* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Draft Information Document Generating Unit Technical Requirements ID# 2011-012R
Telecommunications engineering wikipedia , lookup
Opto-isolator wikipedia , lookup
Power inverter wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Transmission line loudspeaker wikipedia , lookup
Electric power system wikipedia , lookup
Three-phase electric power wikipedia , lookup
Electrification wikipedia , lookup
Power MOSFET wikipedia , lookup
Buck converter wikipedia , lookup
Power electronics wikipedia , lookup
Stray voltage wikipedia , lookup
Voltage regulator wikipedia , lookup
Surge protector wikipedia , lookup
Amtrak's 25 Hz traction power system wikipedia , lookup
Electrical substation wikipedia , lookup
Power engineering wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Voltage optimisation wikipedia , lookup
Alternating current wikipedia , lookup
Draft Information Document Generating Unit Technical Requirements ID# 2011-012R Information documents are for information purposes only and are intended to provide guidance. In the event of any discrepancy between the information document and the related authoritative document(s) in effect, the authoritative document(s) governs. Please submit any questions or comments regarding this information document to [email protected]. 1 Purpose and Background This information document supports section 502.5 of the ISO rules, Generating Unit Technical Requirements and provides additional guidance which may be of interest to legal owners of synchronous generating units in Alberta. This guidance, as well as any examples provided hereinin this information document, are not meant to be authoritative, and do not introduce any additional requirements for market participants; they. They are intended only as information. To assist users, the AESO has cross-referenced each subsection in this information document with the corresponding subsection in section 502.5. 2 Related Authoritative Documents The AESO’s authoritative documents consist of ISO rules, the ISO tariff and the Alberta reliability standards. Authoritative documents contain binding rights, requirements and obligations for market participants and the AESO. Market participants and the AESO are required to comply with provisions set out in its authoritative documents. Market participants are encouraged to review the following related authoritative documents: Section 502.5 of the ISO rules, Generating Unit Technical Requirements Section 502.5 sets out the minimum technical requirements for a new synchronous generating unit connecting to the transmission system, one already connected and in existence, and one already connected and in existence which is undergoing a material change to any components comprising the generating unit Section 502.6 of the ISO rules, Generating Unit Operational Requirements Section 502.6 sets out operating requirements for a legal owner of a generating unit to operate the generating unit as it is designed to operate. Section 304.4 of the ISO rules, Maintaining Network Voltage Section 304.4 sets out voltage adjustment requirements for generating units. Alberta Reliability Standard VAR-001-AB-1a Voltage and Reactive Control VAR-001-AB-1a sets out requirements such that transmission voltage levels, reactive power flows, and reactive power resources are monitored, controlled and maintained within limits in real-time to protect equipment and the reliable operation of the Interconnection. Alberta Reliability Standard VAR-002-AB-1.1b Generator Operation for Maintaining Network Voltages VAR-002-AB-1.1b sets out requirements to ensure generating units and aggregated generating facilities provide reactive power and voltage control necessary to ensure voltage levels, reactive power flows and reactive power resources are maintained within applicable facility ratings to protect equipment and the reliable operation of the Interconnection. Alberta Reliability Standard VAR-002-WECC-AB-1 Automatic Voltage Regulators and Voltage Regulating Information Document Effective: xxxx-xx-xx Page 1 Public Information Information Document Generating Unit Technical Requirements ID# 2011-012R Draft Information Document Generating Unit Technical Requirements ID# 2011-012R Systems VAR-002-WECC-AB-1 sets out requirements to ensure that automatic voltage regulators on generating units and synchronous condensers are in service and controlling voltage; and voltage regulating systems at aggregated generating facilities are in service and controlling voltage. Alberta Reliability Standard VAR-501-WECC-AB-1 Power System Stabilizer VAR-501-WECC-AB-1 sets out requirements to ensure that power system stabilizers on generating units are kept in service. AESO Protection Standard The AESO Protection StandardSection 502.3 of the ISO rules, Interconnected Electric System Protection Requirements Section 502.3 sets out the minimum level of protection for facilities connecting to the transmission system prior to the effective date of section 502.5. 23 Functional Specification (Corresponds to section 502.5, subsection 2) Section 502.5 sets out the expectations regarding functional specifications. The AESO recognizes that legal owners that connected a generating unit to the transmission several years ago may not have received a functional specification. In these cases, as described in section 502.6, the AESO will work with the legal owner and create a functional document setting out the important operational parameters associated with that generating unit such that the legal owner and the AESO are clear and aligned on the operating capabilities of the generating unit. Please refer to section 502.6 and AESO Information Document 2012-023R for additional information. 34 Maximum Authorized Real Power (Corresponds to section 502.5, subsection 4) This example is intended to provide guidance on how maximum authorized real power is determined. (a) maximum authorized real power = 100.0 MW; (b) lagging reactive power obligation (0.90 power factor) = 48.4 MVAr; (c) leading reactive power obligation (0.95 power factor) = 32.9 MVAr; and (d) MVA rating at this value = 111.1 MVA. In many cases the maximum authorized real power will not be the same as the nameplate rating. Examples include: (a) A generating unit with a nameplate of 100 MVA at 0.85 power factor that has a rated output of 85 MW. Section 502.5 only requires the generating unit to operate up to 0.90 power factor which could result in this same generating unit being able operate at 90 MW and still meet the requirements of section 502.5. (b) A generating unit equipped with a gas turbine and a nameplate of 100 MVA at 0.90 power factor that has a rated output of 90 MW. The nameplate rating of gas turbines are for specific temperatures and pressures; in. In Alberta, the colder temperatures allow gas turbines to operate at values significantly above the nameplate values. Depending on the generating unit cooling and automatic voltage regulator supplied with the generating unit, the outputgenerating unit may be able to achieve an output over 110 MW and still be in compliance with the requirements of Information Document Effective: xxxx-xx-xx Page 2 Public Information Information Document Generating Unit Technical Requirements ID# 2011-012R Draft Information Document Generating Unit Technical Requirements ID# 2011-012R section 502.5. (c) There are other factors which could result in the maximum authorized real power not being the same as the nameplate rating, including the capability of the turbine, shaft or coupling ratings, etc. An example would be a generating unit that has a turbine capable of producing 200 MW andwhich is coupled to a generator that is also capable of 200 MW at 0.90 power factor. The coupling may only have a rating of 190 MW; in this case, this would be the maximum authorized real power for this generating unit. Section 502.5 requires a legal owner to consider the under and over-excitation limiter settings when determining the maximum authorized real power. If the limiters cause the reactive power capability of the generating unit to be reduced such that the 0.90 or 0.95 power factor requirements cannot be met, then the maximum authorized real power will be reduced accordingly. As part of the AESO’s connection process, the legal owner may apply to the AESO to mitigate this through the use of external dynamic reactive power resources such as static VAr compensators, synchronous condensers, etc., which the AESO will document in the functional specification for the generating unit 45 Voltage Ride-Through for Existing Generating Units (Corresponds to Section 502.5, subsection 6) When determining the voltage ride-through capability for an existing generating unit, the legal owner should consider the voltage level at the point of connection which would be used as the 100% voltage for the voltage ride-through requirements. In Alberta, voltages may vary considerably from the nominal voltage. For example the voltages at Anderson substation area are listed in Table 1 below: Table 1 - Anderson Substation Voltage Substation Name and Number Nominal Voltage (kV) Anderson A801S Minimum Operating Limit (kV) Desired Maximum Range Operating Limit (kV) (kV) 240 255 257 - 268 275 144 145 146 - 152 155 As illustrated in Table 1 for both the nominal 144 kV and 240 kV levels, the minimum operating limit is above the nominal voltage value and the desired range can exceed ten percent (10%%) above the nominal voltage value. The AESO plans the transmission system to operate at voltage levels of +/-plus or minus five percent (+/- 5%%) for N-0 (normal system) and plus or minus 10%ten percent (+/- 10%) for N1 contingencies. Based on the AESO’s operating practices, it is necessary for the AESO to ensure that the generating units will remain on-lineonline during N-1 contingencies. The length of time that the transmission system operates at the higher limits is dependent on the nature of the contingency and as such, the generating units are required to operate continuously at the limits. A generator trip is when the generating unit breaker or the transmission system breaker that supply the generating unit open based on a trip signal from the generating unit protection. This protection may be electrical, mechanical or process based. The AESO suggests that the legal owner of the facility consider the following factors when determining the voltage ride -through capability: (a) protection functions pick-up, time out and results in the generatorgenerating unit or critical device(s) tripping; Information Document Effective: xxxx-xx-xx Page 3 Public Information Information Document Generating Unit Technical Requirements ID# 2011-012R Draft Information Document Generating Unit Technical Requirements ID# 2011-012R (b) contactors drop out, causing a critical device to go off- line; (c) critical motors stallstalling; and (d) other conditions that will result in the generating unit going off-line as a direct result of the voltage disturbance. In addition, the legal owner should consider the same factors for the post -transient voltage deviations as defined withset out in section 502.5. In appendix 1 of section 502.5, the solid line defines the transmission system voltages for which the generating unit must ride-through and the shaded area defines the time frame that the generating units and auxiliary systems must stay on-line for. Section 502.5 refers to normal clearing times. However, the specific clearing times are not set out in section 502.5 because they are set out in the AESO’s Protection Standard.Transmission Reliability Criteria, Part II System Planning. In some cases, the normal fault clearing times are greater or less than the typical values shown in the AESO’s Protection Standard.section 502.3. In these cases, if the clearing time is: (a) greater than nine (9) cycles, as section 502.5 specifies 49four (4) to nine (9) cycles, use nine (9) cycles for the study; or (b) less than four (4) cycles, as section 502.5 specifies 4to four (4) to nine (9) cycles, use four (4) cycles for the study. If the legal owner of the generating unit is unsure of the values to be useduse, the AESO suggests that the legal owner contact the legal owner of the transmission facility to which the generating unit is connected. 56 Voltage Ride-Through for New Generating Units (Corresponds to section 502.5, subsection 7) Section 502.5, subsection 7 sets out voltage ride-through requirements for new generating units. The concepts of how the voltage ride-through is determined is similar to the approach described above for existing generating units. . 67 Voltage Regulation (Corresponds to section 502.5, subsection 8) The AESO uses the term “point of control” in regards to the automatic voltage regulators to describe the electrical point controlled by the automatic voltage regulator. Generally, this is the same point as the voltage input to automatic voltage regulator which is typically the stator winding terminals of the generating unit. Automatic voltage regulators commonly have control features that allow the point of control to be moved away from voltage input to the automatic voltage regulator. This control feature is commonly referred to as reactive current compensation or, in some cases, voltage droop. Figures 2 through 4 provide examples onof various points of control to provide additional guidance. Figure 2 Point of Control, Simplified Impedance Diagram Of a Single Generating Unit Information Document Effective: xxxx-xx-xx Page 4 Public Information Information Document Generating Unit Technical Requirements ID# 2011-012R Draft Information Document Generating Unit Technical Requirements ID# 2011-012R Point of Control range the AESO may consider as per section 502.5 Stator Winding Terminals Point of Control as per section 502.5 Transmission System Transmission System Step-up Transformer Automatic Voltage Regulator Figure 3 - Point of Control, Simplified Impedance Diagram Of Multiple Generating Units on a Common Bus Automatic Voltage Regulator Automatic Voltage Regulator Stator Winding Terminals Common bus Automatic Voltage Regulator Transmission System Transmission System Step-up Transformer Point of Control as per section 502.5 Information Document Effective: xxxx-xx-xx Page 5 Public Information Information Document Generating Unit Technical Requirements ID# 2011-012R Draft Information Document Generating Unit Technical Requirements ID# 2011-012R Figure 4 - Point of Control, Simplified Impedance Diagram Of Multiple Generating Units with a Single Measurement Point Transmission System Step-up Transformer Automatic Voltage Regulator Stator Winding Terminals Automatic Voltage Regulator Transmission System Point of Control range the AESO may consider as per section 502.5 78 Frequency and Speed Governing Requirements (Corresponds to section 502.5, subsection 9) Section 502.5 states that a generating unit is required to have a governor system with droop control. This requirement is in place to assist the AESO in maintaining sixty (60) Hz nominal frequency during: (a) normal system operation that includes fluctuation in load; (b) system disturbances; and (c) islanded operation of a generating unit from the larger transmission system along with some load external to the generating facility. Such an island may include other generating units. During any of the above mentioned conditions, the generating unit may (but is not required to in accordance with the section 502.5) trip off-line if the frequency goes outside of the boundaries illustrated in Appendix 3 of section 502.5. As additional guidance on how droop control works, the AESO offers the following guidance.: (a) Generating units that are base loaded, (i.e. operating at full load) are not expected to respond to low frequency excursions but with the governors free to react these generating units, would respond to high frequency excursions. This includes the steam turbine generators portion of a combined cycle or co-generation facilities. (b) During islanded operation, the operator of a generating unit does not have visibility of the transmission system or the actions of other generating units, therefore adjustments to the generating unit frequency should be coordinated through the AESO system controller. 89 Power System Stabilizer (Corresponds to section 502.5, subsection 10) Section 502.5 setsets out the conditions which require the legal owner of a generating unit to install a power system stabilizer. For additional information on how power system stabilizers work please refer to: Criteria to Determine Excitation System Suitability for PSS in WSCC System: Information Document Effective: xxxx-xx-xx Page 6 Public Information Information Document Generating Unit Technical Requirements ID# 2011-012R Draft Information Document Generating Unit Technical Requirements ID# 2011-012R http://www.wecc.biz/library/WECC%20Documents/Documents%20for%20Generators/Power%20System %20Stabilizers%20Criteria%20to%20Determine%20Excitation%20System%20Suitability.pdf WECC Power System Stabilizer Design and Performance Criteria: http://www.wecc.biz/library/WECC%20Documents/Documents%20for%20Generators/Power%20System %20Stabilizer%20Design%20and%20Performance%20Criteria.pdf Information Document Effective: xxxx-xx-xx Page 7 Public Information Information Document Generating Unit Technical Requirements ID# 2011-012R Draft Information Document Generating Unit Technical Requirements ID# 2011-012R 910 Transmission System Step-Up Transformer (Corresponds to section 502.5, subsection 11) For additional guidance on transformer sizing, the AESO offers the following guidance: (a) In order to meet the requirements of subsection 11 of the section 502.5, the thermal capability of the transformer must be equal to the apparent power of the generating unit (the vector addition of the maximum authorized real power and the reactive power obligation) minus any loads that may be tapped -off between the stator winding terminals and the transmission system step-up transformer. Figure 5 illustrates this concept. (b) The thermal capability is not necessarily the nameplate rating of the transformer. The legal owner may use a higher apparent power capability than the nameplate rating of the transformer. This higher apparent power capability would be acceptable as a variance if submitted with a report that is stamped by an Alberta accredited engineer that documents the basis for the higher capability. Figure 5 -Transmission System Step-Up Transformer Sizing Example Maximum authorized real power = 100 MW Lagging reactive power requirements (0.90 power factor) = 48.4 MVAr Acceptable minimum transformer ratings ONAN = 100MVA ONAN/ONAF = 75/100 MVA ONAN/ONAF/OFAF = 60/80/100 MVA Apparent power = 111.1 MVA Stator Winding Terminals 100.0 MVA 111.1 MVA 1.0 MVA 10.1 MVA Power Potential Transformer Unit Service Transformer Excitation System Auxiliary Systems Transmission System Step-up Transformer In this example all loads are assumed to be 0.90 power factor 11 Auxiliary Systems (Corresponds to section 502.5, subsection 12) The AESO offers the following guidance on auxiliary systems: (a) As pertaining to generating stations, IEEE defines auxiliary as “any item not directly a part of a specified component or system but required for its functional operation”. (b) The Electric Utilities Act defines a generating unit as: “the component of a power plant that produces, from any source, electric energy and ancillary services, and includes a share of the following associated facilities that are necessary for the safe, reliable and economic operation of the generating unit, which may be used in common with Information Document Effective: xxxx-xx-xx Page 8 Public Information Information Document Generating Unit Technical Requirements ID# 2011-012R Draft Information Document Generating Unit Technical Requirements ID# 2011-012R other generating units: (i) fuel and fuel handling equipment; (ii) cooling water facilities; (iii) switch yards; (iv) other items.”. Based on both of the above definitions, it is the AESO’s opinion that the legal owner should consider all components supplying and within the facility that are crucial to the normal operation of the facility as part of the auxiliary systems. 11 Synchrophasor Measurement System (Corresponds to section 502.5, subsection 18) Section 502.5 makes reference to other ISO rules that may contain requirements regarding synchrophasor measurement devices. The AESO encourages market participants to review section 502.9 of the ISO rules, Phasor Measurement Unit Technical Requirements which sets out requirements for a legal owner implementing synchrophasor measurement device. The AESO offers the following guidance on the requirements regarding the installation of a synchrophasor measurement device when replacing protections systems: (a) Most modern generating units are installed with multi-functions relays. Replacement of one of these relays on a planned basis triggers the requirement for a synchrophasor measurement device. It is the AESO’s opinion that most modern multi-function protection relays have synchrophasor measurement capabilities which meet the requirements of section 502.5. (b) For older generating units with protection systems comprised of single element relays, it is the AESO’s opinion that unless the legal owner is replacing a single element due to failure (an unplanned replacement) then the legal owner would generally install a multi-function relay. Such a change triggers the requirement for a synchrophasor measurement device. The AESO also notes that many modern single element relays also have synchrophasor measurement capability. Revision History Effective Date Description of Changes Yyyy-mm-dd yyyy-mm-dd Information Document Effective: xxxx-xx-xx Page 9 Public Information