Download Cables, conduits and trunking

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power over Ethernet wikipedia , lookup

Electrical substation wikipedia , lookup

Islanding wikipedia , lookup

Stepper motor wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Electrical ballast wikipedia , lookup

History of electric power transmission wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Opto-isolator wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Rectifier wikipedia , lookup

Loading coil wikipedia , lookup

Three-phase electric power wikipedia , lookup

Stray voltage wikipedia , lookup

Multimeter wikipedia , lookup

Ohm's law wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Surge protector wikipedia , lookup

Distribution management system wikipedia , lookup

Metadyne wikipedia , lookup

Current source wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Buck converter wikipedia , lookup

National Electrical Code wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
Cable Volt Drop
All cables have resistance, and when current flows in them this results in a volt drop.
Hence, the voltage at the load is lower than the supply voltage by the amount of this
volt drop. Volt drop may be calculated using the basic Ohm's law formula V = I x R
Unfortunately, this simple formula is seldom of use in this case, because the cable
resistance under load conditions is not easy to calculate.
The voltage at any load must never fall so low as to weaken the safe working of that
load, or fall below the level indicated by the relevant British Standard where one
applies.That these requirements will met if the voltage drop does not exceed 6% of
the declared supply voltage. If the supply is single-phase at the usual level of 240 V,
this means a maximum volt drop of 6% of 240 V which is 14.4 V, giving a load
voltage as low as 225.6 V. For a 415 V three-phase system, allowable volt drop will
be 24.9 V with a line load voltage as low as 390.1 V.
To calculate the volt drop for a particular cable we use tables that each current rating,
has an associated volt drop column or table. In the tables each cable rating has a
corresponding volt drop figure in millivolts per ampere per metre of run (mV/A/m). To
calculate the cable volt drop:
1.-take the value from the volt drop table g (mV/A/m)
2.-multiply by the actual current in the cable I (NOT the current rating)
3.-multiply by the length of run in metres 
4.-divide the result by one thousand (to convert millivolts to volts).
V 
gI
V
1000
For example, if a 4 mm² p.v.c. sheathed circuit feeds a 6 kW shower and has a
length of run of 16 m, we can find the volt drop as:
From the table, the volt drop figure for 4 mm² two-core cable is g =11 mV/A/m.
Cable current is calculated from I  P V  6000 240  25 A
Volt drop is then V  11x25 x16 1000  4.4V V%  4.4x100 240  1.83%
Since the voltage drop1.83% is less than the permissible volt drop is 6%,
(1.83%<6%), the cable in question meets volt drop requirements.
Fig. Total volt drop in large installations
The following examples will make the method more clear.
Example 1
An immersion heater rated at 240 V, 3 kW is to be installed using twin with protective
conductor p.v.c. insulated and sheathed cable. The circuit will be fed from a 15 A
miniature circuit breaker type 2, and will be run for much of its 14 m length in a roof
space which is thermally insulated with glass fibre. The roof space temperature is
expected to rise to 50°C in summer, and where it leaves the consumer unit and
passes through a 50 mm insulation-filled cavity, the cable will be bunched with seven
others. Calculate the cross-sectional area of the required cable.
Example 2
A 415 V 50 Hz three-phase motor with an output of 7,5 kW, power factor 0.8 and
efficiency 85% is the be wired using 500 V light duty three-core standard insulated
p.v.c. sheathed cable. If the length of run from the MCB protecting fuses is 40 m,
calculate the size of the correct cable. (Hint: For the safe start of motor take the value
of the line current as 2.5 times the calculated one.)