Download Using Switchgear at Frequencies Other Than 60Hz

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electrical substation wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Loudspeaker enclosure wikipedia , lookup

Transmission line loudspeaker wikipedia , lookup

Spectrum analyzer wikipedia , lookup

Stage monitor system wikipedia , lookup

Waveguide (electromagnetism) wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Buck converter wikipedia , lookup

Loudspeaker wikipedia , lookup

Ringing artifacts wikipedia , lookup

Skin effect wikipedia , lookup

Islanding wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Spectral density wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Wien bridge oscillator wikipedia , lookup

Bode plot wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Atomic clock wikipedia , lookup

Rectiverter wikipedia , lookup

Regenerative circuit wikipedia , lookup

Mains electricity wikipedia , lookup

Mathematics of radio engineering wikipedia , lookup

Chirp spectrum wikipedia , lookup

Alternating current wikipedia , lookup

RLC circuit wikipedia , lookup

Superheterodyne receiver wikipedia , lookup

Utility frequency wikipedia , lookup

Heterodyne wikipedia , lookup

Transcript
Using Switchgear at Frequencies Other Than 60Hz
April 21, 1993
All ANSI circuit breaker and switchgear equipment standards specify a rated frequency of 60 Hz, and all
Powell switchgear is designed for and tested at 60 Hz. The nameplates of PowlVac® circuit breakers
carry a rated frequency of 60 Hz.
However, many applications of Powell switchgear are made at other frequencies, particularly 50 Hz, and
users may question the suitability of the circuit breakers and equipment at other frequency. The following
paragraphs discuss the effect of frequency on various major characteristics of switchgear.
BIL: Since the BIL rating is the ability to withstand a dc impulse, power system frequency has no effect
on the BIL rating of switchgear equipment.
Power Frequency Withstand: Although this rating is best demonstrated by a test at rated frequency,
ANSI/IEEE C37.09 allows the test to be made at rated frequency ±20%. This allows 50 Hz tests to
establish a 60 Hz rating, and vice versa. Since the voltage level is the same, regardless of frequency,
and the rate-of-rise of the voltage increases with frequency, the higher frequency test is slightly more
severe than the lower frequency test. Thus, an equipment which is tested at 60 Hz is satisfactory at any
lower frequency.
Continuous Current: The ac resistant of a conductor, and thus the heat loss at a given current,
increases with frequency. The ANSI standards require continuous current test to be made at a frequency
no lower than the rated frequency. The standards actually allow the assigning of a higher continuous
current rating at very low frequencies, such as 25 Hz.
Momentary, Short Time and Interrupting Currents: Again, ANSI/IEEE C37.09 allows these test to be
made at rated frequency (20%, so tests at either 50 Hz or 60 Hz can cover both frequencies. For lower
frequencies, it may be necessary to derate the interrupting capacity of vacuum interrupters. One of
Powell's vacuum interrupter suppliers has tested at various frequencies and suggests the following
derating formula:
Powell Industries, Inc.
PO Box 12818
Houston, TX • 77217
©2005 Powell Industries, Inc. • All rights reserved.
Tel: 713.944.6900 • Fax: 713.947.4453
www.powellind.com
[email protected]
Using Switchgear at Frequencies Other Than 60Hz
page 2
Where
= power system frequency, 16 2/3Hz <= f < 50 Hz
= short circuit current at frequency f
= short circuit current at 60 Hz
Summarizing, switchgear equipment and power circuit breakers rated 60 Hz may be applied at 50 Hz
without changing ratings. At lower frequencies, some derating of interrupting capacity may be required,
and some increase of continuous current rating may be possible. Of course, devices in the switchgear,
such as relays, instruments and instrument transformers, must be checked for application at the power
system frequency.
Baldwin Bridger, P.E.
Technical Director
Powell Industries, Inc.
PO Box 12818
Houston, TX • 77217
©2005 Powell Industries, Inc. • All rights reserved.
Tel: 713.944.6900 • Fax: 713.947.4453
www.powellind.com