SECTION 16808 INSTRUMENT WIRING STANDARDS 808.01 GENERAL The terms “or equivalent” in the following, means that substitution of like styles or kinds are acceptable with the approval of the specifying Engineer. 808.02 TERMINAL BLOCKS Terminal blocks for Instrument signal and power applications shall be 8 mm DIN Rail Mounting. A. Accesories , such as “End stops”, “End plates”, “Offset brackets”, “Circuit separators “ etc. are to be used as standard. B. C. DIN Rail mounted 8 mm Fuse blocks, with Blown Fuse Indicator (BFI) shall be provided on all +24Vdc supply legs. D. Fuse blocks, with BFI shall be provided on the field return leg. E. Color of blocks to be gray. F. Terminal block screws, shall be of the “sliding shoe” type, this is to avoid the possibility of the screw cutting the wire at the tightening point(s). 808.03 TERMINAL BLOCK LAYOUT A. In general, terminal blocks will be stacked vertically. B. All field connection wiring (to transmitters), shall be connected to the left side. C. All power supply connections (+24Vdc and Com) will be connected to the right side, this includes power supply jumpers. D. All other connection will be on the right side. E. All loops will have the following vertical blocks, from the top down: 1. +24Vdc supply, which shall be bussed. 166808-rev0 16808 - 1 December 2004 SECTION 16808 INSTRUMENT WIRING STANDARDS 2. +24Vdc to field transmitter, 3. Return from transmitter (connected via a BFI) to Signal “home run” (the positive side of the two wires going to the controller or PLC I/O port), 4. Common (connected to the “home run” return), which shall be bussed to the 24Vdc power supply (aka common). 5. Spares. 6. Shield and the drain wires from the field and “home run”. These shall be connected to case ground only. 7. At a minimum there shall be six (6) terminal blocks per loop. 8. “Circuit separators” shall separate each loop. 808.04 WIRING A. All instrument field wiring shall be Belden Industrial # 3076F - Instrumentation/Control Cable DataBus(TM) ISA/SP-50 Fieldbus Cable Type A. Two 18 AWG, stranded, tinned copper conductors. Polyolefin insulation. Overall shield of 100% Foil shield plus stranded, tinned copper drain wire. Orange PVC Jacket, Data Rate: 31.25 Kbits/sec., Voltage Rating: 300V (or equivalent). B. Conductor jacket colors, for pairs, shall be preferably black and white. C. In all cases the color black designates the negative of DC voltage. 808.05 GROUND, SHIELDING, DRAIN WIRES A. Drain wires and the foil shields of both the field and “home run” cables will be terminated ONLY 166808-rev0 16808 - 2 December 2004 SECTION 16808 INSTRUMENT WIRING STANDARDS ONCE and that is to the ground in the Field Power Supply Cabinet. B. When there is an intermediate panel before the final “read-out” device, the drain wires and shields shall be connected but not grounded again. C. The purpose is to prevent the possibility of current flowing, for any reason, along the length of the shield/drain wire, such as towards to the readout device. D. The drain wire and/or shield shall be insulated from becoming grounded at the ends by means of a 2 inch insulating sleeve. E. Typically the unshielded portion of the twisted pair shall be no less than 3/4” and no more than 2.0" in length. 808.06 CABLE AND WIRE IDENTIFICATION A. A shrink wrap sleeve, “Ty-Wrap” style of wire marker holder or other sleeve type of identification or marker shall be fixed permanently to the over jacket of the cable. Preprinted on this jacket marker shall be the Instrument tag ID for the instrument or device that is being serviced by the cable. B. For example, if the cable goes to PCW006TIT-614, so mark the cable sleeve. If the cable goes to PLC450 I/O port 27, so mark the cable sleeve. C. Cable tags shall be continuous from end-point to end-point. D. For “Home run” cables the sleeve shall be marked “Origin Building Number, Origin Junction Box Number, Number of Pairs contained in cable, Destination Junction Box Number, Sequence Number”. E. Sequence number shall be based on Origin and Destination Junction Box numbers only, this means where only two cables go between the same source and destination, the sequence numbers shall be 1 and 2 respectively. 166808-rev0 16808 - 3 December 2004 SECTION 16808 INSTRUMENT WIRING STANDARDS 808.07 TERMINATION A. Care shall be taken to strip wire without nicking or damaging the conductors. Frayed, nicked or missing strands/conductors at the point of termination is not acceptable. B. Where the connection is made to a terminal block, the ends should be stripped bare between 3/8” and 5/8” in length. For stranded conductors, the ends shall be twisted lightly and tinned, then inserted into the opening of the terminal block so that when secured (tightened), a nominal 1/32” of bared, tinned, wire is visible. C. “Spade tongue” insulated crimp termination are required on “under the head” style screws, except for Ground connections which shall be “Ring tongue”. 808.08 IDENTIFICATION TAGS ON INSTRUMENTS A. Instrument Tags shall be stainless steel, either engraved or stamped with the Full Instrument Tag Number. B. A Full Instrument Tag Number. For example PCHW006FQIC-0315 C. A breakdown of the Instrument Tag Number structure follows: PCHW = Process Chilled Water HGST CAD Standards MP05-09) 006 = Building Number FQIC = Flow Totalizing(Q) Indicating Controller (ISA Standards) = Spacer 0315 = Sequence Number D. The Instrument Tag shall be affixed to the instrument so that it is visible and easy to read. E. The Instrument Tag shall be affixed to the instrument by a stainless steel “ty-wrap” or other stainless steel wire method that prevents disassembly of the Tag from the Instrument. 166808-rev0 16808 - 4 December 2004 SECTION 16808 INSTRUMENT WIRING STANDARDS ***END OF SECTION 16808*** 166808-rev0 16808 - 5 December 2004