Installation Instructions
Dual Technology Wall/Corner Mounted Low
Voltage Occupancy Sensor
Model # OAWC-DT-120W
Model # OAWC-DT-120W-R
P/N 9850-000137-01
Location
• ForUsewithGreengateSwitchpacks&Systems
Only
• DonotrunanyGreengateLowVoltageWiringin
thesameconduitaspowerconductors
Specifications
Technology:PassiveInfrared(PIR)andUltrasonic(US)
Power Requirements:
Input:
• 10-30VDCfromGreengateSwitchpackorGreengate
system.Maximumcurrentneededis25mApersensor
Output:
• OpencollectoroutputtoswitchuptotenGreengate
Switchpacks.BASwithIsolatedFormCRelay(-R
model)IsolatedFormCRelayRatings:1A30VDC/VAC
Time Delays:Self-Adjusting,15seconds/test(10minAuto)
orSelectable5,15,30minutes
Coverage:1200sq.ft.
Light Level Sensing:0to300foot-candles(-Rmodel)
Operating Environment:
• Temperature:32°F–104°F(0°C–40°C)
• RelativeHumidity:upto90%non-condensing
Housing:
• Mediumimpactinjectionmoldedhousing
• PolycarbonateresincomplieswithUL94V0
Size:4.4"x3.4"x2"(112mmx86.4mmx50.8mm)
LED Indicators:RedindicatesPIRdetection;Green
indicatesUltrasonicdetection
Themaximumcoverageareamayvarysomewhataccordingtoroomshapeand
thepresenceofobstacles.Followthecoveragediagramconcerningmajorandminor
motioncoverage.Decreasetotalcoverageareaby15%for“soft”rooms(forexample,
heavydraperiesorheavycarpeting).Thesensormusthaveaclearviewofthearea
tobecontrolled.Thesensorwillnot“see”throughglass.Mountingheightshouldnot
exceed12feet.Optimummountingheightis10feet.Mountthesensorsothegrilles
facetheopenportionoftheroomandarenotfacinganearbywall,door,windowor
otherobstructingobject.Avoidpointingintohallways.Topreventfalseactivation,the
sensorshouldbemountedawayfromtheairsupplyductaminimumof4to6feet.
Mountingatfixtureheightismosteffective.FortypicalplacementrefertoLocation
Diagram.
Location Diagram
Installation
Wiring
TheOAWC-DT-120Wcanbemountedtothewall,ceiling,junctionbox,orroundfixturewithraceway.
Description
1. MakesurepoweristurnedOFFatthebranchcircuitbreaker.
2. Wireunitsasshowninwiringdiagramsperapplicablevoltagerequirements.(Usetwist-onwireconnectorsforall
connections)CAPALLUNUSEDWIRELEADS.
3. Mountunittowall,ceiling,junctionboxorroundfixturewithraceway.
4. TurnpowerbackONatthebranchcircuitbreakerandwaittwominutesfortheunittostabilize.
5. Makenecessaryadjustments.(SeeCheckoutandAdjustmentssection)
Occupancy Sensor Mounted to Wallboard
Occupancy Sensor Mounted to Drop Ceiling
Hot
Occupancy Sensor Mounted to Octagon Box
12’
(3.7)
Minor Motion, IR
8’
(2.4 mm)
Major Motion, IR
0
Minor Motion, Ultrasonic
8’
(2.4 mm)
Major Motion, Ultrasonic
One Sensor, One Switchpack
Line
Coverage
24’
(7.3 mm)
20’
(6 mm)
CAUTION: Before installing or performing any service on a Greengate system, the power MUST be turned OFF at the
branch circuit breaker. According to NEC 240-83(d), if the branch circuit breaker is used as the main switch for a
fluorescent lighting circuit, the circuit breaker should be marked “SWD”. All installations should be in compliance
with the National Electric Code and all state and local codes.
NOTE REGARDING COMPACT FLUORESCENT LAMPS: The life of some compact fluorescent lamps (CFLs) is shortened by
frequent automatic or manual switching. Check with CFL and ballast manufacturer to determine the effects of cycling.
SENSOR WIRE LEAD LEGEND
Neutral
Black
(Common)
Red
(10-30 VDC)
**Use Black Lead for 120 VAC
Blue
(Control)
Use Orange Lead for 277 VAC
Yellow
(Control)
Cap Unused Lead Black (Common)
Brown
(Switch-Blue Lead Control)
Blue
Brown/White (Switch-Yellow Lead Control)
Red (15 VDC)
Blue (Control)
Sensor’s Isolated Relay
Switchpack
Orange (Normally Open)
Gray
(Common)
To Additional Sensors.
Purple
(Normally closed)
Maximum of 5 sensors
per switchpack.
**Hot
TheOAWC-DTWall/CornerMountLowVoltageOccupancySensorisaPassiveInfrared(PIR)andUltrasonic(US)motion
sensinglightingcontrol,usedforenergysavingsandconvenience.PIRisusedtoturnthelightsONandtheneitherorboth
technologiesareusedtokeepthelightsON.Whenmotionisdetected,thebluewireiselectronicallyconnectedtothered
wire,energizingtherelayintheswitchpacktoturnONtheload.Ifvacancyisdetected,thebluewireisdisconnectedfrom
thered,causingtherelaytoopenturningOFFtheload.Theredleadis10-30VDCsupply,theblackleadiscommonandthe
blueistherelaycontrol.
Thesensorincludesself-adaptivetechnologythatcontinuallyadjuststoconditionsbyadjustingsensitivityandtimedelay
inreal-time.
TheDaylightingfeature(-Rmodelonly)preventslightsfromturningONwhentheroomisadequatelyilluminatedby
naturallight.
TheWalk-ThroughfeaturemaximizesenergysavingsbynotleavingthelightsONaftermomentaryoccupancy.Thesensor
willswitchthelightsONwhenitdetectsapersonenteringthearea.Ifthesensordoesnotcontinuetodetectmotion30
secondsfollowingtheinitialactivation,itwillautomaticallygotoashorter2minutetimedelay.
InAutomaticONMode,thelightsturnONwhenapersonenterstheroom.InManualOnMode,thelightsareturnedON
byactivatingamomentaryswitch(model#GMDS-*)thatisconnectedtothesensor.Whenusedwith2levellighting
(-Rmodelonly),bi-levelAutomaticONcanbeachievedwhichallowsZone1tocomeONautomaticallyuponoccupancy.
Zone2doesnotcomeONunlesstheoccupantpressestheoptionalmomentaryswitch.
Occupancy Sensor Mounted to Round Fixture with Raceway
Maximum coverage area may
vary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and robotic
method were utilized to verify
coverage patterns.
Black
Red
Blue
Yellow
Brown
Brown/White
Orange
Gray
Purple
Blue
• Readallinstructionsonbothsidesofthissheet
first
• InstallinaccordancewithALLlocalcodes
• Forindooruseonly
White
General Information
Load 1
Optional Greengate GMDS SwitchBlue Control Lead-Manual ON/OFF
Recommended Wire: 18-3 AWG stranded non-shielded
12’
(3.7)
10 ft
(3 mm)
24’
(7.3 mm)
20’
(6 mm)
6 ft
15 ft
(1.7 mm) (4.6 mm)
24 ft
(7.3 mm)
50 ft
(15.3 mm)
Occupancy Sensor Mounted to Octagon Box with Mud Ring
Eaton’s Cooper Controls Business
203 Cooper Circle
Peachtree City, Georgia 30269
www.coopercontrol.com
One Sensor, Multiple Switchpacks
Hot
Hot
Line
Black(Common)
Red (15VDC)
Blue (Control)
Switchpack
Sensor's Isolated Relay
Orange
(Normally Open)
Gray
(Common)
Purple
(Normally Closed)
Black(Common)
Red (15VDC)
Blue (Control)
Switchpack
Blue
Blue
White
Neutral
**Use Black Lead for 120VAC
Use Orange Lead for 277VAC
Load 1 Cap Unused Lead
Blue
**Use Black Lead for 120VAC
Use Orange Lead for 277VAC
Cap Unused Lead
White
Neutral
**Hot
Line
**Hot
SENSOR WIRE LEAD LEGEND
Black
(Common)
Red
(10-30VDC)
Blue
(Control)
Yellow
(Control)
Brown
(Switch-Blue Lead Control)
Brown/White(Switch-Yellow Lead Control)
PIR Sensitivity
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheRedLEDdoesnotturnON,checkforanyobstructions.
3. Standstillsixtoeightfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.
4. IfRedLEDturnsONwithoutmotionorisconstantlyONadjustPIRsensitivityto50%bymovingDIPswitch5UP.
Load 2
Blue
To Additional Switchpacks
10 switchpacks Maximum
Black
Red
Blue
Yellow
Brown
Brown/White
Orange
Gray
Purple
Field-of-view outside the space
1. AdjustPIRsensitivityto50%bymovingDIPswitch5UP.
2. AdjustUltrasonicSensitivity.
Daylight Adjustments (-R model only)
Ifthisfeatureisnotneeded,leavethelightlevelatmaximum(fullyclockwise).
TheDaylightingfeaturepreventsthelightsfromturningONwhentheroomisadequatelyilluminatedbynaturallight.Ifthere
isenoughlightintheroomregardlessofoccupancy,thesensorwillholdthelightsOFF.Ifthereisnotenoughlightintheroom,
thesensorwillallowthelightstoturnONwhenoccupied.
Optional Greengate GMDS SwitchBlue Control Lead- Manual on/off
Full and Half Logic Modes(SeeDIPswitchlegend):
InbothFullandHalfLogicmodes,lightsconnectedtotheyellowcontrolleadwillnotturnONuponoccupancyactivation,
shouldtheambientlightlevelexceedthepresetfoot-candlelevel.
DIP Switch Settings
Time Delay
DIP Switch
Activation
Power Pack One
Activation
PIR Sensitivity
Walk-Through Mode
LEDs
Override
Lighting Sweep
Daylighting Mode
Power Pack Two
(-R model only)
(-R model only)
1
2
3
4
5
6
7
8
9
10
Checkout and Adjustment
AdjustmentsshouldbemadewiththeHVACsystemON.Useonlyinsulatedtoolstomakeadjustments.
Self-Adjust
SensorisshippedintheSelf-AdjustMode.Thisappliestotimedelay,US,andPIRsensitivity.Inpreparationforthe
InstallerTest,thetimedelayissetto15seconds,afterthesensorisinstalled,poweredONandhasstabilized,theunitwill
time-out15secondsafterthelastmotiondetected.CoverageandsensitivitycanbeconfirmedbywatchingtheGreen(US)
andRed(PIR)indicatorLEDsonthefrontofthesensor,whilemovingaroundtheroom.
1. WalkaroundtheroomandmonitorLEDs.LEDsshouldonlyturnONforonesecondwitheachmotion.(IfLEDsdonot
turnON,gotoInstallerAdjustments-SensitivityAdjustmentsSection)
2. Standstillsixtoeightfeetawayfromthesensorforfiveseconds.LEDsshouldnotturnON.(IfanyLEDturnsON,note
LEDandgotoInstallerAdjustments–SensitivityAdjustmentsection)
3. Walkoutsidetheroomandwait15secondsforthelightstoturnOFF.(IflightsdonotturnOFFgotoInstaller
AdjustmentsSection)
4. Re-entertheroomtoactivatesensor.(IflightsdonotturnONgotoTroubleshootingSection)
5. TheunitwillremaininTestModefor5 minutesthenautomaticallyexitTestModeandgofor10min.TimeDelayUser
Modesetting.
Note:ToplaceintoTestMode,toggleDIPSwitch10outofitscurrentposition,wait3seconds,andthenbackintoitsoriginalposition.Toforce
into10minUserModemoveDipSwitches1and2down.(IfDIPSwitches1and2arealreadydown,toggleDIPSwitch1outofitscurrentposition,
wait3seconds,andthenbacktoitsoriginalposition)WhileinTestMode,theLEDswillflashonceper1/4second.
Installer Adjustments
Sensitivity Adjustments
Ultrasonic Sensitivity(GreenLED)–Usingasmallflatheadscrewdriverturnthegreenpotentiometersothatthearrow
pointsUP.
1. Standindifferentareasoftheroomandwaveyourhands.
2. IftheGreenLEDdoesnotturnON,increasetheUSsensitivitybyturningthegreenpotentiometerclockwiseinsmall
increments.RepeatStep1.
3. Standstillsixtoeightfeetawayfromsensorforfiveseconds.LEDshouldnotturnON.
4. IfGreenLEDturnsONwithoutmotionorisconstantlyONdecreasetheUSsensitivitybyturningthegreen
potentiometercounter-clock-wiseinsmalldecrements.RepeatStep3.
Troubleshooting
Issue
Lights
Will Not
Turn ON
automatically
Lights
Will Not
Turn ON
manually
Time Delay Adjustments
PeoplewhoremainverystillforlongperiodsoftimemayneedalongerTimeDelaythanthedefaultsettingof10minutes.
AslongasAutoisenabled,thesensorwillrespondtoeachpairoffalse-OFFswithnonormalOFFinbetween,byalternately
makingslightadjustmentstoeithertimedelay(by2minuteincrements)orsensitivity,sothereshouldbenoneedformanual
adjustment.Ifmanualadjustmentisdesired,refertoTimeDelaysettingsinDIPswitchlegend.
ResetsensortimedelaytofactorysettingsbymovingDIPswitches1and2down.(IfDIPswitches1and2arealreadydown,
toggleDIPswitch1outofitscurrentposition,wait3seconds,andthenbacktoitsoriginalposition)
Automatic Mode
InAutomaticONMode,thelightsturnONwhenapersonenterstheroom.Ifoptionalmomentarylowvoltageswitchesare
usedalongwithAutomaticONMode,activatingtheswitch(es)whiletheloadisONturnstheloadOFF.Whentheloadisturned
OFFmanually,aslongasthesensorcontinuestodetectoccupancytheloadsstayOFF.Afterthetimedelayexpires,thelights
stayOFFandthesensorgoesbacktoAutomaticONMode.Forwiringinformationfortheoptionalmomentarylowvoltage
switch(es),pleaseseethewiringsectionoftheinstallationinstructions.
Manual Mode
InManualONMode,theoptionalmomentarylowvoltageswitch(es)isrequiredtoturntheload(s)ON.Onceactivatedthe
sensorwillmaintainthelightsONuntilmotionceasesandthetimedelayexpires.WhiletheroomisoccupiedtheBASrelay
remainsactive.Afterthetimedelayexpires,theload(s)willautomaticallybeturnedOFFandtheswitch(es)mustbeusedtoturn
theload(s)ONunlessthereismotiondetectedwithinthe10secondre-triggerperiod.
Suggestions
WallSwitchOFF
TurnWallSwitchON
Iflowvoltageswitchoptionisused,lights
mayhavebeenturned-offmanually
Presslow-voltageswitch
DaylightingFeatureEnabled
IfalllightsarerequiredtoturnONadjustDIP
Switch10and/ordaylightpotentiometer
Powerinterruption
Checkincomingvoltageand/orwiring
DaylightingFeatureEnabled
IfalllightsarerequiredadjustDIPswitch
10and/ordaylightpotentiometer
Powerinterruption
Checkincomingvoltageand/orwiring
If lights will still not turn ON, set sensor to override mode and call Technical Services at 1-800-553-3879
After activation:
FullLogicMode–shouldtheambientlightlevelexceedthepresetfoot-candlelevel,thelightsconnectedtotheyellow
controlleadwillturnOFF.ThelightswillremainOFF,untiltheambientlightlevelfallsbelowthesetpoint.
HalfLogicMode–theoutputstateoftheyellowcontrolleadwillnotchangewithambientlightchanges,afteroccupancy
activation.Iftheamountofnaturallightavailablerisesabovethesetpoint,thedaylightsensorwillnotturnthelightsOFFwhile
occupancyisbeingdetected.
Note:Setthelightlevelwhentheambientlightisatthelevelwherenoartificiallightisneeded.Inorderforthisfeatureto
function,theyellowcontrolleadmustbewired.
1. WiththeloadON,putthesensorintoTestMode.ToplaceintoTestMode,toggleDIPswitch10outofitscurrentposition,
wait3secondsandthenbackintoitsoriginalposition.
2. SetDIPswitch10toFullorHalfLogicMode.
3. Setthelightleveltominimum(fullyCCW).
4. Leavetheroomandletthesensortime-outsolightsareOFF.EnterthespaceandlightsshouldremainOFF.
5. MakesurenottoblockthesensorfromthedaylightsourceandadjustthelightlevelpotentiometerCWinsmallincrements
untilthelightsareON.(Pause5secondsbetweeneachadjustment)
6. OncethelightsareON,theloadconnectedtothesensorwillnotturnONiflightlevelsareabovethecurrentillumination.
Possible Causes
Lights
Will Not
Turn OFF
automatically
Lights Will Not
Turn OFF
automatically
Override
MakesuresensorisnotinOverrideMode(DIPSwitch8up)
UltrasonicSensitivitysetHigh
Lowersensitivitybyturninggreen
potentiometerCCWinsmalldecrements
Sensorinstalledclosetoanairvent
Sensorsshouldbeinstalledminimum4-6feetaway
fromanyairventandoutofpathofheavyairflow
Sensorinstalledclosetoindirectlighting
Sensorsshouldbemountedawayfromindirectlighting.
Self-adjust
Itmaybepossiblefortheunittohaveself-adjusted
thetimedelaytoa30minutedelay.Ifthelightsdo
notturnOFFafter30minutesfollownextstep
30MinuteDelay
Maximumtimedelayis30Minutes.CheckDIP
SwitchestoverifyDIPSwitchsettings.Iflightsdo
notturnOFFatthesettimedelay,checknextstep
PIRactivatedbyheat
sourceotherthanoccupant
MoveDIPSwitch5up
Bypass
Checkwiringtomakesuresensoror
switchpackarenotbypassed
Override
MakesuresensorisnotinOverrideMode(DIPSwitch8up)
If lights will still not turn OFF, call Technical Services at 1-800-553-3879
Warranties and Limitation of Liability
Pleaserefertowww.coopercontrol.comundertheLegalsectionforourtermsandconditions.
Lighting Sweep Option
Ifselected,thisDIPswitchoptionforcesaninitial60seconddelayupon“power-up”topreventfalseactivationinbuildings
withcomputercontrolsystems.
1. MoveDIPswitch9UP.
Override
TheOverridesettingallowsthelightstoremainONintheunlikelyeventofsensorfailure.
1. MoveDIPswitch8UP.
WhileinOverrideMode,theoptionallowvoltagemomentaryswitch(es)willtogglethelightingload(s).