* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download clemson university dg conference
Buck converter wikipedia , lookup
Voltage optimisation wikipedia , lookup
Power engineering wikipedia , lookup
Ground loop (electricity) wikipedia , lookup
Fault tolerance wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Three-phase electric power wikipedia , lookup
Mains electricity wikipedia , lookup
Stray voltage wikipedia , lookup
History of electric power transmission wikipedia , lookup
Transformer wikipedia , lookup
Alternating current wikipedia , lookup
Electrical substation wikipedia , lookup
Ground (electricity) wikipedia , lookup
Protective relay wikipedia , lookup
Transformer types wikipedia , lookup
Distribution management system wikipedia , lookup
CLEMSON UNIVERSITY DG CONFERENCE UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION WHAT IEEE 1547 DOESN’T TELL YOU ABOUT INTERCONNECTION PROTECTION Chuck Mozina Consultant Beckwith Electric Co., Inc. CLEMSON UNIVERSITY DG CONFERENCE OUTLINE Update the Current Status of DG Interconnection Protection Tell You What IEEE 1547 Doesn’t Discuss New DG Method and Practices + Calf. Rule 21 CLEMSON UNIVERSITY DG CONFERENCE Types of DG Generators • Induction • Synchronous • Asynchronous CLEMSON UNIVERSITY DG CONFERENCE To Utility System Typical Interconnection Protection Interconnection Transformer Interconnection Relay Utility System IPP System Point of common coupling Local Loads • Disconnects the generator when it is no longer operating in parallel with the utility. • Protects the utility system from damage caused by connection of the generator (fault current and overvoltage). • Protects the DG generator from damage from the utility system, especially through automatic reclosing. CLEMSON UNIVERSITY DG CONFERENCE Typical Generator Protection • Generator internal short circuits. • Abnormal operating conditions (loss of field, reverse power, overexcitation and unbalance currents). Local Loads CLEMSON UNIVERSITY DG CONFERENCE IEEE 1547 Addresses Generators 10 MVA or Less Started Work in 1997 Has Over 300 Participants Met Every Other Month Referred Most Issues of Substance to 3 New Standards Groups CLEMSON UNIVERSITY DG CONFERENCE What 1547 SAYS A DG SHALL: Not Cause Overvoltages or Loss of Utility Relay Coordination Disconnect When No Longer Operating in Parallel With the Utility. + Only Discusses 81O/U and 27, 59 Not Energize the Utility when it is De-energized Not Create an Unintentional Islands Use “Utility Grade” Relays Not Cause Objectionable Harmonics Not Cause Loss of Synchronism That Results in Objectionable Flicker CLEMSON UNIVERSITY DG CONFERENCE What 1547 SAYS A DG SHALL: Not Cause Overvoltages or Loss of Utility Relay Coordination Disconnect When No Longer Operating in Parallel With the Utility. + Only Discusses 81O/U and 27, 59 Not Energize the Utility when it is De-energized Not Create an Unintentional Islands Use “Utility Grade” Relays Not Cause Objectionable Harmonics Not Cause Loss of Synchronism That Results in Objectionable Flicker CLEMSON UNIVERSITY DG CONFERENCE OVERVOLTAGE AND LOSS OF COORDINATION Two Sources of Overvoltage +Choice of Delta Interconnection Transformer Primary Winding + Ferroresonance Loss of Coordination +Choice of Grounded Interconnection Transformer Primary Winding. CLEMSON UNIVERSITY DG CONFERENCE Typical 4-Wire Distribution Feeder Circuit DG Pole-top transformer rated for line-to-neutral voltages example: 13.2 KV 3 7.6 KV CLEMSON UNIVERSITY DG CONFERENCE Ungrounded Interconnection Transformers Advantages Provide no ground fault backfeed for fault at F1 & F2. No ground current from breaker A for a fault at F3. Problems Low Voltage (SEC.) DG High Voltage (PRI.) Can supply the feeder circuit from an underground source after substation breaker A trips causing overvoltage CLEMSON UNIVERSITY DG CONFERENCE Grounded Primary Interconnection Transformers Advantages No ground current from breaker A for faults at F3( ). No overvoltage for ground fault at F1. No overvoltage for ground fault at F1. 2 Problems Provides an unwanted ground current for supply circuit faults at F1 and F2. Low Voltage (SEC.) DG 3 High Voltage (PRI.) Allows source feeder relaying at A to respond to a secondary ground fault at F3( ). CLEMSON UNIVERSITY DG CONFERENCE FERRORESONANCE NEW YORK FIELD TESTS –1989 FIELD TEST CIRCUIT CLEMSON UNIVERSITY DG CONFERENCE FERRORESONANCE NEW YORK FIELD TESTS -1989 50KW Synchronous DG, 9KW load, 100KVAR Capacitance and Wye-Delta Interconnection Transformer A=2.74 pu B=2.34 pu C=2.92 pu CLEMSON UNIVERSITY DG CONFERENCE FERRORESONANCE NEW YORK FIELD TESTS -1989 50KW Synchronous DG, 9KW load, 100KVAR Capacitance and Wye-Delta Interconnection Transformer A=2.74 pu B=2.34 pu C=2.92 pu PROTECTION SOLUTION: MEASURE PEAK OVERVOLTAGE NOT RMS (59I) CLEMSON UNIVERSITY DG CONFERENCE CONDITIONS FOR FERRORESONANCE 1. DG Must be Separated From the Utility System (islanded condition) 2. KW Load in the Island Must be Less than 3 Times DG Rating 3. Capacitance Must be Greater Than 25 and Less Than 500 Percent of DG Rating 4. There Must be a Transformer in the Circuit to Provide Nonlinearity CLEMSON UNIVERSITY DG CONFERENCE PROTECTION FUNCTION BEYOND 81O/U,27 AND 59 Total Interconnect Package Loss of Parallel Fault backfeed removal Damaging conditions Abnormal power flow Restoration CLEMSON UNIVERSITY DG CONFERENCE TYPICAL INTERCONNECTION PROTECTION FOR WYEGROUNDED (PRI.) INTERCONNECTION TRANSFORMER CLEMSON UNIVERSITY DG CONFERENCE TYPICAL INTERCONNECTION PROTECTION FOR UNGROUNDED (PRI.) INTERCONNECTION TRANSFORMER CLEMSON UNIVERSITY DG CONFERENCE RECIPROCATING ENGINE OUT OF SYNCHRONISM CONDITION CLEMSON UNIVERSITY DG CONFERENCE Power Angle Analysis of Out-of-Synchronism Condition Power P = |Eg| |ES| Max X STABLE A2 120 UNSTABLE Pm=Pe If A1>A2 DG goes unstable and slips a pole, results in high levels of transient shaft torque XFAULT Line Recloser A1 Line Recloser Trips PFAULT Angle Utility Substation 180 Q -Q g s DG Local Load CLEMSON UNIVERSITY DG CONFERENCE CONCLUSIONS 1. DGs Interconnected on Distributions Systems Present Significant Technical Problems 2. There are No “Standard” Solutions Only Choices with Undersirable Drawbacks 3. IEEE 1547 Provides Limited Real Guidance – Simply Cites Obvious Requirements 4. Hopefully, the Three Newly Formed IEEE Standards Groups Will Address the Technical Issues Raised in this Paper CLEMSON UNIVERSITY DG CONFERENCE THE END UPDATE ON THE CURRENT STATUS OF DG INTERCONNECTION PROTECTION QUESTIONS