VELOX 4000 INT SERIES
4200 INT - 4400 INT
Intelligent Analog Fire Alarm Control Panels integrated with Paging Microphone Console and Fire Telephone Handset
• Five programmable LED indicators on the panel
• Dedicated RS232 serial port for PC or modem connection
• User-friendly menu and navigation keys
• Multiple language display options
• Variable Time Communication (VTC) Protocol
VOICE ALARM & MASS NOTIFICATION
• Touch screen paging console with in-built loudspeaker
• Monochrome and colour touch screen panels
• Display of all system faults and incidents on the control
panel
• Monitored handheld microphone
• Audio routing, zone selection, and volume control from
the paging microphone console
• Simultaneous routing of up to 48 high-fidelity audio
channels via digital signal processors
• Up to 8192 voice evacuation zones
• Voice alarm messages with professional audio quality
EMERGENCY VOICE COMMUNICATION
• Monitored fire telephone handset
• Up to 8 master handsets on a network
• Up to 256 communication lines
• Disable refuge system
• Addressable, monitored fire telephone jack on the fire
detection and alarm loop
FIRE DETECTION & ALARM
APPLICATION
• Up to 2 fire detection and alarm loops on 4200 INT &
4 loops on 4400 INT
VELOX 4000 INT is a series of analogue addressable
fire alarm control panels that function as control and
indicating equipment for a range of fire detection and
alarm devices. The fire alarm control panel is the central device in a life safety system involving fire detection, encompassing additional control panels, repeater
panels, mimic panels, remote control and display terminals, manual call points, smoke and heat detectors,
sounders, beacons, and relays.
TThe 4000 INT series is available in two models—4200
INT and 4400 INT—with provi - sions for 2 and 4
loops, respectively. The fire alarm control panels are
integrated seamlessly with ATEIS mass notification and
emergency communication systems to house all corresponding control and monitoring equipment within a
single enclosure.
• Up to 240 devices per loop
• Up to 200 fire alarm control panels on a network
• Up to 200 fire zones per fire alarm control panel
• Up to 1000 fire zones in a network of fire alarm control panels
• Loop length extendable up to 6 km, subject to load
calculations
• Up to 1000 event logs per panel for diagnosis of fault
conditions
• IP30 protection
• ‘Soft’ and ‘Safe’ addressing features
• Complex ‘Cause & Effect’ programming options
ATEÏS Middle East FZCO.
The integrated paging microphone console allows audio routing, call paging, message broadcasting, and
P.O. Box: 293640 Dubai United Arab Emirates Tel: +971 4 3262730 Fax: +971 4 3262731 Email: [email protected] http://www.ateis.ae
1
VELOX 4000 INT SERIES
control of digital signal processing parameters via a
user-friendly interface.
The integrated fire telephone handset enables secure,
full duplex emergency voice communication with outstation handsets on a fire telephone network. The emergency voice communication system (EVCS) provides assistance to fire fighters during emergencies in high-rise
buildings, particularly in situation were radio communication may get disrupted.
VELOX 4000 INT is ideal for medium-, and large-scale
installations in properties ranging from but not limited
to commercial and residential spaces such as hotels,
malls, and apartments; infrastructure developments
such as airports and railway stations; and special-purpose buildings such as schools and places of worship.
PHYSICAL CONSTRUCTION & ASSEMBLY
The 4200 INT, 4400 INT and 4800 INT control panels
are made of metal and provide the option of surface or
flush mounting and different finishes such as stainless
steel or RAL colors. Sufficient mounting knockouts are
provided to accommodate all wiring requirements.
The control panel housing has IP30 protection and
restricts access to the control buttons without a key or
special tool. The front-side of the panel has a graphic
LCD screen with LED status indicators, control buttons,
alphanumeric keypad, and navigation buttons.
The fire alarm control panels are available as part of
an integrated unit comprising the panel itself, paging
microphone for public address and voice alarm, and
fire telephone master handset for emergency communications, all housed in a steel enclosure. Depending on
requirements, the 4200 INT and 4400 INT can either
be used as stand-alone fire alarm control panels or expanded to have integrated voice evacuation and voice
communications features.
The panel has two 12V batteries installed at the bottom
of the enclosure for standby operation up to 24 hours,
followed by 30 minutes of alarm. The enclosure can
house larger batteries for a 72-hour backup, followed
by 30 minutes of alarm.
The integrated paging microphone console is attached
with a monitored handheld microphone for addressing
all zones. Three LED indicators show the operational
statuses of the console, such as evacuation, fault, and
power. An in-built loudspeaker makes it possible to listen to all system generated messages and announcements.
The integrated fire telephone handset finished in brushed
stainless steel comprises a 12-key keypad, high-contrast
display, and 8 LED status indicators.
2
TECHNOLOGY
The analogue addressable fire alarm control panel displays the address, type, and status of each device on
the loop. Each fire detection loop can accommodate up
to 240 fire alarm devices with in-built isolators, and the
loop length can extend up to 6 km depending on load
and loop length calculations.
Programming options allow a user to assign zones
to fire detection and alarm devices on the loop and
furthermore link them with actions such as fire or fault
signals and voice messages to be initiated when the
devices are in the alarm mode by means of advanced
AND/OR logic operations.
Various parameters of devices on the loop can be set
and controlled from the control panel. Detectors can be
programmed to operate with different sensitivity levels
and sounders can be synchronised from the panel. The
control panel also indicates the loop output and input
voltages, loop loading, and signalling quality.
The loop driver circuit on the base card is equipped
with in-built short circuit isolators to ensure uninterrupted communication between the panel and first device
on the loop.
Each fire detection and alarm device on the loop is
equipped with an in-built isolator to minimize loss of
communication in case of short circuits. Hence there’s
no need for additional isolators or base isolators. Alternatively, devices can be supplied without isolators.
In such cases, isolators will have to be installed on the
loop.
The fire alarm control panel allows programming of
complex ‘cause & effect’ functionalities to either a single output device or group of output devices (sounders,
beacons, relays) to respond to a fire or alarm signal for
input devices. Up to 200 output groups on a network
of 1000 zones can be programmed from the control
panel. Delays can be introduced to allow phased evacuation in a building.
ATEÏS Variable Time Communication (VTC) Protocol
enables secure data transmission over long distances.
Advanced detection algorithms ensure thorough evaluation of the environments in which the detectors are
placed, and thus, fire signals are activated only when
smoke is actually present.
The integrated paging microphone console on the fire
alarm control panel is wired to the master audio distribution matrix or digital signal processor on the PAVA
rack, enabling the operator to monitor all loudspeaker
circuits, zones, and amplifiers for faults.
In large networks with multiple PAVA racks, the paging
microphone console on the 4000 INT allows selection
of any loudspeaker zone for public addressing and isATEÏS Middle East FZCO.
P.O. Box: 293640 Dubai United Arab Emirates Tel: +971 4 3262730 Fax: +971 4 3262731 Email: [email protected] http://www.ateis.ae
VELOX 4000 INT SERIES
suing voice instructions for evacuation.
INSTALLATION & MOUNTING
The touch screen paging microphone console can be
programmed to enable quick access to various zones
or groups of zones through customizable buttons on
the touch pad. The buttons can be assigned to different zones or zone groups by naming them accordingly.
Additionally, the buttons can perform additional functions such as volume control, priority settings, message
activation, and so on.
The fire telephone handset allows the operator to communicate with outstation handsets by dialling the number of the outstation handset. The name or number of
the outstation handset is indicated on the backlit display.
The fire telephone master handset on the 4000 INT series of fire alarm control panels is connected to an eightline exchange which links the outstation handsets with
the master handset.
An addressable telephone jack can be used to link the
fire detection loop of the control panel and the fire telephone network via the 8 line exchange. Similar to all
devices on a fire panel loop, the telephone jack is fully
monitored from the control panel and a unique address
is assigned to it. Installing the jack on the fire panel
loop supports emergency voice communications via the
fire telephone network by using a portable handset.
Furthermore, security and ‘cause and effect’ features
are significantly enhanced if the telephone jack is monitored on the fire panel loop.
APPROVALS & COMPLIANCE WITH STANDARDS
The VELOX 4000 INT range of integrated fire alarm
control panel and PAVA systems has BSI Kitemark, TUV,
and LPCB certifications, and it complies with the following British and European standards.
BS EN 54-2:1998
(Fire detection and fire alarm systems. Control
and indicating equipment)
BS EN 54-4:1998
(Fire detection and fire alarm systems. Power
supply equipment)
BS EN 60849:1998
(Sound systems for emergency purposes)
Membership No.472288644
ATEÏS Middle East FZCO.
Loop driver cards must be installed in the fire alarm
control panel to expand the number of loops. A base
card in the control panel has slots (2 slots and 4 slots
for 4200 INT and 4400 INT, respectively) allotted for
installation of loop driver cards, which can easily be
guided in place on the base card.
Each loop starts and terminates on the base card of the
control panel and it is wired to the pairs of loop out
and loop in terminals. This loop configuration in which
the wires return to the same control panel provides the
highest redundancy for communication as per the NFPA
Class A, Style 7 wiring. The in-built isolators ensure that
under a single short circuit fault condition, all devices
will continue to operate as normal.
For additional functions, the control panels have provision for installing peripheral cards via an RS485 bus
interface to expand the number of inputs and outputs
as per increasing requirements for ‘cause & effect’ functions.
A mimic panel can be mounted on the fire alarm control
panel to provide a graphical representation of zones
using LED indicators. The mimic panel layout with LED
indicators is designed on the basis of a standard CAD
drawing of a zone. Zonal LED indicators can be mounted on the panel to simultaneously display the status of
all zones under fire conditions.
The mimic panel and fire alarm control panel can be
further customized for smoke control applications with
additional LEDs and switches for manual control of
doors, vents, lifts, etc., as required.
The integrated paging microphone consoles can have
either monochrome or colour touch screens. The devices have dedicated and secured audio and communication links. To increase the distance between the paging
console and the PAVA rack, a local power supply is
required.
COMMISSIONING & TESTING
The ‘Soft Addressing’ feature or ‘Auto Learn’ option on
the panel when selected enables the control panel to
automatically record the total number of addresses and
devices on a loop. The panel notifies the user if it finds
devices missing or replaced then registers the new status of the loop according to the options selected by the
user.
Soft Addressing allows automatic sequential addressing of devices (1–240) on the loop from the fire alarm
control panel, simplifying the commissioning process.
The last sequenced address should correspond to the total number of devices installed on the loop, as recorded
when ‘Auto Learn’ is activated.
P.O. Box: 293640 Dubai United Arab Emirates Tel: +971 4 3262730 Fax: +971 4 3262731 Email: [email protected] http://www.ateis.ae
3
VELOX 4000 INT SERIES
To add a new device to the loop, the ‘Safe Addressing’
feature enables the user to set new addresses to devices
by using the VPU100 hand-held programming unit. This
allows the addressing to match site conditions or even
allows the user to add more detectors to the loop at a
later stage without the need to change or reassign addresses to all the devices.
Each device on the loop or a fire zone can have a
text description beside its name when displayed on the
fire alarm control panel. This provides clear indication
of the location and description of a zone or device in
fire or fault conditions and enables commissioning, testing and maintenance engineers to track the source of a
problem and take appropriate action.
Individual detectors can be tested by selecting the address of the detector on the control panel and activating the ‘Test’ command. Alternatively, detectors can
be tested physically on site by positioning a magnet
on its base. The magnet test verifies the function of all
electronic circuits of the detector and its communication
with the control panel.
The integrated paging microphone console is configured from the PAVA controller and matrix, which allows
adjustment of the microphone sensitivity and speaker
volume level. The input signal can be adjusted with a
3-band parametric equalizer. Priorities can be set for
both the paging microphone console and the various
messages supported by the console. Messages can be
allocated in two categories–evacuation or normal. The
message levels, priorities, equalization, and siren levels
before activation of the message are set for optimum
response.
ARCHITECTURAL & ENGINEERING SPECIFICATIONS
The VELOX 4000 INT range of integrated fire control
and indicating panels shall have the BSI Kitemark certification and comply with the following British codes
of practices for planning, design, installation, commissioning and maintenance of fire detection and fire
alarm systems, voice alarm systems and emergency
voice communication systems–BS 5839-1, BS 5839-8,
and BS 5839-9, in addition to European Standards BS
EN54-2, BS EN54-4, BS EN 60849.
The fire alarm control panel (FACP) shall have the provision to expand number of loops from 2 to 8 on a single
device. Each loop shall have the capacity to address
240 devices, depending on loop length and load calculations.
The FACP shall have networking capabilities to allow up
to 200 panels on a secure ring network with distance
extendable up to 20km. Fiber-optic cabling allows significant extension in the communication distance within
the network.
4
The control panel shall have provision for housing fan
control switches and LEDs for integrated smoke control
management.
The 4000 INT range shall support mounting of a mimic
panel on the main control panel to provide graphical
indication of zones and devices.
The 4000 INT range of fire alarm control panels shall
provide fully integrated functionalities of fire alarm and
detection, voice alarm, mass notification, emergency
voice communication, background music and foreground music with professional audio features.
The communication protocol for the fire alarm network
shall be the ATEIS variable time communication (VTC)
protocol, which allows extension of the loop length to
6km.
Network cabling shall be an easy setup with two-core
twisted pair cables and without requirement for shielded cables. This simplifies installation of the fire alarm
network.
The control panel shall support sophisticated programming logic functions to allow up to 1000 fire zones per
network, along with duplication of zones. Advanced
delay and logic (AND/OR/XOR) operations allow sophisticated cause & effect programming on the control
panel.
The control panel shall allow adjustment of detector sensitivity levels to respond with different setting for day
and night. With a simple programming step, the control panel can provide instructions on the date/time to
the detector head to reduce/increase the sensitivity or
switch off or switch on the heat/photo sensor within the
same head. This increases the response to real fires and
reduces false alarms depending on the application and
location of the detector.
The control panel shall have provision for installing peripheral cards via an internal RS485 bus interface to expand the number of inputs and outputs with dedicated
I/O cards that shall be housed inside the cabinet of the
panel.
The integrated paging microphone console and its components (microphone, power supply, touch screen, audio, and RS485 connections) shall be fully monitored
for faults.
The touch screen panel shall indicate all system faults.
The paging microphone console shall be programmed
either by using a PC or via the PAVA controller and digital signal processor. The console shall have password
ATEÏS Middle East FZCO.
P.O. Box: 293640 Dubai United Arab Emirates Tel: +971 4 3262730 Fax: +971 4 3262731 Email: [email protected] http://www.ateis.ae
VELOX 4000 INT SERIES
protection features for authorized access.
All parameters required for monitoring and controlling
audio distribution across the entire PAVA network on a
site shall be programmed from the paging microphone
console.
The paging microphone console shall have an in-built
loudspeaker for the operator to listen to all messages
and announcements.
The colour touch screen microphone console shall have
three additional hardware keys for user-defined functions.
panels shall be compatible with all the latest communication protocols employed for security and automation
in buildings. In addition to TCP/IP, other open protocols such as BACnet, LON, Modbus, etc., shall be fully
compatible for integration with building management
systems.
The FACP shall be compatible with digital signage devices such as LCD screens for display of evacuation
messages and indications, maps of project sites and
device locations, etc.
The 4000 INT system shall support simultaneous routing
of 48 audio channels on the network when integrated
with a digital signal processor for commercial audio.
The audio distribution network with digital signal processors shall have a loop architecture which provides
full redundancy.
The digital signal processors shall be connected on an
Ethernet based network via fiber optic cables. The network shall support 24-bit audio at sampling rates of 48
and 96 KHz.
The digital signal processors shall provide a vast array
of signal processing tools (compressor-limiter, equalizer, matrixing and delay functions, automatic gain control, etc.) which can be programmed via a user-friendly
graphical user interface as per requirements.
The integrated fire telephone handset on the 4000 INT
range of control panels shall provide emergency voice
communications on the network by means of 32 line
exchange units with 8 lines to link remote handsets and
fire telephone jacks to the master handset on the FACP.
The master fire telephone handset on the 4000 INT series of fire alarm control panels shall provide a secure
communications link to outstation handsets and remote
handsets via telephone jacks, in addition to disabled
refuge points.
The fire telephone network integrated with the voice
evacuation system shall enable routing of emergency
conversations to any desired zone and to record conversations in the MP3 format for future reference during
accident investigations.
The integrated fire telephone network shall have the
provision for installing addressable telephone jacks
on the fire detection and alarm loop and connected
to the master handset via the line exchange unit. The
telephone jack shall be addressed and fully monitored
form the fire alarm control panel.
The 4000 INT range of integrated fire alarm control
ATEÏS Middle East FZCO.
P.O. Box: 293640 Dubai United Arab Emirates Tel: +971 4 3262730 Fax: +971 4 3262731 Email: [email protected] http://www.ateis.ae
5
VELOX 4000 INT SERIES
TECHNICAL SPECIFICATIONS
4400
4200
Dual Flash based Processors with Real Time Clock, ‘Trace’ diagnostics, ‘PuLsE’ communications & programmable languages
Base Technology
Display
Backlit 240x64 Graphical LCD
LED Indicators
3 Red (2 x Fire, 1 x Alarm), 1 Green (Power) & 12 Amber (Fault & System)
Controls
Alpha Numeric Keypad, Navigation Keys & System Keys for Reset, Mute, Silence/
Resound & Evacuate
Protocols
ATEÏS “ VTC ” Variable Time Communication
Number of Fire Zones
1000 ‘Dynamix’
1 – 4. Expandable via individual plug-in
loop driver
Number of Loops
Devices per loop
240
Loop Current
500mA
On Board Sounder circuits
4 x 1 Amp Programmable
2 x 1 Amp Programmable
On Board Relays
2 x 1 Amp 30v AC/DC Programmable
Auxiliary Supply
1 x 24v 500mA
Open Collector / Logic Outputs
Programmable Switch Inputs
8 x Programmable
8 Volt Free Digital Inputs
On Board Power Supply
Mains Supply
Battery Capacity
5Amp High Efficiency Switched Mode
4 Amp High Efficiency Switched Mode
110 - 230 V AC (+10%, -15% tolerance)
50 / 60 Hz 1.7 Amp
110 - 230 V AC (+10%, -15% tolerance)
50 / 60 Hz 1.9 Amp
24v 18 Ah internal. 24v 48Ah external
2.2 Amp DDP monitored, temperature
compensated integral charger
Charger Current
2.0 Amp DDP monitored, temperature
compensated integral charger
Serial ports
1 RS232 Onboard for PC, Modem or External Printer
Programming
Via on-board Keypad or PC running Windows Tools
Event Log
1000 Fire & Event + Diagnostic
Networking
Optional plug in Network card
Printer (Option)
Optional on-board or External Serial Printer
Enclosure / Colour
RAL 7016 / Anthracite Grey
Cable Entry
RAL 7024 / Graphite Grey
20mm Knock-outs. 18 x top, 9 x top rear and 2 x bottom
Size H x W x D mm / Weight
6
1 – 2. Expandable via individual plug-in
loop driver
950x 450 x 200 / 10.5Kg
475 x 450 x 115 / 10.5Kg
475 x 450 x 188 / 10.5Kg (/D Deeper
Enclosure)
Back Box Only (When Recessing) 475 x
450 x 100
Deeper Back Box Only (when Reccessing)
475 x 450 x 173
Metalwork Options
Flushing Bezel, Ancillary Enclosure & Battery Box
Metalwork Options
BS EN54-2:1998, BS EN 54-4:1998, BS EN60849:1998
ATEÏS Middle East FZCO.
P.O. Box: 293640 Dubai United Arab Emirates Tel: +971 4 3262730 Fax: +971 4 3262731 Email: [email protected] http://www.ateis.ae
VELOX 4000 INT SERIES
TECHNICAL SPECIFICATIONS
PSSDT
Specification Details
Connections
Connections: RJ45
Dimensions
Console size: (L x W x D) 250 x 140 x 80 mm
Flex length: 250 mm
Weight: 1.5 kg
Colour: RAL 9006
Front tilted at 30°
Material: metal back, PVC top and sides
Power supply
Power supply: 24DC/450mA
Fire Telephone System
Specification Details
Power Supply
Source
Voltage
Current
Processing
Architecture Clock
Memory
Monitoring
AVR RISK
16MHz
4K
RAM
20K EEPROM
128K Flash
125mS Asynchronous Watchlog Checksum on
EEPROM & Flash
Network Cables
Grade
Cable (per leg)
OR
OR
Distance (per leg) Monitoring
Enhanced Cable (per leg)
1 off four Pair (eg Draka 91 -0245)
2 off four core 1 mm CSA Soft Skin
4 off 1 Pair MICC Twisted
500M Soft Skin types, 300 M MICC
Data & Phantom Voltage
Indication & Controls
Fault LEDs
change)
Status LEDs
LCD
twenty-character
Keyboard
Navigation
Standards Compliance
EMC
Product Family
230V AC + 20%
11mA
12V SLA 3.2AH
4 off yellow (General, Panel, Supply & Ex4 off green (healthy, AC, DC & Network)
High Contrast Green/ Black LCD, four line
5 x 8 pixel format
12 Key Telephone Style
3 Keys (down/left, Accept, up/right)
EN55103-1, EN55103-2
BS5839-Part 9, BS5588-Part
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice
Ref. 4400 INT&4200 INT/FP/R1/V1/060611
ATEÏS Middle East FZCO.
P.O. Box: 293640 Dubai United Arab Emirates Tel: +971 4 3262730 Fax: +971 4 3262731 Email: [email protected] http://www.ateis.ae