* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Improving Voltage Profile in the Egyptian National Power System
Ground (electricity) wikipedia , lookup
Power over Ethernet wikipedia , lookup
Immunity-aware programming wikipedia , lookup
Audio power wikipedia , lookup
Power factor wikipedia , lookup
Electrification wikipedia , lookup
Electric power system wikipedia , lookup
Electrical ballast wikipedia , lookup
Pulse-width modulation wikipedia , lookup
Power inverter wikipedia , lookup
Current source wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
Distributed generation wikipedia , lookup
Three-phase electric power wikipedia , lookup
Schmitt trigger wikipedia , lookup
Amtrak's 25 Hz traction power system wikipedia , lookup
Opto-isolator wikipedia , lookup
Power engineering wikipedia , lookup
Power MOSFET wikipedia , lookup
Power electronics wikipedia , lookup
History of electric power transmission wikipedia , lookup
Electrical substation wikipedia , lookup
Voltage regulator wikipedia , lookup
Buck converter wikipedia , lookup
Surge protector wikipedia , lookup
Stray voltage wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Alternating current wikipedia , lookup
The Online Journal on Power and Energy Engineering (OJPEE) Vol. (2) – No. (1) Improving Voltage Profile in the Egyptian National Power System (Enps) Using Simultaneously Three Specific Remedial Actions for Reactive Power Compensation (Part 1) N. M. Abdel-Gawad A. S. H. Hamza Benha University H. M. Hassanin S. A. Mahmoud Ministry of Electricity & Energy Abstract-This Paper deals with the problem of voltage instability that leads in some cases to voltage collapse and complete blackouts. Voltage instability, being the absence of voltage stability, results in progressive voltage decrease (or increase). A power system at a given operating state and subject to a given disturbance undergoes voltage collapse if the post-disturbance equilibrium voltage is below acceptable limits. Voltage collapse may be total or partial blackout.[1] Many major blackouts throughout the world have been directly associated to this phenomenon, e.g. in France, Italy, Japan, Great Britain, USA, etc. The analysis of this problem shows that the major causes is the system’s inability to meet the reactive power demands. The main objective of this work is to find the most favorite methods to assure the security of the system in terms of voltage stability.[2] In most case studies, using of one remedial action is not enough to solve the voltage instability problem. This paper declares that the usage of combined remedial actions, specially during the peak load hours is a must solution in most cases. Also it is declared that the usage of normal capacitors to add reactive power together with the other suggested methods helps much as being a cheap tool. It is known that the improvement of voltage levels on a power system reduces the losses. In the present case, specially at peak load, it is gained that the same energy demand could be fulfilled with less power generation. In addition to securing the voltage levels on a power system, a feasible return is achieved. I. INTRODUCTION The voltage instability problem in power systems has been demonstrated to be related to the overall stability of the system and is closely associated with the proximity of a system to a voltage collapse condition. as the system approaches a voltage collapse point, its stability region becomes smaller, resulting in a system that is less likely to survive contingencies. Considering the continuous development in the Egyptian Electricity Power System during the past twenty years and the rapid increase of the electricity Reference Number: JO-0002 S. El-Debeiky Ain Shams University demand, which was clearly shown by the technical studies to predict the loads as a result of the continuous increase in population, urbanization, industrial and service projects, the problem of voltage stability gains more and more importance and studies as in everywhere [3],[4],[5]. Special emphasis has been given to the following items: • Designed capacity to secure loads under standard (N-1) contingency operation. • Raising the voltage level of the electric grid or enhancing the voltage levels in the grid. • Reducing the losses in the grid. The values of allowed voltages for the Egyptian national network under different operating conditions (normal and contingency) for the different voltage levels are shown in Table (1): Table (1) The Allowed voltage values for the Egyptian National Network Voltage in case of Voltage in case of Voltage ordinary operation contingency disconnect level Higher Least Higher Least (K.V.) Voltage Voltage Voltage Voltage 500 525 475 550 450 400 420 380 420 360 220 231 209 242 198 The criteria for (N-1) is used for studying the cases of contingency disconnect for the Egyptian national grid. i.e. disconnecting one element of the grid elements (transmission line- generation unit) taking into consideration the following factors: • The power transferred through the transmission lines be less than the rated capacity of these lines. • The level of voltage for the various voltages should be within the allowed values for operation, Table (1). • Preventing any reduction for frequency levels in order to prevent load shedding equipments from working. • Preserving the stability of generation units while operating within the range of their capability curves. 177 The Online Journal on Power and Energy Engineering (OJPEE) II.THE RECOMMENDED SIMULTANEOUS REMEDIAL ACTIONS A study and analysis of the most widespread methods to solve the voltage instability problem were carried, out. Based on these and on the experience of dealing with the Egyptian National Power System (ENPS) and its technical and economical conditions, three remedial actions have been recommended to apply on the two selected systems in this paper. The three remedial actions are the optimal usage of the reactive power produced from generation units on the nodes near the power stations, changing the tap points on the transformers on the nodes near the sub-stations and injection of reactive power at selected buses in various areas along the system capacitors. Using these remedial actions could be used in cascading or combining manners according to the requirements of the system. III. PROPOSED SYSTEMS FOR APPLICATION AND SIMULATION To apply the recommended remedial actions, two power systems were proposed. The first one is the known (IEEE)-30 bus system [6].the second one, the main power system under study is the Egyptian National Power System (ENPS) of Extra-High Voltage 500 KV and High-voltage 220 KV levels. ENPS contains 44 power stations with a total installed capacity of about 25000 MW, 14 substations of 500 KV and 134 substations of 220 KV The total number of buses are 25 and 275 on the 500 and 220 KV respectively[3]. Fig. (1): presents the single line diagram of the network parts under study. The simulation tool used in this paper is the Power System Simulation for Engineering (PSS/E) as an known software package. This package was preferred due to its wide usage in the world, especially in the grand utilities in the field of electricity as similar as the Egyptian Electricity Holding Company (EEHC).and as it is an interactive program for simulating, analyzing and optimizing power system performance. The program contains a set of modules which handle a number of different power system analysis calculations.[7] IV. CONTINGENCY ANALYSIS System Static Security encompasses the ability of the power system to withstand steady-state conditions, some unforeseen, but reasonably expected, unscheduled outages of network elements, with the minimal disruption of the service or its quality. Contingency analysis method is based on simulation of element outages by a deterministic approach. Complete analysis of the N-1 situations has been carried out for both 500 K.V, 220 K.V. transmission networks for the Egyptian National Power System (ENPS) for each target year and for selected characteristic hour load conditions. The network constraints and violations have been detected and reported giving the number of overloads for lines and transformers and the number of nodes with voltage levels out Reference Number: JO-0002 Vol. (2) – No. (1) of limits. As well, cases of generation units contingencies have been studied. IV.1 Transmission Line Contingencies: Case Of One 500 K.V Circuit Tripped Table(2) presents the voltage levels calculated in case of outage of one circuit of 500 K.V. line for 500 K.V. nodes the following results are obtained: Case 1: The outage of one circuit of 500 K.V. line High Dam(B#293) – Nag Hammadi(B#292) caused many critical 500K.V. contingencies that lead to post contingency situations characterized by very low voltage levels with probable risk of widespread voltage collapse. It is cannot be analyzed due to non-convergence of load-flows. This contingency causes a generalized low voltage profile in Upper Zone of Egypt. Case 2: Another case, the outage of one circuit of 500K.V. line Assuit (B#291) – nag hammdi (B#292). This case also cannot be analyzed due to non-convergence of load-flows. This contingency causes a generalized low voltage profile in Upper Zone in Egypt too. Case 3: The third case, the outage of one circuit of 500K.V. line SAML 500 (B#235 - Cairo 500 (B#30) causes small voltage drop in the 500 K.V. network so, the convergence of load flows is existing in this case. Case 4: The outage of one circuit of the 500 K.V. line Nobaria (B#192) - Cairo 500(B#30) cannot be analyzed due to non-convergence of load-flows. This contingency causes a generalized low voltage profile in Cairo and Delta Zones. Case 5: The outage of one circuit of 500 K.V. line A.Zabbl (B#233) - Bassous500 (B#180) causes small voltage drop in the 500K.V. network. Case 6: The outage of one circuit of 500 K.V. line O.Moussa (B#305) - Suze500 (B#303) causes small voltage drop in the 500K.V network. Table (2): The p.u voltage levels calculated in case of outage of one circuit of 500 K.V line on the 500 K.V. nodes. Voltage (p.u.) Bus Normal No. Case 1 Case 2 Case 3 Case 4 Case 5 Case 6 condition 30 0.914 0.907 0.911 0.905 0.888 0.911 0.914 180 0.916 0.911 0.913 0.908 0.894 0.911 0.915 192 0.969 0.968 0.968 0.967 0.972 0.968 0.969 229 0.920 0.914 0.917 0.913 0.901 0.926 0.918 233 0.935 0.928 0.932 0.930 0.920 0.938 0.935 235 0.938 0.900 0.924 0.933 0.924 0.937 0.938 238 0.917 0.911 0.914 0.909 0.894 0.912 0.916 291 0.918 0.858 0.896 0.912 0.909 0.917 0.918 292 0.907 0.816 0.877 0.902 0.904 0.906 0.907 293 1.001 0.990 0.987 0.999 1.000 1.000 1.001 303 0.957 0.956 0.955 0.953 0.944 0.961 0.954 305 0.962 0.961 0.961 0.958 0.950 0.966 0.963 306 0.944 0.945 0.942 0.939 0.931 0.948 0.945 320 0.957 0.947 0.953 0.952 0.943 0.957 0.957 950 0.977 0.977 0.976 0.975 0.974 0.976 0.977 178 The Online Journal on Power and Energy Engineering (OJPEE) Figure (2) illustrates the voltage profile in case of outage of one circuit of 500 K.V. line on the 500 K.V. nodes for different cases. IV.2 Generation Unit Contingencies At Peak Load conditions, it is difficult to lose generation unit(s) as the Power reserved is so little. Loss of generation unit(s) need re-dispatch the output power from all generation units which have reserve active power to compensate the loss of generation. In this section, the outage of Generation units is carried out in different zones in Egypt and recording of the effects of these events on the Voltage Profile on both the 500, 220 K.V networks are presented. Case 1: The outage of Generation unit at bus North West South Gulf (N.W.S.G) (B#206) of 340 MW. In this case, the ENPS loses the Generation unit at bus N.W.S.G(B#206) which is located in the Canal Zone with maximum active power of 340 MW. There are some 220 K.V. substations that suffer from low voltage levels such as SHARM (B#915), NABK (B#917) and GHARD (B#804), which may lead to voltage collapse. Case 2: The outage of Generation unit at bus GN.WALID (B#507) of 320 MW. In this case, the ENPS loses the Generation unit at bus GN.WALID (B#507) which is located in the Upper Zone with maximum active power of 320 MW. There are some 220 K.V. substations suffering from low voltage levels such as SAML220 (B#5038), SAFAGA (B#5051) and QENA220 (B#5046) and other 220 K.V. substations located in the Canal Zone will suffer from low voltage levels such as SHARM SH (B#915), NABK (B#917) and GHARD (B#804), which may lead to voltage collapse. Case 3: The outage of Generation unit at bus GN.KURIM (B#530) of 625 MW. In this case, the ENPS loses the Generation unit at GN.KURIM (B#530) which is located in the Upper Zone with maximum active power of 625 MW. The outage of GN.KURIM (B#530) unit cannot be analyzed due to non-convergence of load-flows. This contingency causes a generalized low voltage profile in Cairo and Upper Zones, as it is one of the largest units in the ENPS. Case 4: The outage of Generation unit 330 MW at bus GN.CW.1 (B# 516). In this case ,the Egyptian power system losses the Generation unit at GN.CW.1 (B#516) which is located in the Cairo zone with maximum active power 330 M.W. Case 5: The outage of Generation unit at bus G.NOBAR (B#538) of 250 MW. In this case, the ENPS losses the Generation unit at GN.KURIM (B#538) which, is located in the Delta Zone with maximum active power of 250 M.W. Table (3) presents the voltage levels calculated in case of outage of Generation units on the 500 K.V. nodes for different cases. Reference Number: JO-0002 Vol. (2) – No. (1) Table (3): The p.u voltage levels calculated in case of outage of Generation units for 500 K.V. nodes for different cases. Voltage (p.u.) Bus No. Base Case 1 Case 2 Case 3 Case 4 Case 5 Case 30 0.914 0.904 0.906 0.898 0.906 0.915 180 0.916 0.904 0.908 0.901 0.907 0.917 192 0.969 0.964 0.966 0.965 0.966 0.967 229 0.920 0.907 0.912 0.903 0.912 0.921 233 0.935 0.924 0.928 0.911 0.931 0.937 235 0.938 0.930 0.916 0.906 0.938 0.948 238 0.917 0.905 0.909 0.901 0.907 0.918 291 0.918 0.913 0.892 0.883 0.921 0.933 292 0.907 0.906 0.888 0.871 0.915 0.927 293 1.001 1.002 0.996 0.978 1.005 1.010 303 0.957 0.941 0.952 0.946 0.952 0.958 305 0.962 0.946 0.957 0.952 0.957 0.963 306 0.944 0.923 0.937 0.933 0.938 0.945 320 0.957 0.949 0.949 0.924 0.954 0.960 950 0.977 0.970 0.972 0.973 0.972 0.975 Figure (3) illustrates the voltage profile in case of outage of Generation units on the 500 K.V. nodes for different cases of outages. V. REMEDIAL ACTIONS V.1 Impact of the recommended Remedial Actions The three remedial actions are the optimal usage of the reactive power produced from generation units on the nodes near the power stations, changing the tap points on the transformers on the nodes near the sub-stations and injection of reactive power at selected buses in various areas along the system. These Remedial Actions have been selected to improve the voltage profile. In the previous sections, the analysis for the effect of losing one element of the network (N-1) were carried out in case of normal conditions without using any remedial actions. In this section, the selected remedial actions will take place. Once again, the analysis for the effects of (N-1) for the same cases in the previous sections are repeated in the presence of the remedial actions. The results and the improvement in the voltage profile are shown in the following subsections. V.2 Optimal Usage Of Reactive Power Produced From The Generation Units The schedule voltage (Vsch.) of certain generation units of the ENPS, which have reserve in the reactive power, is changed to produce more reactive power to improve the voltage profile as possible as can. Changing Vsch. has the largest effect on the 500 K.V. and 220 K.V. profiles of the ENPS. All 500 K.V. substations which are suffering from low voltage levels are going to be in the permissible limits. Some of the 220 K.V. substations are still suffering from low voltage levels, as the voltage is not within the permissible limits such as SHARM 179 The Online Journal on Power and Energy Engineering (OJPEE) (B#915), NABK (B#917), QENA220 (B#5046) and GHARD (B#804). Table (4) illustrates the Changing the schedule voltage at certain generation units of the ENPS. Table (4): The changing of Vsch. at certain generation units of the ENPS Bus No. Pgen (MW) 440 415.4 Qgen (MVA) at base case 227.3 315 Vsch (p.u.) base case 1.015 441 525 240.7 330 1.015 442 525 240.7 330 443 525 240.7 530 600 531 600 624 625 Vsch (p.u.) New Qgen (MVA) New 1.04 294.8 1.04 306.1 1.015 1.04 306.1 330 1.015 1.04 306.1 326 400 0.95 0.98 359.4 326 400 0.95 0.98 359.4 330 127.1 200 1 1.03 140.9 330 127.1 200 1 1.03 140.9 Qmax MVA) Table (5) reports the voltage levels calculated in case of changing Vsch at certain generation units of the ENPS on the 500 K.V. nodes. Table (5): The voltage levels calculated in case of changing Vsch at certain generation units of the ENPS on the 500 K.V. nodes. Bus Vsch (Base case) Vsch (New) (pu) No. (pu) 30 0.914 0.957 180 0.916 0.957 192 0.969 1.021 229 0.920 0.958 233 0.935 0.974 235 0.938 0.992 238 0.917 0.958 291 0.918 0.977 292 0.907 0.970 293 1.001 1.042 303 0.957 0.984 305 0.962 0.988 306 0.944 0.976 320 0.957 0.998 950 0.977 1.017 Figure (4) illustrates the voltage profile in case of changing Vsch at certain generation units of the ENPS on the 500 K.V. nodes. V.3 Changing the Tap Points of Transformers Case 1: Change the tap of Cairo 500 (B#30) Case 2: Change the tap of Cairo West 500 (B#238) Vol. (2) – No. (1) Case 4: Change the tap of Nobaria 500 (B#192) Case 5: Change the tap of kurimtt 500 (B#320) Reactive power limits on generators and the tap limits on tap changing transformers have a significant effect on voltage collapse. The tap ratio of certain 500/220 K.V. transformers is changed to control the reactive power flow in order to get the most suitable voltage profile for the 500 K.V. and 220 K.V. networks. Different scenarios of changing the tap ratio are carried out. Table (6) reports the voltage levels calculated in case of changing the tap ratio of certain 500/220 K.V. transformers on the 500 K.V. nodes in different cases. Figure(5) illustrates the voltage profile in case of changing the tap ratio of certain 500/220 K.V. transformer on the 500 K.V. nodes in different cases. This agrees with previous findings[8]. Table (6): The voltage levels calculated in case of changing the tap ratio of a certain 500/220 K.V. transformers on the 500 K.V. nodes Bus No. 30 180 192 229 233 235 238 291 292 293 303 305 306 320 950 Voltage (pu) Actual Tap 0.914 0.916 0.969 0.920 0.935 0.938 0.917 0.918 0.907 1.001 0.957 0.962 0.944 0.957 0.977 Case 1 0.944 0.937 0.985 0.936 0.946 0.954 0.939 0.933 0.920 1.005 0.965 0.970 0.954 0.968 0.989 Case 2 0.925 0.929 0.983 0.929 0.942 0.947 0.930 0.926 0.914 1.003 0.963 0.968 0.951 0.963 0.988 Case 3 0.922 0.925 0.983 0.923 0.939 0.944 0.925 0.924 0.912 1.002 0.957 0.962 0.943 0.961 0.987 Case 4 0.915 0.916 0.988 0.919 0.935 0.938 0.917 0.917 0.906 1.000 0.956 0.962 0.943 0.957 0.988 Case 5 0.920 0.921 0.983 0.924 0.940 0.944 0.922 0.924 0.912 1.003 0.960 0.965 0.947 0.963 0.988 V.4 Injection of Reactive Power at Certain Nodes According to the System Requirements Thus, the reactive Power output from generation plays a very important role in assuring successful transactions of electric energy[9]. However, The experience with the ENPS shows that the average power factor is 0.85 at the peak load which causes low voltage level at many substations. To improve the average power factor, it is important to select suitable locations for adding capacitors in order to obtain good results[10]. Figure (6) illustrates the voltage levels on the 500 K.V. nodes after improving the power factor from 0.85 to 0.92. Table (7) shows the optimal locations of the reactive power which will be added to improve the power factor from 0.85 to 0.92 to avoid the voltage collapse Case 3: Change the tap of Bassous 500 (B#180) Reference Number: JO-0002 180 The Online Journal on Power and Energy Engineering (OJPEE) Vol. (2) – No. (1) Table (7): The impact of improving the power factor on the voltage levels on the 500 K.V. nodes. Bus Voltage (pu) No PF=0.85 PF=0.88 PF=0.89 PF=0.90 PF=0.91 30 0.914 0.928 0.935 0.942 0.947 180 0.916 0.930 0.938 0.946 0.952 192 0.969 0.974 0.976 0.979 0.981 229 0.920 0.935 0.944 0.953 0.963 233 0.935 0.949 0.957 0.964 0.969 235 0.938 0.977 0.995 1.009 1.010 238 0.917 0.931 0.938 0.945 0.951 291 0.918 0.970 0.996 1.017 1.015 292 0.907 0.972 1.006 1.039 1.031 293 1.001 1.025 1.038 1.049 1.048 303 0.957 0.979 0.994 1.010 1.036 305 0.962 0.985 1.001 1.018 1.046 306 0.944 0.993 1.029 1.069 1.126 320 0.957 0.971 0.978 0.984 0.988 950 0.977 0.982 0.985 0.988 0.989 Voltage (pu) Change Vsch, change tap Base Case ratio and add reactive power 306 0.944 1.048 320 0.957 1.020 950 0.977 1.021 Figure (7) illustrates the voltage levels on the 500 K.V. nodes after changing Vsch. , changing tap ratio and adding 950 MVAR. V.5 Using One or More of The Recommended Remedial Actions In A Combined Manner. Table (9): The voltage levels on the 500 K.V. nodes in case of tripping one circuit 500 K.V. T.L with and without remedial actions. Voltage (pu) Trip of one ct. Normal condition Bus (B#293)–(B#292) No. without with without with Remedial Remedial Remedial Remedial Actions Actions Actions Actions 30 0.914 0.997 0.907 0.990 180 0.916 0.993 0.911 0.987 192 0.969 1.029 0.968 1.027 229 0.920 0.990 0.914 0.984 233 0.935 0.997 0.928 0.990 235 0.938 1.029 0.900 0.996 238 0.917 0.993 0.911 0.987 291 0.918 1.022 0.858 0.969 292 0.907 1.026 0.816 0.942 293 1.001 1.050 0.990 1.028 303 0.957 1.023 0.956 1.019 305 0.962 1.028 0.961 1.025 306 0.944 1.048 0.945 1.044 320 0.957 1.020 0.947 1.011 950 0.977 1.021 0.977 1.020 In this case taking into consideration the following: • The value of (Vsch.) is the same as in subsection (5.2). • In addition to changing the tap ratio of CAI500(B#30) 500/220 K.V. transformers in subsection (5.2) from step No. 2 to step No. 6, changing the tap ratio of Bassous(B#180) 500/220 K.V. transformer from step No. 14 to step No 9". According to the above scenarios the voltage profile on the 500 and 220 K.V. networks has occurred, however not to the desired values. This improvement helps to reduce the value of the reactive power injected by added capacitors. Table (8) shows the results of the voltage levels on the 500 K.V. nodes after changing Vsch., changing tap ratio and adding 950 MVAR. Table (8): The improvement of the voltage after changing Vsch, Changing tap ratio and adding reactive power. Voltage (pu) Bus No. Change Vsch, change tap Base Case ratio and add reactive power 30 0.914 0.997 180 0.916 0.993 192 0.969 1.029 229 0.920 0.990 233 0.935 0.997 235 0.938 1.029 238 0.917 0.993 291 0.918 1.022 292 0.907 1.026 293 1.001 1.049 303 0.957 1.023 305 0.962 1.028 Reference Number: JO-0002 Bus No. VI. CONTINGENCY ANALYSIS AFTER APPLYING THE RECOMMENDED REMEDIAL ACTIONS VI.1. Cases of One 500 K.V. Circuit Tripped In between the contingency cases of one circuit 500 K.V.T.L. shown in subsection (4.1), the most critical case is the outage of H.D.(B#293) - N.H.(B#292). This case has been repeated after applying the remedial actions. and there is no low voltage problem. Table (9) shows the voltage levels on the 500 K.V. nodes in case of tripping one circuit 500 K.V.T.L with and without the remedial actions. Figure (8) illustrates the voltage levels on the 500 K.V. in case of tripping one circuit 500 K.V.T.L with and without remedial actions. VI.2. Generation Unit Contingencies The outage of Generation unit of 625 MW at bus GN.KURIM (B#530) is the most critical Generation outage in the ENPS, After applying the remedial actions, the ENPS can deal with this outage and there is no low voltage problem. Table (10) shows the voltage levels on the 220 K.V. nodes in 181 The Online Journal on Power and Energy Engineering (OJPEE) case of tripping Generation unit of 625 MW at bus GN.KURIM (B#530) with and without the remedial actions. Figure (9) illustrates the voltage levels for 220 K.V in case of tripping the generation unit of 625 MW at bus GN.KURIM (B#530) with and without remedial actions. Table (10): The voltage levels on the 220 K.V nodes in case of tripping Generation unit of 625 MW at bus GN.KURIM (B#530) with and without the remedial actions Voltage (pu) Bus No. Base Case Tripping M/C at (B#530) 804 915 917 5038 5039 5040 5042 5043 5044 5045 5046 5047 5049 without remedial actions 0.832 0.802 0.822 0.867 0.869 0.909 0.829 0.819 0.838 0.808 0.821 0.841 0.804 with remedial actions 0.977 0.988 0.988 0.950 0.958 1.011 0.963 0.966 0.991 0.983 0.996 0.952 0.966 without remedial actions 0.801 0.790 0.810 0.837 0.837 0.872 0.791 0.781 0.801 0.768 0.783 0.807 0.766 5051 5052 5053 5062 5070 0.826 0.852 0.852 0.841 0.862 0.980 0.954 0.952 0.995 0.981 0.794 0.818 0.818 0.805 0.825 with remedial actions 0.970 0.985 0.985 0.943 0.952 1.005 0.955 0.957 0.982 0.972 0.986 0.943 0.956 0.972 0.946 0.944 0.985 0.975 VII. CONCOLUSION AND RECOMMENDATION: With reference to the previous studies, analysis of the methods used in the world to avoid voltage instability and from the background about the technical and economical Reference Number: JO-0002 Vol. (2) – No. (1) conditions relevant to ENPS, three remedial actions have been recommended in this paper to be applied simultaneously. These remedial actions are the optimal usage of reactive power produced from generation units, changing the tap points of transformers and the reactive power compensation at certain locations in the power system. Also, an economical analysis carried out in this work verified that the optimal localizing and qualifying of capacitors is a most feasible mean to reactive power compensation beside the other two.. Benefiting from the obtained results, the main application was on the ENPS. The voltage profile for ENPS in normal conditions clarified that the voltage level in many locations is under the permissible secure limits (0.95 p.u. ≤ voltage level ≤ 1.05 p.u.). The ENPS was put under many contingency cases for outages of extra-high voltage 500 K.V. transmission lines and grand generation units. A comparison between the voltage profile in the base case and the cases of using remedial actions verified the necessity of using remedial actions to improve the voltage levels in ENPS. The following are some specific results: • Increasing the reactive power produced from generation units (i.e. raising the schedule voltage Vsch. From 0.98 to 0.99 p.u.) causes an increase in the voltage levels but not to the desired values. • Changing the tap ratio on all transformers to 0.92 causes an increase in voltage with permissible values above the critical voltage collapse limits (about 0.86 p.u.). • Injection of reactive power at certain locations (i.e. increasing the power factor to 0.90) causing a discrete improvement of the voltage profile, however there is one node has an over voltage (V> 1.05 p.u.). • Once more, injection of reactive power to raise the power factor to 0.91 did not solve the problem of over voltage, however redistributing the qualified reactive power caused all the voltage levels to be maintained. • Using combination of the recommended remedial actions simultaneously presents an effective remedy to the voltage instability problem. 182 The Online Journal on Power and Energy Engineering (OJPEE) Vol. (2) – No. (1) Figure (1): Single Line Diagram of The Network Parts Under Study Reference Number: JO-0002 183 The Online Journal on Power and Energy Engineering (OJPEE) Vol. (2) – No. (1) Figure (2): The voltage profile in case of outage of one circuit of 500 K.V. line on the 500 K.V. nodes for different cases. Figure (3): The voltage profile in case of outage of Generation unit on the 500 K.V. nodes for different cases of outages. Figure (4): The voltage profile in case of changing V sch. at a certain generation units of the ENPS on the 500 K.V. nodes Reference Number: JO-0002 184 The Online Journal on Power and Energy Engineering (OJPEE) Vol. (2) – No. (1) Figure(5): The voltage profile in case of changing the tap ratio of certain 500/220 K.V. transformers on the 500 K.V. nodes for different cases. Figure(6): The voltage levels on the 500 K.V. nodes after improving the power factor from 0.85 to 0.92 Figure(7): The voltage levels on the 500 K.V. nodes after changing V sch & changing tap ratio and adding 950 MVAR Reference Number: JO-0002 185 The Online Journal on Power and Energy Engineering (OJPEE) Vol. (2) – No. (1) Figure(8): The voltage levels on the 500 K.V. in case of tripping one circuit 500 K.V. T.L with and without remedial actions. Figure (9): The voltage levels on the 220 K.V. in case of tripping generation unit of 625 MW at bus GN.KURIM(B#530) with and without the remedial actions. Reference Number: JO-0002 186 The Online Journal on Power and Energy Engineering (OJPEE) REFERNCES [1] Carson W. Taylor "Power System Voltage Stability" The EPRI Power System Engineering Series, Bonneville Power Administration ,1994. [2] Benabid R. and boudour M." Optimal Location and Size of SVC and TCSC for Multi-Objective Static Voltage Stability Enhancement" Nuclear Center Research of Birine . [3] Annual Report " Egyptian Electricity Holding Company "Ministry of Electricity and Energy 2008-2009. [4] Zhihong Jia and Jeyasurya B., "Contingency Ranking for On-Line Voltage Stability Assessment" IEEE Transactions on Power Systems, Vol. 15, No. 3, August 2000. [5] Claudio Cañizares, William Rosehart, Alberto Berizzi, Cristian Bovo "Comparison of Voltage Security Constrained Optimal Power Flow Techniques " IEEE – PES Summer Meeting, Vancouver, BC, July 2001. Reference Number: JO-0002 Vol. (2) – No. (1) [6] http//www.ee.washington.edu/research/ pstca/pf30/pg _tca30bus.htm [7] http//www.ee.iastate.edu/~jdm/EE457/PSSE_Fault_ Intro_Instructions.doc [8] Stefan Johansson & Fredrik Sjögren "Voltage collapse in power systems The Influence of generator current limiter, on-load tap-changers and load dynamics" Chalmers University of Technology 1995. [9] I. Dobson, T. Van Cutsem, C. Vournas, C.L. DeMarco, M. Venkatasubramanian, T. Overbye, C.A. Canizares "Voltage Stability Assessment Concepts, Practices and Tools "IEEE Power Engineering Society Power System Stability Subcommittee Special Publication IEEE product number SP101PS August 2002. [10] S.G. Seifossadat1, M. Saniei1, A. Raeszadeh and Shahid Chamran "Reactive Power Pricing in Competitive Electric Markets Using a Sequential Linear Programming with Considered Investment Cost of Capacitor Banks. International Journal of Innovations in Energy Systems and Power (Vol.4, no.1, April 2009) Page 29 of 43. 187