* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download MECHANICAL AND ELECTRICAL EQUIPMENTS
Thermal conduction wikipedia , lookup
Duct (flow) wikipedia , lookup
R-value (insulation) wikipedia , lookup
Cooling tower wikipedia , lookup
Radiator (engine cooling) wikipedia , lookup
Solar water heating wikipedia , lookup
Fan (machine) wikipedia , lookup
Cogeneration wikipedia , lookup
Evaporative cooler wikipedia , lookup
Vapor-compression refrigeration wikipedia , lookup
Copper in heat exchangers wikipedia , lookup
Dynamic insulation wikipedia , lookup
Hyperthermia wikipedia , lookup
Indoor air quality wikipedia , lookup
Underfloor heating wikipedia , lookup
Intercooler wikipedia , lookup
ME 222 MECHANICAL AND ELECTRICAL EQUIPMENTS COURSE SYLLABUS Practical application of mechanical and electrical system design, operation and maintenance principles pertinent to commercial buildings and emphasizing a designer’s perspective on mechanical and electrical power equipment and distribution systems, energy management, fire protection, communication, control and signal systems, lighting, and security systems. INDOOR AIR QUALITY HEAT FLOW HVAC FOR SMALLER BUILDINGS LARGER BUILDINGS HVAC SYSTEMS ELECTRIC LIGHTING APPLICATION WATER SUPPLY LIQUID WASTE SOLID WASTE FIRE PROTECTION ELECTRICAL SYSTEMS AND MATERIALS PHOTOVOLTAIC SYSTEMS FACILITY TRANSPORTATION INDOOR AIR QUALITY WHY IAQ (Indoor Air Quality) - increasingly large percentage of people’s time is spent indoors. -oil embargo (1973), raised world’s consciousness regarding finite energy sources (energy conserving designs). -proliferations of chemical in our environment has produced a vast array of potential air pollutants synthetic products permanently installed within the building, from equipment used indoors, and from cleaning fluids used in maintenance. With less fresh air and surrounded by more pollution sources, increasing number of buildings have experience sick building syndrome (SBS). SICK BUILDING SYNDROME (SBS) Situation wherein more than 20% of the occupants complain of symptoms associated with SBS- such as headaches, upper respiratory irritations, and irritations of the eye, among others. ACCEPTABLE INDOOR AIR QUALITY (ASHRAE 2004) -Air in which there are no known contaminants at harmful concentrations as determined by cognizant authorities and with which a substantial majority (80% or more) of the people exposed do not express dissatisfaction IAQ DEPENDS UPON 1. 2. 3. 4. Limiting pollution at the source (choosing materials and equipment carefully). Isolating unavoidable sources of pollution. Providing for an adequate supply and filtering of fresh air (and recirculated air). Maintaining a building and its equipment in a clean condition. POLLUTION SOURCES AND IMPACTS Contaminants – gaseous, organic, particulates Effects – odors, irritants, toxic substances ODORS - most immediate indicators of IAQ problem - perceived most strongly on initial encounters - our reactions are positive, negative, or neutral IRRITANTS - often imperceptible at first but cause increasing distress over time. - volatile organic compounds (VOC), chemicals containing carbon molecules that are volatile (i.e. methane, CFC’s, HCFC, formaldehyde) TOXIC PARTICULATES SUBSTANCES - asbestos BIOLOGICAL CONTAMINANTS -bacteria, fungi RADON AND SOIL GASES - radioactive gas that decays rapidly releasing radiation at each stage - can cause lung cancer -other soil gases include methane, pesticides that volatize and enter the buildings with soil gases PREDICTING INDOOR AIR QUALITY Assuming that pollutant sources have been minimized, we need to know how much indoor air and what extent of filtering will produce acceptable IAQ. Ventilation rate - the most common remedy for SBS is to increase the rate of outdoor air ventilation. Very small amount of outdoor air will provide sufficient oxygen, and although human odor control is usually achievable at a rate of from 6 to 9 cfm (3 to 4.5 L/s) of outdoor air per occupant, outdoor air has more to do than provide oxygen and control odors. Comfort formula: G Q 10 ci c o Where: Q = ventilation rate, L/s G = total pollution sources, 0lf Ci = perceived indoor air quality, decipol Co = perceived outdoor air quality, decipol Olf is a unit of pollution (1 olf = the bioeffluents produced by the average person) Decipol = a unit of perceived air quality Ci is recommended to be set at 1.4 decipol, which represents an expectation of 80% of occupants satisfied with IAQ. The concept of replacance affects the design of ventilation systems. Based on studies, the rate of 1 air change per hour (ACH) of outdoor air, an indoor space would have only 63% “new air” after 1 hour; about 8 hours at this rate is required for all the “old” air to be exhausted. The difference between the ACH and replacance is the fraction of air molecules at one specified times that was not in the indoor space at an earlier reference time. ZONING FOR IAQ After pollution control had been implemented at the source, remaining unavoidable pollutant sources should be identified. More sensitive areas of the building should be isolated from the key contaminants. Differential air pressures are often maintained to discourage air flow from dirty to clean zones – with higher pressure in clean areas, lower pressure in dirty areas. Lower pressures can be created by exhaust air from such spaces, as well as by limiting the volume of supply air. Higher pressure areas can be created by installing make-up air equipment, as well as increasing the volume of supply air from the HVAC system. PASSIVE AND LOW-ENERGY APPROACHES TO VENTILATION “the solution to pollution is dilution” a) WINDOWS b) STACK EFFECT c) UNDERSLAB VENTILATION d) PREHEATING VENTILATION AIR EQUIPMENT FOR CONTROL OF IAQ EXHAUST FANS - remove air that is odorous and/or excessively humid before it can spread beyond bathrooms, kitchens, or process areas, creating a negatively pressured area that further limits the spread of undesirable air. ANSI/ASHRAE requires exhaust fan of at least 50 cfm (25 L/s) capacity for bathrooms and 100 cfm (50 L/s) for kitchen. HEATING/COOLING OFMAKEUP AIR - where climates are mild and/or energy is inexpensive, special equipment other than heat exchangers can be used to heat and/or cool a particularly large quantity of makeup air. These simple devices often supplement the building’s main heating/cooling system, which deals primarily with heat gains/losses through the building skin. Even in hot, humid climates, indirect evaporative cooling can help lower the temperature of makeup air. HEAT EXCHANGER - as the tightness of construction increases and fewer air changes per hour (ACH) occur from infiltration (unintended air leaks), forced ventilation becomes more attractive as a means of reducing indoor air pollution. When heat exchanger is used, it is possible to maintain an adequate supply of fresh air without severe energy consumption consequences. Some commercially available heat exchangers are capable of extracting 70% or more of the heat from exhaust air. The lower the volume of air flow the higher the efficiency. DESICCANT COOLING - another rotating wheel process, they are attractive because they use no refrigerants, and they lower humidity without having to overcooling the air. The desiccants (such as silica gel, activated alumina, or synthetic polymers) in an active system must be heated to drive out the moisture they remove from the incoming air TASK DEHUMIDIFICATION AND HUMIDIFICATION - for spaces that need only dehumidification rather than mechanical cooling, refrigerant dehumidifiers are commercially available. Their advantage over desiccant dehumidifiers is that the air temperature remains essentially unchanged during dehumidification (desiccant dehumidifiers raise the temperature of the dried air). Accumulated water must periodically be removed from these units and, if untended, could become a source of disease. Task humidifiers are available and often used to relieve symptoms of respiratory illnesses. FILTERS Particulate filters Panel filters – furnished with HVAC equipment and functions mainly to protect the fans from large particles of lint or dust. They are crude and are not really considered to be air-cleaning equipment. Media filters – are much finer, using highly efficient pleated filter paper within a frame. The larger particles are strained out by the closely spaced filter fibers, while some of the smaller particles that would other wise pass through are pushed into the fibers due to air turbulence. Adsorption filters – are for gaseous contaminant removal and vary according to the pollutant in question. Activatedcharcoal filters are the most common of these type, absorbing materials with high molecular weights but allowing those of lower weights to pass. Air washers – sometimes used to control humidity and bacterial growth. The moisture involved can pose a threat if these devices are not well maintained. Electronic air cleaners – advantage of demanding less maintenance, but can pose a different threat due to ozone production. Static electricity is produced in the self-charging mechanical filters by air rushing through it; larger particles thus cling to the filter. The more humid and/or higher the air velocity, the lower the filtering efficiency. Locating air-cleaning equipment - before the advent of IAQ, buildings were designed with rather crude panel filters located only at the HVAC equipment; they were primarily intended to intercept materials that might adversely affect combustion or heat exchange. In building requiring high IAQ, a combination of highefficiency particle filters and adsorption filters are required. Panel filters are usually located upstream from the fan unit. High efficiency particle and adsorption filtering systems should be located downstream from the HVAC cooling coils and drain pans to ensure that any microbiological contaminants from those wet surfaces are removed rather than being distributed throughout the building. Ultraviolet Radiation (UV) - has been used to kill harmful microorganisms, but under tightly controlled conditions. Now there are UV lamp units that work within HVAC systems, promising to control fungi, prevent the development and spread of bacteria, and reduce the spread of viruses. An additional benefit, cooling coils and drain pans stay cleaner. Individual space air cleaning - energy conservation have reduced the air circulation rate in many central air handling systems moving less air reduces the energy used by fans. One result can be low distribution efficiency, which causes poorly mixed air within the occupied spaces. With local (individual space) air filtering equipment, both a high circulation rate and proper air mixing are achievable. Each unit has its own fan that can operate either with or without the central HVAC fan. Controls for IAQ - a large number of air quality monitoring devices are available, some of which can control the operation of IAQ related equipment. HEAT FLOW Heat flow, also known as heat transfer, heat exchange, or simply heat, is the transfer of thermal energy from one region of matter or a physical system to another. When an object is at a different temperature from its surroundings, heat transfer occurs so that the body and the surroundings reach the same temperature at thermal equilibrium. Such spontaneous heat transfer always occurs from a region of high temperature to another region of lower temperature, as required by the second law of thermodynamics. In engineering, energy transfer by heat between objects is classified as occurring by heat conduction, also called diffusion, of two objects in contact; fluid convection, which is the mixing of hot and cold fluid regions; or thermal radiation, the transmission of electromagnetic radiationdescribed by black body theory. Engineers also consider the transfer of mass of differing chemical species, either cold or hot, to achieve heat transfer. 'Skin' is treated in a broad way. It is regarded as the non-structural covering to a framed structure. Structure supported mainly by a skeleton, or frame, of wood, steel, or reinforced concrete rather than by load-bearing walls. Called by their familiar name, the basic components of a building envelope (skin) includes windows, doors, floors, walls and roofs. The flow of heat through a building envelope varies both by season and by the path of the heat (through the materials of a building’s skin or by way of outdoor air entering the interior through intentional and unintentional pathways.) Heat flows are to two forms: Sensible heat – results in change in temperature Latent heat – results in change in moisture content - Total heat flow is the summation of sensible heat and latent heat. - Materials react differently to sensible and latent heat flows. Heat flow processess - buildings like bodies, experience sensible heat loss to, and gain from, the environment in three principal ways: Convection – heat is exchanged between a fluid (typically air) and a solid, with motion of the fluid due to heating or cooling playing a critical role in the extent of heat transfer. Conduction – heat is transferred directly from molecule to molecule, within or between materials, with proximity of molecules (material density) playing a critical role in the extent of heat transfer. Emittance – radiation heat transfer is highly influenced by surface characteristics. Shiny materials are much less able to radiate than common rough building materials. Thermal classification of materials - Materials generally interact with heat either as insulators that retard heat or conductors that encourages heat flow. It is common that a combination of insulators and conductors can be found in construction. - INSULATIONS 1. Inorganic fibrous or cellular products (such as glass, rock wool, slag wool, perlite, or vemiculite.) 2. Organic fibrous or cellular products (such as cotton, synthetic fibers, cork, foamed rubber, or polystyrene) 3. Metallic or metalized organic reflective membranes (which must face an air space to be effective) Insulating materials are available in: Loose fill Insulating cement Formed-in-place Flexible, semirigid insulation Rigid insulation Reflective material –available in sheets and rolls either single or multiple layers. CONDUCTORS - Materials used as conductors are typically dense, durable, and diffuse heat readily. AIR FILMS and AIR SPACES - Actually void of materials, they have potentially useful thermal properties and contribute substantially to the insulating capabilities of some construction materials. Composite thermal performance: 1 U R U = overall coefficient of thermal resistance (BTU/h-ft2; W/m2-K) R = resistance HVAC FOR SMALLER BUILDINGS Heating, Ventilating, and Air conditioning (HVAC):Typical design processes PRELIMINAR DESIGN Most general combination of comfort needs and climate characteristics are considered: - Activity comfort needs are listed - An activity schedule is developed - Site energy resources are analyzed - Climate design strategies are listed - Building form alternatives are considered - combinations of passive and active systems are considered - One or several alternatives are sized by general design guidelines DESIGN DEVELOPMENT PHASE 1. Establishes design conditions, A. By activity, lists the range of acceptable air and surface temperatures, air motions, relative humidities, lighting levels, and background noise levels. B. Establishes the schedule of operation. II. Determines the HVAC zones, considering: A. Activities. B. Schedule. C. Orientation. D. Internal heat gains III. Estimates the thermal loads on each zone: A. For worst winter conditions. B. For worst summer conditions. C. For the average condition or conditions that represent the great majority of the building’s operating hours. D. Frequently, an estimate of annual energy consumption is made. IV. V. VI. VII. Selects the HVAC systems. Often, several systems will be used within one large building because of orientation, activity, or scheduling differences may dictate different mechanical solutions. Especially common is one system for the all-interior zones of large buildings and another system for the perimeter zones. Identifies the HVAC components and their locations. A. Mechanical rooms. B. Distribution trees – vertical chases, horizontal runs. C. Typical in-space components, such as under-window fancoil units, air grilles, and so on. Sizes the components. Lays out the system. At this stage, conflicts with other systems (structure, plumbing, fire safety, circulations, etc.) are most likely to become evident. Design Finalizing Phase - At this stage, the HVAC system designer verifies the match between the loads on each component and the component’s capacity to meet the load. Final layout drawings then are completed. Equipment location and service distribution - smaller buildings are typically skin-load dominated: that is, for them, the climate dictates whether heating or cooling is the major concern. In some climates, only heating systems are needed; the building can “keep itself cool” during hot weather without mechanical assistance. In other climates, only cooling is needed. In still others, both heating and cooling is required. a) b) Central or Local - a skin dominated building may have such differing but simultaneous needs that a room-by-room solution (“local”) for heating, ventilating, and conditioning is desirable. The advantage of local systems is their ability to respond quickly to individual rooms’ needs. - the central system also has advantages: the equipment is contained within its own space rather than taking up space within each room, and maintenance can be carried out without disrupting activities within those rooms. Central heating or Cooling equipment - in the early stages of design, determining an approximate size for the largest equipment is sometimes useful. Once the heating or cooling capacities are known, manufacturers’ catalogs can be consulted for the dimensions of the heating and cooling equipment. Design temperature – critical decision in sizing the heating equipment. What is the lowest reasonable outdoor temperature for which a heating device can be sized if the desired interior temperature is to be maintained? Design t = inside temperature – outside temperature Required capacity of a building’s heating equipment: Btu/h heating capacity = ((Btu/DD)ft2/24 h)(t)(ft2 floor area) Cooling size (mechanical refrigeration) Sensible Btu/h cooling capacity = [approx. heat gain(Btu/h ft2)][floor area(ft2)] Required capacity in tons: Tons of cooling = heat gain, Btu/h/12,000 1 ton = 12,000 Btu/h (3516 W) c) Distribution trees - Central heating and cooling systems produce heating and cooling in one place, then distribute them to other building spaces according to their respective needs. The distribution tree is the means for delivering heating and cooling: the “roots” are the machines that provide heat and cold, the “trunk” is the main duct or pipe from the mechanical equipment to the zone to be served, and the “branches” are the many smaller ducts or pipes that lead to the individual spaces. The “leaves” are the point of interchange between the piped or ducted heating or cooling and the spaces served. Controls for Smaller Building Systems - Older buildings had mechanical equipment for heating or cooling only, thermostats were simple on-off devices; when the temperature rise or fall below a set point, the heat or cooling load was turned on. - Building management system (BMS) are now capable of regulating far more than temperature. They are capable of remote control, allowing systems to be activated in advance of the occupants’ arrival. - Future developments include neural networks, where automation systems are capable of learning while being used. They thus predict usage pattern, adjusting in advance without needing specific commands from occupants. REFRIGERATION CYCLE Compressive refrigeration: - A scheme for transferring heat from one circulated water system (chilled water) to another (condenser water). This is done by the liquefaction and evaporation of a refrigerant, during which processes it gives off and takes on heat, respectively. The heat it gives off must be disposed of (except in the heat pump), but the heat it acquires is drawn out of the circulated water known as the chilled water, which is the medium for subsequent cooling processes. Absorption Refrigeration cycle - No CFC’s or HCFCs are used here; the process uses distilled water as the refrigerant and lithium bromide (salt solution). In order to remove heat from chilled water, this cycle uses still more heat in regenerating the salt solution. Typically, it is less efficient than the simple compressive cycle and needs about twice the capacity for rejecting heat. Because the high-grade energy (electricity) needed to run a compressor is replaced by the lower-grade heat needed to run the generator, the absorption cycle can enjoy an energy advantage over the compressive cycle, even though it is less efficient. COOLING-ONLY SYSTEMS a) b) c) d) e) Fans Unit air conditioners Evaporative cooling: Misting Evaporative cooling: roof spray Evaporative coolers - affectionately termed swamp coolers or desert coolers and are familiar devices in hot, arid climates. They are used in other climates for special high-heat applications such as restaurant kitchens. They require a small amount of electricity to run a fan and some water to increase the RH of the air they supply to the building, In a typical indirect evaporative air cooler, the essential element is a heat exchanger in which dry air contacts heat-exchange surfaces whose other sides are cooled evaporatively. HEATING/COOLING SYSTEMS A) Cooling coils added to warm air furnaces This common system utilizes a rather simple arrangement of the refrigeration cycle. The condenser heat is carried away by water and the evaporation process draws heat out of water in another circuit to produce chilled water. The heat is moved to a heat rejection location outdoors. Another type of cooling is air to air refrigeration device. Air instead of water can be used to cool the condenser, and indoor air can be cooled directly by being passed over the evaporator coil in which the refrigerant is expanding from a liquid to a gas. Heat is removed from the indoor air to the outdoor air by the step-up action or heat-pumping nature of the refrigeration cycle. When indoor air is cooled by this manner, by expanding the refrigerant , the process is usually known as direct expansion. The cooling coils are referred to as DX coils. B) Hydronic and coils This system combines a perimeter hot water heating pipe with an overhead air-handling systems. A boiler with a tankless coil supplies domestic hot water. The boiler’s heat output supplies both the perimeter loop and a coil in the air-handling unit of the duct system. The total heating load is met by the combination of radiant heat generated by the perimeter loop and heated air from the overhead air-handling system. Air-Air heat pumps – these use the refrigeration cycle in both heating and cooling, thus eliminating the use of boilers and cooling coils. Heat pumps can transfer heat air-air, air-water, water-water. Single or Split-type system In a single package (also called unitary) system only one piece of equipment is involved. A single-package air-air heat pump moves heat between an outdoor air stream and an indoor air stream; although kept separate, both streams pass through a single outdoor unit. A system with both outside and inside components is called a split system. A split-system air-air heat pump moves heat via a refrigerant loop between the outdoor unit (which also contains the compressor), through which outdoor air passes, and the indoor unit (which usually contains backup heating coils) for the treatment and circulation of indoor air. Split systems are popular because the noise of the compressor and the outdoor air fan are removed from the interior, and the size of the indoor unit can be quite small. This indoor element is often mounted either high on the wall or on the ceiling. Such an indoor unit is available with automatically changing louvers; when it is in the cooling mode, it delivers cool air along the ceiling, from where it sinks to the level of occupancy; cold air blowing directly on people is avoided. In the heating mode, the louvers shift to direct hot air steeply downward. The greater the distance between the indoor and outdoor units, the greater the strain on the refrigerant loop. Heat pumps have a high initial cost, and they have in the past shown a relatively high frequency of compressor failure. Noise from the compressor and the outdoor air fan may affect site planning, especially for residences. One of the primary attractions of the heat pump is that in its heating mode it can deliver more energy than it consumes (electrically). Although energy (usually electricity) is required to run the cycle, the pump draws “free” heat from a source such as outdoor air. The total heat delivered to the building is more than the heat (electricity) required to run the cycle. The measure of this heat advantage is called the coefficient of performance (COP), defined as: Ground source heat pump Ground-air heat pumps, also called geothermal heat pumps or geoexchange systems. They often provide domestic hot water in addition to heating and cooling. An environmentally safe refrigerant is circulated through a loop installed underground (or in a pond or lake), taking heat from the soil in winter and dischargingheat to the soil in summer. The loop is often highdensity polyethylene (HDPE). Below the surface, soil temperatures are more stable year-round than outdoor air temperatures, thus raising the COP relative to that of air-air heat pumps. This system is almost completely out of sight, with no maintenance or weathering of exterior equipment. Noise is confined to the compressor in a small indoor mechanical room. Some common configurations are shown. In the closed systems (a–c) the flow rate is typically 2 to 3 gpm/ton of refrigeration (0.3 to 0.5 mL/J), with lower flows in the open loop systems. Horizontal ground source closed loop heat pump Trenches requires 1 – 2 m deep - 400 to 650 ft (120 to 200 m) of pipe are installed per ton (12,000 Btu/h or 3.5 kW) - of heating and cooling capacity a “slinky” coiled pipe is sometimes used. The trenches can be placed below parking lots or lawns and gardens. Vertical ground source closed loop heat pump - particularly applicable where the site area is limited. Vertical holes are bored from 150 to 450 ft (46 to 137 m) deep. Each hole contains a single full-depth loop and is backfilled (or grouted) after the loop is installed. Since summer temperature is much lower at greater depths, less pipe length is required than for horizontal loops. The distance between bore holes varies from a minimum of 15 ft (4.6 m) with high water table and low building cooling loads to as much as 25 ft (7.6 m) for buildings with high cooling loads. A minimum distance of 20 ft (6 m) is usually recommended. Pond or lake closed loop heat pump sometimes used when a building is close to an adequately large body of water. The loop is submerged, and the surrounding water conducts heat far more rapidly than does soil. The resulting shorter length required, and the low cost of placing the coils in water, can make this attractive. the water level in the pond should never drop below a minimum of 8 ft (2.5 m) and must have sufficient surface area for heat exchange. Groundwater-source open loop heat pump (“pump and dump”) is suitable only where groundwater is plentiful, and may be prohibited by local codes and environmental regulators. One variant of this system (Fig. d) takes water from one well, through a heat exchanger within the building, then discharges it to a second well. Another variant (Fig. e) takes water from the bottom and discharges back into the top of the same (standing) well, typically 6 in. (150 mm) in diameter and as deep as 1500 ft (460 m). Ground source heat pumps are often used in retrofits, especially in schools where site areas are plentiful, or historic structures where small-size interior mechanical equipment is highly desirable. LARGE BUILDING HVAC SYSTEM At the onset of the twenty-first century, large building HVAC is showing several trends. One is the increasing willingness to let mechanical equipment share its tasks with natural ventilation and daylighting. Building automation has made this easier to manage. Another trend is toward an underfloor plenum air supply (related to, but not identical to, displacement ventilation approaches commonly used in critical-environment facilities) rather than using ducts connected to diffusers and return grilles, both on the ceiling. Concern about air quality indoors and the environment outdoors is producing a variety of approaches to increased ventilation effectiveness. Refrigerants containing CFCs and HCFCs are being avoided. Fuel cells and photovoltaics are promising increased energy autonomy to larger buildings. BASIC HVAC SYSTEMS: TASKS AND COMPONENTS HVAC SYSTEMS TYPES Four main systems classification: Direct refrigerant systems All-air systems Air and water systems All-water systems (A) DIRECT REFRIGERANT SYSTEMS These systems nearly eliminate the distribution trees of air or water, relying instead on a heating/cooling device adjacent to or within the space to be served. Thus, they are prevalent in skinload- dominated buildings with extensive perimeter zones; these tend to be smaller buildings. (B) ALL-AIR SYSTEMS Fig. 10.12 (a–f) Schematic diagrams of all-air HVAC systems. An underfloor air supply is shown here to simplify the diagram, but a ceiling supply is much more common. The more common variations on all-air systems are shown in Fig. 10.12. Because air is the only heat transfer medium used between the mechanical room (central station) and the zones it serves, and because air holds much less heat per unit volume than water, the distribution trees for this class are quite thick. Sometimes, to reduce duct sizes, higher velocities are used for supply air. This generates more noise and higher friction, resulting in more energy used by fans; higher velocity should be used only sparingly, where space limitations are extreme. For comfort, however, these systems are, over all, the best. The quantities of air moved through the central station(s) are heated or cooled, humidity controlled, filtered, and freshened with outdoor air—all under controlled conditions. Within the zones, supply diffusers/registers and return grilles allow a wellplanned stream of conditioned air to thoroughly permeate all work areas. (C) AIR AND WATER SYSTEMS Fig. 10.13 (a–c) Schematic diagrams of air and water HVAC systems. An underfloor air supply is shown here to simplify the diagram, but a ceiling supply is more common. In (b) the supplementary air is often delivered directly to the fan-coil unit. Most of the heating and cooling of each zone is accomplished via the water distribution tree, which is much thinner than the tree needed by air. For air quality—filtering, humidity, freshness—a small, centrally conditioned airstream, equal to the total fresh air required, is provided. Thus, several distribution trees are involved, yet the total space they require is almost always less than that required by all-air systems. Exhaust air may be gathered in a return air duct system, making heat recovery possible. Or (as a cheaper alternative) air can be exhausted locally to avoid the construction of yet another distribution tree. If the water distribution provides either heating or cooling only, it is called a two-pipe system (shown throughout Fig. 10.13). If it provides simultaneous heating and cooling, it is a four-pipe system. (Three-pipe systems are a lower-first-cost alternative allowing simultaneous heating and cooling [from two supply pipes with a single return pipe], but they waste energy by mixing hot return and cold return water flows in one return pipe. They are no longer permitted in most locales.) (D) ALL-WATER SYSTEM Fig. 10.14 Schematic diagram of all-water HVAC systems. Fourpipe distribution trees require smaller volumes than do those for air systems; however, less thorough provision of outdoor air is a potential concern. The more simple-appearing all-water systems are shown in Fig. 10.14. These systems only heat and cool; the distribution trees are indeed slim. Air quality is dealt with elsewhere—either locally, by means of infiltration or windows; or by a separate fresh air supply system; or simply by fresh air from an adjacent system, such as a ventilated interior zone. This ambiguity about fresh air leads to similar ambiguities about whether a system is air-andwater or all-water. A fan-coil terminal is often employed so that air motion occurs along with heating or cooling. (Sometimes the fan-coil unit is located against the exterior wall so that fresh air may be brought in and mixed with the room air through the fan.) Both baseboard and valence (above-window) units are also commonly available. Because air is handled so locally, there is very little mixing of air from one zone to another, making this attractive where potential air contamination (or smoke from a fire) is a special concern. It is also an easy system to retrofit. However, maintenance is high; filters in each fan-coil must be cleaned, and drain pans are potentially problematic. (e) Equipment Space Allocations An important early design decision is whether to integrate or separate the heating/cooling equipment and the air-handling equipment (see Fig. 10.2). If they are integrated, one or a few central mechanical room(s) can serve many floors, and each mechanical room will need area and height sufficient for both heating/cooling and air-handling equipment. If separated, one (or several, in tall buildings) large space for heating/cooling equipment is typically located in the basement or the penthouse, with a smaller fan room on each floor. Each mechanical room should have both a central location relative to the area it serves and direct access to the outside—contradictory requirements in many cases. Central locations within the area served minimize the distribution tree size; access to the outdoors facilitates the use of outdoor air as a heat source (winter) or sink (summer) and allows equipment to be installed or removed in later remodeling. Mechanical rooms serving both heating/cooling and air-handling equipment need relatively high ceilings; 12-ft (3.7-m) clear is a typical minimum, 20-ft (6-m) clear a typical maximum. Fig. 10.15 Some basic components of HVAC central equipment. (a) A simplified diagram of a cooling cycle, in which chilled water is circulated to air-handling coils and heat is disposed of through a cooling tower. (b) Schematic diagram of major components of central equipment for both heating and cooling. AIR DISTRIBUTION WITHIN SPACES When large office buildings had far greater interior (core) areas than perimeter areas and were filled with less-efficient lighting at high luminance levels, they were considered to always need cooling. Because cool air supplied at the ceiling would naturally fall toward the level of occupants, and because suspended ceilings were ubiquitous, supply air from the ceiling was almost universal. The suspended ceiling was also tempting for the return air provisions, whether as a plenum or for another ducted system. With both supply and return air at the ceiling, the danger of shortcircuiting arose: supply air heading quickly for the return opening, with resulting shortages of both cooling and IAQ. In this section, we first look at approximate duct sizing and then consider three air distribution systems for multistory office buildings. (a) Air Ducts Duct sizes (in cross section) are frequently of interest early in the design process. Duct depths can help determine floor heights; duct cross sections influence the sizes and shapes of the vertical cores that serve multistory buildings. An approximation of duct size can be obtained as follows: 1. Determine the quantity of air to be distributed through the largest duct, using Table 10.5. 2. If necessary, convert cfh to cfm: cfh 1 h/ 60 min = cfm 3. Find the maximum velocity of this air within the duct from Table 9.4, expressed in feet per minute (fpm). 4. The approximate minimum required cross-sectional area of duct A is then: A in.2 = [volume of air (cfm)/ velocity (fpm)] × 144 in.2/ft2 × friction allowance where the friction allowances are • round ducts = 1.0 (may be neglected) • nearly square ducts (ratio of width to depth, 1:1) small (<1000 cfm) = 1.10 large (>1000 cfm) = 1.05 • thin rectangular ducts (ratio of width to depth, 1:5) = 1.25 Then check this against the recommended duct cross-sectional area from Table 10.4. Remember that the minimum duct area will carry a penalty of increased noise and friction.