Download the BAS Application Manual

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Stray voltage wikipedia , lookup

Power inverter wikipedia , lookup

Electrical substation wikipedia , lookup

Islanding wikipedia , lookup

Induction motor wikipedia , lookup

Voltage optimisation wikipedia , lookup

Rectifier wikipedia , lookup

History of electric power transmission wikipedia , lookup

Electric power system wikipedia , lookup

Control theory wikipedia , lookup

Mains electricity wikipedia , lookup

Current source wikipedia , lookup

Stepper motor wikipedia , lookup

Electrification wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Light switch wikipedia , lookup

Control system wikipedia , lookup

Power engineering wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Three-phase electric power wikipedia , lookup

Power electronics wikipedia , lookup

Switch wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Alternating current wikipedia , lookup

Buck converter wikipedia , lookup

AC adapter wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Relay wikipedia , lookup

Opto-isolator wikipedia , lookup

Protective relay wikipedia , lookup

Transcript
Application Manual 2015
Relay and Current Sensor in One
Directly start/stop load and current sensing all in one package (no external ring is needed.) Wire colors to “Load”
and “60 Hz ac” differ depending on the model being used. Configurations are either YELLOW & ORANGE,
BLUE & YELLOW, or ORANGE & ORANGE.
Controller
Digital In
Digital Out
Start
Stop
Relay
Solid
State
Switch
Internal 20 Amp
Internal 10 Amp
Internal 5 Amp
RIBX24BF
RIBX24SBF
RIBX24BA
RIBX24SBA
RIBXLCF
RIBXLSF
RIBXLCA
RIBXLSA
RIBXLCEA
RIBXLSEA
Transducer
Load
60 Hz ac
Motor Starter
Allows relay to control a motor starter while sensing current flowing to the motor.
3-Phase
Line
Voltage
Controller
Digital Out
Motor
Starter
Motor
24 Vac
External
Sensor Ring
Start/Stop Relay
Current Sensor Circuitry
Digital In
External Sensor Ring
RIBXLCRF
RIBXLCRA
RIBXLCJF
RIBXLCJA
RIBXLSRF
RIBXLSRA
RIBXLSJF
RIBXLSJA
Solid State Transducer
Switch
Sensor only for 1.25 Amp to 150 Amp Load
Use sensor only devices without relay where start/stop is not required.
3-Phase
Line
Voltage
Motor
Starter
Motor
External Sensor Ring
RIBXRA
RIBXRF
Controller
Digital Out
Current Sensor Circuitry
Digital In
External
Sensor Ring
Solid State Transducer
Switch
800.888.5538 : www.FunctionalDevices.com
1
Panel Mounted Relay and Internal Sensor
Start/Stop Relays with Internal Current Sensors measure current flow through the relay contacts, no external ring is
needed. Senses current as low as .50 Amp.
Panel
Controller
Internal 20 Amp
20 Amp
Max Load
Digital In
RIBMX24BF
RIBMX24SBF
RIBMX24BA
RIBMX24SBA
Digital Out
RIBMX
Start/Stop Relay
Current Sensor Circuitry
Solid State
Switch
Transducer
60 Hz ac
Interlocking Loads
Some RIBX current sensor relays can be used to sense 1 or more loads to turn on another.
60 Hz ac
Laundromat
Exhaust Fan
Internal 10 Amp
24 Vac
Source
RIBX
Start/Stop Relay
Current Sensor Circuitry
Solid State
Switch
External Sensor
Dryer 1
Transducer
RIBXLCRF
RIBXLCRA
RIBXLCJF
RIBXLCJA
RIBXLSRF
RIBXLSRA
RIBXLSJF
RIBXLSJA
Dryer 2
Interlocking Loads (No Transformer)
Self-powered Current Sensors of the RIBX Series and relays of the Dry Contact Input RIB® Series may be
applied to interlock Load 2 to Load 1.
Current sensing may
be internal or external
Local Power
120, 240, 277 Vac
Load 1
Load Wire
RIBX SERIES
Current Sensor Only
Low Voltage
(Class II)
Dry Contact Input
RIB® Series
Current
Sensor
Status
Load 2
2
Dry Contact Input Relays
Current Sensors
RIB21CDC
RIB01BDC
RIB01SBDC
RIB02BDC
RIB02SBDC
RIBM01ZNDC
RIBM02ZNDC
RIBM013PNDC
RIBD01BDC (Time Delay)
RIBD02BDC (Time Delay)
RIBD01BDC-DOB (Time Delay)
RIBD02BDC-DOB (Time Delay)
RIBXKF
RIBXKTF
RIBXKA
RIBXKTA
RIBXGA
RIBXGF
RIBXGTA
RIBXGTF
RIBXGFL
RIBXGTFL
Functional Devices, Inc. : American Made. American Owned.
RIBXF
RIBXA
RIBXRF
RIBXRA
RIBXJF
RIBXJA
RIBMXF
RIBMXA
RIBMXRF
RIBMXRA
Damper Motor Control with True-HOA
The damper motor can be stopped in mid position for debugging. When auto/manual selector is in auto, relay controls
the load. When in manual, use the manual switch to control the load.
24 Vac From
Controller
10 & 15 Amp
RIBU1SC
RIBH1SC
RIBTU1SC
RIBTH1SC
RIBMU1SC
RIBMH1SC
Auto / Manual Selector
Wht/Blu
Auto
Line (120 Vac)
Man
Wht/Yel
Manual Switch
Wht/Blk
(not used)
Open
N/C
Closed
ORANGE
N/O
Closed
Open
(120 Vac)
YELLOW
Neutral
BLUE
20 Amp
RIB2401SBC
RIB2402SBC
RIBT2401SBC
RIBT2402SBC
RIBM2401SBC
RIBM2402SBC
Damper
Motor
Close
(120 Vac)
RIBU1S vs. RIBU1SC
Stock model RIBU1SC for relay control applications that require true-HOA on either N/O or N/C. No jumpers and no
wrong orders.
120 Vac
24 Vac From
Controller
Wht/Blu
Wht/Yel
RIBU1S
Orange
Orange
LOAD
120 Vac
24 Vac From
Controller
Wht/Blu
Wht/Yel
Yellow
RIBU1SC
RIBU1S has a lower cost
but if N/C is desired on
relay, it must be specified
when ordering.
RIBU1SC is an alternative
to the RIBU1S that allows
one item to be ordered - no
need to specify N/O or N/C.
10 & 15 Amp
RIBU1SC
RIBH1SC
RIBTU1SC
RIBTH1SC
RIBMU1SC
RIBMH1SC
20 Amp
RIB2401SBC
RIB2402SBC
RIBT2401SBC
RIBT2402SBC
RIBM2401SBC
RIBM2402SBC
Orange (N/O)
LOAD
Blue (N/C)
N/O or N/C, you choose
Manual Analog Override Switch
Initial installation or trouble shooting can be smoother and much less costly by adding the RIBMNA1D0. It allows you to
manually control an analog output without accessing complicated algorithms in a controller. An indicator is provided for
visual confirmation of percentage output. When you are finished, you can switch back to auto to put the controller back
in control.
24 Vac/dc
Analog Out
RIBMNA1D0
Controller
Digital In
Analog Out
Load
Dry Contact Feedback Signal
(when device is in manual position)
800.888.5538 : www.FunctionalDevices.com
3
Limit Extra Transformers with Dry Contact Input Relays
Eliminate the expense of extra transformer(s) and associated wiring.
Before
Enclosure
D
R
Y
C
O
N
T
A
C
T
S
Controller
120 Vac
24 Vac
24 Vac
100
VA
D.O.1
D.O.2
D.O.3
Enclosure
C
O
N
T
A
C
T
S
Enclosed Relays
RIB21CDC
RIB01BDC
RIB01SBDC
RIB02BDC
RIB02SBDC
RIBD01BDC (Time Delay)
RIBD02BDC (Time Delay)
RIBD01BDC-DOB (Time Delay)
RIBD02BDC-DOB (Time Delay)
Cont. Pwr.
After
D
R
Y
RIBU1C's
40
VA
Controller
Dry Contact
Input RIB's
120 Vac
24 Vac
Track Relays
RIBM01ZNDC
RIBM02ZNDC
RIBM013PNDC
40
VA
Cont. Pwr.
D.O.1
D.O.2
D.O.3
Detect Water Levels with Dry Contact Input Relays
If the water touches the wires, the relay will turn on (closes COMMON to N/O and opens COMMON to N/C.)
Uses UL Approved low-voltage to sense water and activate relay.
Dry Contact Input Relay
Control
Circuit
Enclosed Relays
RIB21CDC
RIB01BDC
RIB01SBDC
RIB02BDC
RIB02SBDC
RIBD01BDC (Time Delay)
RIBD02BDC (Time Delay)
RIBD01BDC-DOB (Time Delay)
RIBD02BDC-DOB (Time Delay)
120-277 Vac Power
Relay
Load
Any typical non-corrosive
probes may be used.
Water Pan
Track Relays
RIBM01ZNDC
RIBM02ZNDC
RIBM013PNDC
Monitoring Switch Position with a Controller
Digital In 1 and 2 of the controller can be used to monitor the position of the HOA switch. The controller can be
programmed to log the status of the HOA and provide a warning if the switch is in an override position.
Enclosed Relays
10 Amp
RIBU1SM
RIBH1SM
Controller
Digital Out
Common
10-30Vac/dc
Common
Relay
60 Hz ac
120 Vac Not Used
Digital In 1
Closed
Digital In 2
Auto
Common
4
Switch
Pole #2
Common
Switch
Pole #1
Auto
Common
Load
Functional Devices, Inc. : American Made. American Owned.
Track Relays
15 Amp
RIBMU1SM
RIBMH1SM
RIBMNU1SM
RIBMNH1SM
DI 1
Open
Open
Closed
Closed
DI 2
Open
Closed
Open
Closed
Result
Overridden Off
Auto
Overridden On
Error Condition
High Voltage Optoisolated Relays
Optoisolated relays help isolate noisy loads from the controller. Good for controlling power relays from analog outputs.
60 Hz ac
Controller
Power
Supply
Load
Relay
Digital Out
Enclosed Relays
RIBTE01B
RIBTE02B
RIBTE01SB
RIBTE02SB
RIBTE01P
RIBTE02P
Track Relays
RIBME2401B
RIBME2402B
RIBME2401SB
RIBME2402SB
RIBME2401P
RIBME2402P
Opto
Input
(or Analog Out)
Opto RIB®
Low Voltage Optoisolated Relays
Optoisolated relays help isolate noisy loads from the controller. Good for controlling power relays from low power
digital or analog outputs.
60 Hz ac
Controller
Power
Supply
24 Vac/dc
Load
Relay
Enclosed Relays
RIBTELC
RIBTELS
RIBTE24B
RIBTE24SB
RIBTE24P
Track Relays
RIBME2401B
RIBME2402B
RIBME2401SB
RIBME2402SB
RIBME2401P
RIBME2402P
Opto
Input
Analog or Digital Out
Opto RIB®
Polarized Relays
Relays are polarized to work in a supervised system and may be turned on and off by reversing polarity.
For fire alarm systems, smoke control systems, etc.
Load
Load
RIB24C-FA
RIB24C-FA
+
Coil
–
+
Coil
Enclosed Relays
RIB12C-FA
RIB24C-FA
RIB12S-FA
RIB24S-FA
RIBT24B-FA
RIB24P-FA
–
Track Relays
RIBMN12C-FA
RIBMN24C-FA
RIBMN12S-FA
RIBMN24S-FA
End of
Line
Resistor
Controller
Signaling Circuit
800.888.5538 : www.FunctionalDevices.com
5
Condense Work Space and Wiring (Power Control)
Power Control Centers allow you to save large amounts of time, space, and wiring throughout your panel.
Before
After
There is a lot of extra wiring in this enclosure
which not only takes up space but also increases
the difficulty and time associated with installation.
By using one of Functional Devices' Power Control
Centers you will greatly reduce installation time, as
well as save space in your enclosure.
Conduit
Enclosed 4 Amp
PSPT2RB4
PSPW2RB4
Enclosed 10 Amp
PSPT2RB10
PSPW2RB10
Conduit
Power Control Center is pre-wired
Enclosure
Enclosure
Switch
To remainder
of panel
H
N
G
H
N
G
Fuse
Switch, Breaker &
Indicator Light
To remainder
of panel
Sub-Panel
Sub-Panel
Condense Work Space and Wiring (Power Supplies)
The PSC, PSH, and PSB Series Power Supplies allow you to save large amounts of time, space, and wiring
throughout your panel.
Before
After
There is a lot of extra wiring in this enclosure
which not only takes up space but also increases
the difficulty and time associated with installation.
By using one of Functional Devices' Power
Supplies you will greatly reduce installation
time, as well as save space in your enclosure.
Conduit
Enclosure
H
N
G
H
N
G
Fuse
24
Vac
Sub-Panel
To remainder
of panel
Conduit
Power Supplies are pre-wired
Enclosure
Switch
Power Supplies
Any models ending in “B10” in the PSC,
PSH, or PSB Power Supply Series
24Vac Switch/Breaker
120Vac from
10A Switch &
CB to remainder
of panel
24Vac
24Vac
Indicator
Power Supply
Main Power
10A Switch/CB & Indicator Light
Sub-Panel
Switch in a Box Enclosed Controls
Pre-labeled 20 Amp switches are great for new installations or last minute corrections to controls jobs. Switch labels
may be custom selected when ordering.
2 Position
Summer
Winter
Heat
Cool
(Winter)
(Summer)
2 Position
SIB04S
SIB05S
To A/C
Power In
3 Position
24 Vac
Hand
Off
Auto
Contactor
Coil
Controller
Digital Out
6
24Vac Transformer
DO From Controller
Hand
Off
Auto
Contactor Coil
Functional Devices, Inc. : American Made. American Owned.
3 Position
SIB02S
SIBLS
Electronic Air Cleaner
Models RIBXGHF, RIBXGHTF, RIBXGHA, or RIBXGHTA can be used to control an electronic air cleaner based on whether
or not the blower motor is turned on.
LO
HI
Blower
RIBXGHF, RIBXGHTF,
RIBXGHA, or RIBXGHTA
C
Motor
When current drawn
by Blower Motor
exceeds RIBXGH
threshold, SPST
contacts connect
120Vac source to
line input of
Air Cleaner.
120Vac Source
Neutral
Electronic Air Cleaner
Humidifier Control
Solid and split core current sensors can be used along with a humidistat for control of a humidifier based on whether
or not the blower motor is turned on.
Enclosed Mini Current Sensors
RIBXKF
RIBXKTF
RIBXKA
RIBXKTA
RIBXGF
RIBXGTF
RIBXGA
RIBXGTA
Enclosed Mini
Current Sensor
LO
HI
Blower
Humidistat
C
Motor
24Vac
Humidifier
COM
Occupancy Sensor on Open Protocol Network
A LonMark® certified or a BACnet® compatible relay with a digital input can be used with an occupancy sensor in a room
and turn on and off loads based on that status. This saves the cost of buying a LonMark® compatible or BACnet®
compatible occupancy sensor by utilizing the digital input on our device.
Network
24 Vac/dc
LonMark® Certified Relays
RIBTW2401B-LN
RIBTW2402B-LN
RIBTW2401SB-LN
RIBTW2402SB-LN
LonMark® Certifed or
BACnet® Compatible Relay
Class II Dry Contact Input
BACnet® Compatible Relays
RIBTW2401B-BC
RIBTW2402B-BC
Occupancy Sensor
Line
Neutral
Org
Yel
Load
800.888.5538 : www.FunctionalDevices.com
7
Loop-Powered RIBXK420 Series and
RIBXG420 Series (High-Accuracy)
Control Optoisolated Relay with
4-20mA Loop
Add 250Ω across Optoisolated Relay 5-25 Vdc control input.
Relay turns on at approximately 10mA and off at 8mA.
Mini Current Sensor
Mini Current Sensor
DC Supply
-
DC Supply
Load Wire
-
+
Load Wire
+
RED +
RED +
BLACK -
*Add 250 Ohms for
1-5 Vdc Analog In
-
*Add 250 Ohms for
1-5 Vdc Analog In
BLACK 250Ω
+
4-20 mA Analog In
*1-5 Vdc Analog In
Controller
Enclosed Mini Current Sensors
RIBXK420-20
RIBXK420-50
RIBXK420-100
RIBXG420-20
RIBXG420-50
RIBXG420-100
Enclosed Relays
RIBTELC
RIBTELS
RIBTE24B
RIBTE24SB
RIBTE24P
Track Relays
RIBME2401B
RIBME2402B
RIBME2401SB
RIBME2402SB
RIBME2401P
RIBME2402P
Self-Calibrating Current Sensors
Enclosed Mini
Current Sensors
RIBXK420-20
RIBXK420-50
RIBXK420-100
RIBXG420-20
RIBXG420-50
RIBXG420-100
The self-calibrating current sensor begins its 30 second self calibration process the first time current is applied within the operating
range. This procedure uses the user selected differential to set the trip threshold at a 15% or 25% level. Selection is completed prior
to install using the appropriate DIP switch setting, keeping the installer’s hands away from possible shock hazard, as well as saving
installation time.
( OLD WAY )
( NEW WAY )
Danger!!!
Safe
Line
Line
New
RIBXGA-SCAL
Old
Manual Sensor
Open Cover
Closed Cover
Motor
Starter
Load
Screwdriver
Hands and tools exposed
to high voltage while
adjusting potentiometer of
current sensor
8
Self-Calibrating Current Sensors
RIBXGA-SCAL
RIBXGTA-SCAL
Motor
Starter
Load
Hands safely away
from high voltage because
SCAL adjusts itself
Functional Devices, Inc. : American Made. American Owned.
Echelon® Thermistor-In Application
A thermistor is used to read the temperature of a room or area. That data is fed back to the LonWorks® system. When the
temperature is out of range, the relay is commanded by the network, activating the exhaust fan, heater, or other
device. A current sensor is used to feed back load status to the network. If there is a command and status mismatch, the
network can issue an alarm to the operator’s console.
LonMark® Compatible Relay
Enclosed Relay
RIBTW24SB-LNT2
RIBTW24SB-LNT3
Room or Area
Digital Input
FT-10 Network
Track Relay
RIBMW24SB-LNT2
RIBMW24SB-LNT3
Thermistor
24 Vac/dc
Relay Output
COM
Exhaust Fan
Line
Heater
or
RIBX Series
Neutral
Enclosed Mini Current Sensors
RIBXGF
RIBXKF
RIBXGTF
RIBXKTF
RIBXGA
RIBXKA
RIBXGTA
RIBXKTA
RIBXGFL
RIBXGTFL
Echelon® Relay / Current Sensor Application
Save time, money, and messy wiring. LonMark® certified relay contains an internal current sensor for load status. Relay control and
load status are easily accessible from the FT-10 Network.
LonMark® Certified Relay & Current Sensor
FT-10 Network
24 Vac/dc
}
Enclosed Model
RIBTWX2401SB-LN
RIBTWX2402SB-LN
A/C Line Power
Internal
Current
Status
COM
Exhaust Fan
Relay
Heater
Track Model
RIBMNWX2401SB-LN
RIBMNWX2402SB-LN
or
800.888.5538 : www.FunctionalDevices.com
9
Delay on Break (DOB) Time Delay
Load 2 stays on selected amount of time after load 1 goes off.
In this example, voltage can be
any voltage from 120-277 Vac.
Load 1
Blu
(Thermostat Controlled
Heater, for example)
Time Delay Relays
RIBD2421C
Wht/Brn
Blu
Wht/Yel
Yel
Load 2
(Circulating Fan,
for example)
Neutral
Yel
RIBD2421C
RIB®
Select RIB® with coil input
appropriate to sense Load 1.
Echelon® Analog-In Application
Simple and easy load control and status along with analog input provide everything needed to control and
interface to your HVAC application. Save the expense of a controller for smaller remote jobs or complete larger
jobs, as well.
RIBMW24SB-LNAI or RIBTW24SB-LNAI
+5Vdc or
+10Vdc
Digital Input
FT-10 Network
COM
24 Vac/dc
COM
Air Filter
Differential
Pressure
Transducer
Enclosed Relay
RIBTW24SB-LNAI
Track Relay
RIBMW24SB-LNAI
Enclosed Mini Current Sensors
RIBXGF
RIBXKF
RIBXGTF
RIBXKTF
RIBXGA
RIBXKA
RIBXGTA
RIBXKTA
RIBXGFL
RIBXGTFL
Relay Output
HVAC Fan
Line
RIBX Series
Neutral
Activate Load for Pre-Determined Time Using Dry Contact Input / Time Delay
Relay and Normally Closed Switch
Local Power
Neutral
Hot
Wht/Blk
Wht/Blk
• Activate (open) switch until load comes on.
• Release switch.
• Load will be powered until time delay exprires.
Blu
Wht/Red
Normally
Closed
Switch
Fan
Dry
Contact
Wires
Yel
(Not provided)
Enclosed Relays
RIBD01BDC
RIBD02BDC
Wht/Blu
Org
Wire Nut
RIBD01BDC – 120 Vac operation
RIBD02BDC – 208-277 Vac operation
Neutral
10
Functional Devices, Inc. : American Made. American Owned.
AM578M