SECTION 16060 GROUNDING AND BONDING PART 1 1.01 1.02 1.03 SUMMARY A. Section includes: 1. Grounding electrodes. 2. Grounding electrode conductors. 3. Equipment grounding conductors. 4. Main bonding jumper. 5. Ground connections. 6. General requirements for grounding. B. Related sections: 1. The Contract Documents are complementary; what is called for by one is as binding as if called for by all. 2. It is the CONTRACTOR’s responsibility for scheduling and coordinating the Work of subcontractors, suppliers, and other individuals or entities performing or furnishing any of CONTRACTOR’s Work. 3. The following sections are related to the Work described in this Section. This list of related sections is provided for convenience only and is not intended to excuse or otherwise diminish the duty of the CONTRACTOR to see that the completed Work complies accurately with the Contract Documents. a. Section 16050 - Common Work Results for Electrical. b. Section 16950 - Field Electrical Acceptance Tests. REFERENCES A. As specified in Section 16050 B. ASTM International (ASTM): 1. B 3 - Standard Specification for Soft or Annealed Copper Wire. 2. B 8 - Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft. DEFINITIONS A. 1.04 GENERAL As specified in Section 16050. SYSTEM DESCRIPTION A. Ground equipment and raceway systems so that the completed installation conforms to all applicable code requirements. B. Provide bonding jumpers and wire, grounding bushings, clamps and appurtenances required for complete grounding system to bond equipment and raceways to equipment grounding conductors. November 2012 pw://Carollo/Documents/Client/UT/SVWRF/6596H10/Specifications/16060 (A) 16060-1 6596H10 1.05 (NOT USED) 1.06 QUALITY ASSURANCE 1.07 A. As specified in Section 16050. B. All grounding components and materials shall be UL listed and labeled. DELIVERY, STORAGE, AND HANDLING A. As specified in Section 16050. 1.08 (NOT USED) 1.09 (NOT USED) 1.10 (NOT USED) 1.11 WARRANTY A. 1.12 As specified in Section 16050. SYSTEM START-UP A. As specified in Section 16050. 1.13 (NOT USED) 1.14 (NOT USED) 1.15 (NOT USED) PART 2 2.01 PRODUCTS MANUFACTURERS A. Compression connectors: One of the following [or equal]: 1. FCI Burndy. 2. Thomas & Betts. 2.02 (NOT USED) 2.03 MATERIALS A. Equipment grounding conductors: 1. Conductors shall be the same type and insulation as the load circuit conductors: a. Use 600-volt insulation for the equipment grounding conductors for medium voltage systems. 2. Minimum size in accordance with the NEC. November 2012 pw://Carollo/Documents/Client/UT/SVWRF/6596H10/Specifications/16060 (A) 16060-2 6596H10 2.04 (NOT USED) 2.05 (NOT USED) 2.06 (NOT USED) 2.07 ACCESSORIES 2.08 (NOT USED) 2.09 (NOT USED) 2.10 (NOT USED) 2.11 (NOT USED) PART 3 EXECUTION 3.01 (NOT USED) 3.02 (NOT USED) 3.03 INSTALLATION A. As specified in Section 16050. B. Provide a separate, green insulated, grounding conductor in each raceway independent of raceway material: 1. Multi-conductor power and control cables shall include an integral green insulated grounding conductor. 2. Provide a separate grounding conductor in each individual raceway for parallel feeders. C. Provide a separate grounding conductor for each motor and connect at motor terminal box. Do not use bolts securing motor box to frame or cover for grounding connectors: 1. When grounding motors driven by variable frequency drives (VFD) comply with the requirements of the VFD manufacturer. D. Provide a grounding type bushing with lug for connection of grounding conductor for conduits that originate from each motor control center section, switchboard, or panelboard: 1. Individually bond these raceways to the ground bus in the equipment. E. Provide grounding type bushings with lugs for connection of grounding conductor at both ends of metallic conduit runs. Bond ground bushings to the grounding system. F. Provide a green insulated wire-grounding jumper from the ground screw to a box grounding screw and, for grounding type devices, to equipment grounding conductor. G. Shield grounding: November 2012 pw://Carollo/Documents/Client/UT/SVWRF/6596H10/Specifications/16060 (A) 16060-3 6596H10 1. 2. 3. 4. Shielded instrumentation cable shall have its shield grounded at one end only unless shop drawings indicate otherwise: a. The grounding point shall be at the control panel or at the power source end of the signal carried by the cable. Terminate the shield drain wire on a dedicated terminal block. Use manufacturer’s terminal block jumpers to interconnect ground terminals. Connection to the panel main ground bus shall be via a green No. 12 conductor to the main ground bus for the panel. 3.04 (NOT USED) 3.05 (NOT USED) 3.06 (NOT USED) 3.07 FIELD QUALITY CONTROL 3.08 A. As specified in Section 16050. B. Measure grounding electrode system resistance to ground in accordance with IEEE 81. ADJUSTING A. Under the direction of the ENGINEER, add additional parallel connected ground rods and/or deeper driven rods until the ground resistance measurement meets the specified resistance requirements: 1. Use of salts, water, or compounds to attain the specified ground resistance is not acceptable. 3.09 (NOT USED) 3.10 (NOT USED) 3.11 PROTECTION A. 3.12 As specified in Section 16050. (NOT USED) END OF SECTION November 2012 pw://Carollo/Documents/Client/UT/SVWRF/6596H10/Specifications/16060 (A) 16060-4 6596H10