* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download EE369 POWER SYSTEM ANALYSIS
Standby power wikipedia , lookup
Valve RF amplifier wikipedia , lookup
Opto-isolator wikipedia , lookup
Audio power wikipedia , lookup
Radio transmitter design wikipedia , lookup
Voltage regulator wikipedia , lookup
Standing wave ratio wikipedia , lookup
Power MOSFET wikipedia , lookup
Surge protector wikipedia , lookup
Power electronics wikipedia , lookup
Chapter 1 Complex Power, Reactive Compensation, Three Phase 1 Review of Phasors Goal of phasor analysis is to simplify the analysis of constant frequency ac systems: v(t) = Vmax cos(wt + qv), i(t) = Imax cos(wt + qI), where: • v(t) and i(t) are the instantaneous voltage and current as a function of time t, • w is the angular frequency (2πf, with f the frequency in Hertz), • Vmax and Imax are the magnitudes of voltage and current sinusoids, • qv and qI are angular offsets of the peaks of sinusoids from a reference waveform. Root Mean Square (RMS) voltage of sinusoid: T Vmax 1 2 V v (t ) dt , so Vmax 2 V . T0 2 2 Phasor Representation The RMS, cosine-referenced voltage phasor is: V V e jqV V qV , jwt jqV v (t ) Re 2 V e V V cos qV j V sin qV , I I cos q I j I sin q I . e , 3 Advantages of Phasor Analysis Device Resistor Time Analysis v (t ) Ri (t ) di (t ) v (t ) L dt Inductor Phasor V RI V jw LI t 1 v (t ) i (t )dt v (0) C0 Capacitor 1 V I jwC Z = Impedance R jX Z , (Note: Z is a complex number but not a phasor). R = Resistance, X = Reactance, Z = R X , 2 2 X =arctan R . 4 RL Circuit Example v (t ) f R 2 100cos(wt 30), so V 10030, 60Hz, 4 , X w L 2 fL 3, Z I i (t ) 20 2 cos(wt 6.9). 42 32 5, tan 1 (3/ 4) 36.9, V 10030 , Z 536.9 20 6.9 Amps, 5 Complex Power Instantaneous Power : p (t ) v(t ) i (t ), v(t ) = Vmax cos(w t qV ), i (t) = I max cos(w t q I ), 1 cos cos [cos( ) cos( )], 2 1 p (t ) Vmax I max [cos(qV q I ) 2 cos(2w t qV q I )]. 6 Complex Power, cont’d Instantaneous Power is sum of average and varying terms : 1 p (t ) Vmax I max [cos(qV q I ) cos(2w t qV q I )], 2 T Pavg 1 p (t )dt , T0 1 Vmax I max cos(qV q I ), 2 V I cos(qV q I ), Power Factor Angle = =qV q I . 7 Complex Power S V I cos(qV q I ) j sin(qV q I ) , P jQ, V I *, (Note: S is a complex number but not a phasor.) P = Real Power (W, kW, MW), Q = Reactive Power (VAr, kVAr, MVAr), = magnitude of power into electric and magnetic fields, S = Complex power (VA, kVA, MVA), Power Factor (pf) = cos , If current leads voltage then pf is leading, If current lags voltage then pf is lagging. 8 Complex Power, cont’d Relationships between real, reactive, and complex power: P S cos , Q S sin S 1 pf 2 , Example: A load draws 100 kW with a leading pf of 0.85. What are (power factor angle), Q and S ? cos 1 0.85 31.8, 100kW S 117.6 kVA, 0.85 Q 117.6sin( 31.8) 62.0 kVAr. 9 Example Power flowing from source to load at bus Earlier we found I = 20-6.9 amps S V I * 10030 206.9 200036.9 VA, = 1600W + j1200VAr 36.9 pf = 0.8 lagging, S R VR I ( RI ) I 4 20 6.9 206.9, * * 2 PR 1600W I R (QR 0), S L VL I * ( jXI ) I * 3 j 20 6.9 206.9, QL 1200VA r 2 I X, (PL 0). 10 Power Consumption in Devices Resistors only consume real power: 2 PResistor I Resistor R, Inductors only "consume" reactive power: 2 QInductor I Inductor X L , Capacitors only "generate" reactive power: 2 QCapacitor I Capacitor X C QCapacitor VCapacitor XC 1 XC . wC 2 . (Note-some define X C negative.) 11 Example I First solve basic circuit 400000 V I 4000 Amps 1000 V 400000 (5 j 40) 4000 42000 j16000 44.920.8 kV S V I * 44.9k20.8 4000 17.9820.8 MVA 16.8 j 6.4 MVA 12 Example, cont’d Now add additional reactive power load and re-solve, assuming that load voltage is maintained at 40 kV. Z Load 70.7 pf 0.7 lagging I 564 45 Amps V 59.713.6 kV S 33.758.6 MVA 17.6 j 28.8 MVA 13 Power System Notation Power system components are usually shown as “one-line diagrams.” Previous circuit redrawn. 17.6 MW 16.0 MW 28.8 MVR -16.0 MVR 59.7 kV 17.6 MW 28.8 MVR Generators are shown as circles 40.0 kV 16.0 MW 16.0 MVR Transmission lines are shown as a single line Arrows are used to show loads 14 Reactive Compensation Key idea of reactive compensation is to supply reactive power locally. In the previous example this can be done by adding a 16 MVAr capacitor at the load. 16.8 MW 16.0 MW 6.4 MVR 0.0 MVR 44.94 kV 16.8 MW 6.4 MVR 40.0 kV 16.0 MW 16.0 MVR 16.0 MVR Compensated circuit is identical to first example with just real power load. Supply voltage magnitude and line current is lower with compensation. 15 Reactive Compensation, cont’d Reactive compensation decreased the line flow from 564 Amps to 400 Amps. This has advantages: – Lines losses, which are equal to I2 R, decrease, – Lower current allows use of smaller wires, or alternatively, supply more load over the same wires, – Voltage drop on the line is less. Reactive compensation is used extensively throughout transmission and distribution systems. Capacitors can be used to “correct” a load’s power factor to an arbitrary value. 16 Power Factor Correction Example Assume we have 100 kVA load with pf=0.8 lagging, and would like to correct the pf to 0.95 lagging S 80 j 60 kVA 1 cos 0.8 36.9 PF of 0.95 requires desired cos 1 0.95 18.2 Snew 80 j (60 Qcap ) 60 - Qcap 80 Qcap tan18.2 60 Qcap 26.3 kVAr 33.7 kVAr 17 Distribution System Capacitors 18 Balanced 3 Phase () Systems A balanced 3 phase () system has: – three voltage sources with equal magnitude, but with an angle shift of 120, – equal loads on each phase, – equal impedance on the lines connecting the generators to the loads. Bulk power systems are almost exclusively 3. Single phase is used primarily only in low voltage, low power settings, such as residential and some commercial. Single phase transmission used for electric trains in Europe. 19 Balanced 3 -- Zero Neutral Current In Ia Ib Ic V In (10 1 1 Z S Van I a* Vbn I b* Vcn I c* 3 Van I a* Note: Vxy means voltage at point x with respect to point y. 20 Advantages of 3 Power Can transmit more power for same amount of wire (twice as much as single phase). Total torque produced by 3 machines is constant, so less vibration. Three phase machines use less material for same power rating. Three phase machines start more easily than single phase machines. 21 Three Phase - Wye Connection There are two ways to connect 3 systems: – Wye (Y), and – Delta (). Wye Connection Voltages Van V Vbn V Vcn V 22 Wye Connection Line Voltages Vcn Vab Vca -Vbn Van Vbn (α = 0 in this case) Vbc Vab Vbc Vca Van Vbn V (1 1 120 3 V 30 3 V 90 Line to line voltages are also balanced. 3 V 150 23 Wye Connection, cont’d We call the voltage across each element of a wye connected device the “phase” voltage. We call the current through each element of a wye connected device the “phase” current. Call the voltage across lines the “line-to-line” or just the “line” voltage. Call the current through lines the “line” current. VLine 3 VPhase 130 3 VPhase e j 6 I Line I Phase S3 * 3 VPhase I Phase 24 Delta Connection For Delta connection, voltages across elements equals line voltages Ica For currents I a I ab I ca Ic Ib Ibc Iab Ia 3 I ab I b I bc I ab I c I ca I bc * S3 3 VPhase I Phase 25 Three Phase Example Assume a -connected load, with each leg Z = 10020, is supplied from a 3 13.8 kV (L-L) source Vab 13.80 kV Vbc 13.8 0 kV Vca 13.80 kV 13.80 kV I ab 138 20 amps Ibc 138 140 amps I ca 1380 amps 26 Three Phase Example, cont’d I a I ab I ca 138 20 1380 239 50 amps I b 239 170 amps I c 2390 amps * S 3 Vab I ab 3 13.80kV 138 amps 5.7 MVA 5.37 j1.95 MVA pf cos 20 lagging 27 Delta-Wye Transformation To simplify analysis of balanced 3 systems: 1) Δ-connected loads can be replaced by 1 Y-connected loads with Z Y Z 3 2) Δ-connected sources can be replaced by VLine Y-connected sources with Vphase 330 28 Delta-Wye Transformation Proof - + Suppose the two sides have identical terminal behavior. For the side we get Vab Vca Vab Vca Ia Z Z Z Hence Z Vab Vca Ia 29 Delta-Wye Transformation, cont’d For the Y side we get Vab ZY ( I a I b ) Vca ZY ( I c I a ) Vab Vca ZY (2 I a I b I c ) Ia Ib Ic 0 Ia Ib Ic Since Vab Vca 3 ZY I a Hence 3 ZY Vab Vca Z Ia Therefore ZY 1 Z 3 30 Three Phase Transmission Line 31