Download SR2 Modules are designed for interconnection via CSInet which

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power inverter wikipedia , lookup

Standby power wikipedia , lookup

Power factor wikipedia , lookup

Electrical substation wikipedia , lookup

Studio monitor wikipedia , lookup

Islanding wikipedia , lookup

Audio power wikipedia , lookup

Rectifier wikipedia , lookup

Stage monitor system wikipedia , lookup

Voltage optimisation wikipedia , lookup

History of electric power transmission wikipedia , lookup

Stray voltage wikipedia , lookup

Earthing system wikipedia , lookup

Buck converter wikipedia , lookup

Ground (electricity) wikipedia , lookup

Electric power system wikipedia , lookup

Electrification wikipedia , lookup

Three-phase electric power wikipedia , lookup

Power over Ethernet wikipedia , lookup

Power electronics wikipedia , lookup

Uninterruptible power supply wikipedia , lookup

Power engineering wikipedia , lookup

Opto-isolator wikipedia , lookup

AC adapter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

Transcript
SiteRanger™ SR2
Internet-based Site Monitoring System
SR2 Distributed Network monitoring modules
 Remote power via PoE - reliable and redundant
 function modules - targeted monitoring
 Connect via CSInet or direct LAN connection for local monitoring
Individual dedicated function modules are retrofitted/installed in power devices, HVAC, Fire Suppression
and other site systems to provide both contact closure and analog parameter monitoring to provide
significant remote visibility of facility status.
SR2 Modules are designed for interconnection via CSInet which includes an industry standard Cat5E
network with PoE enabled network power distribution to provide reliable central power for the SR2
modules. CSInet provides individual Cat5E connectivity for data and power for the SR2 modules
without proprietary wiring or interconnection limitations. Standard network wiring devices and
components are used for maximum cost and reliability benefit.
Contact closures and analog parameter acquisition provides the maximum in remote visibility. Each SR2
module includes inputs for contact closures from site devices as well as electrical monitoring
connectivity for AC/DC power parameters as well as other analog information such as temperature,
humidity, generator fuel level etc.
SiteRanger SR2 modules include dedicated purpose configurations that allow the end user to decide
which site devices should be monitored and to add these devices as required over time instead of prepurchasing the entire monitoring infrastructure in advance. This ala carte approach saves cost and still
allows the SiteRanger system to be “future proof” by allowing new modules to be added over time in
the future as new equipment is added or selected to be monitored.
SR2 Available Remote Acquisition Modules
ACM: AC Monitor
 Single or three phase. AC volts, amps, watts, VA, power factor, frequency
 Eight contact closure inputs for device alarm contacts
 Used in Automatic transfer switches, UPS systems, service entrance panels, distribution breaker
panels
DCM: DC Monitor
 -48V DC volts, amps, watts, VA, Temperature
Doc# 048–047–00/Jan.01.07


Eight contact closure inputs for device alarm contacts
Used in -48VDC powerplants, rectifier bays, BDFB cabinets, distribution bays
GSM: Generator System Monitor
 Single or three phase. AC volts, amps, watts, VA, power factor, frequency, temperature, starting
battery voltage
 Eight contact closure inputs for generator status alarm contacts. FSM fuel monitor input port for
fuel level sensing
 Used in standby electrical generators
EVM: Environmental System Monitor
 Temperature, Humidity, HVAC status
 Eight contact closure inputs for HVAC status alarm contacts
 Used in hub rooms, headends, facility space
GNSM: Ground Network System Monitor
 Ground fault current for Telephony switch / VOIP infrastructure
 Eight current sense inputs for MGB and other ground current detection locations
CSInet
Cat 5 network with PoE
Central power source for all modules on network
(ACM) AC Module (Installed
in UPS)
 Single phase or
three phase
 Volts,Amps,power,
VA power factor,
frequency
 8 contact inputs
(ACM) AC Module
(Installed in ATS)



Single phase or
three phase
Volts,Amps,pow
er, VA power
factor, frequency
8 contact inputs
(DCM) DC Module



Installs in -48VDC
power system-rectifier
bay or distribution
cabinet
DC volts, amps,power,
temperature
8 contact inputs
To enterprise network
PoE (Power over ethernet) switch
(GNSM) Ground network
system monitor
 Installs on MGB
main ground bus
and secondary
ground feeder
connections.
Detects and
measures ground
fault current on
Telco/Voip switch
ground network

-48VDC
source with
battery
backup
(GSM) Generator Module
 Installs in generator
housing
 AC volts, amps, power, VA,
frequency, starting battery
DC volts
8 current sense
8 contact inputs.
(EVM) Environmental Module
 Installs in Hub room
Temperature, humidity,
HVAC alarm monitoring
 8 contact inputs
(FSM) Generator fuel level sending unit
 Installs on diesel or propane
tank
 Propane rotary gauge sending
module or diesel tank float
sensor
Doc# 048–047–00/Jan.01.07
SiteRanger SR2
Model #
ACM
AC monitor
UPS
Power Parameters
1ph/3ph Volts, amps,
watts, VA, Hz, PF,
phase imbalance
Analog Perameters
Voltage, Current,
Frequency
ACM
AC monitor
ATS
1ph/3ph Volts, amps,
watts, VA, Hz, PF,
phase imbalance
Voltage, Current,
Frequency
DCM
DC monitor
DCV, DCA, watts,
charge A, load A
Temperature
EVM
Environmental monitor
None
Temperature,
humidity, overtemp
alarm
GSM
Generator System
monitor
1ph/3ph Volts, amps,
watts, VA, Hz, PF,
phase imbalance
Starting battery
voltage,
temperature, fuel
level, starter current
GNSM
Ground network system
monitor
Ground fault current in
Amps, current flow
direction, peak
current, AC ripple
current
None
Eight current sensor
inputs for MGB,
SGB, Telephony
switch ground
window etc
None
None
Diesel or propane
fuel level sending
unit. Connects to
GSM module input
GM8
General monitor module
FSM
Generator fuel status
monitor
Contact Closure Inputs
UPS on battery, UPS on
commercial power, UPS
fault, UPS in static bypass,
UPS fan fail, UPS low
battery, battery fault, UPS
distribution circuit trip
Site connected to
commercial power, site
connected to generator
power, ATS not in auto
mode, battery charger
fault, exerciser mode
active, generator run
Rectifier fail, major alarm,
minor alarm, battery
offline, distribution fuse
fail, overtemp alarm, AC
input fail, system fail
HVAC general alarm,
compressor fail, controller
fail, condensate drain
alarm
8 contact inputs for
multiple HVAC unit alarms
Generator summary
alarm, not in auto mode,
generator running, low oil,
low coolant, overcrank,
High temperature, tamper
alarm
None
8 contact inputs for misc
alarms: TVSS fail, Fire
suppression, intrusion
alarm, Tech on site, smoke
detect, fuse fail, breaker
trip, etc
Rupture basin alarm, overfill alarm, low fuel alarm,
leak alarm, low gas
pressure alarm
Doc# 048–047–00/Jan.01.07
PoE powerpoint
-48VDC power injector
point for PoE cat 5
network. Provides
power for CSInet
modules
port
None
None
General Specifications
Model #
P/N 016-900-10
Configuration
SiteRanger SR1 Contact
input-SNMP output
Contact inputs, internal
DC/AC power supply. VFD
display LED interface panel,
19/23” Rack mount housing
P/N 016-905-10
ACM AC power module.
Monitors single or three
phase AC voltage, current,
power parameters. Use for
ATS site power monitoring,
UPS output monitoring
P/N 016-910-10
DCM DC power module.
Monitors -48VDC rectifier
and battery system status.
Measures DC voltage,
current, distribution circuit
breaker trip, battery status,
accepts alarm contact
outputs from DC power
system
EVM Environmental module.
Monitors HVAC alarm
contact outputs,
temperature, condensate
drain alarm, multiple
temperature sensor,
humidity sensor
GSM Generator status
module. Monitors
Generator contact closures,
P/N 016-915-10
P/N 016-920-10
Part #
016-900-10
(8 inp.)
016-901-10
(16 inp.)
016-902-10
(24 inp.)
016-903-10
(32 inp.)
016-905-10
016-906-10
016-907-10
016-908-10
016-910-10
016-911-10
016-912-10
Description
Rack mount housing. Accepts
8/16/24/32 contact inputs, LAN.
Ethernet 10/100 Base T jack with LED
indicators. -48VDC/120VAC input,
internal power supply
Non-metallic housing with terminal
block connections for AC voltage
sense, current transformer input
sense, ATS position sensing
(generator/commercial power),
8alarm contact inputs. CSInet LAN
port. Specify 1,2 or 3 phase, 120V,
240V, 208V, 480V versions. Current
transformers available for 100, 200,
400 and 600A systems
Non-metallic housing with terminal
block connections for DC voltage
sense, DC power system contact
closure inputs, distribution alarm
contact inputs, CSInet LAN port.
Specify input configuration, current
monitoring kit, battery temperature
probe kit
016-915-10
016-916-10
Non-metallic housing with terminal
block connections for 8 HVAC system
alarm contact inputs. Temperature
sensor, humidity sensor, CSInet LAN
port. 8 input ports
016-920-10
016-921-10
016-922-10
Non-metallic housing with terminal
block connections for generator
output AC voltage/current sense, 8
Doc# 048–047–00/Jan.01.07
P/N 016-925-10
P/N 016-927-10
P/N 016-929-10
fuel level, starting battery
voltage. AC power
parameters
FSM Generator fuel status
module. Monitors
Generator fuel level. (Diesel
or propane)
GNSM Ground network
system monitor. Multipoint
ground current monitoring
GM8 General monitor
module. Contact inputs
only. Generic use for devices
alarm contact inputs. CSInet LAN
port. Specify 1,2 or 3 phase
016-930-10
016-931-10
016-932-10
016-933-10
016-935-10
016-940-10
Monitors Generator fuel level. Specify
diesel tank level sensor, propane tank
transducer head (various versions
depending upon tank vendor).
Monitors ground fault current at up
to 8 sensor locations. Specify Shunt
or hall effect sensor modules
Monitors any remote contact closure
or switch. 8 inputs for general use for
site monitoring devices
Common Specifications for All Models:
SiteRanger SR1
Dimensions: 17" W x 3.75” (2RU) T x 12” D
Weight: 13 lbs
Rack mount with 19/23” reversible mounting flanges. Hinged cover w/LED or VFD control panel. Unit
includes wiring diagram / instruction manual, software, spare fuses. Input contact detachable set screw
terminals. 10BT/100BaseT ethernet RJ45 jack
Electrical Specifications:
Input: 120VAC power supply and dual -48VDC redundant inputs. All three power inputs are redundant
and will operate the unit.
SiteRanger SR2
Dimensions: 5" W x 7.5” T x 2.5” D
Weight: 4 lbs
Wall surface mount. Sealed cover w/LED and LCD control panel. Unit includes wiring diagram /
instruction manual, software, spare fuses, 10BT/100BaseT ethernet RJ45 jack, analog input connectors,
input contact connectors.
Electrical Specifications:
Input: Network powered via CSInet PoE power over ethernet. Local power port 12VAC power cube
option.
Order Information
Shipping box packaging for UPS/FedEx shipment. Typical configuration includes bill of materials/parts kit
as per customer site survey order form.
CSI Provides customer site surveys at no charge to provide customer proposals for the correct
SiteRanger component and installation configurations.
Doc# 048–047–00/Jan.01.07