UETTDRTS01B MAINTAIN NETWORK PROTECTION & CONTROL SYSTEMS www.eit.edu.au 3. Interdependent Protection and their Applications www.eit.edu.au TOPICS • Inter-tripping schemes • Bus-bar protection including breaker failure backup and blocking schemes • Pilot wire including phase comparison • Distance protection scheme • Reclosing and check-synchronising • Tie-line protection and load shedding www.eit.edu.au Inter-Tripping Schemes • Inter-tripping is the controlled tripping of a circuit breaker • The main use of this scheme is to Isolate both sides of the faulty circuit • This Schemes are used during the following circumstances – A feeder with a weak in feed at one end, insufficient to operate the protection for all faults – Feeder protection applied to transformer –feeder circuits – Faults between the CB and feeder protection CT’s, when these are located on the feeder side of the CB – For high reliability EHV protection schemes, inter-tripping may be used to give back-up www.eit.edu.au Inter-Tripping Schemes (Cont…) • Direct tripping – In direct tripping applications, inter-trip signals are sent directly to the master trip relay • Permissive tripping – Permissive trip commands are always monitored by a protection relay www.eit.edu.au Inter-Tripping Schemes (Cont…) • Blocking scheme – Blocking commands are initiated by a protection element that detects faults external to the protected zone • Purpose of Inter-tripping in transformer – In order to ensure that both the high and low voltage circuit breakers operate for faults within the transformer and feeder www.eit.edu.au Inter-Tripping Schemes (Cont…) Application of protection signalling and its relationship to other systems using communication www.eit.edu.au Inter-Tripping Schemes (Cont…) • Certain types of fault produce insufficient current to operate the protection associated with one of the circuit breakers. These faults are – Faults in the transformer that operate the Buchholz relay and trip the local low voltage circuit breaker – Earth faults on the star winding of the transformer – Earth faults on the feeder or high voltage delta connected winding www.eit.edu.au Bus-bar Protection • Bus-bars have often been left without specific protection, for one or more of the following reasons – – – The bus-bars and switchgear have a high degree of reliability, to the point of being regarded as intrinsically safe It was feared that accidental operation of bus-bar protection might cause widespread dislocation of the power system It was hoped that system protection or back-up protection would provide sufficient bus protection if needed www.eit.edu.au Bus-bar Protection (Cont…) • Bus-bar faults – The majority of bus faults involve one phase and earth • The special features of bus-bar protection are as follows • Speed: Bus-bar protection is primarily concerned with – Limitation of consequential damage – Removal of bus-bar faults in less time than could be achieved by back-up line protection www.eit.edu.au Bus-bar Protection (Cont…) • Stability – The stability of bus protection is of paramount importance – Dangers exist in practice for a number of reasons. These are • Interruption of the secondary circuit of a current transformer will produce an unbalance, which might cause tripping on load • A mechanical shock of sufficient severity may cause operation, although the likelihood of this occurring with modern numerical schemes is reduced • Accidental interference with the relay, arising from a mistake during maintenance testing, may lead to operation www.eit.edu.au Bus-bar Protection (Cont…) • A number of bus-bar protection systems have been devised – – – – – System protection used to cover bus-bars Frame-earth protection Differential protection Phase comparison protection Directional blocking protection www.eit.edu.au Bus-bar Protection (Cont…) • Busbar blocking system – Advantages • • • • • • • Very low or no cost system Simple Faster than faults cleared by back-up relays Covers phase and ground faults Adequate sensitivity–independent of no. of circuits No additional CTs Commissioning is simple–no primary current stability tests www.eit.edu.au Bus-bar Protection (Cont…) – Disadvantages • Only suitable for simple busbars • Additional relays and control wiring for complex busbars • Beware of motor infeeds to busbar faults • Sensitivity limited by load current www.eit.edu.au Busbar blocking system Bus-bar Protection (Cont…) • System protection schemes – – • System protection includes over-current or distance systems It will inherently give protection cover to the busbars Frame-earth protection (HOWARD PROTECTION) – – Frame leakage protection has been extensively used in the past in many different situations. There are several variations of frame leakage schemes available, providing bus-bar protection schemes with different capabilities www.eit.edu.au Bus-bar Protection (Cont…) Single zone frame-earth protection www.eit.edu.au Current distribution for external fault Bus-bar Protection (Cont…) Three zone frame earth scheme www.eit.edu.au Frame-earth scheme: Bus section breaker insulated on one side only Bus-bar Protection (Cont…) • For satisfactory operation of supervisory protection schemes audible and visual alarms are used. These alarms are used for – – – – – Bus-bar faults Bus-bar protection in service Bus-bar protection out of service Tripping supply healthy Alarm supply healthy www.eit.edu.au Bus-bar Protection (Cont…) • Numerical Bus-bar protection schemes • Differential protection requires sectionalizing the busbars into different zones – High impedance bus zone – Advantages • • • • Relays relatively cheap – offset by expensive CTs Simple and well proven Fast–15…45 m secs Stability and sensitivity calculations easy, provided data is available • Stability can be guaranteed www.eit.edu.au Bus-bar Protection (Cont…) – Disadvantages • • • • • • • • • • • • Very dependent on CT performance CT saturation could give false tripping on through faults Sensitivity must be decreased DC offset of CTs unequal–use filters Expensive class X CTs–same ratio–Vknp = 2 times relay setting Primary effective setting (30...50%) Limited by number of circuits Z grounded system difficult for ground fault Duplicate systems–decreased reliability Require exact CT data Vknp, Rsec, imag, Vsetting High voltages in CT circuits (+/− 2.8 kV) limited by volt dependent resistors • Biased medium impedance differential www.eit.edu.au Bus-bar Protection (Cont…) – Advantages • • • • • • • • • • • • • High speed 8…13 m secs Fault sensitivity +/− 20% Excellent stability for external faults Normal CTs can be used with minimal requirements Other protection can be connected to same CTs No limit to number of circuits Secondary voltages low (medium impedance) Well proven 10000 systems worldwide Any busbar configuration No need for duplicate systems Retrofitting easy No work on primary CTs Biasing may prevent possibility of achieving a sensitive enough ground fault setting of Z grounded systems www.eit.edu.au Bus-bar Protection (Cont…) – Disadvantages • Relays relatively expensive • Offset by minimal CT requirements • Relays with auxiliary CTs require a separate panel www.eit.edu.au Bus-bar Protection (Cont…) • Available protection functions are: – backup over-current protection – breaker failure – dead zone protection www.eit.edu.au Bus-bar Protection (Cont…) Architecture for numerical protection scheme www.eit.edu.au Pilot wire Including Phase Comparison • Following are the reasons for not using current differential relaying – The likelihood of improper operation owing to CT inaccuracies under the heavy loadings that would be involved – The effect of charging current between the pilot wires – The large voltage drops in the pilot wires requiring better insulation – The pilot currents and voltages would be excessive for pilot circuits rented from a telephone company www.eit.edu.au Pilot wire Including Phase Comparison (Cont…) • Purpose of a pilot Transmission-line sections for illustrating the purpose of a pilot www.eit.edu.au Pilot wire Including Phase Comparison (Cont…) • D-C wire-pilot relaying Schematic illustration of a d-c wire-pilot relaying equipment D = voltage-restrained directional (mho) relay O = over-current relay T = auxiliary tripping relay S = auxiliary supervising relay PW = pilot wire www.eit.edu.au Pilot wire Including Phase Comparison (Cont…) Schematic illustration of a d-c wire-pilot scheme where information is transmitted over the pilot D = voltage-restrained directional (mho) relay B = auxiliary blocking relay O = over-current relay TC = trip coil PW = pilot wire www.eit.edu.au Pilot wire Including Phase Comparison (Cont…) • A-C wire-pilot relaying Schematic illustration of the circulating-current principle of a a-c wirepilot relaying www.eit.edu.au Pilot wire Including Phase Comparison (Cont…) Schematic illustration of the opposed-voltage principle of a-c wirepilot relaying www.eit.edu.au Pilot wire Including Phase Comparison (Cont…) www.eit.edu.au Effect of Shorts Effect of Open Circuits Opposed voltage Cause tripping Block tripping Circulating current Block tripping Cause tripping Pilot wire Including Phase Comparison (Cont…) Schematic connections of a circulating-current a-c wire-pilot relaying equipment www.eit.edu.au Pilot wire Including Phase Comparison (Cont…) Schematic connections of an opposed-voltage ac wire-pilot relaying equipment P = current polarizing coil R = voltage restraining coil O = current operating coil www.eit.edu.au Distance Protection Schemes • • The most important and versatile family of relays is the distance-relay group It includes the following types – – – – – – Impedance relays Reactance relays Mho relays Angle impedance relays Quadrilateral relays Elliptical and other conic section relays www.eit.edu.au Distance Protection Schemes (Cont…) Basic principle of operation I f E / Z f Z s V f E Z f /( Z f Z s ) www.eit.edu.au Distance Protection Schemes (Cont…) Balanced beam principle Bridge comparator www.eit.edu.au Plain impedance characteristic Distance Protection Schemes (Cont…) • Tripping characteristics MHO characteristic www.eit.edu.au Offset MHO characteristic Distance Protection Schemes (Cont…) • Application onto a power line Zone 1 MHO characteristic www.eit.edu.au 3 Zone MHO characteristics Distance Protection Schemes (Cont…) • Effect of load current Load encroachment www.eit.edu.au Effect of arc resistance Distance Protection Schemes (Cont…) • Different shaped characteristics Lenticular characteristic www.eit.edu.au Distance Protection Schemes (Cont…) Figure-of-eight characteristic www.eit.edu.au Trapezoidal characteristic Reclosing & Check Synchronising • Reclosers – Adjacent reclosers can be coordinated more closely since there are no inherent errors • Self contained pole mounted ARC – The following are the system service conditions which are suitable for using AR on non-effectively earthed and effectively earthed networks • • • • Nominal system voltage : 11 kV Maximum system voltage : 15 kV Continuous current rating : 630 A Short circuit-breaking capacity: 12.5 kA www.eit.edu.au Reclosing & Check Synchronising (Cont…) • Rated power frequency withstand voltage : 50kVrms • Impulse withstand voltage : 125 kVp • System frequency : 50 Hz; + 1.5 • Number of phases : 3 • Insulation medium : Solid dielectric • Operating mechanism :Magnetic actuator • Ambient temperature (minimum) : 5 °C • Ambient temperature (maximum) : 50 °C • Max. Relative humidity. : 100% www.eit.edu.au Reclosing & Check Synchronising (Cont…) • Check Synchronising – Faults on overhead lines fall into one of three categories: • Transient • Semi-permanent • Permanent www.eit.edu.au Reclosing & Check Synchronising (Cont…) Single-shot auto-reclose scheme operation for a transient fault www.eit.edu.au Reclosing & Check Synchronising (Cont…) Operation of single-shot auto-reclose scheme on a permanent fault www.eit.edu.au Reclosing & Check Synchronising (Cont…) • Application of auto-reclosing – The most important parameters of an auto-reclose scheme are • • • • Dead time Reclaim time Single or multi-shot Advantages of using Auto-reclosing on HV distribution Networks – – – – Reduction to a minimum of the interruptions of supply to the consumer Instantaneous fault clearance can be introduced, with the accompanying benefits of shorter fault duration and fewer permanent faults Improved supply continuity Reduction of substation visits www.eit.edu.au Reclosing & Check Synchronising (Cont…) • Several factors affect the selection of system dead time as follows – – – – System stability and synchronism Type of load ,CB characteristics Fault path de-ionisation time Protection reset time www.eit.edu.au Reclosing & Check Synchronising (Cont…) • Factors affecting the setting of the reclaim time are – – Type of protection Spring winding time www.eit.edu.au Reclosing & Check Synchronising (Cont…) • Auto-reclosing on EHV transmission lines Effect of high-speed three-phase auto-reclosing on system stability for a weak system www.eit.edu.au Reclosing & Check Synchronising (Cont…) • De-Ionisation of Fault Arc – The de-ionisation time of an uncontrolled arc, in free air depends on • The circuit voltage • Conductor spacing • Fault currents • Fault duration • Wind speed • Capacitive coupling from adjacent conductors www.eit.edu.au Line voltage (kV) Minimum deenergisati on time (seconds) 66 0.2 110 0.28 132 0.3 220 0.35 275 0.38 400 0.45 525 0.55 Fault-arc de-ionisation times Reclosing & Check Synchronising (Cont…) • The advantages of single-phase autoreclosing are – The maintenance of system integrity – On multiple earth systems, negligible interference with the transmission of load www.eit.edu.au Reclosing & Check Synchronising (Cont…) Typical three zone distance scheme www.eit.edu.au Reclosing & Check Synchronising (Cont…) Delayed autoreclose scheme logic www.eit.edu.au Reclosing & Check Synchronising (Cont…) • The synchronism check relay element commonly provides a three-fold check – – – • Phase angle difference Voltage Frequency difference Auto-close scheme Standby transformer with auto-closing www.eit.edu.au Tie-Line Protection and Load Shedding • Special protection schemes – • System protection schemes are protection strategies designed to detect a particular system condition that may cause unusual stress to the power system The most common types of system protection schemes are as follows – – – – – Generator rejection Load rejection Under frequency load shedding System separation Turbine valve control www.eit.edu.au Tie-Line Protection and Load Shedding (Cont…) – – – – – – – – Load and generator rejection Stabilizers HVDC controls Out of step relaying Discrete excitation control Dynamic braking Generator runback VAR compensation www.eit.edu.au Tie-Line Protection and Load Shedding (Cont…) • The main objectives of using system protection schemes are – Operation of power systems closer to their limits – Increase power system security particularly during extreme contingencies – Improve power system operation www.eit.edu.au Tie-Line Protection and Load Shedding (Cont…) • Estimation of rate of change of frequency (df/dt) 2H df Dx f P f 0 dt • • • • • • • • H = System Inertia Constant on system base (seconds) f o = Frequency at the time of disturbance (Hz) df/dt =Rate of change of frequency (Hz/Sec) Δ P =( PL-PG)/PG , Power change (per unit in system load base) PL =Load prior to generation Loss in MW PG =System Generation after Loss in MW D =Power/frequency characteristic of the system in pu/Hz Δf =Change in frequency www.eit.edu.au Tie-Line Protection and Load Shedding (Cont…) • The overload may be differentiated by the method that is used to detect and respond to condition – – – – – Dispersed frequency monitoring Dispersed voltage monitoring Utility Scale SCADA System Configuration Monitoring Industrial Scale System Configuration Monitoring Local equipment overload monitoring www.eit.edu.au Tie-Line Protection and Load Shedding (Cont…) • Methods of overload detection and load shedding – – – By Frequency Monitoring By Voltage Monitoring By SCADA System Monitoring • • – • Application to Utility Scale Systems Application to Smaller Industrial Facilities By Current and/or Power Monitoring Drawbacks of breaker interlock load shedding – – – – Load shedding based on worst-case scenario Only one stage of load shedding Almost always, more load is shed than required Modifications to the system are costly www.eit.edu.au Tie-Line Protection and Load Shedding (Cont…) • Pre-disturbance operating conditions – – – – – – Total system load demand Total system power exchange to the grid Generation of each on-site unit Spinning reserve for each on-site unit Control settings for each running unit System configurations www.eit.edu.au Tie-Line Protection and Load Shedding (Cont…) • Post-disturbance operating conditions – – – – – – New system load demand Remaining generation from on-site generation Spinning reserve for each remaining unit Time duration to bring up the spinning reserve New system configurations Status, settings and loading conditions of the remaining major rotating machines www.eit.edu.au Tie-Line Protection and Load Shedding (Cont…) • Nature and duration of the disturbance – – – – – – – Electrical and/or Mechanical faults Complete or partial loss of power grid connection Complete or partial loss of on-site generation Load addition (impact) Location of disturbance Duration of disturbance and its termination Subsequent system disturbances www.eit.edu.au Tie-Line Protection and Load Shedding (Cont…) • System transient response to a disturbance – – – – System frequency response System voltage response Rotor angle stability of each remaining unit Operation of protective devices www.eit.edu.au Tie-Line Protection and Load Shedding (Cont…) • Load shedding system can be designed to meet the following objectives – Map a complex, highly nonlinear, nonparametric, load shedding problem, to a finite space with a limited number of data collection points – Automatic recall of system configuration, operating condition, and system response to disturbances – Pattern recognition capability to predict system response to disturbances – Systems knowledgebase trainable by user defined cases – Self-learning capability to new system changes – Make prompt decisions regarding which loads to shed based on the online status of sheddable loads – Shed the minimum amount of load to maintain system stability www.eit.edu.au Tie-Line Protection and Load Shedding (Cont…) Load Shedding scheme function Block diagram www.eit.edu.au