Electro Industries / GAUGETECH EIG DNP 3.0 Protocol Assignments for Futura+ and DM Series Power Monitors Release Date: March 27, 2000 Version 1.10/03-2000 Electro Industries/Gaugetech assumes no responsibility for any inaccuracies and/or errors that may appear in this document. The information printed in this document is subject to change without notice and should not be construed as commitment by Electro Industries/Gaugetech E.I. Electronics, Inc. All comments pertaining to this document should be forwarded to: Attn: Engineering Dept. - DNP Object Mappings Electro Industries/Gaugetech 1800 Shames Drive Westbury, New York 11590 Tel: (516) 334-0870 Fax; (516) 338-4741 DNP is a trademark of the DNP Users Group. Copyright © 2000 E.I. Electronics, Inc. Electro Industries/Gaugetech. All rights reserved. Printed in the U.S.A. Electro Industries / GAUGETECH Table of Contents 1. DNP IMPLEMENTATION ................................................................................................................ 1 1.1 PHYSICAL LAYER ............................................................................................................................... 1 1.1.1 RS-232C ....................................................................................................................................... 1 1.1.2 RS-485 .......................................................................................................................................... 1 1.1.3 Communication Parameters .......................................................................................................... 1 1.1.4 Baud Rates.................................................................................................................................... 1 1.2 DATA LINK LAYER ............................................................................................................................. 2 1.2.1 Length Field / Buffer Size ............................................................................................................ 2 1.2.2 Control Field................................................................................................................................. 2 1.2.2.1 Control Bits ......................................................................................................................... 2 1.2.2.2 Function Codes ................................................................................................................... 2 1.2.2.2.1 Reset of Data Link ( Function 0 ) ................................................................................... 2 1.2.2.2.2 User Data ( Function 3 ) ................................................................................................. 2 1.2.2.2.3 Unconfirmed User Data ( Function 4 ) .......................................................................... 2 1.2.3 Address ......................................................................................................................................... 2 1.3 TRANSPORT LAYER ............................................................................................................................ 3 1.3.1 Transport Header .......................................................................................................................... 3 1.4 APPLICATION LAYER .......................................................................................................................... 4 1.4.1 Application Headers ..................................................................................................................... 4 1.4.1.1 Application Control Field ................................................................................................... 4 1.4.1.2 Function Codes ................................................................................................................... 4 1.4.1.2.1 Read ( Function 1 ) ......................................................................................................... 4 1.4.1.2.2 Write ( Function 2 ) ........................................................................................................ 4 1.4.1.2.3 Select ( Function 3 ) ....................................................................................................... 4 1.4.1.2.4 Operate ( Function 4 ) .................................................................................................... 4 1.4.1.2.5 Direct Operate ( Function 5 ) ......................................................................................... 4 1.4.1.2.6 Direct Operate - No Acknowledgment ( Function 6 ) .................................................... 5 1.4.1.2.7 Response ( Function 129 ) .............................................................................................. 5 1.4.2 Application Data ........................................................................................................................... 5 1.4.2.1 Object and Variation ........................................................................................................... 5 1.4.2.1.1 Binary Input Status ( Obj. 1, Var. 2 ) ............................................................................. 6 1.4.2.1.1.1 Digital Inputs ( Points 0-3 ) .................................................................................... 6 1.4.2.1.2 Binary Output Status ( Obj. 10, Var. 2 ) ......................................................................... 7 1.4.2.1.2.1 Energy Reset State ( Point 0 ) ................................................................................. 7 1.4.2.1.2.2 Demand Reset State ( Point 1 ) ............................................................................... 7 1.4.2.1.2.3 Relay States ( Points 2-4 )....................................................................................... 7 1.4.2.1.3 Control Relay Output Block ( Obj. 12, Var. 1 ) ............................................................. 8 1.4.2.1.3.1 Energy Reset ( Point 0 ) .......................................................................................... 8 1.4.2.1.3.2 Demand Reset ( Point 1 ) ........................................................................................ 8 1.4.2.1.4 32-Bit Binary Counter Without Flag ( Obj. 20, Var. 5 ) ................................................ 9 1.4.2.1.4.1 Hour Readings ( Point 0 - 3 ) .................................................................................. 9 1.4.2.1.5 16-Bit Analog Input Without Flag ( Obj. 30, Var. 4 ) .................................................. 10 1.4.2.1.5.1 Health Check ( Point 0 ) ....................................................................................... 10 1.4.2.1.5.2 Phase Current ( Point 1 - 3 ) ................................................................................. 10 1.4.2.1.5.3 Phase-to-Neutral Voltage ( Point 4 - 6 ) ............................................................... 10 1.4.2.1.5.4 Total Power ( Point 7 - 8 ) .................................................................................... 11 1.4.2.1.5.5 Phase Power ( Point 9 - 14 ) ................................................................................. 11 1.4.2.1.5.6 CT & PT Ratios ( Point-15 - 18 ) ......................................................................... 11 1.4.2.1.5.7 Neutral Current ( Point 19 ) .................................................................................. 11 1.4.2.1.5.8 Frequency ( Point 20 ) .......................................................................................... 12 1.4.2.1.5.9 VA, Phase and Total ( Point 21 - 24 )................................................................... 12 Electro Industries / GAUGETECH DNP Implementation 1.4.2.1.5.10 Power Factor, Phase and Total ( Point 25 - 28 ) ................................................. 12 1.4.2.1.5.11 Phase-to-Phase Voltage ( Point 29 - 31 ) ............................................................ 12 1.4.2.1.6 Time & Date ( Obj. 50, Var. 1 ) ................................................................................... 13 1.4.2.1.6.1 Current Time ( Point 0 )........................................................................................ 13 1.4.2.1.6.2 Mass Memory Storage Timestamp ( Point 1 - 3 ) ................................................. 13 1.4.2.1.7 Class 0 Data ( Obj. 60, Var. 1 ) .................................................................................... 14 1.4.2.1.8 Internal Indications ( Obj. 80, Var. 1 ) ......................................................................... 15 1.4.2.1.8.1 Device Restart ( Point 7 )...................................................................................... 15 1.4.2.1.9 Short Floating Point ( Obj. 100, Var. 1 ) ...................................................................... 16 1.4.2.1.9.1 Floating Point Units Field ..................................................................................... 16 1.4.2.1.9.2 Instantaneous, Average, Maximum and Minimum ( Point 0 - 203 ) ..................... 16 1.4.2.1.9.3 Harmonics Percentage and Phase ( Point 204 - 587 ) ........................................... 17 1.4.2.1.10 Large-Packed Binary Coded Decimal ( Obj. 101, Var. 3 ) ......................................... 19 1.4.2.1.10.1 Hour Readings ( Point 0 - 4 ) .............................................................................. 19 1.4.2.1.10.2 Action Object ( Point 5 )..................................................................................... 19 1.4.2.1.10.2.1 Switch to EI Protocol ( Value 1 ) ................................................................ 19 1.4.2.2 Qualifier and Range .......................................................................................................... 20 APPENDIX A : ANALOG INPUT SECONDARY TO PRIMARY CONVERSION ............................ 21 CONVERING FRACTIONAL TO SECONDARY ...................................................................................... 21 Example 1 ................................................................................................................................................. 21 CT AND PT RATIOS .................................................................................................................................. 22 Example 2 ................................................................................................................................................. 22 CONVERTING FRACTIONAL TO PRIMARY .......................................................................................... 23 Example 3 ................................................................................................................................................. 23 Example 4 ................................................................................................................................................. 23 APPENDIX B : ANALOG INPUT SCALING FOR ALTERNATE BACK MODULES ..................... 24 STANDARD BACK MODULE (120 V) ............................................................................................................... 24 Electro Industries / GAUGETECH ii DNP Implementation Electro Industries / 1. GAUGETECH DNP Implementation 1.1 PHYSICAL LAYER Electro Industries meters are capable OF using either RS-232C or RS-485 as the physical layer. This is supplied through the use of the appropriate optional communication module, which can be ordered with the meter or separately. 1.1.1 RS-232C RS-232C is used for point-to-point communication only. Electro Industries meters are DCE devices; they transmit on Pin 2 and receive on Pin 3. To connect to a DTE device, like the COM port of a computer, a direct connection cable may be used. To connect to another DCE, a Null Modem cable ( one which flips pins 2 and pin 3 ) must be used. 1.1.2 RS-485 RS-485 provides multi-drop network communication capabilities. Multiple meters may be placed on the same bus, allowing for a Master device to communicate with any of the other devices. Appropriate network configuration and termination should be evaluated for each installation to insure optimal performance. 1.1.3 Communication Parameters Electro Industries meters communicate in DNP 3.0 using the following communication settings: 8 Data Bits No Parity 1 Stop Bit 1.1.4 Baud Rates Electro Industries meters are programmable to use several standard baud rates, including: 1200 Baud 2400 Baud 4800 Baud 9600 Baud Electro Industries / GAUGETECH DNP Implementation 1.2 DATA LINK LAYER The Data Link Layer as implemented on Electro Industries meters is subject to the following considerations. 1.2.1 Length Field / Buffer Size The internal buffers are limited to 256 bytes. After removing checksums and the headers for the Data Link, Transport and Application Layers, this leaves 212 bytes for application data. Thus, the largest Length allowable is 222 ( 0xDE ). Messages should be constructed with this limitation in mind. 1.2.2 Control Field The Control byte contains several bits and a Function Code, Specific notes follow. 1.2.2.1 Control Bits Communication directed to the meter should be Primary Master messages ( DIR = 1, PRM = 1 ). Response will be primary Non-Master messages (DIR = 0, PRM = 1). Acknowledgment will be Secondary Non-Master messages ( DIR = 0, PRM = 0 ). 1.2.2.2 Function Codes Electro Industries meters support all of the Function Codes for DNP 3.0. Specific notes follow. 1.2.2.2.1 Reset of Data Link ( Function 0 ) Before confirmed communication with a master device, the Data Link Layer must be reset. This is necessary after a meter has been restarted, either by applying power to the meter or reprogramming the meter. The meter must receive a RESET command before confirmed communication may take place. Unconfirmed communication is always possible and does not require a RESET. 1.2.2.2.2 User Data ( Function 3 ) After receiving a request for USER DATA, the meter will generate a Data Link CONFIRMATION, signaling the reception of that request, before the actual request is processed. If a response is required, it will also be sent as UNCONFIRMED USER DATA. 1.2.2.2.3 Unconfirmed User Data ( Function 4 ) After receiving a request for UNCONFIRMED USER DATA, if a response is required, it will be sent as UNCONFIRMED USER DATA. 1.2.3 Address DNP 3.0 allows for addresses from 0 - 65534 ( 0x0000 - 0xFFFE ) for individual device identification, with the address 65535 ( 0xFFFF ) defined as an all stations address. Electro Industries meters’ addresses are programmable from 0 - 9999 ( 0x0000 - 0x270F ), and will recognize address 65535 ( 0xFFFF ) as the all stations address. Electro Industries / GAUGETECH 2 DNP Implementation 1.3 TRANSPORT LAYER The Transport Layer as implemented on Electro Industries meters is subject to the following considerations. 1.3.1 Transport Header Multiple-frame messages are not allowed for Electro Industries meters. Each Transport Header should indicate it is both the first frame ( FIR = 1 ) as well as the final frame ( FIN = 1 ). Electro Industries / GAUGETECH 3 DNP Implementation 1.4 APPLICATION LAYER The Application Layer contains a header ( Request or Response Header, depending on direction ) and data. Specific notes follow. 1.4.1 Application Headers Application Headers contain the Application Control Field and the Function Code. 1.4.1.1 Application Control Field Multiple-fragment messages are not allowed for Electro Industries meters. Each Application Header should indicate it is both the first fragment ( FIR = 1 ) as well as the final fragment ( FIN = 1 ). Application-Level confirmation is not used for Electro Industries meters. 1.4.1.2 Function Codes The following Function codes are implemented on Electro Industries meters. 1.4.1.2.1 Read ( Function 1 ) Objects supporting the READ function are: Binary Inputs (Object 1) Binary Outputs ( Object 10 ) Counters ( Object 20 ) Analog Inputs ( Object 30 ) Time & Date ( Object 50 ) Class ( Object 60 ) Floating Point ( Object 100 ) Packed BCD ( Object 101 ) These Objects may be read either by requesting a specific Variation available as listed in this document, or by requesting Variation 0. READ request for Variation 0 of an Object will be fulfilled with the Variation listed in this document. 1.4.1.2.2 Write ( Function 2 ) Objects supporting the WRITE function are: Internal Indications ( Object 80 ) Packed BCD ( Object 101 ) 1.4.1.2.3 Select ( Function 3 ) Objects supporting the SELECT function are: Control Relay Output Block ( Object 12 ) Use of this function starts a 1 second timer for a legal use of the Operate ( Function 4 ) function. 1.4.1.2.4 Operate ( Function 4 ) Objects supporting the OPERATE function are: Control Relay Output Block ( Object 12 ) Use of this function can legally be performed only within 1 second of reception of the appropriate Select ( Function 3 ) function. 1.4.1.2.5 Direct Operate ( Function 5 ) Objects supporting the DIRECT OPERATE function are: Control Relay Output Block ( Object 12 ) Electro Industries / GAUGETECH 4 DNP Implementation 1.4.1.2.6 Direct Operate - No Acknowledgment ( Function 6 ) Objects supporting the DIRECT OPERATE - NO ACKNOWLEDGMENT function are: Control Relay Output Block ( Object 12 ) 1.4.1.2.7 Response ( Function 129 ) Application responses from Electro Industries meters use the RESPONSE function. 1.4.2 Application Data Application Data contains information about the Object and Variation, as well as the Qualifier and Range. 1.4.2.1 Object and Variation The following Objects and Variations are supported on Electro Industries meters. Binary Input Status (Object 1, Variation 2) † Binary Output Status ( Object 10, Variation 2) † Control Relay Output Block ( Object 12, Variation 1 ) 32-Bit Binary Counter Without Flag ( Object 20, Variation 5 ) † 16-Bit Analog Input Without Flag ( Object 30, Variation 4 ) † Time & Date ( Object 50, Variation 1 ) † Class 0 Data ( Object 60, Variation 1 ) † Internal Indications ( Object 80, Variation 1 ) Short Floating Point ( Object 100, Variation 1 ) † Large-Packed Binary Coded Decimal ( Object 101, Variation 3 ) † † READ requests for Variation 0 will be honored with the above Variations. Electro Industries / GAUGETECH 5 DNP Implementation 1.4.2.1.1 Binary Input Status ( Obj. 1, Var. 2 ) Binary Input Statuses support the following functions: Read ( Function 1 ) A READ request for Variation 0 will be responded to with Variation 2. Binary Input Statuses may be indexed with Qualifier Codes 0, 1, 2 or 6. Binary Input Statuses are used to communicate the following data measured by Electro Industries meters: Digital Inputs 1.4.2.1.1.1 Digital Inputs ( Points 0-3 ) Some Electro Industries meters are optionally capable of monitoring digital inputs. Binary Input Status points report the state of these inputs. If the feature is not present on this device, the point is reported as being off-line. If the feature is present, the point is reported as being on line. Electro Industries / GAUGETECH 6 DNP Implementation 1.4.2.1.2 Binary Output Status ( Obj. 10, Var. 2 ) Binary Output Statuses support the following functions: Read ( Function 1 ) A READ request for Variation 0 will be responded to with Variation 2. Binary Output Statuses may be indexed with Qualifier Codes 0, 1, 2 or 6. Binary Output Statuses are used to communicate the following data measured by Electro Industries meters: Energy Reset State Demand Reset State Relay States 1.4.2.1.2.1 Energy Reset State ( Point 0 ) Electro Industries meters accumulate power generated or consumed over time as Hour Readings, which measure positive VA Hours and positive and negative W Hours and VAR Hours. These readings may be reset using a Control Relay Output Block object ( Obj 12 ). This Binary Output Status point reports whether the Energy Readings are in the process of being reset, or if they are accumulating. Normally, readings are being accumulated and the state of this point is read as ‘0’. If the readings are in the process of being reset, the state of this point is read as ‘1’. 1.4.2.1.2.2 Demand Reset State ( Point 1 ) Electro Industries meters maintain maximum readings on most paramters. These readings may be reset using a Control Relay Output Block object ( Obj 12 ). This Binary Output Status point reports whether the Demand Readings are in the process of being reset, or if they are active. Normally, maximums are being monitored and the state of this point is read as ‘0’. If the readings are in the process of being reset, the state of this point is read as ‘1’. 1.4.2.1.2.3 Relay States ( Points 2-4 ) Some Electro Industries meters are optionally capable of producing digital outputs using relays. These Binary Output Status points report the state of these relays. If the feature is not present on this device, the point is reported as being off-line. If the feature is present, the point is reported as being on line. A reading of ‘1’ equals Open, or de-energized. A reading of ‘0’ equals Closed, or energized. Electro Industries / GAUGETECH 7 DNP Implementation 1.4.2.1.3 Control Relay Output Block ( Obj. 12, Var. 1 ) Control Relay Output Blocks support the following functions: Select ( Function 3 ) Operate ( Function 4 ) Direct Operate ( Function 5 ) Direct Operate - No Acknowledgment ( Function 6 ) Control Relay Output Blocks may be indexed with Qualifier Codes 7, 8 or 9 when used with the Select ( Function 3 ) and Operate ( Function 4 ) functions. Control Relay Output Blocks may be indexed with Qualifier Codes 0, 1 or 2 when used with the Direct Operate ( Function 5 ) and Direct Operate No Acknowledge ( Function 6 ) functions. Control Relay Output Blocks are used for the following purposes: Energy Reset Demand Reset 1.4.2.1.3.1 Energy Reset ( Point 0 ) Electro Industries meters accumulate power generated or consumed over time as Hour Readings, which measure positive VA Hours and positive and negative W Hours and VAR Hours. These readings may be reset using Point 0. Use of the SELECT ( Function 3 ) and OPERATE ( Function 4 ) functions will operate using any settings for the parameters of Control Code, Count, On Time, Off Time and Status. Use of the DIRECT OPERATE ( Function 5 ) or DIRECT OPERATE - NO ACKNOWLEDGE ( Function 6 ) functions will operate only with the settings of Pulsed ON ( Code = 1 of Control Code Field) once ( Count = 0x01 ) for ON 1 millisecond and OFF 0 milliseconds. 1.4.2.1.3.2 Demand Reset ( Point 1 ) Electro Industries meters maintain maximum readings on most paramters. These readings may be reset using Point 1. Use of the SELECT ( Function 3 ) and OPERATE ( Function 4 ) functions will operate using any settings for the parameters of Control Code, Count, On Time, Off Time and Status. Use of the DIRECT OPERATE ( Function 5 ) or DIRECT OPERATE - NO ACKNOWLEDGE ( Function 6 ) functions will operate only with the settings of Pulsed ON ( Code = 1 of Control Code Field) once ( Count = 0x01 ) for ON 1 millisecond and OFF 0 milliseconds. Electro Industries / GAUGETECH 8 DNP Implementation 1.4.2.1.4 32-Bit Binary Counter Without Flag ( Obj. 20, Var. 5 ) Counters support the following functions: Read ( Function 1 ) A READ request for Variation 0 will be responded to with Variation 5. Counters may be indexed with Qualifiers Codes 0, 1, 2 or 6. Counters are used to communicate the following data measured by Electro Industries meters: Hour Readings 1.4.2.1.4.1 Hour Readings ( Point 0 - 3 ) Point Readings Unit 0 +kW Hour kWH 1 -kW Hour kWH 2 +kVAR Hour kVARH 3 -kVAR Hour kVARH These readings may be cleared by using the Control Relay Output Block. Electro Industries / GAUGETECH 9 DNP Implementation 1.4.2.1.5 16-Bit Analog Input Without Flag ( Obj. 30, Var. 4 ) Analog Inputs support the following functions: Read ( Function 1 ) A READ request for Variation 0 will be responded to with Variation 4. Analog Inputs may be indexed with Qualifier Codes 0, 1, 2 or 6. Analog Inputs are used to communicate the following data measured by Electro Industries meters: Health Check Phase Current Phase-to-Neutral Voltage Total Power Phase Power CT & PT Ratios Neutral Current Frequency VA, Phase and Total Power Factor, Phase and Total Phase-to-Phase Voltage 1.4.2.1.5.1 Health Check ( Point 0 ) The Health Check point is used to indicate problems detected by the meter. A value of zero ( 0x0000 ) indicates the meter does not detect a problem. Non-zero values indicate a detected anomaly. 1.4.2.1.5.2 Phase Current ( Point 1 - 3 ) Point Reading 1 Phase A Current 2 Phase B Current 3 Phase C Current These points are formatted as 2’s compliment fractions. They represent a fraction of a 10 A Secondary input. Inputs of above 10 A Secondary will be pinned at 10 A Secondary. For a further explanation of the format of these readings, see Appendix A. 1.4.2.1.5.3 Phase-to-Neutral Voltage ( Point 4 - 6 ) Point Reading 4 Phase AN Voltage 5 Phase BN Voltage 6 Phase CN Voltage These points are formatted as 2’s compliment fractions. For a standard back meter, they represent a fraction of a 150 V Secondary input. Inputs of above 150 V Secondary will be pinned at 150 V Secondary. For a further explanation of the format of these readings, see Appendix A. For units with back modules other than the standard back module, (G or 300 V, or L or 75 V), see Appendix B. Electro Industries / GAUGETECH 10 DNP Implementation 1.4.2.1.5.4 Total Power ( Point 7 - 8 ) Point Reading 7 Total Watt 8 Total VAR These points are formatted as 2’s compliment fractions. For a standard back meter, they represent a fraction of 4500 W Secondary in normal operation, or 3000 W Secondary in Open Delta operation. Inputs above/below +/-4500 or +/-3000 W Secondary will be pinned at +/-4500 or +/-3000 W Secondary, respectively. For a further explanation of the format of these readings, see Appendix A. For units with back modules other than the standard back module, (G or 300 V, or L or 75 V), see Appendix B. 1.4.2.1.5.5 Phase Power ( Point 9 - 14 ) Point Reading 9 Phase A Watt 10 Phase B Watt 11 Phase C Watt 12 Phase A VAR 13 Phase B VAR 14 Phase C VAR These points are formatted as 2’s compliment fractions. For a standard back meter, they represent a fraction of 1500 W Secondary. Inputs above/below +/-1500 W Secondary will be pinned at +/-1500 W Secondary. When in Open Delta operation, these points are always zero. For a further explanation of the format of these readings, see Appendix A. For units with back modules other than the standard back module, (G or 300 V, or L or 75 V), see Appendix B. 1.4.2.1.5.6 CT & PT Ratios ( Point-15 - 18 ) Point Value 15 CT Ratio Numerator 16 CT Ratio Denominator 17 PT Ratio Numerator 18 PT Ratio Denominator These points are formatted as 2’s compliment integers. They can be used to convert from units in terms of the Secondary of a CT or PT into units in terms of the Primary of a CT or PT. The ratio of Numerator divided by Denominator is the ratio of Primary to Secondary. Electro Industries meters typically use Full Scales relating Primary Current to 5 Amps and Primary Voltage to 120 V. However, these Full scales can range from mA’s to thousands of kA’s, or mV’s to thousands of kV’s. The following rules apply: Full Scales containing fractions of Amps or Volts are truncated before being represented. Full Scales below 32,767 A : 5 A or 32,767 V : 120 V will be represented exactly, in that format. ( Ex. 14.40 kV : 120 V ( 120 : 1 ) would be represented as PT Ratio Numerator = 14,400 ( 0x3840 ), PT Ratio Denominator = 120 ( 0x0078 ) ) Full Scales above 32,767 A : 5 A or 32, 767 V : 120 V get represented as a Primary in terms of a Secondary which is a power of 2. This may produce a ratio that is not exact. ( Ex. 50 kA : 5 A ( 10,000 : 1 ) would be represented as CT Ratio Numerator = 20,000 ( 0x4E20 ), CT Ratio Denominator = 2 ( 0x0002 ) ) Full Scales which are above 32,767 A : 1 A or 32,767 V : 1 V get pinned at 32,767 A : 1 A or 32,767 V : 1 V 1.4.2.1.5.7 Neutral Current ( Point 19 ) This point is formatted as a 2’s compliment fraction. It represents a fraction of 15 A Secondary. Inputs above 15 A Secondary will be pinned at 15 A Secondary. When in Open Delta operation, this point is always zero. For a further explanation of the format of these readings, see Appendix A. Electro Industries / GAUGETECH 11 DNP Implementation 1.4.2.1.5.8 Frequency ( Point 20 ) This point is formatted as a 2’s compliment integer. It represents the Frequency as measured on Phase A Voltage in units of cHz ( centiHertz, 1/100 Hz ). Inputs below 45.00 Hz are pinned at 0 ( 0x0000 ), while inputs above 75.00 Hz are pinned at 9999 ( 0x270F ). 1.4.2.1.5.9 VA, Phase and Total ( Point 21 - 24 ) Point Reading 21 Phase A VA 22 Phase B VA 23 Phase C VA 24 Total VA These points are formatted as 2’s compliment fractions. Points 21-23 represent a fraction of 1500 W Secondary. Inputs above/below +/-1500 w Secondary will be pinned at +/-1500 W Secondary. When in Open Delta, points 21-23 are always zero. Point 24 represents a fraction of 4500 W Secondary in normal operation, or 3000 W Secondary in Open Delta operation. Inputs above/below +/-4500 or +/-3000 W Secondary will be pinned at +/-4500 or +/-3000 W Secondary, respectively. For a further explanation of the format of these readings, see Appendix A. For units with back modules other than the standard back module, (G or 300 V, or L or 75 V), see Appendix B. 1.4.2.1.5.10 Power Factor, Phase and Total ( Point 25 - 28 ) Point Reading 25 Phase A Power Factor 26 Phase B Power Factor 27 Phase C Power Factor 28 Total Power Factor These points are formatted as 2’s compliment integers. They represent Power Factors from –1.000 ( 0x0FC18 ) to +1.000 ( 0x003E8 ). When in Open Delta operation, Phase Power Factor ( Points 25-27 ) are always zero. 1.4.2.1.5.11 Phase-to-Phase Voltage ( Point 29 - 31 ) Point Reading 29 Phase AB Voltage 30 Phase BC Voltage 31 Phase CA Voltage These points are formatted as 2’s compliment fractions. For a standard back meter, they represent a fraction of a 300 V Secondary input. Inputs of above 300 V Secondary will be pinned at 300 V Secondary. For a further explanation of the format of these readings, see Appendix A. For units with back modules other than the standard back module, (G or 300 V, or L or 75 V), see Appendix B. Electro Industries / GAUGETECH 12 DNP Implementation 1.4.2.1.6 Time & Date ( Obj. 50, Var. 1 ) Time & Dates support the following functions: Read ( Function 1 ) A READ request for Variation 0 will be responded to with Variation 1. Time & Dates may be indexed by Qualifier Codes 0, 1, 2 or 6. Time & Dates are used to report the following information stored in an Electro Industries meter: Current Time Time of most recently stored Snapshot, Event and Waveform Meters that do not have real-time capability do not support the Time & Date Object. 1.4.2.1.6.1 Current Time ( Point 0 ) Meters that have real-time capability use this point to report the Current Time. Meters that could have real-time capability, but do not have it installed, return the default time of midnight, January 1, 1970. 1.4.2.1.6.2 Mass Memory Storage Timestamp ( Point 1 - 3 ) Point Reading 1 Most Recent Snapshot 2 Most Recent Event 3 Most Recent Waveform Meters that have Mass Memory capability use these points to report the time of the most recent Snapshot, Event and Waveform. Should a log be empty or not present on a particular meter, it will return the default time of midnight, January 1, 1970. Electro Industries / GAUGETECH 13 DNP Implementation 1.4.2.1.7 Class 0 Data ( Obj. 60, Var. 1 ) Class Data support the following functions: Read ( Function 1 ) A request for Class 0 Data from an Electro Industries meter will return four Object Headers. Specifically, it will return 16-Bit Analog Input Without Flags ( Object 30, Variation 4 ), Points 0 - 31, followed by 32-Bit Counters Without Flags ( Object 20, Variation 5 ), Points 0 – 3, followed by Binary Output Status ( Object 10, Variation 2 ), Points 0-4, followed by Binary Input Status ( Object 1, Variation 2), Points 0-3. A request for Object 60, Variation 0 will be treated as a request for Class 0 Data. Class Data may be indexed with Qualifier Code 6. Electro Industries / GAUGETECH 14 DNP Implementation 1.4.2.1.8 Internal Indications ( Obj. 80, Var. 1 ) Internal Indications support the following functions: Write ( Function 2 ) Internal Indications may be indexed by Qualifier Codes 0, 1, or 2. 1.4.2.1.8.1 Device Restart ( Point 7 ) This bit is set whenever the meter has reset. The polling device may clear this bit by Writing ( Function 2 ) to Object 80, Point 7. Electro Industries / GAUGETECH 15 DNP Implementation 1.4.2.1.9 Short Floating Point ( Obj. 100, Var. 1 ) Floating Points support the following functions: Read ( Function 1 ) A READ request for Variation 0 will be responded to with Variation 1. Floating Points may be indexed with Qualifier Code 0, 1, 0r 2. Floating Points are used to communicate the following data measured by Electro Industries meters: Instantaneous, Average, Maximum and Minimum Readings Harmonics Percentages and Phases Floating Point representation of these quantities allows for transfer of values without overrange worries. For example, with appropriate programming, Electro Industries meters can display Power readings down to 1 W Primary and up to 9,999 MW Primary, signed positive or negative. This is a range of +/-10 billion values. 16- and 32-Bit Integer representations possess ranges of +/-32,767 and +/-2,147,483,648 values, respectively. Either they will produce over/under range situations, or will require the use of multiple Object Points, either for extending their bit-range by concatenation or for scaling, by multiplication. Short Floating Point, which complies with the IEEE-754 standard for floating-point number representation, possesses a range greater than +/-1038. This range allows for a consistent representation using a single Object Point of all readings. 1.4.2.1.9.1 Floating Point Units Field The following values are used in the Units Field of Short Floating Point objects: Unit Field Value Engineering Units 2 Volts RMS ( VRMS ) 3 Amperes RMS ( ARMS ) 4 kiloWatts ( kW ) 5 kiloVA ( kVA ) 6 kiloVAR ( kVAR ) 9 Power Factor 10 Frequency ( Hz, cycles/second ) 123 † % Total Harmonic Distortion ( % ) 124 † Harmonics Magnitude ( % ) 125 † Harmonics Phase ( , degrees ) 126 † K-Factor 127 † Reserved † Values of 123 - 127 are not defined in DNP 3.0, and have been given the above meanings. 1.4.2.1.9.2 Instantaneous, Average, Maximum and Minimum ( Point 0 - 203 ) Readings Inst. Point Ave. Point +Max Point +Min Point Phase AN Volt † Phase BN Volt † Phase CN Volt † Phase AB Volt Phase BC Volt Phase CA Volt Phase A Current Phase B Current Phase C Current Phase N Current † Total Watt 0 1 2 3 4 5 6 7 8 9 10 45 46 47 48 49 50 51 52 53 54 55 90 91 92 93 94 95 96 97 98 99 100 135 136 137 138 139 140 141 142 143 144 145 Electro Industries / GAUGETECH -Max Point -Min Point 180 192 Unit Field 2 2 2 2 2 2 3 3 3 3 4 16 DNP Implementation Total VAR Total VA Total PF Total Freq Phase A Watt † Phase B Watt † Phase C Watt † Phase A VAR † Phase B VAR † Phase C VAR † Phase A VA † Phase B VA † Phase C VA † Phase A PF † Phase B PF † Phase C PF † AN Volt THD †‡ BN Volt THD †‡ CN Volt THD †‡ A Current THD †‡ B Current THD †‡ C Current THD †‡ AN Volt KF †‡ BN Volt KF †‡ CN Volt KF †‡ A Current KF †‡ B Current KF †‡ C Current KF †‡ Reserved Reserved Reserved Reserved Reserved Reserved 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 146 147 148 149 150 151 152 153 154 155 156 157 158 159 160 161 162 163 164 165 166 167 168 169 170 171 172 173 174 175 176 177 178 179 181 193 182 194 183 184 185 186 187 188 195 196 197 198 199 200 189 190 191 201 202 203 6 5 9 10 4 4 4 6 6 6 5 5 5 9 9 9 123 123 123 123 123 123 126 126 126 126 126 126 127 127 127 127 127 127 † Meters in Open Delta operation will report these values as zero. ‡ Meters that do not compute these values will report them as zero and Unit Field = 127 These points are Floating Point values. They represent the Primary of quantities that the meter measures. 1.4.2.1.9.3 Harmonics Percentage and Phase ( Point 204 - 587 ) Reading Phase AN Volt Percent Phase 0 ( DC ) 204 205 1 ( Fund ) 206 207 2 208 209 Phase BN Volt Percent Phase 268 269 270 271 Phase CN Volt Percent Phase 332 333 Phase A Current Percent Phase 396 397 Electro Industries / GAUGETECH ... 31 266 267 Unit Field 124 125 272 273 330 331 124 125 334 335 336 337 394 395 124 125 398 399 400 401 458 459 124 125 17 DNP Implementation Phase B Current Percent Phase 460 461 462 463 464 465 522 523 124 125 Phase C Current Percent 524 526 528 586 124 Phase 525 527 529 587 125 These points are Floating Point values. They represent the Percentage and Phase information for the DC Offset, Fundamental Frequency and Harmonics up to the 31st Order. Electro Industries / GAUGETECH 18 DNP Implementation 1.4.2.1.10 Large-Packed Binary Coded Decimal ( Obj. 101, Var. 3 ) Large-Packed Binary Coded Decimals support the following functions: Read ( Function 1 ) Write ( Function 2 ) A READ request for Variation 0 will be responded to with Variation 3. Large-Packed Binary Coded Decimals may be indexed with Qualifier Codes 0, 1, 2 or 6. Large-Packed Binary Coded Decimals are used to communicate the following data measured by Electro Industries meters: Hour Readings the Action Object 1.4.2.1.10.1 Hour Readings ( Point 0 - 4 ) Point Reading Unit 0 +W Hour WH 1 -W Hour WH 2 +VAR Hour VARH 3 -VAR Hour VARH 4 +VA Hour VAH These readings may be cleared by using the Control Relay Output Block. 1.4.2.1.10.2 Action Object ( Point 5 ) The WRITE ( Function 2 ) function may be used to request different actions of an Electro Industries meter. The following actions are supported: Switch to EI Protocol 1.4.2.1.10.2.1 Switch to EI Protocol ( Value 1 ) Using the WRITE ( Function 2 ) function to write the value 1 to the Action Object ( Object 101, Variation 3, Point 5 ) requests the meter to reprogram itself, changing the protocol assignment for the current port from DNP 3.0 to EI Protocol. This allows for other available software to be used with the current meter. Electro Industries / GAUGETECH 19 DNP Implementation 1.4.2.2 Qualifier and Range Electro Industries meters operate with Qualifier Codes 0, 1, 2 or 6. For codes 0, 1 and 2, the Range field contains 1 byte ( Q-code = 0 ), 2 byte ( Q-code = 1 ) or 4 byte ( Q-code = 2 ) Start Range and Stop Range values, as Indices of data. Qualifier Code 6 may also be used with the following objects: Counter (object 20) Analog Inputs (object 30) Time & Dates (object 50) Class & Data (object 60) Large-Packed Binary Coded Decimals (object 101) Request with Qualifier Code 6 will return all of the points of the specified object. Electro Industries / GAUGETECH 20 DNP Implementation Electro Industries / GAUGETECH Appendix A : Analog Input Secondary to Primary Conversion Converting Fractional to Secondary Most of the Analog Input ( Object 30 ) points are formatted as 2’s compliment fractions. The Analog Input value varies from +32,767 to -32,768. Divided by 32,768, this produces the fraction. Multiplying the fraction by the Secondary scale of the particular Analog Input produces the Secondary value. The equation is therefore: Secondary Value Analog Input Secondary Scale 32768 Example 1: Analog Input Point 4 ( Phase AN Voltage ) returns with the value of 16,384 ( 0x4000 ). The Secondary Scale for this point is 150 Volts Secondary. By the above equation, the Secondary Value is: 16384 150 V Secondary = 75 V Secondary 32768 Electro Industries / GAUGETECH DNP Implementation : Appendix A CT and PT Ratios To convert from Secondary to Primary, the CT and/or PT Ratio is needed. These ratios may be found by dividing the Ratio Numerator ( Object 30, Point 15 or 17 ) by the corresponding Ratio Denominator ( Object 30, Point 16 or 18 ). The equation is therefore: Ratio = Ratio Numerator Ratio Denominator Example 2: Analog Input Point 17 ( PT Ratio Numerator ) = 19,200 ( 0x4B00 ) and Point 18 ( PT Ratio Denominator ) = 16 ( 0x0010 ). By the above equation, the PT Ratio is: 19200 12001 : 16 Electro Industries / GAUGETECH 22 DNP Implementation : Appendix A Converting Fractional to Primary Combining the above two equations, the method of converting a 2’s compliment fraction representing a Secondary value into the equivalent Primary value would use the following equation: Primary Value = Analog Input Ratio Numerator Secondary Scale 32768 Ratio Denominator Example 3: Analog Input Point 1 ( Phase A Current ) returns with a value of 9,871 ( 0x268F ), Analog Input Point 15 ( CT Ratio Numerator ) with a value of 2,000 ( 0x07D0 ) and Analog Input Point 16 ( CT Ratio Denominator ) with a value of 5 ( 0x0005 ). The Secondary Scale for Point 1 is 10 A Secondary. By the above equation, the Primary Value is: 9871 2000 10 A Secondary 1205 A Primary 32768 5 Example 4: The meter is in Open Delta operation. Analog Input Point 7 ( Total Watt ) returns with a value of -12,754 ( 0xCE2E ), Analog Input Point 15 ( CT Ratio Numerator ) with a value of 1000 ( 0x03E8 ), Analog Input Point 16 ( CT Ratio Denominator ) with a value of 5 ( 0x0005 ), Analog Input Point 17 ( PT Ratio Numerator ) with a value of 12,000 ( 0x2EE0 ) and Analog Input Point 18 ( Pt Ratio Denominator ) with a value of 120 ( 0x0078 ). When operating in Open Delta, the Secondary Scale for Point 7 is 3000 W Secondary. By the above equation, the Primary Value is: 12754 1000 12000 3000 W Secondary 23.35 MW Primary 32768 5 120 Electro Industries / GAUGETECH 23 DNP Implementation : Appendix A Electro Industries / GAUGETECH Appendix B : Analog Input Scaling for Alternate Back Modules Standard Back Module (120 V) Voltage readings are scaled relative to the range of the voltage back module. A standard back meter is capable of measuring voltages Phase-to-Neutral up to 150 Volts secondary, and Phase-to-Phase up to 300 Volts secondary. PT Ratios are entered relative to 120 Volts secondary. Voltage and Power readings are scaled as described in their respective sections. G Back Module (300 V) A G back meter is capable of measuring voltages Phase-to-Neutral up to 300 Volts secondary, and Phase-to-Phase up to 600 Volts secondary. PT Ratios are entered relative to 300 Volts secondary. The difference in PT Ratios introduces a difference in scaling voltage and power readings. An extra factor of 300/120, or 2.5, is introduced when interpreting voltage and power readings on a G back meter. The scaling of phase-to-neutral voltages is to 375 Volts secondary, not 150 Volts secondary, phase-to-phase voltages is to 750 Volts secondary, not 300Volts secondary. Watt, VAR and VA per phase is scaled to 3750 Watt, VAR or VA secondary, and not to 1500. Total Watt, VAR and VA values are scaled to 7500 Watt, VAR or VA secondary in DELTA and 11,250 Watt, VAR or VA secondary WYE, instead of 3000 in DELTA or 4500 in WYE. L Back Module (75 V) An L back meter is capable of measuring voltages Phase-to-Neutral up to 75 Volts secondary, and Phase-to-Phase up to 150 Volts secondary. PT Ratios are entered relative to 75 Volts secondary. The difference in PT Ratios introduces a difference in scaling voltage and power readings. An extra factor of 75/120, or 5/8 (0.625), is introduced when interpreting voltage and power readings on an L back meter. The scaling of phase-to-neutral voltages is to 93.75 Volts secondary, not 150 Volts secondary, phase-to-phase voltages is to 750 Volts secondary, not 187.5 Volts secondary. Watt, VAR and VA per phase is scaled to 937.5 Watt, VAR or VA secondary, and not to 1500. Total Watt, VAR and VA values are scaled to 1875 Watt, VAR or VA secondary in DELTA and 2812.5 Watt, VAR or VA secondary WYE, instead of 3000 in DELTA or 4500 in WYE. Electro Industries / GAUGETECH DNP Implementation : Appendix A