Download CT Phase Shift and its Affect on Power Factor

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power inverter wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Islanding wikipedia , lookup

Voltage optimisation wikipedia , lookup

Wireless power transfer wikipedia , lookup

Decibel wikipedia , lookup

Standby power wikipedia , lookup

History of electric power transmission wikipedia , lookup

Mains electricity wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Power over Ethernet wikipedia , lookup

Audio power wikipedia , lookup

Electrification wikipedia , lookup

Power electronics wikipedia , lookup

Electric power system wikipedia , lookup

Power factor wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Alternating current wikipedia , lookup

Power engineering wikipedia , lookup

AC adapter wikipedia , lookup

Three-phase electric power wikipedia , lookup

Transcript
CT Phase Shift and its Affect on Power Factor
Eric Christensen
Magnelab, Inc.
10 April 2014
Page 1 of 5
When metering or monitoring the amount of power dissipated in a circuit it is important
to have an accurate measurement of each of the two contributing waveforms, voltage and
current. Accuracy is not only necessary for amplitude of the two waveforms, but also the phase
relationship between the waveforms must be considered. Any phase angle difference between the
two waveforms is known as phase shift and causes an error when trying to determine the true
power consumption. When metering or monitoring, the use of components that add minimal or at
least predictable amounts to the phase shift are important to allow for accurate results.
For the current measurement in metering or monitoring it is common to use a current
transformer (CT) assembled around the conductor under test. However, a phase shift of the
current waveform from the input of a current transformer to the output is a common problem. As
with any inductive device there is a lag in time from when the signal arrives in the CT to the time
the CT inductively responds and produces an output. Understanding the phase shift in the current
transformer requires a look at the equivalent circuit of a transformer and an understanding of the
effects of each component (See “Magnelab Equivalent Circuit” for more on that subject). This
discussion will focus on the fact that there is a phase shift and how it affects the power factor
calculations.
Power factor (PF) expressed as a fraction is the ratio between the true power (Watts)
dissipated by the load and the apparent power (Volt Amps) that must be generated to satisfy the
load. The amount of apparent power is determined by a third component, the reactive power
(Volts-Amps-Reactive). The power factor is a dimensionless number between 0 and 1. When this
ratio is equal to one (1) the voltage and current are in phase with each other and the true and
apparent power are equal. Any shift in the current waveform from the voltage wave form creates
a power factor of less than 1.
When looking at these components of power in relationship with their polar magnitudes,
any PF less than 1 forms a right triangle also known as “The Power Triangle”. The true power
(W) is the “X” axis (Adjacent side), the apparent power (VA) is the slope (Hypotenuse) and the
reactive power (VAR) is the “Y” axis (opposite side). Because the true power and apparent
power form the adjacent side and the hypotenuse side the power factor ratio is also equal to the
cosine of the phase angle.
Page 2 of 5
Apparent Power (VA)
Reactive Power (VAR)
Phase Angle
True Power (W)
The power triangle relating apparent power to true power and reactive power
Chart 1 below shows the resulting calculated power factor as a result of the phase shift.
Due to the cosine function being nonlinear, and as can be seen in the chart, a linear change in the
phase shift does not result in a linear change in the PF. When measuring power using a CT for
the current portion of the measurement, the phase shift of the CT results in an increases
magnitude of PF error depending on the point on the curve.
Chart 1
1.2
1
1
0.9848
0.9397
0.866
Power Factor
0.8
0.766
0.6428
0.6
0.5
0.4
0.342
0.2
0.1737
0
0
90
0
10
20
30
40
50
Phase Shift
Page 3 of 5
60
70
80
When looking at the effect of the CT phase error on the power measurement it becomes
obvious that the lower power factor will result in a higher measurement error as seen in Chart 2,
showing the power measurement error verses the power factor with examples of CT phase angle
errors.
Chart 2
14%
Power Measurment Error
12%
10%
8%
CT Phase 0.5deg
6%
CT Phase 2.0deg
CT Phase 5.0deg
4%
2%
0%
1
0.9
0.8
0.7
0.6
Power Factor
An example of this is measuring the PF error of a circuit at a phase shift of 1 deg and
another PF error of a circuit with a phase shift at 60 deg. Both examples using a CT with a 2 deg
shift:
If measuring a circuit with a 1 deg phase shift using a CT with a 2 deg phase shift the resulting
PF measurement is:
Cos 1 = 0.999848 (actual PF)
Cos (1+2) = 0.998630 (measured PF)
Error = 0.001218 or 0.122%
Page 4 of 5
If measuring a circuit with a 60 deg phase shift using a CT with a 2 deg phase shift the resulting
PF measurement is:
Cos 60 = 0.500000 (actual PF)
Cos (60+2) = 0.469472 (measured PF)
Error = 0.03053 or 6.1%
In the two examples the CT has not changed and is still accurate to 2 deg, however the PF
accuracy has almost no added error when added to the 1deg phase shift, but is significantly
affected by the small phase shift in the CT when added to the phase shift of 60 deg. The 6.1%
error above may seem small, but consider a common household power consumption in one
month may be 500KWH or more, and the PF error caused by the phase shift at 60deg:
Apparent power = True power/Power factor
VA = 500,000/0.500000 =
1,000,000 (actual VA)
VA = 500,000/0.469472 =
1,065,026 (measured VA)
65,026 VA error
As shown above, the error can add up and cause large discrepancies in power generation
requirements and usage.
When designing or evaluating a power measuring system the affect of the CT phase shift
on the power factor must be considered based on the characteristics of the circuit under test and
the affect they can have on the resulting measurements.
Eric Christensen
Director of Engineering and Sales
Magnelab, Inc.
Page 5 of 5