Download APCQ-L capacitor banks series The ABB comprehensive solution for

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Three-phase electric power wikipedia , lookup

Buck converter wikipedia , lookup

Coilgun wikipedia , lookup

Decibel wikipedia , lookup

Control system wikipedia , lookup

Voltage optimisation wikipedia , lookup

Rectifier wikipedia , lookup

History of electric power transmission wikipedia , lookup

Power over Ethernet wikipedia , lookup

Audio power wikipedia , lookup

Electrification wikipedia , lookup

Electric power system wikipedia , lookup

Electrical substation wikipedia , lookup

Alternating current wikipedia , lookup

Resonant inductive coupling wikipedia , lookup

Wireless power transfer wikipedia , lookup

Power factor wikipedia , lookup

Mains electricity wikipedia , lookup

Power engineering wikipedia , lookup

Tantalum capacitor wikipedia , lookup

Aluminum electrolytic capacitor wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Capacitor plague wikipedia , lookup

Niobium capacitor wikipedia , lookup

Capacitor wikipedia , lookup

Transcript
APCQ-L capacitor banks series
The ABB comprehensive solution for automatic power factor
correction
QCap
RVC
RVT
UA contactor
Standard and reinforced range
Power (kvar)
Regulation (x*kvar)
Standard and reinforced (457V) range
ABB automatic capacitor banks type
APCQ-L provide the ideal power factor
correction solution for light industrial and
commercial applications.
400V 50Hz - clean and slightly polluted network
37.5
12.5 + 25 kvar
50
12.5 + 12.5 + 25 kvar
62.5
12.5 + 25 + 25 kvar
75
25 + 25 + 25 kvar
87.5
12.5 + 25 + 25 + 25 kvar
100
25 + 25 + 25 + 25 kvar
The customer benefits are:
−− Solving utility penalty charges due to low cos j
−− Improving energy efficiency
−− Releasing additional capacity or increasing system load
without additional equipment
−− Increasing service life time of infrastructure
Main features
The capacitor bank APCQ-L characteristics include:
−− Powerful and compact
−− Easy to install and use thanks to the RVC or RVT controller
−− Exceptional reliability and safety thanks to a strict selection
of components:
−− QCap capacitor unit, the latest evolution of ABB
capacitors
−− RVC or RVT controllers, a reliable and easy interface
−− ABB UA contactor
−− ABB capacitor technology using dry type design
−− Built-in thermal protection against overheating
Easy to install and use
The equipement is ready to use, install, operate and service
while ensuring exceptional reliability, efficiency and safety.
Busbar
Internal
Protection
Plexiglas
(option)
Circuit
breaker
(option)
Air inlet
Fan - air outlet
UA contactors
RVC controller (RVT)
Auxiliary connections
Auxiliary transformer
QCap Capacitors
Technical specifications
Voltage range
400V at 50Hz
For other voltages, please consult us
Working ambient temperature
-5°C (23°F)/+40°C (104°F) according to EN 61921
Installation
APCQ-L: wall mounted, bottom cable entry
Clearance lateral : not necessary
Three-phase, balanced network
Protection
APCQ-L: IP20 (closed door)
Optional: IP23 and IP54
Execution
Indoor
Color
Beige RAL 7035
Dimensions and weight
500x290x820 mm (WxDxH) - max 30 kg
Ventilation
Air forced cooling
Noise
About 55 dBA (1m)
Power factor setting
From 0.7 inductive to 0.7 capacitive
Starting current setting (C/k)
From 0.01A to 3A for the RVC controller
From 0.01A to 5A for the RVT controller (optional)
Operation
During operation, RVC (RVT) controller displays:
- the number of active outputs
- the inductive or capacitive power factor
- the alarm conditions; target cos
j, over/undervoltage, THDV, overtemperature
- the demand for switching on/off a capacitor step
Losses at 400V 50 Hz
Less than 1.5 Watt/kvar
Capacitors QCap type
- Dry type self healing according to IEC 60831-1&2
- Dielectric: 2.15 Un between terminals during 10 sec at rated frequency
- Acceptable overvoltage: +10% max. intermittently
- Acceptable overcurrent: +30% permanently
- Temperature range: -25°C (-13°F)/ class D according to IEC 60831-1&2
Standards
EN 61921
IEC 60831-1&2 (capacitors)
CE marked
Options
RVT controller
Circuit breaker
Temperature probe (with RVT only)
Internal plexiglas protection
IP23 and IP54 enclosure
For more information please contact:
s.a. ABB n.v.
Power Quality Products
Avenue Centrale, 10
Z.I.Jumet
B-6040 Charleroi, Belgium
Phone: +32 71 250 811
Fax:
+32 71 34 40 07
E-Mail:[email protected]
www.abb.com
While all care has been taken to ensure that the information contained
in this publication is correct, no responsibility can be accepted for
any inaccuracy. We reserve the right to alter or modify the information
contained herein at any time in the light of technical or other developments.
Technical specifications are valid under normal operating conditions
only. We do not accept any responsibility for any misuse of the product
and cannot be held liable for indirect or consequential damages.
©Copyright 2014. All rights reserved. ABB 2GCS302011A0040
Top and bottom: 200 mm
Connection