Download Protection, control, and monitoring for the

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Immunity-aware programming wikipedia , lookup

Three-phase electric power wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Stray voltage wikipedia , lookup

Alternating current wikipedia , lookup

Voltage optimisation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electrical substation wikipedia , lookup

Mains electricity wikipedia , lookup

SCADA wikipedia , lookup

Buck converter wikipedia , lookup

Opto-isolator wikipedia , lookup

Hendrik Wade Bode wikipedia , lookup

Control theory wikipedia , lookup

Distributed control system wikipedia , lookup

Control system wikipedia , lookup

Metadyne wikipedia , lookup

Rectiverter wikipedia , lookup

Resilient control systems wikipedia , lookup

Transcript
File: 841002203
M-6283 THREE-PHASE DIGITAL CAPACITOR BANK CONTROL
SUGGESTED SPECIFICATIONS
Pole-Top/Pad Mount Capacitor Bank Control, metering, and monitoring for the
Capacitor Bank shall be provided by a microprocessor-based package. The
microprocessor-based package shall be suitable for Pole-Top or Pad Mounted
Capacitor Banks, as well as Single-Stage Substation Capacitor Banks operating in
Non-Series configurations. The control shall have the following minimum
functional and behavioral attributes:
CONTROL FUNCTIONS
The capacitor bank control shall include the following features and can be used for either pole-top
or pad mounted capacitor banks as well as non-series, single-stage, substation banks where
SCADA communications are desired.
LOCAL AUTOMATIC CONTROL MODE
The Control shall have the following selectable Local Automatic Capacitor Control
Methods: Classic Voltage, Adaptive Voltage, VAr, and Current with settings appropriate
to the method selected.
Capacitor Control Local Automatic Overrides: Maximum / Minimum Voltage Limits,
Temperature, and Time.
CLOSE and OPEN timers shall be provided with selectable Definite or Inverse TimeDelays.
Timer Types: Selectable as Integrating or Instant Reset
CLOSE and OPEN Output Pulse Duration adjustments shall be provided.
CLOSE and OPEN Warning delays shall be provided.
A mandatory reclose delay shall be provided to permit capacitors to discharge before reclosing after a prior trip.
A minimum time-between-operations timer shall be provided that begins timing when any
operation completes and prevents the OPEN or CLOSE timer from beginning operation
due to an out-of-band condition until the timer’s setting is reached.
LOCAL MANUAL MODE
Local Manual Mode of cap bank operation shall be indicated on the front panel when switched
into Local/Manual by a technician or an operator, and shall not be able to be operated by remote
SCADA or other host computer(s) to maintain the safety of the technician or operator. Locally, the
technician shall be able to CLOSE or OPEN the cap bank with all safety timers non-defeatable.
Delta Voltage calculations shall be enabled during Local/Manual operation to block a technician
command that would cause the Maximum or Minimum Voltage Limits to be violated.
Page 1 of 10
File: 841002203
CAPACITOR BANK CONTROL OPERATION
Control Operating Characteristic: The capacitor bank-control shall have independent phaseswitching and the operating characteristic shall be configurable for classic voltage, adaptive
voltage, VArs, or current. The control’s configurable operating characteristic shall employ definite
as well as inverse timing and provide an adjustable bandwidth to optimize bank operation and
eliminate unnecessary switching. The configurable operating characteristic shall allow time and/or
temperature overrides. The selected operating characteristic shall have further user-configurable
selections to refine its switching decision.
SENSING MODES
Single-Phase Selection: This option will allow the user to choose which phase; A, B or C is used
as the controlling parameter. Once this is selected, the control will use that phase value in Classic
voltage control mode or Autodaptive® mode to make decision on how to regulate the load voltage.
The option is valid for all three methods of control namely Voltage, VArs and Current.
Three-Phase Average/Total: If three-phase average is selected the measured value of all three
phases shall be averaged and used as the Effective Bandcenter for operation and to make it’s
open or close capacitor bank switching decisions. When the control uses the VAr control
characteristic, the averaging shall be replaced by the total sum of the VArs of all three phases.
The CT multiplier shall be assumed equal when the VAr control method is selected. In Control
Mode Limits, the three-phase maximum and minimum voltage shall be used to evaluate userassigned voltage limit violations.
CONTROL MODES
Classic Voltage Control: Classic voltage control shall make its CLOSE and OPEN switching
decisions based on Control Close and Open Voltage settings and measured Line Voltage
conditions and Time and/or Temperature overrides when applied. The control Close and Open
Voltage settings shall apply based on the setting of the Control Phase Selection. Voltage
excursions beyond the set value for greater duration than the time-delay will result in appropriate
control operation on the affected phase.
Adaptive Voltage Control: Adaptive voltage control shall contain two control methods, Fixed or
Average.

The Fixed method shall provide means to establish a bandcenter setting for each phase
that the control uses for comparison to measured voltage to make CLOSE or OPEN
capacitor bank switching decisions on the affected phase.

The Average method shall monitor each phase independently and develop an Effective
Bandcenter based on a long-term average of the input voltage on that phase for
comparison to measured voltage to make CLOSE or OPEN switching decisions for the
capacitor bank on the affected phase.
VAr Control: VAr control shall make its CLOSE and OPEN switching decisions based on Control
Open and Close VAr settings compared to Line VAr conditions. The control shall monitor each
phase, and independently switch individual phase capacitor banks based on the individual phase
VArs. A single pair of Control Open and Close Time settings shall apply to all three phases and
VAr excursions that exceed the time-delay setting shall result in control operation on the affected
phase.
When the control uses the VAr control method, the VAr load shall replace the averaging on each
separate phase. The CT multiplier shall be assumed equal when the VAr control method is
selected. In Control Mode Limits, the maximum and minimum voltage shall be used to evaluate
user-assigned voltage limit violations.
Autodaptive Voltage Control method employs an inverse timer and bandwidth to optimize bank
operation, eliminating unnecessary switching, and allow application of Time and/or Temperature
overrides.
Page 2 of 10
File: 841002203
Automatic VAr Control Mode Option: This option allows the control to make its Open and
Close switching decisions based on measured line VAr conditions and Time and/or Temperature
overrides when applied. VAr excursions beyond the set value for greater duration than the time
delay will result in appropriate control operation. In addition, the control shall offer the option for
Line Post Current Sensor inputs to provide phase current measurement to the control.
Current Control: Current control shall make its CLOSE and OPEN switching decisions based on
Control Open and Close Current settings compared to Line Current conditions. The control shall
monitor each phase, and independently switch individual phase capacitor banks based on the
individual phase current. A single pair of Control Open and Close Time settings shall apply to all
three phases and current excursions that exceed the time-delay setting shall result in control
operation on the affected phase.
All Control Methods shall provide a Definite time-delay or an Inverse time-delay allowing faster
response for larger excursions while eliminating unnecessary switching. All Control Methods shall
provide a standard Instant Timer Reset or alternatively, an Integrating Timer Reset to facilitate
bringing the controlled parameter solidly back in band.
SCADA REMOTE MANUAL CONTROL MODE:
SCADA Remote Manual Mode: The IVVC algorithm residing at the Master Control Center of the
SCADA computer or other Host computer may use Remote Manual Mode for control. The control
shall be capable of operating from SCADA signals received through wired or wireless
communications media to command bank switches for OPEN and CLOSE operations. The cap
bank control shall maintain an Overvoltage and Undervoltage Limit supervision to protect the
“never to exceed” voltages set as standard by the utilities and SCADA shall be allowed to make
OPEN and CLOSE commands as necessary when operating within those safety limits. The cap
bank control shall provide a means to switch from Remote Mode to Automatic Mode if
communications fail and continue to operate autonomously until communications are restored.
The control shall provide contingency responses upon extended loss of communications.
The capacitor bank control shall utilize a SCADA integrity monitor (SCADA Heartbeat) as well as
additional means to monitor the on board communications module for loss of its own operation.
Either failure or loss of communications from master or from slave shall trigger the cap bank to
switch to Automatic operation. After communications are restored for a specified length of time,
the cap bank control shall revert to SCADA Remote Manual Control Mode. This may be done
automatically after a time-delay or as directed by SCADA Master.
SCADA Remote Manual Mode - SCADA Heartbeat: A SCADA Heartbeat Remote Mode shall
be provided as a means for the SCADA system to place the unit in Remote Operation to perform
Open and Close operations as directed by a central control source. This mode shall have a timer,
and as long as the Remote Timer setting in the control is refreshed by the SCADA system
receiving a valid DNP 3.0 command, and before timing out, the control shall remain in Remote
Manual Operation. If the delay times out, the control shall revert to Local Automatic Operation.
The Local Automatic Operation shall switch back to Remote Manual Operation upon receipt of a
valid DNP 3.0 command via SCADA.
SCADA REMOTE MANAGEMENT OF LOCAL AUTOMATIC CONTROL MODE:
SCADA Remote Management of Local Automatic Control Mode: The capacitor bank control
shall have the capability to allow Remote SCADA Management of Local Automatic Capacitor
Control. In this way, the Centralized Control can monitor cap bank controls allowing them to
operate autonomously and only controlling them directly when emergencies arise. Management
via SCADA or other Host computer capable of operating through wired or wireless
communications media allows SCADA to effect control by either changing the local automatic
control settings via analog signal or by sending binary commands for direct OPEN and CLOSE
operations. Sending analog settings to the control and letting it operate based on its new
Page 3 of 10
File: 841002203
marching orders instead of directing each open and close commands conserves bandwidth
substantially and thereby minimizes the communications burden and total cost of operation.
The control shall provide a SCADA Test Mode that blocks the unit’s physical outputs and
removes the reclose delay, that normally prevents a Close operation for a minimum of five
minutes after an OPEN. The control LEDs, front panel, and remote status indications shall still
indicate bank operations as if the outputs were not blocked to allow user verification of settings,
correct SCADA communications point mapping, and operation.
INSTALLATION CONFIGURATION SETTINGS:
VT Ratio Correction: The control shall provide VT ratio correction
Phase Shift Compensation: The control shall provide phase shift compensation correction when
in VAr or Current Control mode to correct for phase shifts normally encountered in line post
sensors, and when current information sources are located on phases other than the measured
voltage source.
Operations Counter: The control shall provide a software counter that increments by a
selectable X or 2X count for either a CLOSE or an OPEN operation.
Re-settable Operations Counter: The control shall provide a second software counter similar to
the operations counter that may be reset by the user.
COMMUNICATIONS
The communication ports shall provide access to all features, including metering, software
updates, and programming of all functions. This shall be accomplished using a modem or direct
serial connection from any PC-compatible personal computer running the control’s
Communications Software package or via SCADA communications software.
Communications Ports: Communication ports shall be optionally available in the following
forms:
 Ethernet 10/100 Mbps through a copper RJ-45 connection (100 Base-T)
 Ethernet 100Mbps Fiber Optic with ST connectors (100 Base-FX)
 Serial Ports with RS-485, ST or V-Pin Fiber Optics, or RS-232
Protocols: The control shall support the following standard protocols: DNP3.0 and MODBUS.
The USB port shall utilize MODBUS for local interface communications. The Ethernet port
supports DNP 3.0, MODBUS, and IEC 61850 protocols over TCP/IP.
Page 4 of 10
File: 841002203
Advanced SCADA Communications:
True Ethernet
The control shall provide an imbedded, true 10/100 Mbps Ethernet, auto negotiable, capable of
supporting up to eight concurrent sessions and simultaneous multiple protocols with up to eight
sockets (concurrent sessions) open at a time. The eight sockets shall be capable of supporting
Modbus and DNP over TCP/IP and up to five of the eight sockets shall be capable of supporting
DNP 3.0. This requirement allows users simultaneous remote access to the control via the same
physical Ethernet port to view/change settings or retrieve data, without affecting the SCADA
communications.
Full DNP Implementation
The control shall provide full DNP implementation to support both report-by-exception and
unsolicited reporting within DNP 3.0 to aid in the reduction of bandwidth requirements. The
control shall also provide DNP File Transfer to permit the recovery of data logs and triggered
events, oscillography, and device discovery to facilitate setting up the integrated system.
In serial communication, the control shall have DNP addressing capability that allows networking
of multiple controls. The DNP implementation shall support the pre-defined global addresses
within DNP 3.0 and allow the user to define two additional global addresses. Each control shall be
able to be assigned a Device Address, Feeder Address, and Substation Address ranging from 1
to 65519. The control shall support broadcast commands from the master to all controls on the
network in order to allow some or all controls to act on one command at the same time. This
capability reduces bandwidth and is critical for rapid response to changing system requirements
with settings changes in multiple controls in selected zones. The control shall provide a
configuration program that allows any point to be mapped into any DNP location and allows
dummy filler points to be added to facilitate interoperability by replicating legacy vendor pointmaps to SCADA. This program shall also allow for individual point dead-banding and individual
point assignments into Class 1, 2, or 3.
Cyber Security
The control shall provide the following information security mechanisms when operating within
DNP:
 Permit multiple master source-address authentications, source-address validation, and
multilevel access codes logged with date and time, with DNP authentication using FIPS
180-2 Secure Hash Standard (SHA-1)
 Full compliance with DNP 3.0 user group and IEC 62351-5 requirements, including all
settings and configuration options
 Require password protected access to the control functions and maintain an audit log in
compliance with NERC CIP standards
 Storage of 30 unique passwords in each control for user login via serial port, USB,
modem, TCP/IP, or a password-keyed SD card, and include time-out and expiration
features
 The ability to disable ports and services not required for normal or emergency services
 Enclosure intrusion detection device that asserts a SCADA alarm and triggers a
temporary blocking signal to the control’s functions
Bluetooth®
The control shall have an option for Bluetooth® capability to enable 128-bit wireless encrypted
access to the control that allows the user to configure the control, read status and metering
values, as well as change set points. The control’s Bluetooth® capability shall include a generic
serial service to facilitate establishing initial communications with other Bluetooth ® units.
Page 5 of 10
File: 841002203
MONITORING
Harmonic Analysis: The control shall measure, log, and display individual harmonics including
Total Harmonics Distortion (THD) of the load voltage and load current up to the 31 st harmonic.
Trip and Lockout Function: The control shall include the following trip and lockout functions:



Trip and lockout occurs when voltage or current THD increases above the control’s THD
Trip Pickup setting
The control remains in Lockout and the THD Lockout Reset-Delay period begins only
after the THD decreases below the Voltage or Current THD Lockout Reset setting and
continues for the duration of the THD Lockout Reset-Delay setting; indicating THD was
above the THD Trip Pickup setting for a sufficient period to cause capacitor bank
resonance and possible explosion
The Trip and Lockout shall remain in effect only for the duration of the THD Lockout
Reset-Delay setting when the voltage or current THD levels drop below the THD Trip
Pickup setting within 1 second following the trip; indicating the capacitor bank was part of
the L/C system circuit and functioning as the filter, partially sinking the harmonics
Lockout/Reset Operations Counter: The control shall have an internal counter that increments
each time the following sequence occurs:
1. A Voltage or Current THD Measurement exceeds its associated THD Trip pickup setting
for the duration of the THD Trip time-delay
2. The control trips the bank and locks out
3. The Voltage or Current THD measurement drops below the THD Lockout Reset Setting
as soon as the Trip occurs (within one second)
4. The THD Lockout Reset-Delay times out and the Lockout resets
Maximum THD Lockout/Reset Operations: The control shall have a Maximum THD
Lockout/Reset Operations setting to limit the maximum number of Trip and Lockout/Reset
Operations allowed within a time-period specified by a Maximum Time for THD Lockout/Reset
Operations before the control permanently locks out and requires a user reset, either locally or
remotely, to continue operation.
Settings Profiles and Triggers: The control shall provide up to eight settings profiles
programmable in the control that can be initiated based on Time, Temperature, Loss of
Communications, Reverse Power, or from SCADA. This feature shall allow the user the flexibility
to customize the operation of the control based on many different operational factors while
minimizing communications bandwidth. It shall also assist in maintaining local intelligence at the
device level in the event of either a loss of communications or with systems designed to operate
without communications.
Alarms: The alarm relay shall be user-programmable with a non-latching output contact that
closes on one or more of the following conditions:
●Maximum/Minimum Voltage Limit ●Comm Block or Self-Test*
●Voltage/Current Harmonics
● Resettable Counter Limit
●Power Factor – Leading/Lagging
●Daily Operation Counter Limit
●Bank/Switch Failed - Level 1
●Bank/Switch Failed - Level 2
●Remote Overvoltage/Undervoltage Limit
*Only available with VAr and Current Control Mode option
Page 6 of 10
●Remote Manual
● Phase Overcurrent*
●VAr – Leading/Lagging
●Delta Voltage Alarm
File: 841002203
Oscillographic Recorder: The control shall have a built-in Oscillographic Recorder that
continuously records voltage and current waveform data in a buffered memory. This memory
shall be configurable from 1 to 16 partitions with corresponding cycles per partition of 1638 to 192
respectively. A snapshot of waveform data from 235 to 2,000 cycles shall be captured when
triggered. The captured data shall be specified from 5% to 95% post-trigger event. The remainder
of the percentage shall be pre-trigger data (samples per cycle shall be selectable as 16, 32, or 64
samples/cycle) reporting both even and odd harmonics to the 31st harmonic.
Data Logging: Data logging shall be provided that continually records data in non-volatile
memory. The device shall have sufficient non-volatile memory to store a minimum of one year’s
worth of data with a Data Log Interval of 5 minutes. Data logging will continue indefinitely as long
as the data interval is set to a non-zero value.
Sequence Of Events (SOE): The Sequence of Events recorder shall be provided for
comprehensive data recording time stamped to the nearest millisecond. It shall be capable of
downloading the Sequence of Events data to an SD Card, or PC running the control’s
communications software. The control’s SOE shall be capable of storing up to 129 events utilizing
a first in/first out memory scheme.
User-Programmable Alarm Contacts: A user programmable alarm shall be provided that alerts
the operator to one or more of the following system conditions:
●Maximum Voltage Limit
●Remote Under-Voltage Limit
●Re-settable Counter Limit
●Current Harmonics Alarm
●Minimum Voltage Limit
●Bank/Switch Failed Level 1
●Voltage Harmonics Alarm
●Comm. Block, or Self-Test
●Remote Over-Voltage Limit
●Bank/Switch Failed Level 2
●Daily Operation Counter Limit
Computer Business Equipment and Manufacturers Association (CBEMA) Sag and Swell
Recorder: The control shall sample the input signals 64 times per cycle to allow for the detection
of sags and swells. The magnitude and duration for up to four different levels of CBEMA events
shall be defined by the user. There shall be a counter for each level that increments the total
number of sags/swells as well as DNP points to alarm and report the duration, in cycles, of each
sag/swell. The control shall also capture and record the waveforms with oscillography during the
sag/swell. These sag/swell channels may be configured to aid in the reporting of Customer
Average Interruption Duration Index (CAIDI), System Average Interruption Duration Index
(SAIDI), Momentary Average Interruption Frequency Index (MAIFI), and Average Service
Availability Index (ASAI) numbers.
INPUTS
The control shall have the following inputs:
Switch Power Input: Nominal 120 Vac, 60 Hz (50 Hz optional); but the control shall operate
properly from 95 to 140 Vac. If set at 60 Hz, the operating system frequency shall be from 55 to
65 Hz; if set at 50 Hz, the operating system frequency shall be from 45 to 55 Hz. The burden
imposed on the input shall be 8 VA or less. The unit shall withstand twice the nominal voltage for
one second and four times the nominal voltage input for one cycle.
V1, V2, and V3 Monitor Voltage Inputs: 0 to 10 Vac Line Post Voltage Sensor input, optional 0 to
150 Vac VT input and these inputs shall be suitable for use with high impedance voltage dividers.
Input impedance shall be approximately 1 MΩ. The inputs will withstand twice the maximum
voltage rating for one second and four times the voltage the voltage maximum voltage rating for
one cycle.
Phase Current Input: 0 to 10 Vac Line Post Current Sensor input. External current to voltage
conversion shall be required if 5 A CT is used. Appropriate multiplier shall be used to calculate
the primary phase current. Line Post Current Sensor option shall also include a phase shift
compensation setting.
Page 7 of 10
File: 841002203
Neutral Unbalance Current Input: 0 to 10 VAC Line Post Current Sensor, 200 mA, or 5 A input
shall also be supported. Appropriate multiplier shall be used to calculate the primary neutral
unbalance current.
Switch Status Inputs: The control shall have three inputs for connection to the auxiliary switch
status contacts supplied with each phase of the capacitor switches to permit detection of
individual phase switch operation.
OUTPUTS
The control shall have the following outputs:
Three CLOSE Outputs: The CLOSE output signal shall be capable of switching 10 A for 30
seconds or 45 A for 25 ms.
Three OPEN Outputs: The OPEN output signal shall be capable of switching 10 A for 30
seconds or 45 A for 25 ms.
The CLOSE and OPEN outputs shall have two modes of operation for the intended switch type.
The first shall be a pulsed mode of operation, adjustable from 50 to 100 ms in duration, for use
with solenoid driven switches. The second shall be a pulsed mode of operation, adjustable from 5
to 15 seconds in duration for use with motor driven switches.
User-Programmable Alarm Output: The control shall have one (1) Form A “CLOSED” contact
capable of switching 6 A at 150 VAC or 200 mA at 125 Vdc.
FRONT PANEL HUMAN MACHINE INTERFACE (HMI)
The control shall have menu-driven access to all functions by way of navigational pushbuttons
and an alphanumeric display. There shall be two programmable password levels available to
provide limited or more complete access to the control functions. One of the HMI navigation
buttons shall allow user to retrieve important metering data instantly (with a single button-push) in
any order the user would like to see it displayed. The data shall also scroll at a configurable rate.
Display: The control shall have at a minimum a 2-line by 20-character LCD display for enhanced
viewing in direct sunlight. The control shall also offer a low-level LED backlight for reading in
darker environments.
SD Card Slot: The control shall have an SD Card slot that allows the user to perform the
following functions without the need for a laptop:
●Load/Save Set Points
●Load/Save DNP Configuration
●Save Oscillographic Records
●Save Wake Screen Data
●SD
● DNP Map Files
●Clone Load/ Save
● Save Sequence of Events
●Multi-user Password File
●Save Data Log
●Firmware Update
●Save Metering Data
● Password Access Log
Card User Access (Physical Security Key)
LED Indicators: The control shall have the following LED Indicators on the front panel:
●AUTO
●
(Remote)
LOCAL/MANUAL
●RSSI
●CLOSE
●ALARM
●OK
(CPU)
●OPEN
●
●TX
(Transmit)
(Received Signal Strength Indication)
RX (Receive)
●NEUTRAL
UNBALANCE
Switches: The control shall have the following switches on the front panel:



The control shall have a momentary toggle switch for initiating CLOSE and OPEN
operations when in the Manual Mode of Operation
The control shall have a 3-position switch for hardwired Voltage Source Selection of
INTERNAL, EXTERNAL (Front Panel Jacks), or OFF
The control shall have a 2-position switch for “Remote/Auto” or “Local/Manual” operation
Page 8 of 10
File: 841002203
Terminals: The control shall have front panel binding posts for External Power, Common, and
Meter Out (voltage).
TESTS AND STANDARDS
Voltage Measurement Accuracy
The control shall have a voltage measuring accuracy of + 0.3 % when tested over a temperature
range of – 40° C to + 85° C.
The control shall comply with the following type tests and standards:
Voltage Withstand
Dielectric Withstand
IEC 60255-5: 1,500 VAC for 1 minute applied to each independent circuit to earth; 1,500 VAC for
1 minute applied between each independent circuit.
Impulse Voltage
IEC 60255-5 -2000: 5,000 V pk, +/- polarity applied to each independent circuit to earth; 5,000 V
pk, +/- polarity applied between each independent circuit 1.2 by 50 s, 500 Ω impedance, three
surges at 1 every 5 seconds IEC 60255-5 > 100 MΩ.
Electrical Environment
Electrostatic Discharge Test
IEC 60255-22-2-2008: Class 4 (±8 kV)—point contact discharge
IEC 60255-22-2-2008: Class 4 (±15kV)–air discharge
Fast Transient Disturbance Test
IEC 60255-22-4-2008: Class A (±4 kV, 5 kHz)
Surge Withstand Capability
 ANSI/IEEE® 2,500 V pk-pk oscillatory applied to each independent circuit to earth
 C37.90.1- 2,500 V pk-pk oscillatory; applied between each independent circuit
 1989 5,000 V pk Fast Transient applied to each independent circuit to earth
 5,000 V pk Fast Transient applied between each independent circuit
 ANSI/IEEE 2,500 V pk-pk oscillatory applied to each independent circuit to earth
 C37.90.1- 2,500 V pk-pk oscillatory; applied between each independent circuit
 2002 4,000 V pk Fast Transient burst applied to each independent circuit to earth
 4,000 V pk Fast Transient burst applied between each independent circuit
NOTE: The signal shall be applied to the digital data circuits (RS-232, RS-485, Ethernet
communication port coupling port) through capacitive coupling clamp.
Surge Immunity
IEC 60255-22-5 2,000 V pk, ± polarity applied, 1.2 s by 50 s, five surges, 1 every 5 seconds
Radiated Electromagnetic Withstand Capability


IEC 60255-22-2 2007 Radiated RFI Immunity
IEC 60255-22-6-2001 Conducted RFI Immunity
All units shall be protected against electromagnetic radiated interference from portable
communications transceivers.
Page 9 of 10
File: 841002203
Atmospheric Environment
Temperature: Control shall operate from – 40° C to +85° C




IEC 60068-2-1 Cold, – 40° C
IEC 60068-2-2 Dry Heat, + 85° C
IEC 60068-2-78 Damp Heat, + 40° C @ 95% RH
IEC 60068-2-30 Damp Heat Condensation Cycle, 25° C, + 55° C @ 95% RH
Mechanical Environment
The control shall meet the following mechanical environmental specifications:
Vibration
IEC 60255-21-1
Vibration response Class 1, 0.5 g
Vibration endurance Class 1, 1.0 g
IEC 60255-21-2
Shock Response Class 1, 5g
Shock Response Class 1, 15g
Bump Endurance Class 1, 10g
Cyber Security Compliance
The control’s design shall be in compliance with the following Cyber Security standards:
NERC CIP-002 to 009 Critical Infrastructure Protection Cyber Security standards
NIST SP 800-121
Guide to Bluetooth Security
NIST FIPS180-2
186-2 Secure Hash Standard
IEC 62351-1
Data and Communications Security - Part 1: Introduction
IEC 62351-2
Data and Communications Security - Part 2: Glossary
IEC 62351-3
Data and Communications Security - Part 3: Communication Network
and System Security- Profiles Including TCP/IP
IEC 62351-5
Data and Communications Security - Part 5: Security for IEC 60870-5 and
derivatives
ISO/IEC 9798-4
Information Technology- Security techniques- Entity authentication Part 4: Mechanisms using cryptographic check function
RFC 2104
HMAC: Keyed - Hashing for Message Authentication
RFC 3174
US Secure Hash Algorithm (SHA-1)
FIPS 186-2
Digital Signature Standard (DSS), USA NIST, February 2000 Including
Change Notice #1, October 2001. Only the random number generation
algorithms in the appendix are used.
RFC 3394
Advanced Encryption Standard (AES) Key Wrap Algorithm
FIPS 180-2
Secure Hash Standard (includes SHA-1, SHA-224, SHA-256,
SHA-334 and SHA-512)
RFC 3629
UTF-8 a transformation format of ISO 10646
cULus-Listed per 508 – Industrial Control Equipment
Industrial Control Equipment Certified for Canada CAN/CSA C22.2 No. 14-M91
cULus-Listed Component per 508A Table SA1.1 Industrial Control Panels