Document Number: ECP 11-0511g
Date: 09/09/2016
LUCY VCN2A AND VCE2A TEST FORM
Substation Name
Substation Number
Voltage
Switchgear
Installed Mode
Free-standing
()
Switchboard Number
Manufacturer
Serial Number
Type
Transformer-mounted
()
Lucy
Protection CTs
Ratio in Use
TLF
Rating
Transformer Rating
Preliminary Checks
kVA
()
Visual inspection satisfactory (no visible signs of damage etc)
Earthing satisfactory
SF6 gas pressure satisfactory
Functional/Interlock Checks
()
Open and close circuit-breaker
Earth switch cannot be operated when service selected
Circuit-breaker cannot be operated when earth selected
Open and close earth switch
Test access/earth star bar cannot be opened when circuit-breaker in On and Off
position
Test access/earth star bar can be opened when earth switch closed
Transformer Winding Insulation Resistance using Test Voltage from ECS 11-0006
(transformer-mounted units only)
HV windings to earth (LV windings connected together and to earth)
M
LV windings to earth (HV windings connected together and to earth)
M
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
Version: 5.0
Lucy VCN2a and VCE2a Test Form
Document Number: ECP 11-0511g
Version: 5.0
Date: 09/09/2016
Switchgear Continuity Test
Circuitbreaker
Terminals Under Test
Circuitbreaker
Terminals Under Test
Closed
L1 - L1

Earthed
L1 -E

L2 - L2

L2 - E

L3 - L3

L3 - E

Continuity
Continuity
HV Insulation Tests using Test Voltage from ECS 11-0006
Circuit-breaker
Terminals
Under Test
Earthed
Closed
L1
L2, L3
Closed
L2
L1, L3
Closed
L3
L1, L2
Open
L1, L2, L3
L1, L2, L3
Voltage
(kV)
Duration
(min)
IR
(M)
Protection CTs Insulation Resistance using 1kV Test Voltage
(test from marshalling box – refer to Figure 1 and Figure 2)
Check selector switch is in the service position
()
Remove CT wiring earth link
C70 - C90
()
CTs, AC trip coils and TLFs
C70 - Earth
M
Replace CT wiring earth link
C70 - C90
()
Refer to Figure 2
Figure 1 – Marshalling Box
© UK Power Networks 2017 All rights reserved
Earth link
C70-C90
Figure 2 – Protection CT connections in
Marshalling Box
2 of 5
Lucy VCN2a and VCE2a Test Form
Document Number: ECP 11-0511g
Version: 5.0
Date: 09/09/2016
Protection CTs Loop Continuity
(test CT and trip coil from TLF ratio terminal block with test link removed)
Remove CT ratio shorting link
()
100/5 Ratio
50/5 Ratio
L1
C110 - C72

C210 - C72

L2
C130 - C72

C230 - C72

L3
C150 - C72

C250 - C72

Replace CT ratio shorting link
()
C110-C130-C150-C70-C210-C230-C250
100/5
50/5
Note: For a complete list of Lucy SABRE A drawings refer to ECP 11-0511 Lucy SABRE A
Schematic Drawings.pdf.
© UK Power Networks 2017 All rights reserved
3 of 5
Lucy VCN2a and VCE2a Test Form
Document Number: ECP 11-0511g
Version: 5.0
Date: 09/09/2016
Primary Injection Test (free-standing units only)
Earth Fault Release Test
Remove TLFs and replace with shorting links
()
CB
Conductors Under Test
CT
Ratios
Trip Range
Closed
L1 - L1
50/5
25 - 30A
A
100/5
<40A
A
50/5
25 - 30A
A
100/5
<40A
A
50/5
25 - 30A
A
100/5
<40A
A
Closed
L2 - L2
Closed
L3 - L3
Trip Current
Overcurrent Release Test
Remove TLF shorting-links, connect shorting-link to L1, L2, L3 on one side
CB
Conductors
Under Test
Closed
L1 - L2
Closed
Short
Conductors
L2 - L3
()
CT
Ratios
Trip Range
Trip Current
50/5
19-26A
A
100/5
<45A
A
50/5
19-26A
A
100/5
<45A
A
Secondary Injection Test (transformer-mounted units only)
Earth Fault Release Test
(remove TLFs and replace with shorting links)
CB
Test Connections
CT Ratios
Trip Range
Trip Current
Open
C31 - C70
50/5
2 - 2.7A
A
100/5
1.2 - 1.6A
A
Overcurrent Release Test
(remove shorting links)
CB
Test Connections
CT Ratios
Trip Range
Open
C11 - C31
50/5
1.5 - 2.7A
A
100/5
1 - 1.7A
A
50/5
1.5 - 2.7A
A
100/5
1 - 1.7A
A
Open
C31 - C51
Trip Current
Note: If the circuit-breaker does not operate when the injected current is gradually applied
then the maximum value of current should be applied instantaneously.
© UK Power Networks 2017 All rights reserved
4 of 5
Lucy VCN2a and VCE2a Test Form
Document Number: ECP 11-0511g
Version: 5.0
Date: 09/09/2016
Final Checks
()
Check correct CT ratio selected
Check correct TLF rating selected and fitted
Check all links are replaced and secure
Asset data form completed and submitted
Test Equipment
Make/Type
Serial Number
Calibration Date
Certification
()
All tests have been completed satisfactorily
Comments
Commissioning
Engineer
Signature
Date
The completed test form shall be left on-site in a plastic wallet and in secure location.
A copy of the completed test shall be sent to the relevant ART mailbox.