* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download uninterruptible power supplies
Resilient control systems wikipedia , lookup
Public address system wikipedia , lookup
Wireless power transfer wikipedia , lookup
Control system wikipedia , lookup
Stray voltage wikipedia , lookup
Opto-isolator wikipedia , lookup
Power factor wikipedia , lookup
Immunity-aware programming wikipedia , lookup
Power over Ethernet wikipedia , lookup
Utility frequency wikipedia , lookup
Audio power wikipedia , lookup
Pulse-width modulation wikipedia , lookup
Electrical substation wikipedia , lookup
Three-phase electric power wikipedia , lookup
Electrification wikipedia , lookup
Electric power system wikipedia , lookup
Mercury-arc valve wikipedia , lookup
Buck converter wikipedia , lookup
Power engineering wikipedia , lookup
History of electric power transmission wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Solar micro-inverter wikipedia , lookup
Amtrak's 25 Hz traction power system wikipedia , lookup
Voltage optimisation wikipedia , lookup
Alternating current wikipedia , lookup
Distribution management system wikipedia , lookup
Power inverter wikipedia , lookup
Power supply wikipedia , lookup
Switched-mode power supply wikipedia , lookup
XXX UNINTERRUPTIBLE POWER SUPPLIES UPS 1 GUSTAV KLEIN GUSTAV KLEIN – a company introduces itself The GUSTAV KLEIN company was founded in Schongau, Germany, in 1948. In 1969, a subsidiary factory was opened in Austria, at that time our principal export country, located in Inzing to the west of Innsbruck. The GUSTAV KLEIN company has approx. 200 employees in this two factories. FACTORY SCHONGAU (GERMANY) The manufacture of transformers was the beginning of our rapidly expanding product palette, followed by stabilizers and mains voltage controllers for broadcast and television stations of the German federal post. The first thyristor rectifiers were presented in 1960. And since 1962 used together with thyristor controlled inverters as a UPS - uninterruptible power supply. In 1968 the uninterruptible electronic bypass device for inverters was manufactured. Switched-mode rectifiers and DC converters were delivered since 1970. Later, high-current transistors became available on the market, and in 1985 the GUSTAV KLEIN company began to manufacture pulse-width modulated transistor inverters and UPS equipment up to 100 kVA. New IGBT transistors made it possible to improve the efficiency of our UPS equipment in 1996. Since the year 2000 UPS equipment with microprocessors and IGBT-rectifiers are in our product range. Today we manufacture not only secured power supplies, but also high power test systems up to 1000 V DC and frequency converters in IGBT technology. FACTORY INZING (AUSTRIA) REASONS for choosing GUSTAV KLEIN: Experience More than 250.000 delivered units speak for themselves. The knowledge of our experienced engineers is also available for YOU. Confidence and Consistency GUSTAV KLEIN is established since 1948 on the market of power supplies. Renowned companies from the Railway, Chemical Industry, Telecom Power Stations and Industry are from the beginning our regular customers. High Product Reliability Decades of practical experience in high security zones of rail networks, electricity power stations, telecommunications networks, hospitals and industrial plants guarantee the highest reliability and quality. Competence in Consulting and Support Starting from your inquiry until After-Sales-Service – YOU will be supported by our experienced engineers. Competence in Technique In-house development in the fields of equipment and microprocessor technology, as well as our own printed-circuit design and our own software programming department, emphasise our continuously innovative activities. Custom Designed Power Supplies Our special competence is to produce complete customized solutions to match YOUR specific requirements. After-Sales We guarantee the supply of spare parts for 15 years and a worldwide service. 2 General Static uninterruptible power supply (also known as UPS systems) is for many applications indispensable today. Statistics shows that in Germany an average between two and four extended AC mains failures, and more than one hundred short interruptions in the range of milliseconds every year. Systems failures caused by these interruptions can lead to long downtime and data losses. Special characteristics of our UPS systems: State-of-the-art technology High efficiency Very good dynamic regulation Power ratings 5 – 500 kVA System ratings up to 2000 kVA (n+1 -operation) Customized versions Parallel operation of up to 8 units ➜ ➜ ➜ ➜ ➜ ➜ ➜ UPS systems protect against: Classification ➜ ➜ ➜ ➜ ➜ ➜ Short-duration interruptions AC mains failure Voltage variations Superimposed interference voltages Frequency variations AC mains voltage waveform distortion In most data processing applications and in many automation and control installations, the increasing safety and reliability requirements can be met only by UPS equipment. Sensitive users include: ➜ Railway signalling ➜ Remote control facilities for electricity supply utilities ➜ Control equipment for power plants ➜ Traffic control installations ➜ Vital medical equipment in operating theatres ➜ Process control equipment and automation in manufacturing plants ➜ Data centres ➜ Air traffic control systems ➜ Telecommunication systems ➜ Tunnel surveillance and lighting 1. Single phase UPS systems Type USV-7001 (thyristor rectifier) Type USV-7011 (transistor rectifier) 2. Three phase UPS systems Type USV-7003 (thyristor rectifier) Type USV-7013 (transistor rectifier) 3. Small single phase UPS systems type Minicompact can be found in our special brochure On-line UPS systems Type Minicompact The use by telecommunications, railway, power plants, air traffic control, hospitals and industrial applications is itself evidence of the high quality and reliability or our power supplies. Zertifizieru f- und VDE Prü ngsinstitut OTECHNIK e.V. D DER ELEKTR TECHNIK VDE VERBAN INFORMATIONS ELEKTRONIK F I K AT ZERTI Registrier-Nu Hiermit wird mmer: 20121/ bescheinigt, QM/02.96 dass das Unternehmen & Co. KG KLEIN GmbH au GUSTAV räte-B Elektro-Ge et 3 Im Forch Schongau D-86956 mit den Stando rten Schongau D-86956 A-6401 Inzing ts-Manageme ntsystem für den Bereic h von endienst und Kund , Montage g, Produktion versorgungen Entwicklun Strom ein Qualitä eingeführt stem erfüllt Dieses QM-Sy det. hat und anwen ungen der die Forder DIN EN ISO Dieses Zertifika ierung und Zertifiz VDE Prüfsstelle Zertifizierung ch/Main, 63069 Offenba 05 Datum: 27.06.20 folgenden Norm: 9001:2000 t ist gültig bis 13.06.2 008 sinstitut Merianstraße 28 Extensive certifications (DIN ISO 9001, KTA 1401, DB …) Our UPS protect your investments and supplies a save power to your resources at any time. Many years of experience, together with our extensive range of systems, guarantee that we have the comprehensive professional competence to find the technically and economically optimal solution for your problem in accordance with our motto: Your partner for all aspects of power supply equipment worldwide 3 Description Our UPS systems are equipped with a colored touchscreen display and consist of the following components: ➜ ➜ ➜ ➜ ➜ Rectifier Battery Inverter Electronic Bypass Manual Bypass Classification according to EN/IEC 62040-3: VFI SS-111 The individual components are matched to each other and controlled by different microprocessors. The rectifier converts the mains voltage into a DC voltage, from which the subsequent connected inverter forms a regulated, sinusoidal alternating voltage (AC). Apart from the inverter supply the parallel connected battery will be charged. The regulation of the rectifier is made by a fully controlled three-phase thyristor bridge in 6 pulse or 12 pulse technology. Optional: IGBT rectifier (sinusoidal power input). In case of a mains failure, the inverter will be fed from the battery, thus without change-over process a nobreak supply of the consumers is ensured. (On-LinePrincipe). After power recovery the rectifier starts to charge the battery automatically. Additional the rectifier takes over the supply of the inverter. The charge technology is optimized to the selected battery. The battery servers as an energy storage and is preferably implemented as a stationary lead acid battery. Depending upon the requirement, the battery will be sized based on an economically optimized solution between 5 minutes and 120 minutes. For special cases up to several hours. Depending upon application sealed lead acid (SLA), valve regulated lead acid (VRLA) batteries or NiCd batteries can be used. The main component of the UPS is the inverter, with high partial load efficiency. At an overload, short circuit at the consumer side or a disturbance of the inverter and/or a disturbance of the intermediate DC side, the UPS switches over to the electronic bypass uninterrupted. The automatic retransfer to the Inverter is as well uninterrupted. 4 Technical Data Technical Data UPS rated Power kVA UPS System 1-phase UPS System 3-phase 5 – 200 5 – 500 UPS input AC mains voltage V Input power factor 400/230 V, ± 10%, 3~, N, PE, 50 or 60 Hz ± 5% 6-pulse, 12 pulse or IGBT (λ > 0,99) Rectifier intermediate voltage DC voltage (–15 +20%) V 60 – 372 V Rectifier output tolerance % ± 1 (IU – characteristic accordance to DIN 41772) UPS output Nominal output voltage V 230V, 1-phase, N, PE 400/230V, 3-phase, N, PE Voltage regulation: static % ±1 dynamic % ± 4 at 100% load step unbalanced load % Regulation time ms ± 2 at 100% unbalanced load <4 (instantaneous value regulation) Overload character 150% for 1 min., 125% for 10 min., 110% for 20 min. Short circuit character 2 x Inom for 5 sec. 2 bis 4 x Inom for 5 sec. Frequency Hz 50 or 60 ± 0,1% crystal controlled or synchronised to the mains Synchronisation range % ±3 Waveform Distortion factor sinusoidal % EMC accordance to EN 62040-2 any power factor (power derating, if power factor deviates from 0,8 lagging) Permissible power factor ≤ 2,3 (at 100% Load) Crest factor of the load current Acoustic noise level ≤ 3 with linear load dB (A) 50 – 70 °C 0 to +40 Standard data Permissible ambient temp. Permissible climate 3K3 to IEC 60721-3-3 (85% rel. Humidity, no condensation) Permissible operating altitude 1000m above m.s.l. without derating Protection class IP20 according to EN 60529 Paint finish RAL 7035, structured finish, other painting on request Cooling Efficiency (overall) Display “AN” natural cooling or “AF” forced air cooling % up to 93,5 % TFT full graphic coloured touchscreen display incl. fault history 5 Options ➜ Convection cooling for high power systems ( “AN” natural cooling) + ➜ Isolation transformer at the rectifier input ➜ Isolation transformer at the bypass ➜ 12 pulse rectifier bridge ➜ IGBT rectifier with sinusoidal power consumption NEW ➜ Capacity test via rectifier feed back to the mains ➜ Enlarged rectifier for higher charging current ➜ Intermediate voltage 60V / 110V / 220V ➜ Enlarged inverter for a higher short circuit current ➜ Redundant power inputs via 2 mains (e.g. 50 Hz / 16 2/3 Hz) ➜ Temperature controlled charge voltage ➜ Fans elapsed control (battery room fan) ➜ Earth fault monitoring ➜ Battery circuit monitoring ➜ RS 232 interface ➜ Remote panel ➜ Remote monitoring via modem type “Datafern” ➜ Frequency converter ➜ Special input and output frequency ➜ Power plant design ➜ SNMP adapter incl. software ➜ Profibus, Modbus ➜ Shut-Down-Software ➜ Event printer ➜ Different IP rating ➜ Battery cabinets ➜ Distributions ➜ External manual bypass 6 Manufacturing Program UPS systems 1-phase: 1 – 200 kVA 3-phase: 5 – 500 kVA System performance: – 2000 kVA Inverter 1-phase: 1,0 – 200 kVA (24 – 1000 V DC, 16 2/3 Hz – 400 Hz) 3-phase: 3 – 500 kVA System performance: – 2000 kVA Thyristor technology (24 – 700 V DC) 5 – 2000 A Switch mode technology (24 – 372 V DC) 5 – 2000 A Transistor technology (60 – 1000 V DC) 5 – 1000 A Ferrous magnetic technology (24 – 220 V DC) 5 – 800 A Rectifier systems DC-voltage converter (24 – 220 V) 0,1 – 4 kW System performance: Frequency converter (16 2/3 Hz – 400 Hz) High power test systems – 50 kW 1 – 500 kVA 5 – 400 kVA (bis 1000 V DC, bis 400 Hz) Mains voltage regulator 1 – 1600 kVA Customer specific systems on demand! 04/2008 · subject to change without notice 7 XXX Power supply solutions Made in Germany & Austria Industrial applications Power stations supply Stationary railway supply Frequency converters Laboratory power supply Battery simulation Charge- and discharge units Industrial UPS GUSTAV KLEIN 8 GmbH & Co. KG D-86956 Schongau · Im Forchet 3 D-86952 Schongau, Postfach 12 48 Tel. +49 (0) 8861/209-0, Fax +49 (0) 8861/209-180 E-Mail: [email protected] Internet: http://www.gustav-klein.com GUSTAV KLEIN GmbH & Co. KG A-6401 Inzing/Tirol · Schießstand 2 Tel. +43(0)5238/54209-0 Fax +43(0)5238/54209-23 E-Mail: [email protected] Internet: http://www.gustav-klein.at Gesamtherstellung: Druckerei Joh. Walch, Augsburg Special UPS for hospitals