Download Motor Starting Characteristics of Star

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power inverter wikipedia , lookup

Islanding wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Electrical substation wikipedia , lookup

Electrical ballast wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power engineering wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Commutator (electric) wikipedia , lookup

Ohm's law wikipedia , lookup

Electrification wikipedia , lookup

History of electric power transmission wikipedia , lookup

Rectifier wikipedia , lookup

Opto-isolator wikipedia , lookup

Electric machine wikipedia , lookup

Power electronics wikipedia , lookup

Brushless DC electric motor wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Current source wikipedia , lookup

Stray voltage wikipedia , lookup

Distribution management system wikipedia , lookup

Buck converter wikipedia , lookup

Surge protector wikipedia , lookup

Dynamometer wikipedia , lookup

Three-phase electric power wikipedia , lookup

Electric motor wikipedia , lookup

Mains electricity wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

AC motor wikipedia , lookup

Induction motor wikipedia , lookup

Brushed DC electric motor wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Stepper motor wikipedia , lookup

Transcript
BE Semester – V
Elements of Electrical Design
(2150904)
DC And AC Starters
Presented by:-
Sr.
1
2
3
4
Name of student
Yadav Sushilkumar
Deshmukh Mandar
Upadhyay Ravi
Shah Dhruvin
Guided By:-
Enrollment No.
130240109542
130240109511
130240109534
120240109085
Prof. Raj Patel
Prof. Jigar thakkar
HASMUKH GOSWAMI COLLEGE OF ENGINEERING
Necessity of starter
• At starting ,the speed of motor is zero so that
the back e.m.f. In the armature is zero.
• Armature resistance is so low, if it is
connected to power supply directly ; huge
current will pass thru armature.
• The huge current may damage the machine,
major heat, very high speed in case of DC
series motor.
• Ia = V/Ra
Function of starter
•
•
•
•
Start and stop the motor.
Limit inrush current where necessary.
Permit automatic control when required
Protect motor and other connected equipments from over
voltage, no voltage, under voltage, single phasing etc.
Motor Starter Features.
•
•
•
•
•
Rated by current (amperes) or power (horsepower)
Remote ON/OFF control
Motor overload protection
Starting and stopping (electrical life)
Plugging and jogging (rapid making and breaking current)
Type of starter
For DC Motor
• Two point starter for DC series motor
• Three point starter for shunt motor
• Four point starter for compound motor
For AC Motor
• DOL Starter
• Star-Delta
• Auto-transformer
• Variable Frequency drive
Wiring Diagram of DOL
Starter:
Motor Starting Characteristics on DOL
Starter:
• Available starting current: 100%.
• Peak starting current:
6 to 8 Full Load
Current.
• Peak starting torque:
100%
Advantages of DOL Starter:
•
•
•
•
•
•
•
Most Economical and Cheapest Starter
Simple to establish, operate and maintain
Simple Control Circuitry
Easy to understand and trouble‐shoot.
It provides 100% torque at the time of starting.
Only one set of cable is required from starter to motor.
Motor is connected in delta at motor terminals.
Disadvantages of DOL
Starter:
• It does not reduce the starting current of the motor.
• High Starting Current: Very High Starting Current (Typically 6
to 8 times the FLC of the motor).
• Mechanically Harsh: Thermal Stress on the motor, thereby
reducing its life.
• Voltage Dip: There is a big voltage dip in the electrical
installation
• High starting Torque: Unnecessary high starting torque, even
when not required by the load.
Suitability
•
•
•
•
DOL is Suitable for:
Small water pumps, compressors, fans and conveyor belts.
Motor rating up to 5.5KW
DOL is not suitable for:
The peak starting current would result in a serious voltage
drop on the supply system
Motor rating above 5.5KW
Star delta starter
• Most induction motors are started directly on line, but when
very large motors are started that way, they cause a
disturbance of voltage on the supply lines due to large starting
current surges.
• To limit the starting current surge, large induction motors are
started at reduced voltage and then have full supply voltage
reconnected when they run up to near rotated speed.
Star-Delta Connection in transformer
Star-Delta Connection in
motor
Star delta power circuit
Star delta control circuit
Motor Starting Characteristics of StarDelta Starter:
• Available starting current: 33% Full
Load Current.
• Peak starting current: 1.3 to 2.6 Full
Load Current.
• Peak starting torque: 33% Full Load
Torque.
Advantages of Star-Delta
starter:
• The operation of the star-delta method is
simple and rugged
• It is relatively cheap compared to other
reduced voltage methods.
• Good Torque/Current Performance.
• It draws 2 times starting current of the full
load ampere of the motor connected
Disadvantages of Star-Delta starter:
•
•
•
•
•
Low Starting Torque, only 33% starting torque
Break In Supply – Possible Transients
Six Terminal Motor Required (Delta Connected).
It requires 2 set of cables from starter to motor.
The delta of motor is formed in starter and not on motor
terminals.
• Applications with a load torque higher than 50 % of the motor
rated torque will not be able to start using the start-delta
starter.
• Low Starting Torque: reduction of the line voltage by a factor
of 1/√3 (57.7%) to the motor and the current is reduced to 1/3
of the current at full voltage, but the starting torque is also
reduced 1/3 to 1/5 of the DOL starting torque .
Auto transformer
Circuit and function
• An auto-transformer starter makes it possible to start squirrelcage induction motors with reduced starting current, as the
voltage across the motor is reduced during starting.
• In contrast to the star-delta connection, only three motor
leads and terminals are required. On starting, the motor is
connected to the tappings of the auto-transformer.
Starting Characteristics:
• Motor terminal voltage less than line voltage (by transformer
ratio).
• Motor current exceeds line current (by inverse of transformer
ratio).
• Starting torque is reduced by the square of the terminal voltage.
Applications:
• Where complete acceleration at reduced amperes is needed.
• Where line ampere reduction requirements are severe, and load
torque is not minimal.