Download AL600ULXD Power Supply/Charger

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Variable-frequency drive wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Stray voltage wikipedia , lookup

Power engineering wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Three-phase electric power wikipedia , lookup

Power inverter wikipedia , lookup

History of electric power transmission wikipedia , lookup

Voltage optimisation wikipedia , lookup

Alternating current wikipedia , lookup

Schmitt trigger wikipedia , lookup

Rectifier wikipedia , lookup

Mains electricity wikipedia , lookup

Power electronics wikipedia , lookup

Buck converter wikipedia , lookup

Electric battery wikipedia , lookup

Opto-isolator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Transcript
AL600ULXD
Power Supply/Charger
Overview:
The AL600ULXD power supply converts a 115VAC or 230VAC / 50/60Hz input to a 12VDC or 24VDC non powerlimited output (see specifications).
Specifications:
Supervision:
Agency Listings:
• UL Listed for Standard for Safety Access
Control System Units (UL 294), Power
Power Supplies for Fire-Protective Signaling Systems
(UL 1481).
• CE European Conformity.
• AC fail supervision (form “C” contacts).
• Low battery supervision (form “C” contacts).
Input:
• Low battery disconnect.
• Unit is complete with power supply, grey enclosure, cam lock and transformer.
• Battery leads included.
• 115VAC 60Hz, 1.9A or 230VAC 60Hz 0.95A.
Output:
• 12VDC or 24VDC selectable output.
• 12VDC or 24VDC @ 6A supply current.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Battery Backup:
• Built-in charger for sealed lead acid or gel type batteries.
• Automatic switch over to stand-by battery when AC fails.
• Maximum charge current 0.7A.
Visual Indicators:
• AC input and DC output LED indicators.
Features:
Enclosure Dimensions (H x W x D approx.):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm).
- Accommodates up to two (2) 12VDC/12AH batteries.
AL600ULXD: Grey Enclosure.
AL600ULXDR: Red Enclosure.
Power Supply Voltage Output Selections:
Output
12VDC
24VDC
Switch Position
SW1 ON
SW1 OFF
Stand-by Specifications:
Output
12VDC / 40AH Battery
4 hr. of Stand-by and
5 min. of Alarm
Stand-By = 6.0A
Alarm = 6.0A
24VDC / 12AH Battery
------------
24VAC / 40AH Battery
Stand-By = 6.0A
Alarm = 6.0A
24 hr. of Stand-by and
5 min. of Alarm
Stand-By = 1.0A
Alarm = 6.0A
Stand-By = 200 mA
Alarm = 6.0A
Stand-By = 1.0A
Alarm = 6.0A
60 hr. of Stand-by and
5 min. of Alarm
Stand-By = 300 mA
Alarm = 6.0A
-----------Stand-By = 300 mA
Alarm = 6.0A
Installation Instructions:
The AL600ULXD should be installed in accordance with article 760 of The National Electrical Code or NFPA 72 as
well as all applicable Local Codes.
1. Mount the AL600ULXD in the desired location.
2. Connect input power from a separate unswitched AC circuit to the transformers. Secure green wire lead to
earth ground. (Fig. 1).
For 115VAC input:Connect Yellow and White leads from transformer primary to neutral.
Connect Blue and Black leads from transformer primary to line (Fig. 2).
For 230VAC input:Connect Blue and Yellow leads of transformer 1 together. Connect Blue and Yellow leads of
transformer 2 together. Connect White lead from both transformers to neutral.
Connect Black lead from both transformers to line (Fig. 3).
Keep power-limited wiring separate from non power-limited wiring (115VAC 50/60Hz or 230 50/60Hz Input,
Battery Wires). Minimum 0.25” spacing must be provided.
AL600ULXD
- 1 -­
4.
5.
6.
7.
Measure output voltage before connecting devices. This helps avoiding potential damage.
Connect devices to be powered to the terminals marked [+ DC –] (Fig. 1).
For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the
loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
Connect battery to the terminals marked [+ BAT –] (Fig. 1) (battery leads included). Use two (2)
12VDC batteries connected in series for 24VDC operation.
Connect appropriate trouble reporting devices to AC Fail & Low battery (Fig. 1) supervisory relay outputs marked [NC, C, NO]. Use 22 AWG to 18 AWG for AC Fail / Low Battery reporting. AC Failure will report in 5 minutes. For a 6 hour delay on reporting cut resistor R1 (Fig. 1).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level
(Power Supply Voltage Output Selection Chart).
Battery Test: Under normal load conditions, check that the battery is fully charged, check specified voltage both at the battery terminal and at the board terminals marked [+ BAT –] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 0.7A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.
Fig. 1
Fig. 2
ON
3
2
BLUE
BLACK
YELLOW
4
1
XFMR
XFMR
WHITE
5
OFF = 24V SW1 ON = 12V
115VAC input
50/60 Hz, 1.9A
LINE
NEUTRAL
230VAC input
50/60 Hz, 0.95A
Input
115VAC115VAC
Input
Fig. 3
2
1
WHITE
3
BLUE
4
YELLOW
BLACK
5
Green
Lead
(ground)
230VAC Input
230VAC Input
- 2 -­
AL600ULXD
LED Diagnostics:
Red (DC)
ON
ON
OFF
OFF
Green (AC)
ON
OFF
ON
OFF
Power Supply Status
Normal operating conditions.
Loss of AC. Stand-by battery supplying power.
No DC output.
Loss of AC. Discharged or no stand-by battery. No DC output.
Terminal Identification:
Terminal Legend Function/Description
AC / AC
Low voltage AC input (28VAC / 200VA). Two (2) Altronix part # T2885D.
+ DC –
12VDC / 24VDC @ 6A continuous non power-limited output.
Used to notify loss of AC power, e.g. connect to audible device or alarm panel.
AC FAIL
Relay normally energized when AC power is present.
NC, C, NO
Contact rating 1A @ 28VDC
Low Battery
NC, C, NO
+ BAT –
AL600ULXD
Used to indicate low battery condition, e.g. connect to alarm panel.
Relay normally energized when DC power is present.
Contact rating 1A @ 28VDC.
Stand-by battery connections. Maximum charge rate 0.7A.
- 3 -­
Enclosure Dimensions (H x W x D approximate):
15.5” x 12” x 4.5” (393.7mm x 304.8mm x 114.3mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
1.75”
(44.45mm)
1.375”
(34.925mm)
1.125”
(28.575mm)
1.25”
(31.75mm)
4.5”
(114.3mm)
12.23”
(310.64mm)
1.1”
(27.94mm)
0.91”
(23.114mm)
1.5”
(38.1mm)
4.5”
(114.3mm)
1.1”
(27.94mm)
1.25”
(31.75mm)
0.91”
(23.114mm)
2.0”
(50.8mm)
1.5”
(38.1mm)
15.5”
(393.7mm)
2.0”
(50.8mm)
5.0”
(127.0mm)
5.0”
(127.0mm)
1.1”
(27.94mm)
1.25”
(31.75mm)
0.79”
(20.06mm)
1.25”
(31.75mm)
1.75”
(44.45mm)
1.5”
(38.1mm)
4.615”
(117.22mm)
4.615”
(117.22mm)
1.5”
(38.1mm)
Altronix is not responsible for any typographical errors. Product specifications are subject to change without notice.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
web site: www.altronix.com, e-mail: [email protected]. Lifetime Warranty, Made in U.S.A.
IIAL600ULXD - Rev. 013103