1 Purpose Define and establish DeviceNet design, installation, and performance testing criteria in accordance with ODVA physical media specifications. In doing so, this document describes the bidder requirements, the basis of DeviceNet services, the services to be supplied, test equipment requirements and usage, documentation requirements, and services warranty. 2 Bidder Requirements 2.1 Technical 2.1.1 Trained Personnel Service Supplier personnel should have completed the Rockwell Automation DeviceNet Training Course, CCP163, or equivalent. The training should provide in-depth DeviceNet knowledge from a company that is a member of ODVA. 2.1.2 Experience Due to the newer technology involved with DeviceNet and the associated test equipment, Service Supplier personnel must show prior experience with DeviceNet systems installations. This prior experience should also include the testing of DeviceNet systems or equivalent network. Service Supplier personnel must show prior experience with all test equipment or equivalent, the ability to interpret the test results, and provide recommendations for any test or verification that did not meet test specification criteria. Because of the variety of tests described in this document, Service Supplier personnel ensure that each test meets all performance and safety requirements, including any applicable laws, regulations, codes and standards. 2.2 Commercial 2.2.1 Quotation Submittal Requirements (Specific requirements by issuing company) 2.2.2 (TBD by End User) (Specific requirements by issuing company) 3 Basis of DeviceNet Services 3.1 Agency Specification All tests, verifications, checks, and recommendations shall be in conformance with the ODVA specifications. ODVA specifications define electrical and mechanical parameters that are the basis for all tests and test equipment usage defined in Sections 4 & 5. 3.2 Manufacturer’s Specifications and Guidelines All tests, verifications, checks, and recommendations shall be in conformance with all applicable vendor specifications and guidelines. Manufacturers’ specifications and guidelines may define additional electrical and mechanical parameters beyond ODVA specifications, and must be included in the basis for all tests and test equipment usage defined in Sections 4 & 5. 3.3 National and International Codes and Regulations (if applicable) National and International codes deemed applicable by (customer name) may define additional electrical and mechanical parameters beyond ODVA and Manufacturer’s specifications, and must be included in the basis for all tests and test equipment usage defined in Sections 4 & 5. National and International Codes may include: • National Electric Code (NEC) • Canadian Electric Code (CeCode) • European Communities (EC) Directive • UL • CSA • JIC • Local Codes and Regulations 4 Services to be Supplied 4.1 Engineering Design Review The engineering design review consists of reviewing the network prints and the necessary information supplied by the end user and calculating and verifying the following based on the supplied information. All review data shall be supplied in a database format for (customer name) review and approval. Any design not consistent with the applicable ODVA and Manufacturer’s specifications, and National and International codes shall be noted and a recommendation for conformance shall be supplied. 4.1.1 Calculations • Maximum segment length based on media type and communication baud rate • Maximum cumulative drop line length • Network power requirements and power supply placement 4.1.2 Verifications • Multiple power supply configuration if necessary • Proper power supply cabling • Proper grounding 4.2 On-site Installation Checks (OEM/Vendor Site) The on-site installation checks include Pre-activation and Active measurements and verifications with respect to the latest ODVA DeviceNet Specification. All review data shall be supplied in a database format for (customer name) review and approval. Any test or verification that is not consistent with the applicable specifications and codes shall be noted and a recommendation for conformance shall be supplied. These tests and verifications may be repeated at the end user site, but are needed for proper network communications during the testing stage. 4.2.1 Installation Verifications • Walk-through of the network to verify all applicable specifications were followed during installation • Proper network grounding • Resistance to ground • Multiple power supply configuration • Proper power supply cabling 4.2.2 Pre-Activation Measurements • Employ time domain reflectometry techniques to electrically measure trunk lengths. • Employ time domain reflectometry techniques to identify and locate short or open conductors within the trunk. • Measure terminated resistance. • Electrically verify proper point-to-point connections of trunk line conductors and fabricated drop lines. 4.2.3 Active Network Measurements • Power supply output. • CAN H and CAN L, high and low levels. • DeviceNet signal analysis. • Common mode voltage, high, low and average. • Percentage of bus utilization • CAN Frame Errors / second • Total CAN Frame Errors • Communication Baud Rate 4.3 On-site Installation Checks (Plant Site) The on-site installation checks include Pre-activation and Active measurements and verifications with respect to the latest ODVA DeviceNet Specification. All review data shall be supplied in a database format for (customer name) review and approval. Any test or verification that is not consistent with the applicable specifications and codes shall be noted and a recommendation for conformance shall be supplied. These tests and verifications may be completed at the OEM or vendor site, but need to be repeated due to the final network installation at the end user site compared to the temporary installation during the testing stage at the OEM or vendor site. 4.3.1 Installation Verifications • Walk-through of the network to verify all applicable specifications were followed during installation • Proper network grounding • Resistance to ground • Multiple power supply configuration • Proper power supply cabling 4.3.2 Pre-Activation Measurements • Employ time domain reflectometry techniques to electrically measure trunk lengths. • Employ time domain reflectometry techniques to identify and locate short or open conductors within the trunk. • Measure terminated resistance. • Electrically verify proper point-to-point connections of trunk line conductors and fabricated drop lines. 4.3.3 Active Networks Measurements • Power supply output. • CAN H and CAN L, high and low levels. • DeviceNet signal analysis. • Common mode voltage, high, low and average. • Percentage of bus utilization • CAN Frame Errors / second • Total CAN Frame Errors • Communication Baud Rate 5 Test Equipment Usage and Equipment Specifications The following is a list of test equipment along with their specifications to be used during testing. NOTE: All test equipment must have current proof of calibration from the equipment manufacturer or approved service supplier. 5.1 Oscilloscope • Bandwidth 200MHz • Real Time Sample Rate 2.5 Gigasamples per second • Inputs 2 plus external, Independently floating • Input Isolation 1000V between inputs, references and ground. • Timebase Range 5 ns – 2 min / division • Input Sensitivity 5 mV – 100 V / division • Trigger Types Free run, single, edge, delay, pulse width & external. • Glitch Capture 50 ns • True RMS Multimeter 5000 counts, volts, amps, ohms, continuity, & diode. • PC & Printer Interface Optically isolated • Safety Certified 1000V CAT II / 600V CAT III 5.2 DeviceNet Active Network Test Device 5.3 Rockwell Automation 1788-MCHKR MediaChecker Media Test Device (or equivalent) 5.4 Test Cable for Calibration of the 1788-MCHKR MediaChecker (or equivalent) • Detect and edit network node configurations • Display High, Low & Average Network supply and CAN bus voltages • Report CAN errors per second and total CAN errors detected • Log CAN frame errors detected for each node • Detect % Traffic Load on the network • Scan & report node object data • Cable specific programmability • Multi conductor cable test capability • Measure trunk length • Detect and locate opens, shorts and miswires along trunk During installation, a 100-foot (minimum) sample of the installed cable shall be set aside for calibrating the MediaChecker to ensure maximum accuracy of length measurements. Calibrating with cables longer than 100ft will improve the accuracy of length measurements. The MediaChecker is calibrated at the factory to provide length measurements that are accurate enough for most applications, but cables from different batches or manufacturers can have characteristic variances of up to 20 %, causing deviations in length measurements. To ensure maximum accuracy of length measurements, calibrate the MediaChecker to a known length of the cable to be tested. 6 Documentation Requirements 6.1 Report Content The following summarizes the requirements of the final report content. This will include an executive summary that summarizes the results and provides recommendations to ensure proper network operation, or approves the installation with no recommendations. The final report should also include all test results in a database format that is widely known (MS EXCEL or equivalent) and which the end user has the ability to access, process, analyze, share, and display the information. • Executive Summary and detailed test results. A network identifier specific to each network Total network node count Total network power tap count Network media type Network baud rate Network calculated maximum length Network maximum cumulative drop length Network trunkline miswires if applicable Network trunkline measured length Network terminated measured resistance Network measured resistance to ground Network power supply cable diameter and length Network power supply output measurement Network common mode voltage measurement CAN H and CAN L measurements Ground loop verification Network Load percentage Network error count Network errors/second count Signal waveform samples with analysis (see detail below) Documented exceptions to the installation specifications in detail. This should include exceptions that were fixed and exceptions that are still open issues. Documented open issues with recommendations and risk analysis. 6.2 Signal Waveform Analysis with Respect to Agency and Mfg Specs The signal waveform analysis section will include captures of packets using the Scopemeter. These will then be analyzed for any network installation problems.