Download Maahantuoja ja edustaja

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Mercury-arc valve wikipedia , lookup

Ground (electricity) wikipedia , lookup

Utility frequency wikipedia , lookup

Electrification wikipedia , lookup

Power over Ethernet wikipedia , lookup

Audio power wikipedia , lookup

Power factor wikipedia , lookup

Ohm's law wikipedia , lookup

Electric power system wikipedia , lookup

Current source wikipedia , lookup

Electrical ballast wikipedia , lookup

Decibel wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Electrical substation wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power inverter wikipedia , lookup

Triode wikipedia , lookup

Rectifier wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Metadyne wikipedia , lookup

Power engineering wikipedia , lookup

Power MOSFET wikipedia , lookup

Voltage regulator wikipedia , lookup

Islanding wikipedia , lookup

Opto-isolator wikipedia , lookup

History of electric power transmission wikipedia , lookup

Three-phase electric power wikipedia , lookup

Surge protector wikipedia , lookup

Stray voltage wikipedia , lookup

Buck converter wikipedia , lookup

AC adapter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
The quality of low voltage and middle voltage
installations is very important. The presence
of distortions such as harmonics can have a
severe influence on this quality. The European
regulation EN 50160 is one of the most
important regulations for measurements of
LV-installations. The essential values for
LV-installations are subscribed in this regulation.
The Power Quality Analyser PQA6600 is a
complete instrument engineered for analysis of
the quality of a three-phase system. Basically,
the PQA6600 is equal to the PHA3300, but
more functions have been included.
The PQA6600 has the following extra
features:
- Waveforms measurement
- Fast logging
- Transients measurement
- Flicker analysis
Using these functions identifying the
distortions in engines, computers and other
appliances is easy.
Depending on the value to be measured,
several accessories and probes can be used.
For measuring currents, several current clamp
adapters are available (see pages 33-34, chapter
Current Clamp Adapters). With these adapters,
a complete three-phase installation can be
measured and analysed up to 3000 Amps.
In order to measure and analyse a
LV-installation, according to the EN50160,
two Power Analysers are available within the
Nieaf Instruments program:
The Power Harmonics Analyser PHA3300
is a portable instrument for measuring and
analysing single- and three phase systems.
Also irregular or interrupted voltage supplies
can be detected or recorded. Data recording
is one of the most relevant functions of the
instrument. After a period of statistical or
periodical analysis, the data can be transferred
to the PC software easily.
For optimal analyses of the measured values,
the included Windows software can be used.
This software can be used for storing the test
data and to make several reports and graphical
displays, all according to the EN50160
regulation. Obviously, the data and the reports
can be stored and printed. For report
modification into a customised report, the data
and reports can be exported to .xls-files.
Maahantuoja ja edustaja : Inel Oy
www.inel.fi
POWER ANALYSERS
POWER HARMONICS ANALYSER PHA3300
The PHA 3300 is an instrument for measuring
and analysing single- and three-phase systems
in compliance with the European regulation
EN 50160.
Main functions of the PHA 3300 are:
- Real time monitoring, recording and analysing
single- and three phase power supply systems.
- Measuring of a wide range of values, such as
True RMS voltage, True RMS current,
Power/Energy (Watt, VAR and VA),
Power Factor/ Cos phi, and Harmonics.
- Internal memory for storage of data (2Mb)
- Calculation of minimum, average and
maximum value for use on standard reports.
- Oscilloscope mode for viewing (real-time)
and storing of current and voltage waveforms.
- Harmonics measurements up to the 63rd
Realtime and stored.
- Energy monitoring and analysis.
- RS232 serial interface for connection to a PC.
Windows software for data analysis and
instrument controls included.
For the specifications for the PHA3300, check page
52-53-54
Dimensions
Weight
265 x 110 x 185 mm.
± 2,1 kg
Article number
Packing
EAN code
626 000 463
per set in a box
-
Including
manual, carrying bag,
batteries, test leads, RS232
cable, alligator clamps,
extra carrying bag with 3
1000A/1V current clamp
adapters, software
The power supply of the instrument can be
served by a rechargeable battery (max. 5 hours)
or mains voltage.
POWER QUALITY ANALYSER PQA6600
The PQA 6600 is basically equal to the Power
Harmonics Analyser 3300. Some extra features
and functions are integrated in the instrument
for optimal measuring, recording and analysing
the quality of single- or three phase systems,
in compliance with the European regulation
EN 50160.
The extra features/functions of the PQA 6600
are:
- Measuring of waveforms
- Fast logging
- Measuring of transients
- Flicker analysis
For the specifications for the PQA6600, check page
52-53-54
Dimensions
Weight
265 x 110 x 185 mm.
± 2,1 kg
Article number
Packing
EAN code
626 000 557
per set in a box
-
Including
manual, carrying bag,
batteries, test leads, RS232
cable, alligator clamps,
extra carrying bag with 3
1000A/1V current clamp
adapters, software
The tester has an EN 50160 Auto Mode with
reports and results based on this standard.
Maahantuoja ja edustaja : Inel Oy
www.inel.fi
POWER ANALYSERS
POWER HARMONICS AND POWER QUALITY ANALYSERS
(PHA 3300)
(PQA 6600)
Scope function allows viewing of current
and voltage waveforms
Meter menu for display of all measured
parameters
Voltage and Current Harmonic Analysis up
to 63th component
Accurate Energy Measurement Active
& Reactive, Import & Export, Inductive
& Capacitive, Separate registers for Total,
Sub-total & Last Integration Period
True real-time operation for capturing
anomalies, voltage interruptions and power
breaks. 2 Mb of memory allows data logging
to several months
Configuration menu for setting measuring
method, integration period, current scaling
factor and selection of signals
SOFTWARE (INCLUDED)
Simple set-up
On line measurements
Analysis
Over 300 quantities
(64 at the same time)
can be recorded and
stored in this mode.
All important quantities
and events can be
selected:
- average, minimum and
maximum voltage and
current RMS values
- harmonics and THD of
voltage and current
- voltage events and
anomalies (interruptions,
dips, sags), type and
duration
- particular and total
power
Selection of signals
and type of analysis
(periodics, anomalies,
statistics, EN50160)
6 channels oscilloscope
Selection of recording
time and averaging
cycles integration
period. Recording can
be set also from
instrument directly
harmonics up to 63th
Maahantuoja ja edustaja : Inel Oy
www.inel.fi
POWER ANALYSERS
SPECIAL FUNCTIONS FOR POWER QUALITY ANALYSER
Special tools enable a detailed, time domain based signal analysis. They represent a powerful, modern troubleshooting tool for solving all kinds of problems,
which are appearing in power distribution systems. The user can choose between three modes, differing in terms of sampling speed, trigger possibilities
and recording time.
WAVEFORMS
Recording of voltages and currents with 128
samples/period. Half period RMS values of
recorded quantities are also calculated and
shown in this mode. Best suited for:
- monitoring of switching phenomena,
- locating of noise and disturbance sources,
- defining disturbance type,
- locating excessive harmonics sources.
Typical problems that can be solved by
WAVEFORM analysis: capacitor banks switch
over, transformer overheating, UPS problems,
SMPS failures, etc.
FAST LOGGING
Recording of half period RMS voltage and
currents values. Recommended when record
length is critical and signal’s details are not of
importance. Best suited for:
- observing start up and inrush events,
- locating impedance problems,
- long term analysing of unstable mains.
Typical problems that can be solved with FAST
LOGGING analysis: too high inrush currents of
large motors, undersized fuses and installation
wiring, too weak voltage source, etc.
TRANSIENTS
The recording mode with fastest sampling rate
that the instrument can provide. Up to 50 kHz
transients detect ability in this mode. Best
suited for:
- monitoring atmospheric discharging,
- analysing switching problems,
- detailed analysing of high frequency noise
and notching.
Typical problems that can be solved with
TRANSIENT analysis: frequency noise, voltage
spikes caused by switching of capacitor banks,
etc.
EN 50160
Usually the NET quality is tested according the EN 50160 standard.
The PQA6600 can be set up to perform a basic measurement
according this standard. Results of such measurements are an
automatically generated report with good/fault indication.
REPORT
The (included) software contains a large number of possibilities for
reproduction of graphics for several measurements. It is also possible to
generate a complete EN50160 report. Graphics, reports and measurement
values can transferred to Excel or Word for further processing.
The PHA3300 and PQA 6600 perform tests according the following standards: EN 61000-4, EN 61000-7, EN 61000-11.
The instruments are produced according EN61010-1 (safety), EN50081-1 and EN 6100-6-1 (EMC) standards.
Maahantuoja ja edustaja : Inel Oy
www.inel.fi
POWER ANALYSERS
Technical Specifications – PHA 3300 / PQA 6600
Voltage
3 Fully differential channels
Input Voltage Range
Resolution
Accuracy
Frequency range
Current
Display range
Resolution
Accuracy
Permissible overload
Computer and DISPLAYED quantities
Scope
Waveforms
Power factor, Frequency,
Phase sequence
THD and Crest factor:
Meter
3x Urms, 3x Irms, Inone,
Frequency, cos phi
P, Q, S
Power factor
Spectrum
Harmonics
10 - 550Vrms L-N, 900Vrms L-L
0.1 V
± 0.5% of readings ± 2 digits
43 - 68Hz
Frequency
Ni-Cd batteries
Internal battery charger
Display
Display type
0.02 V – 1 V / 0,2 A – 3000 A
(depending on current clamp type)
0.3mV (0.3 A)
± 0.5% of readings ± 2 digits
+ current clamp accuracy
50% *sinusoidal current
3x
3x
3x
U, 3x I
(Urm s, Uavg, Umax)
(Irm s, Iavg, Imax)
Multimeter
Oscilloscope
Harmonics histograms
Configuration and programming menus
42 - 63 Hz
provides full operation for up to 5 hours
LCD graphic 160 x 116 display
with LED backlight
quantities in numerical mode
current and voltages waveforms
Internal memory
2Mbytes eeprom
Communications
Opto isolated RS 232 serial interface
for connection to PC
Baud rate
2400 – 57600
U, I
Extra features for PQA 6600:
(phase & total)
(phase & total)
EN50160 Analysis mode
Voltage dips, swells, sages and breaks resolution 10 ms, no gaps
Voltage unsimetry, Voltage RMS values,
Frequency
Harmonics
up to 43th component
Fickers Plt Pst
no gap
DC…63 (on display DC…25)
percentual and absolute amplitudes
for selected quantities
Flicker measurement
The instrument computes flickers
according to IEC 61000-4-15
THD Urms, Irms
Recorder
Integration period
1 sec – 900 sec
Statistics analysis of each period (20 ms.)
Voltage anomalies – based on half
period (10 ms) and selected window
(± Un), configurable recording registers.
Recording of periods (selectable data,
max. 64 parameters.)
General
Overvoltage category
Pollution category
Max. voltage between terminals
Max. voltage against ground
Protection degree
Waveforms
Sampling rate
Trigger
Buffer
128 scans / period
level, manual, timer
Min 10 periods of pre/post size.
Up to 7812 periods can be recorded
3x U, 3x I, U lines, min/max rms
values, avg
Channels
Pf, cos phi Crest factor, THD U,
I Frequency, Harmonics magnitudes /
direction positive / negative
CAT III / 600 V
2
900V
550V
IP54
Fast logging
Sampling rate
Trigger
Buffer
128 scans / period min / max avg rec
level, manual, timer each half period
pre / post size, up to 166 minutes
of recording
3x U, 3x I, Single or multichannel
mode
Channels
Dimensions
Size (H x W x D)
Weight (without accessories,
with batteries)
Power requirements
Voltage operating range
265 x 110 x 185 mm
Transients
Capturing
Trigger
Buffer
2.1 kg
230 Vac (±10% 20%)
(110 Vac on request)
>20 µs transient detect ability
level, slope, manual
Min 10 periods of pre/post size.
Up to 1000 periods can be recorded
3x U, 3x I, Single or multichannel mode
Channels