Download Technical Statement - The Lighting Industry Association

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Three-phase electric power wikipedia , lookup

Stepper motor wikipedia , lookup

Islanding wikipedia , lookup

Transistor wikipedia , lookup

Fault tolerance wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Stray voltage wikipedia , lookup

Ohm's law wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Electrical ballast wikipedia , lookup

Rectifier wikipedia , lookup

Flexible electronics wikipedia , lookup

History of electric power transmission wikipedia , lookup

Ground (electricity) wikipedia , lookup

Regenerative circuit wikipedia , lookup

Multimeter wikipedia , lookup

Current source wikipedia , lookup

Distribution management system wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Two-port network wikipedia , lookup

Buck converter wikipedia , lookup

Integrated circuit wikipedia , lookup

Voltage optimisation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Opto-isolator wikipedia , lookup

Electrical substation wikipedia , lookup

Residual-current device wikipedia , lookup

Earthing system wikipedia , lookup

Surge protector wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Circuit breaker wikipedia , lookup

Transcript
Technical Statement
LIA TS31
Issue 1 - 06/2014
Page 1 of 3
Application Guide on the use of Mains Circuit
Breakers with luminaires containing Electronic
control gear (ECG) for LEDs
The market trend towards LED lighting has led to situations where mains circuit breakers
maybe nuisance tripped when connected to similar loads to that of fluorescent circuits due
to the higher inrush current that is drawn by some devices.
Inrush current refers to the briefly occurring high input current which flows into the ECG
during the initial start-up to charge the capacitors on the input side. Typically, the
amplitude is much greater than the operating or steady-state current, as illustrated below:
Note: Yellow trace = Supply Voltage
Green trace = Supply Current
It is this inrush current that can lead to nuisance tripping of circuit breakers.
BS EN 60898 relates to low voltage circuit breakers for use in household and similar
installations. In the UK these are traditionally known as miniature circuit breakers or
MCB’s.
BS EN 60947 relates to low voltage circuit breakers for use in industrial and similar
installations and are traditionally known as moulded case circuit breakers or MCCB’s.
Mains circuit breakers in their simplest form come in 3 main ranges of sensitivity known as
B, C and D Type
Type B: Suitable for general, domestic and commercial installations having little or no
switching surges. These are not suitable for lighting circuits containing electronic control
gear (ECG).
Type C: Suitable for general use in commercial or industrial applications where the greater
use of fluorescent lighting and small motors can produce switching surges, which may
cause nuisance tripping of Type B breakers.
Technical Statement
LIA TS31
Issue 1 - 06/2014
Page 2 of 3
Type D: Suitable for general Industrial applications where there are a lot of high inrush
switching surges associated with equipment such as transformers, large motors , welding
and X ray equipment.
These sensitivities relate to their normal trip current as follows:
IEC/EN 60598
Type
Instantaneous
Trip Current (x In)
Typical
Application
B
C
3 to 5
5 to 10
D
10 to 20
General Distribution
Commercial
Light Industrial
General
Industrial
Technical Statement
LIA TS31
Issue 1 - 06/2014
Page 3 of 3
The above graph helps to calculate the maximum number of luminaires you can connect to
a circuit protected by a mains circuit breaker. From this it can be seen that the time period
that the breaker will cope with the initial inrush surge is extended by the use of C or D type
breakers over B type.
It should also be noted that:





The impedance of the mains supply plays a contributing factor; the higher the
impedance then the number of ECGs connected to a MCB may be increased.
In some cases the maximum number of ECGs is not determined by the MCB but by
the maximum electrical load of the installation.
The number of ECG’s connected to a MCB may be increased if they are not going
to be switched simultaneously.
Some luminaires may contain more than one ECG
When considering multiple ECG’s on one breaker, the individual surge currents
from each ECG must be added together when choosing the correct breaker.
Note: Use manufacturer’s data to ensure you do not exceed the 30 mA limit.
Conclusion
The information above should help in determining the quantity of luminaires that can be
connected to a MCB. It should be noted that some LED luminaires contain more than one
ECG, and that in retro fit installations the number of ECG in the new luminaire may be
different to the one being replaced. Surge current limiting devices are available which may
be helpful if trying to use an existing breaker whilst updating the lighting to incorporate
LED technology, as the inrush characteristics of LED luminaires may not be identical to the
existing control gear.
Most quality manufacturers of luminaires publish data which can assist in the correct
choice of breaker.
Neither the Lighting Industry Association Ltd, nor any person acting on its behalf, makes any warranty of
representation, expressed or implied with respect to the information contained in this report, or assumes any liability
with respect to the use of, or damages resulting from, the use of this information. In assessing the suitability of any
specific product or installation the user must make his own judgement and/or take appropriate advice.
© Lighting Industry Association [2014] All Rights Reserved