* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download Emergency Generators
Survey
Document related concepts
Transcript
111001 SECTION 26 3213 EMERGENCY GENERATORS PART 1 - GENERAL 1.01 SUMMARY A. Provide all labor, materials, and equipment necessary for a complete and operable emergency/standby electric generating system. Materials and equipment shall be new, and delivered to the project site completely wired, tested, and ready for installation. B. Related Requirements: C. 1.02 1. Division 01 - General Requirements. 2. Section26 0500: Common Work Results for Electrical. 3. Section26 0513: Basic Electrical Materials and Methods. 4. Section26 0526: Grounding and Bonding. 5. Section 26 0519: Low Voltage Wires (600 Volt AC). 6. Section26 3600: Automatic Load Transfer Switches. 7. Section26 5200: Emergency Power Systems. 8. Section03 3000: Cast in Place Concrete. Applicable Codes and Standards: 1. The emergency generator system shall comply with the following codes and standards: NFPA Codes and related adoptions (amendments) by the State of California, IEEE Standards, Environmental Protection Agency (EPA) Emission Standards, South Coast Air Quality Management District (SCAQMD), California Air Resource Board (CARB), and ANSI/NEMA standards. 2. All products shall be listed and labeled for the application by UL or another Nationally Recognized Testing Laboratory (NRTL). PROJECT REQUIREMENTS A. Engine-generator set rated as indicated on Drawings. B. Engine-generator control consoles resiliently mounted on generating sets shall include complete engine start/stop controls and monitoring systems. PROJECT NAME SCHOOL NAME 10/01/2011 EMERGENCY GENERATORS 26 3213-1 111001 C. Provide control devices, components, accessories, parts, tests, documents, and services needed to meet the requirements of this Specification; or as otherwise indicated on drawings. D. Electric generating system must meet requirements of NFPA 110 including design specifications, prototype tests, one-step full-load pickup, installation and testing. E. Starting batteries and battery charger. F. Manual and Automatic start. G. Voltage and frequency regulation. H. Generator set mounted on vibration isolation supports to provide 96 percent isolation in order to minimize vibration of the remainder of the skid-mounted equipment and transmission of vibration to the supporting pad. I. Prime and finish paint with manufacturer’s standard paint finish; paint shall be lead free. J. Outdoor units shall be totally enclosed and rated for outdoor use. The housing shall have hinged side-access doors and rear control door. Doors shall be lockable. Indoor units shall be properly vented and ducted as per the manufacturers requirement for engine exhaust and engine cooling. K. Fuel tanks and piping: underground fuel tanks are not acceptable. Above ground fuel tanks shall double wall welded steel construction and sized to provide the generator set system with fuel for a minimum of 24 hours operating at continuous load power output. Above ground tanks may be sub-base or remote located as appropriate for the application, and shall be provided with a rupture basin. L. Complete monitoring and alarms. M. Generator(s) greater than 50 brake horse power or within 100 meters of students occupied sites shall be equipped with a diesel particulate matter exhaust filter with all legally required monitoring and control equipment as required by South Coast Air Quality Management District or other regulatory agencies having jurisdictions. All generators equipped with a diesel particulate matter filter shall be equipped with a permanently installed load bank which can be controlled with service switches to present a 50 percent or a 75 percent or a 100 percent load to the generator as desired. All generators over 50 brake horsepower shall be equipped with a permanently installed load bank controlled by a service switch to present a 50 percent load to the generator. 1.03 SUBMITTALS A. Provide in accordance with Division 01. PROJECT NAME SCHOOL NAME 10/01/2011 EMERGENCY GENERATORS 26 3213-2 111001 B. Shop Drawings shall include control diagrams, list of materials, catalog cuts, technical data, manufacturer's specifications, and applicable installation details. C. Submit three copies of service manuals including the following: D. 1.04 1. A detailed explanation of the operation of the system. 2. Instructions for routine maintenance. 3. Detailed instructions for repair of major components of the system. 4. Pictorial parts list and part numbers. 5. Pictorial and schematic electrical drawings of wiring systems, including operating and safety devices, control panels, annunciators, and major components. 6. Installation instructions for system components. 7. Final test report. 8. Record drawings of the system exactly as it was installed, including plan and elevation views with overall and interconnection point dimensions, and diagrams including schematic and interconnection diagrams. Submit a detail typewritten sequence of operations as part of the approval documents. Approved sequence of operations shall be permanently encapsulated in plastic laminate and permanently attached to the equipment. Format shall be 8.5 by 11 inches or 11 by 17 inches as appropriate. QUALITY ASSURANCE A. Equipment, including engine-generator sets shall be from a single manufacturer regularly engaged in the production of engine-generator sets for a minimum of 10 years. Entire system shall be factory built, tested, and shipped so there is one source of supply and responsibility for warranty, parts, and service. B. Submit certified performance test for this or an exact duplicate prototype unit for Engineer of Record review. Refer to part three for additional requirements. C. Equipment, fuel and exhaust components shall be sized in accordance with manufacturer’s recommendations and requirements. 1.05 WARRANTY A. Complete standby electric power system including all accessories shall be warranted by the manufacturer for a period of two years or 1,500 operating hours, whichever occurs first. PROJECT NAME SCHOOL NAME 10/01/2011 EMERGENCY GENERATORS 26 3213-3 111001 B. 1.06 Multiple warranties for individual components are not permitted. Satisfactory warranty documents must be provided. MAINTENANCE A. Provide a supply of oil, fuel, coolant, and air filter elements required for one complete engine generator system tune-up. PART 2 - PRODUCTS 2.01 ENGINES A. Manufacturers: Onan, Kohler Power Systems, Generac, or equal. B. General: System shall include engine-generator sets rated for the KW, and KVA, at 0.8 PF, three-phase, four-wire, and volts on a continuous standby basis, as indicated on Drawings. C. Engine-generator sets shall be installed on heavy-duty steel bases to maintain proper alignment between components. Sets shall incorporate vibration isolators of type and quantity specified by set manufacturer, whether mounted internally or externally to set. D. Diesel engines shall meet the following requirements: 1. Engine shall be stationary, liquid-cooled, diesel for use with number 2 diesel fuel. Design shall be four-cycle, six cylinders, turbocharged and intercooled where required by engine manufacturer. Engine shall be certified by engine manufacturer as capable of developing rated BHP at 1800 r/min., and driving a generator yielding a KW rating as specified herein. Engine shall be capable of driving generator of this rating on a continuous standby basis for duration of normal utility source interruptions per SAE J1349 conditions. Fuel injection and valves shall not require adjustment while in service. 2. Engine equipment shall include following: PROJECT NAME SCHOOL NAME a. An electric starter, as required. b. Positive displacement, mechanical full pressure lubrication oil pump, full flow lubrication oil filters with replaceable elements and dipstick oil level indicator. c. Fuel filter with replaceable element, and an engine driven, mechanical positive displacement fuel pump, mounted on engine. Replaceable dry element air cleaner. 10/01/2011 EMERGENCY GENERATORS 26 3213-4 111001 E. d. Engine speed isochronous electronic governing system to control generator frequency within plus or minus 0.25 percent of rated frequency under steady state load conditions, and capable of parallel operation with load sharing controls. e. Engine protection devices shall be furnished with sensing elements located on engine to initiate following preliminary alarms and engine shutdowns: 1) Low coolant temperature alarm. 2) Pre-warning for low lubrication oil pressure alarm. 3) Pre-warning for high coolant temperature alarm. 4) Low lubrication oil pressure shutdown. 5) High coolant temperature shutdown. 6) Overspeed shutdown. 7) Overcrank lockout. 8) Low fuel. f. Provide low coolant level shutdown, which shall activate high engine temperature lamp and shutdown. g. Engine starter battery charging alternator with solid-state voltage regulator. h. Provide engine mounted thermostatically controlled water jacket heater and necessary circuit from normal utility power source to aid engine’s quick start. Engine Cooling Systems: 1. Engine shall be radiator cooled by engine mounted radiator system including belt-driven blower fan, coolant pump, and thermostat temperature control. Performance of components shall be as required by set manufacturer. For indoor units, radiators shall be provided with a duct adapter flange permitting attachment of air discharge duct directing discharge of radiator air through the wall. Provide ducts and flexible duct connection between duct adapter flange and wall louver or damper. 2. Provide 50 percent ethylene glycol antifreeze solution to fill engine cooling system. Provide gaskets and packing in the cooling system which are unaffected by the ethylene glycol base coolant. PROJECT NAME SCHOOL NAME 10/01/2011 EMERGENCY GENERATORS 26 3213-5 111001 F. G. 3. For generators installed indoors, provide automatic motorized dampers for inlet air and radiator discharge air located and sized as indicated on Drawings. Dampers for inlet air shall provide adequate air volume for engine combustion, ventilation, and radiator cooling air. Dampers shall operate automatically to close when engine stops and to open when engine starts, power for dampers shall be taken from an emergency panel. 4. Provide coolant temperature safety device. Engine Lubricating System: 1. Provide full pressure type with engine driven positive displacement sump pump, full flow strainer and flow filter, pressure relief and automatic by pass valves. 2. Provide indicating pressure gages on the upstream and downstream side of the strainer and filter, and water shutoff valves and drain on the oil cooler to facilitate drainage of water without draining the complete engine cooling system. 3. Low oil pressure safety shutoff device. 4. Drain connection. 5. Crankcase ventilator with filter and connection for outside venting. Engine Exhaust Systems: 1. Exhaust mufflers shall be provided for each engine of size as recommended by manufacturer. Mufflers shall be of residential type and shall be installed so its weight is not supported by engine. 2. Flexible exhaust connections shall be provided as required for connection between engine exhaust manifolds and exhaust line, in compliance with applicable codes and regulations. 3. Provide an exhaust condensation trap with manual drain valve to trap and drain off exhaust condensation and to prevent condensation from entering engine. 4. Provide a suitable rain cap at stack outlet. Provide necessary flanges and special fittings for proper installation. 5. Mount and install exhaust components as indicated on Drawings and as required to comply with applicable codes and regulations. Components shall be properly sized to assure proper operation without excessive backpressure when installed as indicated on Drawings. Provide provisions as required for pipe expansion and contraction. PROJECT NAME SCHOOL NAME 10/01/2011 EMERGENCY GENERATORS 26 3213-6 111001 H. 2.02 6. Cover indoor installed exhaust mufflers, and piping with proper insulating material in a manner not to interfere with flexible exhaust connections. 7. Where outdoor housings are provided, exhaust mufflers shall be mounted inside or outside housing. Engine Fuel Systems: 1. Provide fuel system piping sized as indicated on Drawings or as required for proper fuel flow of natural gas to engine. Provide supply return, vent, and fill lines as indicated on Drawings, along with fittings. Provide connections for connecting fuel system to engines in compliance with applicable codes and regulations. 2. Provide 24-hour minimum sub-base tank, gages, valves, tank filler fittings, tank vent fittings, day tank float and necessary items as indicated on Drawings to comply with applicable codes and regulations. Fuel sub-base tank and fuel accessories shall be new. Sub-base tank shall be of double-walled construction and located underneath skid base of engine-generator set. 3. A low fuel supply sensing device shall be installed on fuel tank. Sensing device shall be adjusted to signal low fuel level when tank contains less than a threehour supply. The three-hour supply level shall be as recommended by manufacturer of engine-generator set. 4. A fuel-in-rupture basin alarm shall be provided with contacts available for annunciation. 5. Fuel tank shall be filled to capacity with low sulfur diesel fuel; fuel shall comply with the Air Quality Management District requirements. Provide necessary documentation as requested by SCAQMD at time of the delivery of fuel. GENERATORS A. Generators shall be single-bearing, self-aligning, four-pole, synchronous type, revolving field, with amortisseur windings, with direct drive centrifugal blower for proper cooling and minimum noise, with temperature compensated solid-state voltage regulator, with brushless rotating rectifier exciter system. Brushes will not be allowed. Generator shall be directly connected to engine flywheel housing and driven through a flexible coupling to insure permanent alignment; gear driven generators are not permitted under this Specification. Insulation shall meet NEMA standards for Class F, in addition to the quality assurance requirements indicated above. Maximum temperature rise shall not exceed 130 degrees C. Generator design shall prevent potentially damaging shaft currents. B. Three-phase, broad range, reconnectible generator shall be furnished with 12 leads brought out to allow connection by user to obtain any of available voltages for unit. PROJECT NAME SCHOOL NAME 10/01/2011 EMERGENCY GENERATORS 26 3213-7 111001 2.03 C. Voltage regulator shall be solid-state design and shall function by controlling exciter magnetic field between stator and rotor to provide no load to full load regulation of rated voltage within plus or minus two percent during steady-state conditions. Enginegenerator set and regulator must sustain at least 90 percent of no-load voltage for 10 seconds with 250 percent of rated load at near zero power factor connected to its terminals. D. Voltage regulator shall be insensitive to severe load induced waveshape distortion from SCR or thyrister circuits such as those used in battery charging (UPS) and motor speed control equipment. E. A rheostat shall provide a minimum of plus or minus five percent voltage adjustment from rated value. F. Generator, exciter and voltage regulator shall be designed and manufactured by enginegenerator set manufacturer so that characteristics shall be matched to torque curve of prime mover. This design allows prime mover to use its fullest power producing capacity (without exceeding it or over compensating) at speeds lower than rated to provide fastest possible system recovery from transient speed dips. A system that routinely selects a linear-type (straight line) constant volts/hertz characteristic, without regard for engine power and torque characteristics, will not meet this Specification. These characteristics shall be demonstrable as follows: 1. With engine-generator set operating at rated speed, voltage and load, reduce engine speed to half rated by manually overriding engine speed governor control. Engine-generator set must recover to full speed with rated load connected when engine speed governor control is returned to its normal mode. 2. Calculations must demonstrate that exciter and voltage regulator will permit utilization of at least 80 percent of maximum available prime torque at all engine speeds between 50 percent and rated speed, and with rated unity power factor load connected to its terminals. G. Exciter shall be three-phase, full-wave, rectified, with heavy-duty silicon diodes mounted on common rotor shaft and sized for maximum motor starting loads. Systems utilizing three wire solid-state control elements, such as transistors or SCR's rotating on rotor are not permitted. H. Generator design shall be of self-protecting type, as demonstrated by prototype shortcircuit test as described herein. All other generator performance criteria shall meet that of specified equipment. I. When engine-generator sets will be paralleled with another source, each set shall be furnished with a cross-current compensation control and rotating exciter transient suppressors. ENGINE-GENERATOR SET CONTROLS PROJECT NAME SCHOOL NAME 10/01/2011 EMERGENCY GENERATORS 26 3213-8 111001 A. Provide a lighted, unit-mounted control module that is factory built, wired, tested, and shock-mounted by generator manufacturer. Control module shall be installed on generator end of set. Control wires between generator set and transfer switches shall be provided with termination identification on both ends. Identification shall be provided for each device or function and shall be silk-screened white on a black background. B. Engine-generator set controls shall be provided with the following for each unit: 1. Gages and Meters: Oil pressure gage, coolant temperature gage, charge rate ammeter and running time meter. 2. Manual Selector Switch: Run-stop-remote. 3. Remote, two-wire, 12 or 24-volt DC controls start/stop terminals. 4. Manual Reset Field Circuit Breaker. 5. Automatic engine shut down for following fault conditions: 6. PROJECT NAME SCHOOL NAME a. Overcrank. b. Overspeed. c. Low lube oil pressure. d. High engine temperature. Indicator lamps shall signal the following faults or status conditions: a. Overcrank: Indicates starter has been locked out because cranking time was excessive. b. Overspeed: Indicates engine has shut down because of excessive r/min. c. High engine temperature: Indicates engine has shut down because of critically high temperature. d. Low oil pressure: Indicates engine has shutdown because of critically low oil pressure. e. Pre-high engine temperature: Indicates engine temperature is marginally high. f. Pre-low oil pressure: Indicates oil pressure is marginally low. g. Low engine temperature: Indicates engine temperature is marginally low for starting. 10/01/2011 EMERGENCY GENERATORS 26 3213-9 111001 2.04 h. Switch off (flashing): Indicates control switch is in stop position. i. Low fuel: Indicates fuel supply is marginally low. j. Remote stop button/switch k. Provide two spare fault condition lamps. 7. Provide a fault reset switch to clear fault indications and allow restarting of engine after shutdown faults. Control design shall be such that fault indication shall remain until reset. Fault indicator memory shall not be dependent on presence of either AC or DC voltage and shall retain fault status memory even through complete removal and replacement of starting batteries. Fault reset function shall operate only when run-stop-remote switch is in the stop position. 8. Provide a locking screwdriver type potentiometer (electronic governor) to adjust speed plus or minus two percent from rated value. 9. Provide AC voltmeter, 90 degree scale, 2 ½-inch flange, two percent switchboard meter. 10. Provide AC ammeter, 90 degree scale, 2 ½-inch flange, two percent switchboard meter. 11. Provide frequency meter 55-65 Hz, 90 degree scale, 2 1/2-inch flange, plus or minus 0.6 Hz panel meter. 12. Provide four-position AC meters phase selector switch to read line current and voltage in each phase with off position. 13. Provide manual reset exciter field circuit breaker. AUXILIARY EQUIPMENT A. Starting Batteries: Provide battery(ies) as required by manufacturer. Install battery(ies) in racks within engine-generator set skidbase. B. Battery Chargers: Voltage regulated battery chargers shall be provided for enginegenerator sets. Chargers shall be furnished with float, taper, and equalize charge settings. Charger power shall be supplied from normal source; provide circuits as required. C. Vibration Isolators: Each engine-generator set shall be installed on vibration isolators external to set skidbase. D. Remote Audible Annunciator: Provide remote audible annunciator with silence alarm feature and a light emitting diode (LED) indicator. The remote annunciator shall provide a common alarm indication of all engine related status conditions or faults as specified PROJECT NAME SCHOOL NAME 10/01/2011 EMERGENCY GENERATORS 26 3213-10 111001 under section 2.03-6 of these specifications. The remote annunciator shall be located in the Plant Managers office or as an alternate location the main administrative office. E. Emergency Shutdown Button: Provide a remotely located generator shutdown button or switch with an STI protective cover and with appropriate signage adjacent to the main service if this generator serves multiple buildings or adjacent to the main distribution switchboard of a building with the appropriate signage if this generator serves this one building. In no case shall an emergency shutdown switch or button be located outdoors unless it is located behind a lockable gate of a service area not accessible to students or unauthorized staff. PART 3 - EXECUTION 3.01 PERMITS A. Obtain from the South Coast Air Quality Management District (SCAQMD) and from any other regulatory agency having jurisdiction all necessary permits to construct and operate diesel generators with more than 50 brake horsepower ratings. B. Pay all fees or costs associated with obtaining the construction and operations permit(s); provide all labor necessary to demonstrate full compliance with all applicable codes and regulations to secure and deliver to the District’s Maintenance and Operation Energy Unit a valid permit to operate the installed generator. Permit(s) shall be procured at start of construction. C. Los Angeles Unified School District, Energy Unit, with address: 333 S. Beaudry Avenue, 22nd Floor, Los Angeles, California 90017 shall be listed in the permit(s) as the owner. Contact with the Energy Unit shall be coordinated through the project’s OAR. 3.02 TESTING A. A 48 hour notice shall be provided to the Inspector before final testing. B. Installer is responsible for identifying required testing, coordinating, scheduling, and conducting tests before Substantial Completion. Test shall include the following: 1. Perform separate series of tests as follows: a. PROJECT NAME SCHOOL NAME Factory Prototype Model Tests: Electric generating system consisting of prime mover, generator, governor, coupling and controls must have been tested as complete unit on representative engineering prototype model as required by NFPA 110. Tests, being potentially damaging to the equipment tested, must not be performed on equipment to be sold, but on separate prototype models as specified by NFPA 110 and their accomplishment certified by means of documentation of tests accompanying submittal data. These tests shall include: 10/01/2011 EMERGENCY GENERATORS 26 3213-11 111001 PROJECT NAME SCHOOL NAME 1) Maximum power level (maximum KW). 2) Maximum motor starting capacity (maximum KVA and voltage dip recovery within seven cycles of applied load). 3) Structural soundness (short-circuit and endurance tests). 4) Torsiograph analysis: Manufacturer of engine-generator set shall verify that engine-generator combination, as configured, is free from harmful torsional stresses. Analysis shall include correlation of empirical data from tests on a representative prototype unit. Empirical data must include spectrum analysis of torsional transducer output within critical speed range of enginegenerator set. Results of this analysis shall be made available to Architect on request. Calculations based on engine and generator separately are not permitted. 5) Engine-generator cooling air requirements. 6) Transient response and steady-state speed control and voltage regulation. 7) Generator temperature rise per NEMA MGI-22.40. 8) Harmonic analysis and voltage waveform deviation per MILSTD-705C, method 601.4b. 9) Three-phase short-circuit test for mechanical and electrical strength. With system operating at rated volts, amps, power factor, and speed, generator terminals must be short circuited 10 times on all three phase for a duration of 30 seconds. Enginegenerator set must build up and perform normally without manual interventions of any kind such as resetting or circuit breakers or other tripping devices when short circuit is removed. 10) Failure mode test for voltage regulator: With engine-generator set operating at no load, rated speed and voltage, AC sensing circuit to regulator must be disconnected for a period of at least one hour. Engine-generator set must be fully operative after test, and without evidence of damage. 11) Endurance testing is required to detect and correct potential electrical and mechanical problems associated with typical operation. 12) Full load test conducted at the specified ambient temperature for at least four hours. The test results shall identify all components 10/01/2011 EMERGENCY GENERATORS 26 3213-12 111001 and performance data for 0-to-50 percent, 0-to-100 percent, and 50-to-100 percent instantaneous load applications. b. c. 13) Steady state performance shall be recorded at 15 minutes intervals; test shall be performed for four hours minimum at 100 percent rating, with load characteristics of 80 percent power factor and total harmonic distortion of 50 percent. 14) Results shall include oil pressure, oil temperature, coolant temperature, fuel pressure, ambient temperature, load in kW, kVA, amperes, output voltage, and Load characteristics, which are required to be sinusoidal with a minimum 80 percent power factor. Factory Production Model Tests: Before shipment of equipment, enginegenerator sets shall be tested under rated loads and power factor for performance and proper functioning of control and interfacing circuits. Testing at unity power factor, and the KVAR for motor starting and regulation loads varies with power factor. Tests shall include: 1) Single step load pickup per NFPA 110. 2) Transient and voltage dip responses and steady state voltage and speed (frequency) checks. 3) Fuel consumption (no-load, 1/4 load, 1/2 load, 3/4 load, and full load). 4) Generator temperature rise by resistance method. 5) Architect has the option of witnessing these tests. A summary of test results shall be submitted to the Inspector. 6) For paralleling applications manufacturer shall have performed and certified that engine-generator sets can withstand 180 degrees out-of-phase paralleling from full rated voltage and speed without sustaining any mechanical or electrical damage. Field Tests After Installation: 1) PROJECT NAME SCHOOL NAME Complete installation shall be initially started and observed for operational compliance by factory-trained representatives of engine-generator set manufacturer. Engine lubrication oil and as recommended by manufacturer for operation under environmental conditions specified, shall be provided by engine-generator sets supplier. 10/01/2011 EMERGENCY GENERATORS 26 3213-13 111001 3.03 2) Upon completion of initial start-up and system checkout, supplier of system shall perform a field test, with Architect and Inspector notified in advance, to demonstrate load carrying capability and voltage and frequency stability. 3) With emergency load at normal operating level, a power failure is initiated by opening switches or breakers supplying normal power to building or facility. Records shall be maintained throughout tests of time-of-day, coolant temperature, cranking time until prime mover starts and runs, time required to come up to operating speed, voltage and frequency overshoot, time required to achieve steady-state condition with switches transferred to emergency position, voltage, frequency, current, oil pressure, ambient air temperature, kilowatts, power factor, battery charger rate at five minute intervals for first 15 minutes, and at 15 minute intervals thereafter. Continue this load test for two hours observing and recording load changes and resultant effect on voltage and frequency. Return to normal power, record time delay on re-transfer for each switch (set for 15 minutes minimum) and time delay on prime mover cooldown period and shutdown. 4) Upon completion of above test, allow prime mover to cool for five minutes. Then apply full rated load (nameplate KW) consisting of building load supplemented by a load bank if required. Unity power factor is suitable for Project site testing; provided that rated load tests at power factor have been performed by manufacturer before shipment. This full-load pickup shall be in one step immediately upon reaching rated r/min. TRAINING A. Before Substantial Completion, provide the services of a manufacturer's representative on the Project site to instruct persons designated by the Owner in the operation and maintenance of the system. Instruction time shall not be less than one day. B. Manufacturer shall have a local representative who can provide factory-trained technicians, required stock of replacement parts, and technical assistance. 3.04 SERVICE CONTRACT A. Provide an agreement whereby the system will be inspected and tested by manufacturer in accordance with NFPA 110 emergency and standby power systems. Testing shall be conducted by a local factory trained technician who will, upon completion of testing, provide the Owner with written records of visual inspections and testing. This agreement PROJECT NAME SCHOOL NAME 10/01/2011 EMERGENCY GENERATORS 26 3213-14 111001 shall be in effect for a period of two years after Substantial Completion of the Work. Cost of service contract shall be included as a part of this Contract. 3.05 PROTECTION A. 3.06 Protect the Work of this section until Substantial Completion. CLEANUP A. Remove rubbish, debris, and waste materials and legally dispose of off the Project site. END OF SECTION PROJECT NAME SCHOOL NAME 10/01/2011 EMERGENCY GENERATORS 26 3213-15