Download C6200 Generator Controller Application

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Decibel wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Electric machine wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Control theory wikipedia , lookup

Control system wikipedia , lookup

Power factor wikipedia , lookup

Ohm's law wikipedia , lookup

Utility frequency wikipedia , lookup

Electrical ballast wikipedia , lookup

Electric power system wikipedia , lookup

Power inverter wikipedia , lookup

P–n diode wikipedia , lookup

Triode wikipedia , lookup

Power MOSFET wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power engineering wikipedia , lookup

Electrification wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Current source wikipedia , lookup

Electrical substation wikipedia , lookup

Rectifier wikipedia , lookup

History of electric power transmission wikipedia , lookup

Three-phase electric power wikipedia , lookup

Stray voltage wikipedia , lookup

Islanding wikipedia , lookup

Opto-isolator wikipedia , lookup

Surge protector wikipedia , lookup

Voltage regulator wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Power electronics wikipedia , lookup

Buck converter wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
C6200 Generator Controller
•
•
•
•
•
•
•
•
•
Combined Synchronizer and Loadsharer
Synchroscope on the front panel
Reverse power protection
Excitation loss protection
8 programmable inputs and outputs for
auxiliary functions
RS485 Modbus communication
CAN bus for optional user interface
Direct control of electronic governors
Increase/ decrease pulse outputs for
speed and voltage control
29 30 31
32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53
AUX
SUPPLY
GOV
AVR
+ -
+ -
CONTROL
C/B
C/B
CLOSE
UN
LOAD
PROT UNLOAD
TRIP
TRIP
54 55 56 58 58 59 60 61 62 63 64 65 66 67
PROGRAMMABLE
OUTPUTS
ANA
OUT
ALARM
1 2 3 4 5 6 7 8
C6200
GENCONTROLLER
RS232
123456
RS485
BUSBAR
VOLTAGE
1
2
GENERATOR
VOLTAGE
3
4
5
CANBUS
1 2 3 4 5 6 7 8
SYNC
6
7
GENERATOR
CURRENT
8
9
10
11
12
13
PROGRAMMABLE
INPUTS
14
ANA
IN
PAR
LINES
15 16 17 18 19 20 21 22 23 24 25 26 27 28
PRG
Figure 1. Front of C6200
Application
C6200 is a combined synchronizer and
loadsharer for paralleling of generators.
The unit can be used in any application
where generator should run in parallel
with each other or with the grid. For
easy commissioning the unit includes a
synchroscope on the front panel.
C6200 also includes reverse power and
excitation loss protection of the generator.
8 sets of programmable auxiliary inputs
and outputs are available. They can be
used for auxiliary functions like external commands for start synchronizing
or load ramp functions.
In case the engine is equipped with
an electronic governor, the analogue
outputs can be used for control of the
speed. The output signal can be a voltage, current or PWM signal.
It is possible to program the output
signals regarding level and reference,
so they can be adapted to virtually any
governor in the market such as GAC or
Woodward.
In case it alternatively is desired to
control the speed through a motorized
potentiometer or the servomotor of a
conventional governor a set of open collector outputs can be used.
Voltage Control
RS485 Modbus communication allows
read out of the status of the unit or external control of the unit e.g. by a PLC.
An analogue output can be used for
indication of actual measurement
values such as load or frequency of the
generator.
For voltage matching and reactive load
sharing (kVAr) C6200 offers two sets of
outputs for voltage control:
The Automatic Voltage Regulator (AVR)
of the alternator can be controlled by
an analogue signal (voltage, current or
PWM signal).
A User Interface Unit S6500 can be connected through CAN bus.
Easy accessible modular connectors are
furnished on the front side of the unit.
It is possible to program the output
signals regarding level and reference,
so they can be adapted to virtually any
AVR on the market.
Speed Control
In case a motorized potentiometer shall
be used for control of the AVR a set of
open collector outputs can be used. The
open collector outputs will then control
For synchronizing and active load
sharing (kW) C6200 offers two sets of
outputs for speed control:
relays which will control the motorized
potentiometer.
Synchronizing
In case increase/ decrease pulse
contacts are used for speed control,
synchronizing is performed according
to the dynamic synchronizing principle.
This means that the incoming generator
will be connected with a slightly higher
frequency than the busbar frequency.
The purpose of this function is to make
sure that the incoming generator will be
loaded immediately in order not to take
reverse power.
If alternatively the analogue outputs are
used, synchronizing is done according
to the static synchronizing principle.
Frequency and phase angle will then
be adjusted so the parameters of the incoming generator match the parameters
of the busbar (frequency of the incoming generator = frequency of the busbar). This is possible as the regulation
is much faster when using the analogue
outputs. The loadsharer will load the
generator immediately after connection
thus avoiding a reverse power situation.
Voltage Matching
During synchronizing C6200 will adjust
the voltage of the generator according
to the busbar voltage.
Load Sharing (kW)
The load sharing function will make
sure that the active load in an installation will be proportionally distributed
between the parallel running generators. The load will be shared according
to the percentage of nominal power of
the generators. It is possible to adjust
a load deviation in case a generator
should be loaded at a different rate than
the other generators.
Reactive Load Sharing (kVAr)
The reactive load sharing function will
make sure that the reactive load in an
installation will be proportionally distributed between the parallel running
generators. The reactive load will be
shared according to the percentage of
nominal reactive power of the generators. Also here it is possible to adjust a
load deviation.
Reverse Power Protection
C6200 includes a reverse power protection function with fixed time characteristics.
It is possible to define a trip level in %
of the nominal power and a trip delay
in seconds [s].
The unit includes two trip relays, one for protection trips and another for
operational (unload) trips. The reverse
power protection function trips the
protection trip relay.
Excitation Loss Protection
In case generators are running in parallel their output voltages are the same. If
one of the generators looses its excitation, it will take a reverse inductive
current. As this phenomenon will load
the other generator with reactive load,
it can lead to a decreasing busbar voltage. Eventually this could cause a low
voltage trip on all connected generators
resulting in a blackout.
To avoid this, C6200 can measure the
level and direction of the reactive current. If the reactive current is leading
into reverse direction and is larger than
a certain level, the C/B of the faulty
generator will be tripped. As the
healthy generators will keep supplying the busbar, this function can avoid
blackouts.
The excitation loss protection is defined
by a trip level in % of the nominal reactive power in reverse direction and a
trip delay in seconds [s]. It will trip the
protection trip output relay.
Programmable Auxiliary I/O
C6200 includes 8 programmable inputs
and 8 programmable outputs that can
be used for functions such as indication
of protection trips, external commands
for start of synchronizing or load sharing and manual control of speed and
voltage.
DG1
GND
1
2
Figure 3. Simple 2 generator application
6
5
C/B
S2/ S1/
L3 L3
13 14
Manual
L2
42
Unload
46
Parallel Lines
27
28
kW gnd VAr
49
50
Prg. Out. 2
55
Prg. Out. 1
54
Prot. Trip
48
56
Prg. Out. 3
26
47
C/B Close
45
52
53
65
66
Alarm
67
Unload Trip
51
C /B
DG2
GND
1
2
L2
L2
6
L1
5
Gen.
Voltage
Busbar
Voltage
L1
-
31
S2/ S1/
L3 L3
13 14
Gen.
Current
Aux.
Supply
+
29
46
Parallel Lines
27
28
kW gnd VAr
26
49
50
55
Prot. Trip
48
54
47
C/B Close
45
Prg. Out. 1
G o ve rn o r
Analogue Out 1
Speed Control
V/
DC
32 33 34 35
ref pwm mA
C6200
44
43
42
41
40
Prg. Out. 2
G o ve rno r
Analogue Out 1
Speed Control
V/
ref pwm mA
DC
32 33 34 35
43
Reset Alarm
41
C/B
C6200
44
Freq. Ctrl.
Disable
40
GND
C/B Block
L1
Gen.
Current
-
31
Gen.
Voltage
+
29
Aux.
Supply
L2
Busbar
Voltage
L1
GND
Unload
C /B
L3
L2
S1
L1
Reset Alarm
S1
Freq. Ctrl.
Disable
56
Prg. Out. 3
52
53
65
66 67
Alarm
Unload Trip
51
Specifications
C6200 Engine Controller
Voltage Generator voltage Generator rated frequency Generator max. current
Current transformer secondary current
Power consumption
Ambient temp. range
Relay contacts
Open collector outputs
External communication
Programmable digital inputs
Programmable digital outputs
Programmable analogue outputs
Current measurement
Weight
Dimension (mm)
24 VDC (-30% / +20%)
63V to 690V
50Hz/ 60Hz
30.000A
5A
Max 200mA
-20°­ C / +70° C
230VAC / 2A & 30VDC / 2A
200mA per channel
MODBUS RTU
8
8
2
Single phase
1,500 Kg
(282 x 182 x 50)mm
Type Selection
Type
C6200.0010
C6200.0020
Supply voltage
24VDC
24VDC
Generator voltage
63V – 690V
63V – 690V
Current transformer
5A
1A