
device shall be effectively coordinated with the rated gas pressure and the pressure rise due to arcing
as described in IEEE Std. C37.122/IEC 62271-203.
Expansion and installation alignment shall be considered in the design of the bus and the enclosure. If
required, expansion joints shall be provided with compensators for the enclosure and sliding plug-in
contacts used for the conductors.
Support insulators shall maintain the conductor and enclosure in the proper relation for the rated
maximum voltage, rated insulation level (BIL), and rated low frequency phase-to-ground withstand
voltage.
Connections between adjacent conductor sections shall be made by means of plug-in type contacts.
Shields shall be placed to capture metallic particles that may result from contact rubbing. All welding of
high voltage conductors shall be made in the Contractor's fabrication facilities. Field welding of the
conductors is not acceptable.
Shipping sections shall be joined in the field using bolted, gasketed, flange connections of the
enclosure. Flanged connections shall have a gas seal between the flange surfaces. A second seal
ring, sealants, or other suitable means are required to protect the gas seal from the external
environment. Connections, including bolts, washers, and nuts, shall be adequately protected from
corrosion and shall be easily accessible with the proper tools.
Field welding of the enclosure is not acceptable.
Structures to support the equipment, platforms, and walkways for operation and maintenance access to
operating and monitoring devices shall be designed to permit access without use of special devices or
portable ladders.
GIS grounding pad terminals shall be located to permit proper connection to SMUD's station grounding
grid and to minimize external bus enclosure voltage gradients to a safe limit. All support structures and
control cabinets shall be grounded.
Surge arresters/surge suppressors across the insulating joint of enclosures to eliminate VFT due to
switching or circuit breaker operation shall be provided by the Contractor.
All wiring of devices and terminations internal to the GIS and all shielded control cables (and associated
raceways), above foundation, between the equipment and the GIS local control cabinets (LCC), and all
low voltage raceways and wiring furnished by the Contractor are to be designed in accordance with
NFPA (US) 70 (NEC) and the local authority’s requirements. Raceways and conduits shall be installed
so as not to present a safety hazard or require removal by personnel inspecting, maintaining, or
servicing the equipment.
16878.1.9 Circuit Breakers
Circuit breakers shall be the SF6 gas-insulated type, dead tank design, and with the ratings as
specified. The breaker shall have ratings described in IEEE Std C37.122/IEC 62271-100 and 62271203, and specific ratings in accordance with other applicable IEEE/IEC standards. The breaker shall be
capable of performing the specified duty cycle without derating.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 20 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
Each circuit breaker shall be factory assembled, adjusted, and tested, and shall be shipped as a
complete three-phase, gang-operated unit.
The breaker shall include a suitable operating mechanism to ensure proper opening and closing and
shall permit checking adjustments and operating characteristics. The mechanism shall be capable of
reclosing within the time range specified.
Each breaker shall include a weatherproof (NEMA 3X) cabinet for housing the operating mechanism
and all accessories. Necessary valves and connections (DN8) as manufactured by Dilo shall be
provided to ensure ease in handling the SF6 gas.
Each circuit breaker shall be equipped with an operation counter. The preferred arrangement for this
device is to operate only during the opening cycle. An indicator that shows the position of the contacts
should be provided. All gauges, counters, and position indicators shall be readable by an operator
standing near the equipment at floor level (additional portable ladders or platforms shall not be
required). All gauges, counters, and position indicators shall be in (English) and shall utilize (US) units
of measurement.
Closing resistors, when required, shall meet the rated line-closing switching surge factor as specified in
the applicable standards.
A minimum of 18 "a" and 18 "b" auxiliary contacts shall be provided for SMUD’s use.
The circuit breaker operating system shall be spring-operated. Pneumatic, hydraulic, or hydraulicspring operating systems are not acceptable.
The circuit breaker spring charging motor shall be a universal AC/DC motor. Operating on an AC
supply under normal conditions and DC as a backup. A manual throw-over switch shall be provided at
the circuit breaker to allow maintenance personnel to switch from AC to DC supply.
Circuit breaker trip and close coils shall be low-energy type requiring not more than 6 amperes at 125
VDC nominal for proper operation.
Each circuit breaker shall have dual trip coils.
Each LCC cablinet shall have SEL-2523 ( Part # 252301H13A0AXXX) annunciator to monitor breaker
health.
16878.1.10 Disconnect and Grounding Switches
Disconnect switches shall be gang and motor-operated, non-load break, with one operating mechanism
per three-pole switch. Operating mechanisms shall be provided with position indication.
Grounding switches shall be gang and motor-operated.
The motor-operated disconnect and grounding switches, shall be equipped with electrically and
mechanically operated devices to uncouple the motor when the switch is operated manually to prevent
coincident power operation of the switch and the drive mechanism(s).
Each disconnect and grounding switch shall open or close only due to manual or motor driven
operation. The switch blade shall not move due to gravity or other means, if a part fails. Once initiated,
the motor mechanism shall complete an open or close operation without requiring the initiating contact
to be held closed.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 21 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
Each disconnect switch and grounding switch shall be furnished with electrically independent auxiliary
switches. The auxiliary switches shall indicate the position of the switch blades and shall be provided
so that the contacts can be adjusted to be fully engaged and in proper alignment when in the closed
position. A minimum of 12 "a" and 12 "b" auxiliary contacts shall be provided for each disconnect and
maintenance grounding switch for SMUD's use. A minimum of 8 “a” and 8 “b” auxiliary contacts shall
be provided for each high-speed grounding switch for SMUD’s use.
Visual verification, via a viewport accessible by personnel, shall be provided to verify each pole position
of each disconnect switch and grounding switch blade. External position indicators connected directly
to the mechanism shaft shall be provided. The switch position indicator shall not contain removable
links.
Viewport removable covers, if supplied, shall be easily removable without the use of any tools. The
covers shall be permanently attached or fixed such that loosening finger-tight captive hardware will
permit the cover to be shifted to view the switch enclosure interior. SMUD’s personnel shall not be
required to remove, reposition, etc., any other devices/mechanisms/hardware in the vicinity or to
engage any type of mechanism or tool to access the viewport.
All viewports shall be a minimum of 4” diameter and easily accessible
If an external light source is required, the viewports shall be arranged such that one person has the
ability to operate the light source and inspect the main switch contacts.
The area around the viewport shall have a weatherproof identification tag or sign shall be installed in
accordance with IEEE C37.122.
Suitable means of access shall be provided to each disconnect switch and grounding switch housing
and mechanism for repair and/or maintenance of contacts. Viewports connection point shall be
accessible from fixed maintenance platforms or the floor.
Low voltage test provisions shall be supplied to permit testing of each grounding switch at voltages up
to 10 kV, and up to 200 A. The provisions shall allow the test voltage and current to be applied to the
conductor without removing SF6 gas or other components.
16878.1.11 Gas System
The GIS shall be furnished, with sufficient SF6 gas to pressurize the complete system in a sequential
approach, one zone or compartment at a time, to the rated nominal density. The SF 6 gas shall conform
to ASTM (US) D2472 and IEC 60376 and shall be at least 99 percent pure. An amount equal to 1
percent of the SF6 gas in the total GIS assembly for this project shall also be included as spare gas.
The spare gas shall be delivered in conventional quantity (weight) of SF6 gas shall be documented for
each SF6 gas cylinder shipped to SMUD.
The Contractor shall provide guidelines and recommended practices for the reuse and recycling of SF6
gas removed from the equipment.
The GIS enclosure system shall be divided into several sections separated by gastight barrier insulators
(identified using orange color paint marks). Each section shall be provided with the necessary piping
and valves to allow isolation, evacuation, and refill of gas without evacuation of any other section.
Location of gas barrier insulators shall be clearly discernable outside the enclosure by a band of distinct
color normally used for safety purposes and acceptable to SMUD.
For the purpose of gas monitoring and maintenance, each circuit breaker assembly (including circuit
breaker, CTs, disconnect switches, and maintenance grounding switches), high-speed grounding
switch, voltage transformer, metal-enclosed surge arrester, cable sealing end enclosure, bus sections
to gas-to-air-bushings, bus sections to cable sealing end enclosures, and interface connections for
future expansion of the GIS shall be independent from all other gas compartments, as a minimum.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 22 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
Buffer gas compartments shall be provided between circuit breakers and associated disconnect
switches; cable sealing ends and bus compartments; voltage transformers and buses, to allow
maintenance to be performed on the circuit breaker, cable termination, bushing, or VT without having to
depressurize the adjacent gas compartment.
Gas zones for main buses shall be segregated on a per diameter basis. Main bus Gas zone should
account for future expansion of ring bus without taking two line positions out at same time for future
addition. (i.e., gastight barriers shall be installed in the main bus enclosures between each ring bus
position connected to the bus).
Gas zones shall be arranged such that the boundaries of the electrical outage(s) required to maintain
any piece of equipment shall be minimized. The Contractor shall furnish with the proposal a description
of the work rules associated with taking elements out of service during maintenance activities.
Gastight barrier insulators shall be designed to withstand the differential pressures to which they may
be subjected during preventive or corrective maintenance. This shall not require lowering of gas
pressure in the adjacent gas zones or disturbing the adjacent compartments.
A gas schematic diagram shall be provided including the necessary valves, connections, density
monitors, gas monitor system and controls, indication, orifices, and isolation to prevent current
circulation. Once the gas schematic diagram is approved, it shall be used to create suitable gas zone
diagram plates for each bay of GIS equipment monitored by an LCC. The Contractor shall submit shop
drawings for review/approval by SMUD prior to fabricating these plates.
The gas system shall be provided with means of calibrating density monitors without de-energizing the
equipment.
The external fixtures shall be made of corrosion-resistant material and shall be capped.
For 3-in-1 enclosure type GIS equipment, three-phase gas pressure and density monitoring shall be
provided. For single-phase encapsulated type GIS equipment, single-phase gas pressure and density
monitoring shall be provided. Interphase piping (connecting phases) shall not be allowed for singlephase encapsulated type equipment.
The leakage rate of SF6 gas from an individual gas compartment shall be guaranteed not to exceed 0.5
percent (V/V) per year. The total leakage rate from the total GIS system shall be guaranteed not to
exceed 0.5 percent (V/V) per year.
Each gas zone with a switching device shall be furnished with a gas density monitoring device
(manufactured by Trafag, Solon, or Wika) capable of signaling two adjustable, independent alarms.
Each device shall be individually adjustable, and shall have electrically-independent contacts that
operate at the following alarm levels:
First alarm - Low gas density (nominally 5-10 percent below nominal fill density) to local
annunciator and to SMUD’s SCADA RTU.
Second alarm – Block trip circuit breakers associated with the affected gas zone before
minimum gas density to achieve equipment ratings is reached and block closing of
circuit breakers associated with the affected gas zone.
Each gas zone without a switching device shall be furnished with a gas density monitoring device
(manufactured by Trafag, Solon, or Wika) capable of signaling two adjustable, independent alarms.
Each device shall be individually adjustable, and shall have electrically-independent contacts that
operate at the following alarm levels:
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 23 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
First alarm - Low gas density (nominally 5-10 percent below nominal fill density) to local
annunciator and to SMUD’s SCADA RTU.
Second alarm - Minimum gas density to local annunciator and to SMUD’s SCADA
RTU.
The Contractor shall provide connections for a gas density relay/monitoring system, the gas handling
equipment, and moisture detection instrumentation to each one of the gas compartments. Facilities
utilizing Dilo DN type fittings (no substitute will be allowed) shall be included that permit addition of SF 6
gas while GIS components are in service (energized).
The Contractor shall also supply a stand-alone GDM system using SF6 gas density transducers. The
GDM shall have Ethernet communication with distributed network protocol (DNP) version 3.0 to
transmit gas zone and system alarms to the future SMUD SF6 gas monitoring system.
The GDM system shall be capable of trending densities and pressures, identifying a leak by gas zone,
and maintaining a complete gas inventory.
The GDM system shall include a gas zone mimic diagram local display which indicates alarm level by
zone on a schematic.
16878.1.12 Current Transformers
Each current transformer shall be provided so that the enclosure current does not affect the accuracy or
the ratio of the device or the conductor current being measured. Provision shall be made to prevent
arcing across the enclosure insulation.
Current transformer secondaries shall be terminated to six-point shorting terminal blocks in the LCC.
Testing of each current transformer shall be possible without the removal of the SF6 gas. The current
transformer location, polarity, ratios, and accuracy shall be as specified and in accordance with IEEE
C57.13
16878.1.13 Inductive Voltage Transformers
Each voltage transformer shall be SF6 gas insulated type.
Each voltage transformer shall be fabricated to mitigate the possibility of ferroresonance during
operation. If damping equipment connected to a secondary winding is necessary to mitigate
ferroresonant effects, it is preferred that such damping equipment be mounted in the voltage
transformer secondary wiring junction box on the voltage transformer.
Transformers shall be of either plug-in construction or the disconnect-link type, and shall be attached to
the GIS system in such a manner that they can be easily disconnected while the system is being
dielectrically tested. The metal housing of the transformer shall be connected to the metal enclosure of
the GIS with a flanged, bolted, and gasketed joint so that the transformer housing is grounded to the
GIS enclosure.
Special covers and any necessary corona shields shall be supplied so that the system can be
pressurized and dielectrically tested after removal of the transformer.
Primary and secondary terminals shall have permanent markings, for identification of polarity, in
accordance with IEEE C57.13.
Voltage transformer secondaries shall be fused (except the neutral) and connected through a Visible
Secondary Break (VSB) disconnect device and then terminated on terminal blocks in the LCC.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 24 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
Each secondary lead (except the neutral) shall be connected through the VSB disconnect device.
Additional test switches to be added in the LCC after VSC to provide additional isolation. Test switches
to be ABB FT-1 switches, with red handles (See attached SMUD test switch Color definitions sheet)
16878.1.14 Metal-Enclosed Surge Arresters
High voltage surge arresters of the voltage rating called for herein before shall be either "plug-in" type
construction or disconnect-link type construction and shall be attached to the GIS in such a manner that
they can be readily disconnected from the GIS while the GIS is being dielectrically tested. The metal
housing of the arresters shall be connected to the metal enclosure of the GIS with a flanged, bolted,
and gasketed joint.
The arrester grounding connection shall be sized for the fault level of the GIS, insulated from the GIS
enclosure, and grounded externally to permit periodic maintenance and monitoring of the arrester
leakage current. Access to the arrester grounding connection shall not be obstructed.
If the arrester is not equipped with removable links, special covers and any necessary corona shields
shall be supplied so that the GIS system can be pressurized and dielectrically tested after removal of
the arrester.
16878.1.15 SF6 Gas-to-Air Bushings
N/A
16878.1.16 GIS to Cable Connections
GIS CSE enclosures for cable terminators (provided/installed by others) shall be provided for
connecting SMUD’s high voltage underground cable circuits to the GIS equipment. The CSE enclosure
shall be proportioned to permit independent testing of the connecting cable and shall provide means to
permit such testing. The CSE enclosure shall be equipped with a removable link to permit separation of
cable and GIS for high voltage testing. The Contractor shall include in the proposal, the maximum
voltage which can be applied to the gas-filled CSE enclosure while the removable link is removed for
testing of the underground cable system.
The CSE enclosure and connection support structure shall be equipped with provisions for isolating the
cable sheath to permit effective bonding of the cable system, as necessary. The Contractor shall
coordinate placement, ratings, and testing of the cable circuit bonding system with SMUD’s
underground cable circuit supply/installation Contractor/Contractor to ensure effectiveness of the
bonding system in handling power frequency fault current within the GIS.
To ensure accurate alignment/mating/dimensioning of the GIS CSE enclosure and the underground
cable circuit cable terminator, the GIS Contractor shall coordinate the interface design directly with the
underground cable circuit cable terminator Contractor in accordance with IEC 62271-209 and other
applicable standards.
16878.1.17 Local Control Cabinets
The Contractor shall furnish one local LCC for each circuit breaker. Each cabinet shall be completely
fabricated, wired, assembled, and tested at the factory. Each cabinet furnished shall be fully equipped
and completely wired to the terminal blocks for termination of circuit breaker and switch control,
instrument transformer, indication, gas alarm and other miscellaneous cables.
Each indoor cabinet, junction box, or marshalling box shall be a NEMA 12 enclosure, as a minimum.
Each cabinet shall have stainless steel hinges, door hardware, fastening hardware, and pad lockable
etc.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 25 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
Each cabinet shall have a rear access door. All external cabling shall be brought into and terminated in
the rear of the cabinet.
Each cabinet shall contain the following equipment, as a minimum, for control, indication and protection
of switches, circuit breakers, and associated components: (utilize LEDs provided by Electroswitch)
One combined open-close control and remote-local switch for each three-phase circuit
breaker. (Electroswitch 88PD907LA)
One open-close control and remote-local switch (Electroswitch 24204B) for each
motor-operated disconnect switch. (Electroswitch 88PB907LA)
One open-close control switch for each motor-operated or spring-operated grounding
switch.
One or two (one for each circuit breaker trip coil) red light-emitting diodes (LEDs) and
one green for each circuit breaker (utilize Electroswitch lights), each disconnect and
grounding (maintenance or high-speed) switch, or contact position indication on the
mimic diagram. LEDs shall be visible when illuminated from a minimum of 2 meters (6
feet) away in bright sunlight. All indicating lights shall be capable of being seen without
the necessity of opening any doors on the LCC.
Control switches, fuse blocks, fuses, etc., for alternating current (ac) and dc supply to
each LCC and for each device being controlled electrically from the LCC.
A mimic diagram showing connections of all furnished equipment and showing location
of all gas zones.
An annunciator with the following alarms connected (one SEL-2523 36 point
annunciator per LCC):
Gas system alarms for each gas zone.
Circuit breaker close system discharged alarm.
Loss of dc alarm for each supply.
Loss of ac alarm for each supply.
Charging motor excessive run alarm.
All other equipment trouble alarms for the GIS bay.
The following points, as a minimum, shall be wired out to terminal blocks for connection
to SMUD’s SCADA system:
Circuit breaker position (52a and 52b).
Disconnect switch position (89a and 89b).
Ground switch position (57a and 57b).
High-speed grounding switch position (57a and 57b).
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 26 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
Interlocking status for each circuit breaker, disconnect, grounding
switch, and high-speed grounding switch.
Control switch remote-local status.
ABB Test switches shall be utilized to isolate the contacts from control switches in the
trip and close circuits of circuit breakers, disconnect switches, grounding switches, and
high-speed grounding switches.
Terminal blocks and terminations for each temperature compensated gas density relay
and/or density monitoring equipment.
Terminal blocks and terminations for electrical interlock contacts.
Terminal blocks and terminations for alarm and miscellaneous remote control circuits.
Terminal blocks and terminations for all instrument transformer leads. A lead shall be
installed and terminated for each tap of a multi-ratio current transformer and all
secondary winding taps for voltage transformers.
VSB disconnect devices in the voltage transformer wiring circuit for isolating all
ungrounded voltage transformer secondary wiring circuits (refer to Article 16878.1.13).
Terminal blocks and terminations for all required spare contacts.
Terminal blocks and terminations for the external control, instrumentation, and
protection equipment wiring of SMUD.
A total of 20 percent spare termination points per LCC.
Engraved nameplates for each device in the cabinet.
Other nameplates as discussed in IEEE Std. C37.122/IEC 62271-203 and SMUD
wiring standard SS1009.
16878.1.18 Audible Noise
All apparatus (i.e., operating mechanisms) shall operate within OSHA levels of sound generation for an
industrial area. In no case shall the apparatus exceed 65 decibels (dBA) sound levels for a time period
in excess of 5 minutes.
16878.1.19 Ladders, Platforms, Stairs, and Walkways
Safe, efficient access is required to all viewports, actuator mechanisms, switch operators, gas density
monitoring equipment, etc., for maintenance personnel. In accordance with OSHA standards,
permanent facilities shall be provided to meet this requirement. Appropriate railings and toeplates shall
be installed on all ladders, elevated platforms, and maintenance walkways. Open grating shall be
employed for all platforms and stair/ladder treads. Treads shall be painted yellow. Each structure shall
have provisions for safety grounding at two points on diametrically opposite sides.
The intent is to eliminate the need for climbing on the apparatus or for portable ladders to perform
routine operations or view routine indicating devices, switch positions (viewports), or alarms. Working
or performing routine maintenance inspections from a ladder or stairway is not acceptable. Tethering
will not be accepted as a method of compliance with OSHA fall prevention regulations.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 27 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
Each ladder, platform, stair, or walkway shall be a minimum of 800 mm (30 inches) in width, and be
clear of overhead or projecting obstructions for a minimum of 2000 mm (6 feet-6 inches). The main
operations platform or walkway shall have egress means at either end as a minimum. Each stairwell
shall have a top landing area of at least 1200 mm (48 inches) by 1200 mm (48 inches).
16878.1.20 Special Tool Requirements
The Contractor shall provide one set of special tools or devices required for installation/maintenance of
the GIS.
A removable, manual charging wrench for a spring-charged operating mechanism shall be furnished by
the Contractor.
The Contractor shall also describe the preferred type of tools (e.g., box-end wrenches, open-end, deep
socket set).
16878.1.21 Factory Testing
Factory testing of the GIS equipment shall be provided as specified in Article 16878.1.26 and
additionally as follows:
The GIS equipment shall be high voltage tested as a complete assembly (unless test
facility restrictions necessitate testing in sections). The Contractor shall include in the
proposal any restrictions on the amount of GIS equipment that can be factory tested as
an assembled unit.
SMUD shall have the right to witness factory testing.
16878.1.22 Studies
The studies shall include but not be limited to the following:
Transient/overvoltage (TRV) conditions.
Insulation coordination studies.
Ferroresonance.
GIS Resistance and Capacitance.
Grounding and bonding of the GIS and the secondary equipment.
The following are study specifics related to some of the required studies:
The Contractor shall perform insulation coordination studies as specified hereinbefore
and the supplemental requirements specified below.
The Contractor shall perform a review of the GIS design to establish if any transients
generated during a switching operation may lead to significantly elevated and
damaging voltage levels.
The Contractor shall furnish all necessary remedial measures and protective devices to
limit over voltage transients, particularly at transitions (e.g., GIS gas-to-air bushing
interface, etc.).
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 28 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
The Contractor shall provide the calculated and measured capacitance and resistance
values for each component in the GIS, including, but not limited to, the bushings, bus
runs, switches, and circuit breakers.
The Contractor shall ensure that the GIS equipment grounding is in conformance with
IEEE 80 and IEC
All studies shall be provided in formal reports forwarded to SMUD according to the
Schedule of Submittals. All documentation including, but not limited to, calculations,
curves, assumptions, graphs, computer outputs, etc., shall be provided to support the
conclusions reached.
16878.1.23 Final Exhibits
As part of the "as-built" documentation for the GIS equipment, the Contractor shall provide two full-size
copies, suitably framed, of the final overall GIS equipment gas zone diagram (GZD) for mounting in
SMUD’s GIS and/or control building. The GZD shall cover the entire GIS. All text and other information
shall be fully legible from a distance of 2 meters (6 feet away). These final GZD framed items are in
addition to the GZD plate(s) required in IEEE C37.122.
16878.1.24 Training
The Contractor shall provide the services of one or more GIS factory representative(s) fluent in oral and
written English to train SMUD’s operating and maintenance personnel. The training shall cover both
classroom theory and practical "hands-on" training. Prior to commercial operation, the Contractor shall
conduct training of SMUD’s personnel. SMUD has the need to train up to 40 operating and
maintenance personnel. There shall be 2 repeat, 1 day classroom sessions (maximum 20
persons/session) and 8 repeat, 1 day hands-on training (maximum five persons/day to train field
personnel) sessions. The hands-on training should emphasize activities that SMUD’s test and
maintenance personnel will have to perform. These are maximum numbers and may be adjusted to fit
specific training requirements.
The Contractor shall submit to SMUD in writing a detailed outline of the proposed training course
curricula for review/approval at least 60 days prior to the scheduled presentation of the training. As a
minimum, the following topics shall be included in the classroom session.
16878.1.24.1 GIS Application Theory - Overall Introduction
SF6 As An Insulating Medium.
Advantages of GIS.
Review of Similar Installations.
Ferroresonance and Voltage Transformers.
Very Fast Transient Conditions.
Testing Methods.
16878.1.24.2 Equipment Principles of Operation
Breakers.
Disconnects.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 29 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
Grounding and Grounding Switches.
Voltage and Current Transformers.
Surge Arresters.
Bus/Insulators/Particle Traps.
Gas Zones.
16878.1.24.3 Assembly
Flange Connections and Bus Plug Arrangements.
Alignment/Thermal Expansion.
Cleanliness/Particle Contamination.
16878.1.24.4 Testing
Insulation Resistance Test.
Series Resonant Tests (AC versus DC).
Breaker Tests:
Contact Resistance.
Timing.
Travel.
Partial Discharge.
SF6 Gas Sampling.
16878.1.24.5 SF6 Gas
Characteristics.
Handling and Storage Requirements.
Safety Considerations.
Arc Byproducts.
Gas Processing/Handling Equipment.
Gas Analysis.
Leak Detection.
The total number of SMUD’s training session attendees will be approximately 40 persons. The
Contractor shall supply a copy of all drawings, texts, overheads, or other instructional materials for each
individual trainee as well as additional copies for SMUD’s training usage for future in-house training.
SMUD will arrange for the classroom facilities.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 30 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
A complete understanding of the GIS equipment furnished for the project on the part of the instructor is
essential. The training shall cover the specific types of GIS equipment provided.
16878.1.25 Videos and Photographs
The Contractor shall provide videos which provide an overview of the operation and maintenance of the
GIS equipment provided for the project. The videos shall cover the safety aspects, contact relationship
observable through the view ports when the switch is open/closed, the means available to determine
the switch positions, and additional information necessary for SMUD’s operation/maintenance
personnel involved with the GIS. Three copies of each set of videos shall be furnished to SMUD.
The Contractor shall provide photographs in both hard copy and electronic format of the external GIS
apparatus configuration and the internal mechanisms or interior of each type of apparatus. The intent is
to have a ready reference in the event of an equipment problem or maintenance question. The
photographs shall be approximately ISO A4 (8-1/2 inches by 11 inches) in size, shall be in color, and
shall be taken from all four sides, top, and bottom of the equipment. Three copies shall be provided.
Where multiple pieces of the same apparatus are involved, a single set of photographs is sufficient.
Photographs shall be taken of the following, including but not limited to:
Breaker, mechanism, contacts, closing resistors, operating cabinet.
Disconnect and grounding switches, contacts, drive mechanism.
Bushings.
LCC.
Expansion joints (bellows).
GDM. For circuit breaker and other gas density monitored "zones."
Rupture disk assembly.
Voltage transformers.
Surge arresters.
Gas handling equipment.
Gas leakage detector.
CTs.
CSE enclosure.
16878.1.26 Tests
The tests shall verify that all components of the GIS perform satisfactorily, both electrically and
mechanically, at the specified ratings. The tests shall establish that production sections have been
properly assembled and that they have essentially the same characteristics as those sections subjected
to type tests.
The following type tests as specified in IEEE/IEC standards shall have been performed prior to
equipment delivery:
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 31 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
a. Impulse withstand voltage (BIL).
b. Power frequency withstand voltage.
c. Circuit breaker and disconnect switch open-gap withstand voltage.
d. Rated continuous-current carrying tests.
e. Short-time current rating test.
f.
Mechanical operation tests.
g. Pressure tests.
h. Circuit breaker tests (including short-circuit testing for the short-line fault condition).
i.
Disconnect switch tests.
j.
Instrument transformer tests.
k. Surge arrester tests.
l.
Grounding (maintenance and high-speed) switch tests.
m. Arc burn-through tests.
n. Radio interference voltage (RIV) tests.
o. Switching impulse voltage tests.
p. Degree of protection tests.
q. Temperature tests.
Routine tests shall be made in the course of component assembly and at the complete or shipping
assembly state. Tests shall include, but not be limited to, the following:
a. Circuit breaker test in accordance with IEEE C37.09/IEC 62271-100/IEC 62271203.
b. Pressure test on all individual enclosures and barrier insulators.
c. Gas tightness tests of enclosure and barrier insulators, if applicable.
d. Mechanical operation test.
e. Low voltage wiring test, including insulation tests.
f.
Voltage drop measurement of the conductor and contacts.
g. Power frequency withstand voltage.
h. Partial discharge test of insulators and/or shipping sections.
i.
Current transformer and voltage transformer tests.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 32 of 43
STG-GIS
j.
Final
01/31/2017
SMUD STATION G GIS
Surge arrester tests.
k. Functional tests on control and indication circuits.
Field tests performed and successfully completed prior to achieving the Substantial Completion by the
Contractor shall include, but not be limited to, the following:
a. Gas tightness test.
b. Operational test.
c. Gas moisture measurement.
d. Resistance test of conductor.
e. CT testing.
f.
High voltage tests.
g. Partial discharge tests.
h. Control and installation wiring checks, including insulation tests.
i.
Inductive voltage transformer tests.
j.
Capacitive coupler test, if applicable.
k. Circuit breaker contact timing travel and velocity, contact resistance, and power
factor.
l.
Disconnect and grounding switch contact resistance and proper operation.
m. GIS bus power factor.
16878.1.27 Gas Leak Detector
The Contractor shall furnish SF6 gas leak detection equipment capable of "sniffing" SF6 gas leaks in the
GIS. The leak detector shall be portable and hand-held for operation by one person.
16878.1.28 Gas Handling Equipment
The gas handling unit shall be as manufactured by Dilo.
The Contractor shall furnish a mobile SF6 gas handling unit for the recovery, storage, transportation,
conditioning, and dispensing of SF6 gas for maintenance of the GIS equipment and will remain on site
for use by SMUD and SMUD. The unit shall be capable of performing the following functions:
a. Removing SF6 gas from the GIS compartment and storing it in a storage tank or in
SF6 gas cylinders.
b. Recharging the gas compartment with the stored gas.
c. Drying, filtering and purifying of the SF6 gas.
d. Evacuating moisture and air from the gas compartment prior to refilling.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 33 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
The unit shall be capable of degassing, storing, and evacuating, as a minimum, the SF6 gas from the
largest gas compartment in the GIS, plus one half of the gas from each of the adjacent gas
compartments within 8 hours. The Contractor shall state in the proposal the amount of SF6 gas that the
unit can process as well as the time required to evacuate and fill the largest gas compartment in the
GIS.
The unit shall be designed to perform the intended functions while operating over the environmental
range of –30° C to + 40° C and as high as 100 percent humidity.
A service hose shall be provided that will enable the unit to service all the GIS components from the
maintenance aisles provided.
Electric power supply for the unit shall be 208Y/120 VAC three-phase, 60 hertz. The electrical system
shall be protected by a circuit breaker, and motor circuits shall be protected by thermal overloads of
equivalent devices.
Starting buttons and indicating lights for each major electrical system, such as the gas compressor,
vacuum pump, tank heater, etc., shall be provided on the unit control panel.
Thirty meters (30 m or 100 feet) of 600 volt power cable shall be provided on a reel mounted on the unit
for connecting the unit to a power source.
The gas handling unit shall be mobile with heavy-duty casters and allowing movement by one person.
The gas handling unit shall be usable and accessible without removing from the trailer.
The gas handling unit shall be leak tested using a helium leak detector while the system is under high
vacuum.
The gas handling unit shall be functionally tested prior to shipment to SMUD. Factory test reports shall
be forwarded to SMUD confirming the passing of all functional and other testing at the factory before
the gas handling unit is shipped.
16878.1.29 Shipment
All equipment shall be suitably packed and protected during shipment. Each shipping unit shall be
sealed in a clean, dry condition with leaktight shipping covers securely mounted for shipment. Each
shipping section shall be carefully sealed and filled with dry gas to a slightly positive pressure or sealed
in evacuated plastic with a desiccant to prevent the entrance of moisture and contamination. The
Contractor shall place temporary labels on the shipping sections stating whether the shipping sections
contain SF6 gas or another type of dry gas under pressure.
Components requiring indoor storage shall be identified. The Contractor shall provide complete,
detailed, customized instructions for the receiving, handling, storage, installation, operation, and
maintenance of the equipment.
The Contractor shall affix mechanical shock monitoring devices to each shipping section. Each monitor
shall be inspected by SMUD and Contractor's shipper/transporter at time of delivery to SMUD’s site.
The Contractor will be notified by the shipper/transporter/representative and/or SMUD if any shock
monitors indicated possible damage or if visible damage is apparent.
The Contractor shall notify and allow SMUD to inspect the equipment at the port of entry to the
destination country.
16878.1.30 Packaging
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 34 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
The size of transportation units shall be as large as possible so as to reduce the amount of field
installation work.
The type of packing used must be suitable for the means of transportation used from the manufacturer
location to the installation site.
The packing must, if required, be suitable for outdoor storage of the equipment. In this case, sufficient
drying agent shall be provided in the packing to absorb condensed moisture.
Marking of transportation containers must be approved by SMUD. Guidelines for special marking must
be followed meticulously to ensure positive identification at the jobsite.
A packing list must be provided for each individual packing unit.
All packaging shall be subject to the approval of SMUD.
16878.1.31 Spare Parts
In addition to the replacement (spare) parts identified elsewhere in these specifications or on the
drawings, the Contractor shall furnish the following parts for each item of equipment he furnishes. All
spare part shall be packed and crated separately from rest of GIS equipment and clearly marked as
spare parts.
50 percent or manufacturer recommendation replacement of fuses for each type and
size of fuse.
50 percent or manufacturer recommendation replacement of each type of lamp, bulb,
etc., for each type of indicating light and light fixture.
Gaskets (no gaskets shall be reused for any permanent seal broken or disturbed in the
field). Spare gaskets and O-rings shall be supplied in a vacuum sealed package.
Pressure relief devices (if pressure relief devices are rupture disks or other selfdestructive devices, then at least six spare disks and associated gaskets/O-rings of
each pressure rating shall be provided. Rupture disks and gaskets/O-rings shall also
be included as part of normal replacement parts stock). Gaskets/O-rings shall be
supplied in a vacuum sealed package.
Circuit breaker trip and close coils - at least two of each unique type.
16878.2 Erection, Site Testing, and Commissioning Specifications
16878.2.1 General
The Contractor shall provide the services of one (or more) factory trained personnel to perform the
erection personnel, supervise the erection of the complete GIS equipment at the site, field test the GIS
equipment after erection, and assist SMUD during energization/commissioning of the GIS facility.
The Contractor shall furnish with the proposal a complete listing of all tools, consumables,
lifting/handling equipment, etc., required for the complete assembly/erection and disassembly of the
GIS. This shall include all commonly available tools, "special" tools, and jigs necessary for equipment
alignment/erection.
The Contractor shall furnish a complete set of the "special" hand and power tools required to
completely disassemble and reassemble the complete GIS facility. These tools shall be new at the
start of installation. These tools are those that are not commonly available or are of non-standard
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 35 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
manufacture. These tools shall be furnished with the equipment and will be stored inside the GIS
Building at the site for installation/maintenance/repair purposes.
The Contractor shall include a list or description of all labor, tools, equipment, etc., required for the
receiving, unloading, handling, and erection of the GIS at the site.
16878.2.2 Equipment Erection
Erection work by the Contractor shall include receiving, unloading, storage, removal from storage,
hauling, cleaning, erection on foundations, and other work necessary to place all equipment into
successful operation.
In addition, erection work shall include complete assembly of equipment shipped unassembled;
dismantling and reassembly of equipment to make adjustments; and provisions for personnel and
equipment in testing and placing the equipment into operation.
Erection procedures not specified herein shall be in accordance with the recommendations and
drawings of the Contractor and submitted to and approved by SMUD. In general, the erection and
handling of the equipment shall consider the guidelines described in IEEE Std C37.122.1, Section 4.2.
Safe SF6 gas handling during the filling and removal of gas from the GIS shall consider the guidelines
described in IEEE Std C37.122.1, Section 4.4.
16878.2.3 Miscellaneous Material
All miscellaneous materials, except those specified to be furnished by SMUD or other Contractors, shall
be furnished as required for the complete erection of the equipment. These materials shall include, but
shall not be limited to, shims, wedges, dowels, anchors, supports, bolting, and gaskets.
16878.2.4 Equipment Protection
All equipment shall be protected from damage of any kind from the time it is unloaded until it is ready
for initial operation.
During the erection period, all equipment having drive motors or rotating parts shall be protected with a
weatherproof flame-resistant sheeting which completely covers the exposed parts of the equipment.
Sheeting shall be PYRO-KURE 613 or acceptable equal.
No welding shall be allowed on site unless for anchor welding for connecting GIS to building floor.
Equipment housed or covered with glass or equipped with easily broken components shall be
protected, as required, to prevent damage throughout the construction period.
16878.2.5 Cleaning
The exterior and interior surfaces of each equipment item shall be cleaned of sand, dirt, and other
foreign materials after removal from storage and immediately before movement to the final location.
Before initial operation of the individual items of equipment, the Contractor shall remove all dirt, mortar,
and other material which has been spilled, misplaced, or otherwise been allowed to mar the finish
surfaces. The interior of all electrical equipment, including relays and electrical contacts, shall be
thoroughly wiped and vacuumed clean before the equipment is energized. All debris shall be removed
from the site and disposed of as directed by SMUD.
16878.2.6 Maintenance Tools
All "special" tools furnished with the equipment for maintenance shall be stored as directed by SMUD.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 36 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
16878.2.7 Contractor’s Inspection and Supervision
Competent and experienced installation, commissioning, and service staff, including a minimum of one
full-time, factory-trained Contractor's supervisor, shall be present at the erection site throughout the
installation, testing, and commissioning of the equipment.
16878.2.8 Testing
The Contractor shall perform field (acceptance) testing of all of the GIS equipment installed at the
project site as part of achieving “Substantial Completion”. Final commission testing (connections to
equipment outside of GIS, e.g. control and relay panels in control building) will be performed by SMUD.
It is the intent of this specification that field testing be extensive and complete, as specified, to provide
positive assurance of totally correct installation and operation of equipment. The final acceptance tests
for the GIS shall be as approved by SMUD and shall be certified by the Contractor. SMUD will review
and approve the proposed test procedures and test results (refer to Article 16878.1.26). Testing hold
points will be established by SMUD. Continued testing beyond the hold points must be approved by
SMUD.
The following list summarizes the tests and checks that shall be performed on the GIS control system,
as a minimum, and the associated activities and/or responsibilities. All test equipment type and
manufacturer shall be approved by SMUD. These tests may need to be witnessed by SMUD and/or
SMUD while being performed. Which tests will require witnessing will be determined at a later date.
Primary Equipment Tests
AC high potential test (may include partial discharge)
Primary current injection
Gas tightness test
Moisture, purity test
Contact/connection resistance test
Switch Alignment test
Alarms for gas monitoring system
Interlocking
CT Equipment Tests
Insulation resistance test
Visual inspection of all equipment, wiring, etc.
Verification of polarity and ratio on all taps
Saturation excitation
Verification of single point grounding on CT circuits
VT Equipment Tests
Insulation resistance test
Visual inspection of all equipment, wiring, etc.
Verification of polarity and ratio on all taps
Polarity
High voltage ratio verification (if possible)
Control Cable and Secondary Wiring
Visually inspect all wiring for damage
Insulation resistance test
Continuity
Proper installation and latching of plugs
Tightness of all connections
Proper operation of any shorting devices
Primary Switches
Synchronization of all phases
Proper operation of motor-operators
Visual inspection of all equipment
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 37 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
Verify proper operation of auxiliary contacts
Contact resistance
Circuit Breakers
Verify nameplate data
Contact timing
Travel and velocity
Contact resistance
Operating mechanism alarm testing
Equipment ground verification
Verify proper operation of auxiliary contacts
Check breaker control (including, but not limited to, anti-pumping, gas tripping, etc.
Minimum DC voltage for operation
Surge Arresters (prior to installation)
Power factor testing
LCCs
Annunciator testing
Proper operation of control switches
Molded-case circuit breaker trip test
Proper operation of indicating lamps
Proper installation of fuse blocks
Tightness of all connections
Verification of proper wiring (according to drawings)
Functional testing of the overall LCC controls (including all interlocking)
Equipment ground verification
This specification includes, but is not limited to, the following:
Testing all wire, cable, electrical equipment, and systems installed or connected to the
GIS, up to and including the LCCs, to ensure proper installation, adjustment, setting,
connection, and functioning in accordance with the Contractor's and SMUD's drawings,
these specifications, and the Contractor's recommendations.
Furnishing all qualified personnel and labor required for and incidental to testing.
Furnishing all test equipment required and qualified personnel and labor, including
special equipment for testing of all protective relays, instruments, and meters furnished
with the Contractor's equipment.
This specification includes all testing required during installation and energization of GIS equipment and
Contractor-provided electrical systems.
All factory calibrated equipment (transducers, pressure switches, etc.) shall be tested to verify
calibration. The Contractor shall not modify calibration settings without agreement from SMUD. If
equipment does not meet specifications, SMUD shall be notified of the problem immediately.
The typical drawings indicating the types of systems to be tested should include one-line diagrams for
the station, "typical" ac and dc elementary diagrams, circuit lists, and other miscellaneous drawings.
These documents do not represent a complete set of drawings, but are indicative of the types of
systems to be tested.
The Contractor shall submit reports for all tests performed. The reports shall be in accordance with the
following:
Maintain a written record of all tests showing date, personnel making test, equipment or
material tests performed, and results. A copy of these reports shall be submitted to
SMUD as required by SMUD.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 38 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
Notify SMUD 2 weeks prior to commencement of all testing.
Submit two copies of final test reports, as specified.
The Contractor shall document test results as specified by SMUD. The Contractor may use standard
report forms, if approved by SMUD.
The types of tests covered by this specification shall include, but not be limited to, the following:
Insulation resistance tests of all 600 volt power and control cable with a 1000 volt
insulation resistance tester for 1 minute. Values at the end of one minute must be
1 megohm, at a minimum.
Insulation resistance tests of all instrument cable with a 500 volt insulation resistance
tester for 1 minute, including each conductor of a multiconductor cable to all other
conductors and the shield.
Values with all switchboards, panelboards, fuse holders, switches, and overcurrent
devices (fuses and/or molded case circuit breakers) in place. Do not connect motors
and transformers during the insulation resistance test. Insulation resistance tests
should be performed on wire and cable after installation, not on the cable reels.
Visually check polarity mark orientation on all CTs with respect to three-line diagrams in the
Contractor's drawings. Check all CT polarity markings.
The following CT tests shall also be performed in accordance with IEEE C57.13:
Complete testing of all CTs as follows:
Ratio CTs at all ratios.
Perform demagnetization and excitation tests on CTs.
Check excitation test data against CT excitation curves.
Insulation resistance tests on all CTs to ground.
All CTs are to remain shorted until testing procedures show the CTs are properly
loaded.
Check all voltage transformer polarity markings with a transformer turns ratio tester.
Alarm sensor tests shall be performed in accordance with the following:
Insulation resistance tests of all leads of device to case. (Consult instruction manual
for voltage level to be used to ensure no damage across open contacts.)
Induce the device to operate with the proper input medium (heat, cooling, pressure,
vacuum, voltage, current, etc.) and verify operation of the device at the correct input
medium level by monitoring the output contacts with an ohmmeter. All analog type
devices shall be checked at 0, 25, 50, 75, and 100 percent of scale.
Check each unit of annunciators by closing or opening the trouble contact and
observing operation of the control board. Check all annunciator lamps, bell and cutoff
and reset operation.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 39 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
The Contractor shall submit to SMUD a proposed plan for testing which shall show that it possesses
qualified personnel and test equipment to satisfactorily perform the testing required. All wire, cable, and
electrical equipment installed or connected by the Contractor shall be tested to ensure proper
installation, setting, connection, and functioning.
The Contractor shall furnish the services of a factory trained engineer, who is an electrical engineer,
thoroughly familiar with GIS and GIS controls who shall perform the following:
Be personally present on the jobsite during the testing of all wiring, controls, and
systems furnished, installed, or connected by the Contractor until they are all in
complete and satisfactory operation and the substation is in full operation.
Conduct and direct the complete program of testing specified herein.
Personally check all wiring installed by the Contractor for proper connection according
to the diagrams shown in the plans and connection diagrams.
Testing requirements shall include all tests recommended by the Contractor. Additional tests shall be
performed as deemed necessary by SMUD because of field conditions or to determine that equipment
material and systems meet SMUD’s requirements.
The Contractor shall be responsible for all damage to equipment or material because of improper test
procedures or test apparatus handling.
SMUD reserves the option to assign personnel to assist the Contractor in checking out certain control
schemes where SMUD concludes such assistance is necessary to meet the project schedule. If SMUD
should exercise this option, the Contractor will be notified in advance of the extent of SMUD's
involvement. SMUD will witness tests and review and approve test results.
After completing testing and checkout of equipment, wiring, control schemes, and other items
associated with individual systems, and believing a system to be ready for operation, the Contractor
shall notify SMUD, and SMUD may elect to witness a final operational test of each individual system.
After the Contractor has completed all testing and turned the systems over to SMUD, no further
modifications or testing shall be done by the Contractor without providing SMUD and SMUD with a
written plan for said modifications and testing.
It is anticipated that there will be frequent occasions when testing will have to be performed outside
regular working hours. This testing would primarily be related to work during initial energization testing
and load testing of equipment and systems. Other possible work of this nature would be under critical
situations where the safety of men or equipment and progress of the overall project work is concerned.
Connections shall not be made or testing done on existing equipment, facilities, circuits, or systems
without receiving proper authorization from SMUD. SMUD reserves the right to have personnel present
when connections are made or testing is done on any piece of equipment installed by the Contractor.
Scheduling for such work shall be through SMUD. Work may be rescheduled at SMUD's discretion.
Test procedures, equipment, temporary circuits, etc., shall be designed and utilized to minimize danger
to testing technicians and surrounding personnel, e.g., CT temporary test circuits utilizing alligator clips
will not be permitted. Safety devices such as rubber gloves and blankets shall be furnished and used.
Protective screens and barriers, yellow tape, and danger signs shall be provided to adequately protect
and warn all personnel in the vicinity of the tests.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 40 of 43
STG-GIS
Final
01/31/2017
SMUD STATION G GIS
All electrical controls shall be tested by trial operation of control equipment in the presence of SMUD
and Contractor after all wiring is completed, to verify that each interlock and control function operates
according to the Contractor's schematics and operating instructions.
The Contractor shall furnish all necessary labor, supervision, testing equipment, and tools required to
locate the cause of any malfunction and shall make the necessary corrections in wiring, equipment, or
connections furnished by the Contractor, as necessary, to obtain the intended operation.
All terminal block disconnecting links shall be tightened before testing. All control cable terminations
shall be verified and tightened before testing.
All control, interlock, etc., functions shown on the Contractor's drawings shall be tested. Any
malfunctions noted in the operations shall be recorded, and when repairs are completed, the tests shall
be repeated and the date that the scheme functioned satisfactorily and who conducted the tests shall
be recorded on the connection drawing.
The Contractor shall use the "yellow line" method of recording that functional tests have been
completed. This method requires that a yellow highlighter be used to mark those portions of the control
circuits, potential circuits, or CT strings that have been tested and are functioning correctly.
The following tests and checks shall be performed on all CT circuits:
Injection of currents at the source of each CT string and checking of the string at each
device with a clamp-on ammeter to verify that the CT strings are connected in
accordance with the drawings.
Simulation of actual load current and fault current operation of the substation electrical
systems by injecting appropriate currents in the CT strings.
Measurement and record of the burden of each connected CT.
The following tests and checks shall be performed on all potential circuits:
Pulling of fuses from voltage transformer junction boxes and application of proper
phase-to-phase and phase-to-ground voltages to the load side of the fuse blocks. A
check for proper voltages at all relays, instruments, switches, etc., to verify that the
potential circuit is connected in accordance with the drawings.
Measurement and record of the burden of each potential circuit.
16878.2.9 Commissioning
Commissioning/energization shall proceed as outlined in this section.
A commissioning/energization procedure shall be developed by the Contractor and submitted for
approval by SMUD at least 2 months prior to energization. SMUD will conduct the necessary cutover
work prior to each step. SMUD will ensure that the cutover sequence is being followed and that proper
switching and tagging procedures are being followed. All switching and tagging will be under the
control of the switching and tagging authority. The following individuals are to be present during
energization:
SMUD's Construction Manager or authorized representative(s).
SMUD or authorized representative(s).
Contractor or authorized representative(s).
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 41 of 43
STG-GIS
SMUD STATION G GIS
Final
01/31/2017
Responsibilities of those present during energization are as follows:
SMUD
Energizing or operation of equipment. Obtain and
hold work clearances on existing facilities to allow
final permanent connections to be made. SMUD
may stop work from proceeding if such work will
cause the SMUD’s electrical system to operate
unsatisfactorily or to drop load.
Ensure that the cutover sequence is followed.
Perform or witness final tests on equipment and
install final relay settings and perform final relay
testing.
Make final HV GIS connections as required for
initial energization
Be responsible for the installation of all equipment
and materials.
Perform necessary switching to energize the
station in accordance with the cutover sequence.
Contractor
Certify that equipment is ready for energization
and supply SMUD with a letter stating this
certification/guarantee.
Perform all corrective work required during initial
energization.
Ensure that the initial energization procedure is
followed
Prior to SMUD’s energization, the Contractor shall submit final as-built drawings with the field markups
incorporated and final field test reports.
The Contractor shall provide personnel during initial energization of the GIS, as required, on a 24-houra-day, 7-day-a-week basis. Contractor shall assume a minimum of 40 hours will be required for first
energization.
Following energization, partial discharge measurements shall be made by the Contractor to benchmark
the GIS equipment.
Source: 16878, (2016), v.1.0
Gas Insulated Switchgear Equipment
Page 42 of 43
STG-GIS
Source: 16878, (2016), v.1.0
SMUD STATION G GIS
Gas Insulated Switchgear Equipment
Final
01/31/2017
Page 43 of 43