Stray voltage wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Portable appliance testing wikipedia , lookup
Surge protector wikipedia , lookup
Alternating current wikipedia , lookup
Opto-isolator wikipedia , lookup
Rectiverter wikipedia , lookup
Mains electricity wikipedia , lookup
Electrical wiring wikipedia , lookup
Transcript
8 THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 2. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH CAUSE MAJOR DEVIATIONS IN THE WORK SHOWN, THE CONTRACTOR SHALL CONTACT SIMPLEXGRINNELL IN A TIMELY MANNER SO AS NOT TO IMPAIR THE CONSTRUCTION SCHEDULE. A STAMPED SET OF APPROVED FIRE ALARM DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION. 5. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT BREAKER, AND SHALL HAVE A RED MARKING, LOCK-ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. 6. UPDATE THE AS-BUILT DRAWING SET DAILY WITH JOB PROGRESS. RETURN THE AS-BUILT DRAWING SET TO SIMPLEXGRINNELL NO LATER THAN 7 DAYS AFTER FINAL TEST. 7. THE CONTRACTOR WILL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMAN LIKE MANNER. 8. DO NOT APPLY POWER EXCEPT IN THE PRESENCE OF A FACTORY TRAINED SIMPLEXGRINNELL TECHNICAL REPRESENTATIVE. 9. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO PROTECT FROM DUST. ANY FALSE ALARMS DUE TO DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER. 10. THE FIRE ALARM INSTALLER WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY BEING PERFORMED. 11. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND NEC. 12. ALL WIRING SHALL BE INSTALLED ACCORDING TO NFPA 70 (NEC). 13. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPROPRIATE SECTION OF NEC 760. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH NEC 760 SECTIONS FOR POWER LIMITED AND NON-POWER LIMITED WIRE. 15. C OCCUPANCY TYPE: CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENTS IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED CHANGE. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 4. 14 SYMBOL BUILDING IS FULLY SPRINKLED FAA ALL WIRING TO BE CLASS B. WIRING IS STYLE Y FOR NOTIFICATION APPLIANCE CIRCUITS, STYLE B FOR INITIATING DEVICE CIRCUITS, AND STYLE 4 FOR SIGNALING LINE CIRCUITS. AUTOMATIC FIRE ALARM SYSTEM SHALL TRANSMIT THE ALARM, SUPERVISORY AND TROUBLE SIGNALS TO AN APPROVED SUPERVISING STATION. THE SUPERVISING STATION SHALL BE LISTED AS EITHER UUFX OR UUJS UNDERWRITERS LABORATORY OR SHALL MEET THE REQUIREMENTS OF FACTORY MUTUAL RESEARCH APPROVAL STANDARD 3011. SUPERVISION OF SYSTEM AND LEASED TELEPHONE LINES SHALL BE ARRANGED BY THE OWNER. P FIRE ALARM CABLE INSTALLED IN UNDERGROUND CONDUIT OR OTHER WET LOCATIONS SHALL BE UL LISTED FOR WET LOCATIONS. CALIFORNIA ELECTRIC CODE, 2013 EDITION, TITLE 24, PART 3 17. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOOR SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 70 ARTICLES 760, 770, 725 AND 800 WHERE APPLICABLE. CALIFORNIA ELEVATOR SAFETY CONSTRUCTION CODE, 2013 EDITION 18. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS. 3. 19. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE. 20. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT. 21. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING. 22. MAINTAIN 40 PERCENT CONDUIT FILL RATIO AS PER NEC REQUIREMENTS. 23. EXISTING CONDUITS MAY BE USED BY THE INSTALLATION CONTRACTOR AS DEEMED NECESSARY, HOWEVER, ANY EXISTING CONDUIT WILL BE USED ONLY IF CONDUITS MEET CURRENT STANDARDS AND CODES. SIMPLEXGRINNELL MAKES NO STATEMENTS WRITTEN OR VERBAL AS TO THE CONDITION OF EXISTING CONDUITS. 4. 5. 6. E 7. UPON COMPLETION OF THE INSTALLATION OF THE SYSTEM, A SATISFACTORY TEST OF THE ENTIRE SYSTEM SHALL BE MADE IN THE PRESENCE OF A DSA PROJECT INSPECTOR. A STAMPED SET OF APPROVED FIRE ALARM DESIGN DOCUMENTS SHALL BE MAINTAINED ON THE JOB SITE AND USED FOR INSTALLATION. 22. CONTROL PANELS AND REMOTE ANNUNCIATORS SHALL BE INSTALLED WITH THEIR BOTTOMS MOUNTED AT 48” ABOVE FINISHED FLOOR. 13. VISUAL APPLIANCES SHOULD NOT EXCEED 2 FLASHES PER SECOND AND SHOULD NOT BE SLOWER THAN 1 FLASH EVERY SECOND. THE DEVICE SHALL HAVE A PULSING LIGHT SOURCE NOT LESS THAN 15 CANDELA. VISUAL APPLIANCES WITHIN 55' FROM EACH OTHER SHALL BE SYNCHRONIZED. 23. THE INSTALLING CONTRACTOR SHALL PROVIDE SYSTEM PROGRAMMING FOR SUPERVISORY MONITORING PER CBC SECTION 901.6.2. ANY DISCREPANCIES BETWEEN THE DRAWINGS AND THE CODE OR RECOGNIZED STANDARDS SHALL BE BROUGHT TO THE ATTENTION OF DSA AND THE ARCHITECT/ENGINEER OF THE PROJECT. 17. DSA, ARCHITECT/ENGINEER AND OWNER SHALL BE NOTIFIED A MINIMUM OF 48 HOURS PRIOR TO THE FINAL INSPECTION AND /OR TESTING. ALL PENETRATIONS THROUGH RATED ASSEMBLIES REQUIRING OPENING PROTECTION SHALL BE PROVIDED WITH A PENETRATION FIRE STOP SYSTEM AS IDENTIFIED IN CBC CHAPTER 7, UL OR OTHER LAB TESTING CRITERIA. 8. WALL MOUNTED VISUAL NOTIFICATION APPLIANCES SHALL HAVE THEIR BOTTOMS MOUNTED AT 80” MINIMUM AND 96” MAXIMUM ABOVE FINISHED FLOOR. 9. WALL MOUNTED AUDIBLE NOTIFICATION APPLIANCES SHALL HAVE THEIR TOPS MOUNTED AT 90” MINIMUM AND 96” MAXIMUM ABOVE FINISHED FLOOR AND NO CLOSER THEN 6” TO A HORIZONTAL STRUCTURE. 10. AUDIBLE APPLIANCES TO PROVIDE SOUND LEVEL AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT SOUND LEVEL BUT NOT LESS THAN 75 dB AT 10 FEET OR MORE THAN 110 dB AT THE MINIMUM HEARING DISTANCE . SOUND LEVEL SHALL ACHIEVE 5 dB ABOVE MAXIMUM SOUND LEVEL HAVING DURATION OF AT LEAST 60 SECONDS. MEASURE SOUND LEVEL AT FIVE FEET ABOVE FINISHED FLOOR. F 11. ALL FIRE ALARM CIRCUITS SHALL BE IN CONDUIT, SURFACE RACEWAY OR OPEN RUN ABOVE CEILINGS, UNDER FLOORS AND IN WALLS IN A NEAT AND PROTECTED MANNER AS INDICATED ON DESIGN DOCUMENTS. EXPOSED CIRCUITS ARE ONLY PERMITTED WHEN NOTED AS EXPOSED ON DESIGN DOCUMENTS. 19. FIRE ALARM PANEL, REMOTE PANELS, POWER SUPPLIES AND COMPONENTS SHALL BE SECURED TO MOUNTING SURFACES PER MANUFACTURERS SPECIFICATIONS. NO SINGLE DEVICE SHALL EXCEED THE WEIGHT OF 20 LBS. WITHOUT SPECIAL MOUNTING DETAILS. 20. AUDIBLE APPLIANCES SHALL BE SYNCHRONIZED TEMPORAL CODE 3 PATTERN. 21. 24. SUPERVISORY MONITORING SHALL BE TESTED AND VERIFIED AS SENDING CORRECT SIGNALS IN CONJUNCTION WITH FINAL ACCEPTANCE TEST. 25. OWNER SHALL BE RESPONSIBLE FOR ESTABLISHING A FIRE SYSTEM MONITORING CONTRACT OR PROVISIONS. SMOKE DETECTORS SHALL NOT BE INSTALLED CLOSER THAN 1' FROM FIRE SPRINKLERS OR 3' FROM ANY SUPPLY DIFFUSER. IN AREA OF CONSTRUCTION OR POSSIBLE DAMAGE/CONTAMINATION, NEWLY INSTALLED FIRE ALARM DEVICES SHALL BE COVERED UNTIL THAT AREA IS READY TO BE TURNED OVER TO THE OWNER. 18. NO GRIP MANUAL PULL STATION SIMPLEX 4099-9020 4" SQUARE BOX 2 1/8" DEEP W/SINGLE GANG COVER 7150-0026:0224 SMOKE SENSOR / BASE SIMPLEX 4098-9714 SIMPLEX 4098-9792 BASE 4" OCTAGONAL BOX 1 1/2" DEEP 7272-0026:0218 7300-0026:0217 SIMPLEX 4098-9733 SIMPLEX 4098-9792 BASE 4" OCTAGONAL BOX 1 1/2" DEEP 7270-0026:0216 7300-0026:0217 RELAY IAM SIMPLEX 4090-9002 4" SQUARE BOX 2 1/8" DEEP W/TWO GANG COVER 7300-0026:0223 # ADDRESSABLE MULTI-CANDELA SPEAKER/STROBE, WALL MOUNT, WHITE # =CANDELA RATING, #W = SPEAKER TAP **USE 70 VOLT TAP** SIMPLEX 4906-9253 4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" EXTENSION RING W/4905-9946 ADAPTER SKIRT WHEN SURFACE MOUNTED 7320-0026:0322 # ADDRESSABLE MULTI-CANDELA SPEAKER/STROBE, CEILING MOUNT, WHITE # =CANDELA RATING, #W = SPEAKER TAP **USE 70 VOLT TAP** SIMPLEX 4906-9254 4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" EXTENSION RING 7320-0026:0322 #W C # C THE CONTRACTOR SHALL ADJUST/INSTALL ALL DEVICES TO MAXIMIZE PERFORMANCE AND TO MINIMIZE FALSE ALARMS. PER CEC STANDARDS, ALL WIRING IS TO BE PULLED THROUGH EACH JUNCTION BOX AND CONNECTED DIRECTLY TO EACH FIRE DEVICE. DO NOT SPLICE THE WIRE. THERE MUST BE AT LEAST 6" OF LEAD WIRE FROM THE BOX TO THE DEVICE. ALL BOXES TO BE SIZED PER CEC. 7120-0026:0179 AOM #W 12. 16. 6 GANG BOX 3 1/2" DEEP 7300-0026:0223 # ALL FIRE ALARM WIRING SHALL BE FLP OR FPLP (FIRE POWER LIMITED OR FIRE POWER LIMITED PLENUM) AS REQUIRED FOR APPLICATION. WIRING IN CONDUIT ABOVE GROUND MAY BE THHN OR THWN. SIMPLEX 4603-9101 SERIAL LCD ANNUNCIATOR SINGLE GANG BOX 2 1/2" DEEP WITH COVER # 15. 7165-0026:0251 SIMPLEX 4100-9111 REFER TO BATTERY CHARTS SIMPLEX 4090-9001 NFPA 72, 2013 EDITION WITH CALIFORNIA AMENDMENTS UNDERGROUND AND EXTERIOR CONDUITS TO HAVE WATERTIGHT FITTINGS AND WIRE TO BE APPROVED FOR WET LOCATIONS. SUPPLIED BY SIMPLEXGRINNELL (REFER TO MOUNTING DETAIL FOR SPECIFIC DIMENSIONS) FIRE ALARM CONTROL PANEL W / VARIOUS BATTERY SETS INDIVIDUAL ADDRESSABLE MODULE CALIFORNIA BUILDING CODE, 2013 EDITION, TITLE 24, PART 2 16. 14. # AC C E RC RD RL RR = = = = = = = ABOVE CEILING CEILING MOUNTED EXISTING TO REMAIN EXISTING TO REMOVE AND COVER EXISTING DEVICE TO BE RELOCATED RELOCATED DEVICE REMOVE EXISTING AND REPLACE W/NEW WP XP H AFF AHJ ALM ANN BMS CBC CD CSFM DET DGP EOL EPO FACP FATC FBO FCC FAA FTR FSD = = = = = = = = = = = = = = = = = = = = = = WEATHERPROOF EXPLOSION PROOF HIGH HUMIDITY ABOVE FINISHED FLOOR AUTHORITY HAVING JURISDICTION ALARM ANNUNCIATOR BUILDING MANAGEMENT SYSTEM CALIFORNIA BUILDING CODE (eg. 15CD) CANDELA CALIFORNIA STATE FIRE MARSHAL DETECTOR DATA GATHERING PANEL END OF LINE EMERGENCY POWER OFF FIRE ALARM CONTROL PANEL FIRE ALARM TERMINAL CABINET FURNISHED BY OTHERS FIRE COMMAND CENTER FIRE ALARM ANNUNCIATOR FIRE ALARM TRANSPONDER FIRE SMOKE DAMPER HT HVAC IMS MAX MIN N/A NAC NDU NEC NFPA NIC NPU NTS PAP SCC SLC SMK SUPV TAC TRBL TS TYP UON VCC VT WF W W/ W/O = = = = = = = = = = = = = = = = = = = = = = = = = = = = = HEIGHT HEATING, VENTILATION, & AIR CONDITIONING INFORMATION MANAGEMENT SYSTEM MAXIMUM MINIMUM NOT APPLICABLE NOTIFICATION APPLIANCE CIRCUIT EXTENDER NETWORK DISPLAY UNIT NATIONAL ELECTRICAL CODE NATIONAL FIRE PROTECTION ASSOCIATION NOT IN CONTRACT NETWORK PROCESSING UNIT NOT TO SCALE PRE-ACTION PANEL STATUS COMMAND CENTER SIGNALING LINE CIRCUIT SMOKE SUPERVISORY TRUEALERT ADDRESSABLE CONTROLLER TROUBLE TAMPER SWITCH TYPICAL UNLESS OTHERWISE NOTED VOICE COMMAND CENTER VALVE TAMPER WATER FLOW (eg. 1/2W) WATT WITH WITH OUT SIMPLEX 49VO-WWF 4" SQUARE BOX 1 1/2" DEEP W/4905-9940 ADAPTER SKIRT WHEN SURFACE MOUNTED 7125-0026:0373 ADDRESSABLE CEILING MOUNT MULTI-CANDELA STROBE ONLY WHITE # =CANDELA RATING SIMPLEX 4906-9204 HANDY BOX 1 1/2" DEEP 7125-0026:0235 SPEAKER ONLY, WALL MOUNT #W = SPEAKER TAP SIMPLEX 4902-9717 7320-0026:0242 **USE 70 VOLT TAP** 4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" RING W/4905-9942 ADAPTER SKIRT WHEN SURFACE MOUNTED SPEAKER ONLY, CEILING MOUNT #W = SPEAKER TAP SIMPLEX 4902-9721 4" SQUARE BOX 1 1/2" DEEP W/ 1 1/2" RING 7320-0026:0242 **USE 70 VOLT TAP** WALL MOUNT MULTI-CANDELA WEATHERPROOF STROBE ONLY, WHITE # = CANDELA RATING SIMPLEX 49VO-WWFO-BA 49WPBB-AVVOWW BACK BOX SUPPLIED BY SIMPLEXGRINNELL 7125-0026:0371 #W WP SPEAKER ONLY, WALL MOUNT, WEATHERPROOF #W=SPEAKER TAP WHEELOCK ET-1010W WBB-W 7320-0785:0105 VS TAMPER SWITCH SUPPLIED BY OTHERS INSTALLED BY MECHANICAL CONTRACTOR WF WATERFLOW SWITCH SUPPLIED BY OTHERS INSTALLED BY MECHANICAL CONTRACTOR A DEDICATED BRANCH CIRCUIT SHALL BE PROVIDED FOR FIRE ALARM EQUIPMENT. THIS CIRCUIT SHALL BE ENERGIZED FROM THE COMMON USE AREA PANEL AND SHALL HAVE NO OTHER OUTLETS. THE BREAKER SHALL HAVE A RED LOCKING DEVICE TO BLOCK THE HANDLE IN THE “ON” POSITION. THE CIRCUIT BREAKER SHALL BE LABELED “FIRE ALARM CIRCUIT CONTROL”. CIRCUIT ID TO BE LABELED AT FIRE PANEL/EXTENDERS. DUCT SMOKE SENSOR SIMPLEX 4098-9756 MOUNT TO DUCTWORK 3240-0026:0241 REMOTE TEST STATION W/ LED AND KEY SWITCH SIMPLEX 2098-9806 SINGLE GANG BOX 2 1/2" DEEP 7300-0026:0150 ENCAPSULATED RELAY SIMPLEX 4098-9843 SINGLE GANG BOX 2 1/8" DEEP W/COVER END-OF-LINE RESISTOR 3.3K (EOL) END-OF-LINE RESISTOR 4.7K (EOL) END-OF-LINE RESISTOR 6.8K (EOL) END-OF-LINE RESISTOR 10K (EOL) SIMPLEX 4081-9002 SIMPLEX 4081-9003 SIMPLEX 4081-9004 SIMPLEX 4081-9008 LINE ISOLATOR MODULE SIMPLEX 4090-9116 P 10K LIM ALARM DEVICE ADDRESS BRANCH/REPEATER DESIGNATOR (OPT.) (#) BRANCH, (E#:#) REPEATER:BRANCH A1:2-1(1) SPEAKER CIRCUIT A G B K L M RUI/N2 COMMUNICATION 1 PAIR 18 AWG TWISTED OVERALL SHIELD SG ANIX./PAIGE 740215 AREA=0.0196 SQ. INCH SG ANIX./PAIGE 740214L AREA=0.0196 SQ. INCH ANIXTER PART NUMBER T740215 ANIXTER PART NUMBER FAMC-1802C-1-2S-03B5 REMOTE TEST SWITCH/ LED CIRCUIT - (2) 2 CONDUCTOR 18 AWG SOLID SG ANIX./PAIGE 454703ARE AREA=0.0204 SQ. INCH ANIXTER PART NUMBER FA-1802C-1-1N-03-BX SG ANIX./PAIGE 740132R AREA=0.0141 SQ. INCH REMOTE LED CIRCUIT 2 CONDUCTOR 16 AWG SOLID SG ANIX./PAIGE 454731ARE AREA=0.0272 SQ. INCH ANIXTER PART NUMBER FA-1602C-1-1N-03-BX MAPNET/IDNET CIRCUIT 1 PAIR 18 AWG TWISTED OVERALL SHIELD H P R POWER CIRCUIT 2 CONDUCTOR 16 AWG SOLID (SUBSCRIPT "r" IF RESETTABLE) SITE PLAN - FIRE ALARM 1ST FLOOR PLAN - PHYSICAL EDUCATION BUILDING - FIRE ALARM 2ND FLOOR PLAN - PHYSICAL EDUCATION BUILDING - FIRE ALARM SG ANIX./PAIGE 454740ARE AREA=0.0208 SQ. INCH FA4.01 ONE-LINE DIAGRAM - FIRE ALARM ANIXTER PART NUMBER FA-1602C-1-2N-03 FA5.01 CONTROL PANEL DIAGRAM - FIRE ALARM FA6.01 FA6.02 CALCULATIONS - FIRE ALARM CALCULATIONS - FIRE ALARM FA7.01 FA7.02 FA7.03 FA7.04 DETAILS - FIRE ALARM DETAILS - FIRE ALARM DETAILS - FIRE ALARM DETAILS - FIRE ALARM ANIXTER PART NUMBER T740215 ANIXTER PART NUMBER FAMC-1802C-1-2S-03B5 SG ANIX./PAIGE 454731ARE AREA=0.0272 SQ. INCH SG ANIX./PAIGE 454740ARE AREA=0.0208 SQ. INCH (2) #14 AWG AREA=0.0097 SQ. INCH (EACH) SG ANIX./PAIGE 454719ARE AREA=0.0333 SQ. INCH ANIXTER PART NUMBER FA-1402C-1-2N-03 ANIXTER PART NUMBER FA-1602C-1-1N-03-BX ANIXTER PART NUMBER FA-1602C-1-2N-03 F REMARKS G ARCHITECT'S STAMP FIRE ALARM WIRING: SIGNALING LINE CIRCUIT (SLC) - CLASS B: SINGLE OPEN SINGLE GROUND WIRE-TO-WIRE SHORT THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. NOTIFICATION APPLIANCE CIRCUIT (NAC) - CLASS B: SINGLE OPEN SINGLE GROUND WIRE-TO-WIRE SHORT H CONSULTANT PROJECT CONTACT Vb WELLNESS CENTER SHEET INDEX E N G I N E E R I N G 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com WFA2.03 FLOOR PLANS - WELLNESS CENTER - FIRE ALARM J VISUAL/SIGNAL CIRCUIT - 2 CONDUCTOR 12 AWG STRANDED, UNSHEILDED DIRECT BURIAL/UNDERGROUND IN CONDUIT/AERIAL (REQUIRES MESSENGER) - CABLE CONDUIT ONLY: THWN (2) #12 AWG (RED/BLACK) AREA=0.0133 SQ. INCH (EACH) SPEAKER CIRCUIT - 1 PAIR 18 AWG TWISTED OVERALL SHIELD DIRECT BURIAL/UNDERGROUND IN CONDUIT/AERIAL (REQUIRES MESSENGER) - CABLE ANIXTER PART NUMBER 2AS-1801POS AREA=0.0615 SQ. INCH CONDUIT SIZE 1/2" 3/4" 1" 12 PRO F E S S I ON ON LA AS AL No. E16806 AT EL E CT RICA N E O OR F CAL I F 11 SYMBOLS LISTS, GENERAL NOTES AND SHEET INDEX FIRE ALARM PROJECT NO: 1089-0001 CONDUCTOR AREA 0.60 SQ INCH * 0.82 SQ INCH * 1.34 SQ INCH * CONDUIT SIZE CONDUCTOR AREA 1-1/4" 0.12 SQ INCH * 1-1/2" 0.21 SQ INCH * 2" 0.34 SQ INCH * * 40% FILL PER N.E.C. DATE: 1.12.2015 THE CABLES SPECIFIED HERE ARE FOR REFERENCE OF REQUIRED ELECTRICAL CHARACTERISTICS AS WELL AS CODE REQUIREMENTS. ALTERNATE SUPPLIERS MAY BE SUBSTITUTED PROVIDING EQUIVALENT CHARACTERISTICS ARE MAINTAINED. ITEMS SUCH AS CAPACITANCE BETWEEN CONDUCTORS AND WIRE GAUGE CAN BE CRUCIAL TO THE CIRCUIT DESIGN OF THIS SYSTEM INSTALLATION. REFERENCE https://www.anixter.com/customer/tycofs FOR SG ANIXTER CABLE DATA K D MAPNET/IDNET CIRCUIT - 1 PAIR 18 AWG TWISTED OVERALL SHIELD DIRECT BURIAL/UNDERGROUND IN CONDUIT/AERIAL (REQUIRES MESSENGER) - CABLE ANIXTER PART NUMBER 2A-1202 AREA=0.0820 SQ. INCH Sb 2014-0174 Joe Ripp INTERFACE ANIXTER PART NUMBER 2AS-1801POS AREA=0.0615 SQ. INCH J APPROVAL ST SG ANIX./PAIGE 454731ARE AREA=0.0272 SQ. INCH SG ANIX./PAIGE 454740ARE AREA=0.0209 SQ. INCH MISC. I NE ER ANIXTER PART NUMBER FA-1602C-1-2N-03 SUPERVISORY U (4) #16 AWG AREA=0.0072 SQ. INCH (EACH) WIRING THAT LEAVES THE BUILDING Mb FA1.01 FA2.01 FA2.02 SG ANIX./PAIGE 740214L AREA=0.0196 SQ. INCH SG ANIX./PAIGE 454718ARE AREA=0.0380 SQ. INCH ANIXTER PART NUMBER FA-1402C-1-1N-03-BX AUDIO CIRCUIT 1 PAIR 16 AWG TWISTED UNSHIELDED (2) #16 AWG AREA=0.0072 SQ. INCH (EACH) SYMBOLS LISTS, GENERAL NOTES AND SHEET INDEX - FIRE ALARM ANIXTER PART NUMBER FA-1802C-1-2N-03 SG ANIX./PAIGE 740215 AREA=0.0196 SQ. INCH ANIXTER PART NUMBER FA-1602C-1-1N-03-BX RELAY CIRCUIT 2 CONDUCTOR 14 AWG SOLID (4) #18 AWG AREA=0.0055 SQ. INCH (EACH) SHEET INDEX FA0.01 TROUBLE ENG S SINGLE CONDUCTOR(THHN,TFFN) E 7300-0026:0252 MANUAL PULL STATION AREA SMOKE DETECTOR SMOKE DETECTOR ELEV. LOBBY SMOKE DETECTOR ELEV. MACH. ROOM HEAT DETECTOR HEAT DETECTOR ELEV. MACH. ROOM DUCT MOUNTED SMOKE DETECTOR WATERFLOW SWITCH TAMPER SWITCH POST INDICATOR VALVE SWITCH SYSTEM RESET SIGNAL SILENCE AC POWER FAILURE FIRE ALARM SYSTEM LOW BATTERY SPEAKER DEVICE PLENUM RATED: FPLP SG ANIX./PAIGE 454725ARE AREA=0.0468 SQ. INCH ANIXTER PART NUMBER FA-1202C-1-2N-03 RISER RATED: FPLR CAUSE DEVICE DESIGNATOR S2-1 FIRE ALARM WIRE LIST DATE SEQUENCE OF OPERATION ADDRESSABLE DEVICES NUMBERING WIRE SCHEDULE ISSUE DEVICE ADDRESS CHANNEL DESIGNATOR ADDRESSABLE POWER SUPPLY (EPS, TPS) SG ANIX./PAIGE 454720ARE AREA=0.0491 SQ. INCH ANIXTER PART NUMBER FA-1202C-1-1N-03 4" SQUARE BOX 2 1/8" DEEP W/TWO GANG COVER M2-1 THE INSTALLING CONTRACTOR SHALL PROVIDE A RECORD OF COMPLETION PER NFPA 72, FIGURE 10.18.2.1.1. C D DEVICE ADDRESSING LEGEND ADDRESSABLE CARD (IDNET OR MAPNET) PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING NO. WP ABBREVIATIONS LEGEND SAN JOSE CITY COLLEGE SAN JOSE, CALIFORNIA WALL MOUNT MULTI-CANDELA STROBE ONLY, WHITE # = CANDELA RATING ADDRESSABLE NOTIFICATION DEVICE CIRCUIT DESCRIPTION ADDRESSABLE NOTIFICATION CIRCUIT 12 AWG SOLID UNSHIELDED TWISTED PAIR CSFM # BACKBOX AIM FIRE ALARM APPLICABLE CODES & STANDARDS CALIFORNIA FIRE CODE, 2013 EDITION, TITLE 24, PART 9 INSTALLATION OF THE SYSTEM SHALL NOT BE STARTED UNTIL DETAILED DESIGN DOCUMENTS AND SPECIFICATIONS, INCLUDING STATE FIRE MARSHAL LISTING NUMBERS FOR EACH COMPONENT OF THE SYSTEM, HAVE BEEN APPROVED BY DSA. MODEL# B DSA NOTES 2. DESCRIPTION HEAT SENSOR / BASE FIRE ALARM CABLE INSTALLED IN THE VERTICAL RUNS AND PENETRATE MORE THAN ONE FLOOR OR CABLES INSTALLED IN VERTICAL RUNS IN SHAFTS SHALL BE TYPE FPLR. D 1 A PROVIDE AND INSTALL A NEW AUTOMATIC AND MANUAL FIRE ALARM SYSTEM AS SHOWN ON DRAWINGS. FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP. APPLICABLE STANDARD AND CODES: 2013 NFPA 72 2013 CALIFORNIA FIRE CODE 2013 CALIFORNIA BUILDING CODE 2013 CALIFORNIA MECHANICAL CODE 2013 CALIFORNIA ELECTRICAL CODE 2 FIRE ALARM SYMBOLS LEGEND A-3 ASSEMBLY GROUP A-4 ASSEMBLY GROUP B BUSINESS GROUP S-1 STORAGE GROUP SPRINKLER PROTECTION: 3 SYMBOL KEY JURISDICTIONS WITHIN THE STATE MAY HAVE AMENDMENTS TO THE STATE ADOPTED CODE. CHECK WITH THE LOCAL JURISDICTION AUTHORITY FOR MORE DETAILS. 1. 4 L B 5 IA 1. 3. 6 SYSTEM DESCRIPTION / SCOPE OF WORK GENERAL NOTES A 7 J 9 RE 10 R EG I S T E 11 AL AR EF AL M A AR T F FEC A A L M A CP T AR T A M N AC SIG NU TIV N NC RE AT AL T IAT CA E A O OR CE U L EL L EL DIB NT EV EV LE RA L A A AC TO ATO ND MO TIV R P R T VIS NI AT OW O D IB TOR L E FIR ER ESI E AL ING G S TR EM HU NA AR ST OU AN NT TE MS ATI D 'S T O T TR BLE HA RIP FL HR N OU AT OO OU T IN R GO TR BLE FAC SI UT DE O U AT P BL A EL N E EV SI NU .C GN NC AB SU AL IAT PE O T O R SU RVI CE PE SO NT R RA SU RVI Y A LM PE SO T F R ON RV Y AC IT A P IS OR OR T A N IN Y N DI G SI UN SP ST GN C LA AT I AL AT DE Y IO O T C AC H N O R CE SH TIV ANG N A UT T E TR E O AL SY DOW AU F S MO ST N DIB TA NI EM H LE TU TO NO VAC AN S RI NG RM UN D V ST AL IT ISI BL AT E IO AL N AR MS 12 10 K SHEET NO: FA0.01 9 8 7 6 5 4 3 2 1 DSA SUBMITTAL 12 11 10 9 8 7 6 5 4 3 2 1 A # A B D H B Y SAN JOSE CITY COLLEGE PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING SAN JOSE, CALIFORNIA C C WV NO. ISSUE DATE PIV DCDA FH Mb D D FAA 1" FA CONDUIT 2" FA CONDUIT WELLNESS BUILDING VT T D Mb,Sb,Vb D D D 2" FA CONDUIT # WV Mb,Sb,Vb FACP # PHYSICAL EDUCATION BUILDING # E # # E # # # # # FH UP F F ∀ RAMP # # Α # LAMP G # G APPROVAL # ARCHITECT'S STAMP # THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. # THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H CONSULTANT 2014-0174 Joe Ripp J ON LA AS AL No. E16806 ST # AT EL L E CT RICA N E O OR F CAL I F IA # F E S S I ON I NE ER # 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com PRO U E N G I N E E R I N G D ENG INTERFACE RE CONTACT # # PROJECT R EG I S T E # # H # # J J # SITE PLAN - FIRE ALARM 1 SITE PLAN - FIRE ALARM 0' 20' 40' 1" = 20'-0" PROJECT NO: 1089-0001 DATE: 1.12.2015 K K SHEET NO: FA1.01 12 11 10 9 8 7 6 5 4 3 2 1 DSA SUBMITTAL 12 11 10 9 8 7 6 5 4 3 2 1 SHEET KEYNOTES A B A.5 C D E F F.2 G H J A VS AIM 1 WF AIM 1 PROVIDE (1) 2" CONDUIT TO WELLNESS CENTER. PROVIDE CONNECTION FROM 2" CONDUIT TO RESTROOM BUILDING VIA HANDHOLE, 2" CONDUIT, AND A WEATHERPROOF JUNCTION BOX. IF WELLNESS CENTER IS NOT CONSTRUCTED, CONDUIT AND WIRING TO STOP AT RESTROOM BUILDING. 2 MULLION MOUNT PULL STATION. USE MANUFACTURER'S SURFACE MOUNT BACK BOX AND CONCEAL WIRING WITHIN MULLION. A M1-17 M1-18 M1-32 AIM TO PIV Mb 2 P M1-13 P M1-4 STAFF LOCKER 30 105 1/2W C M A,M,S FAA OPEN OFFICE 102 A1:1-17(1) S1-18 MACH. ROOM 120 2A,B,M,P,2S 2A,B,M,P,2S M1-6 A,M,S MENS 106 OFFICE 103 DEAN'S OFFICE 104 1/2W 75 75 A,M,S 1/4W A1:1-16(1) S1-17 C A,M,S 1/4W HALL 167 WOMENS 107 C S1-16 1/4W A,M,S A1:1-15(1) S1-15 A1:1-14(1) S1-14 30 LOBBY 101 A,M,S C STAFF LOCKER 30 108 C OFFICE 110 OFFICE 109 1/2W EOL OFFICE 111 A1:1-13(1) S1-13 30 B A1:1-12(1) S1-12 C 1/4W M1-7 M1-8 M1-9 M1-10 M1-11 2A,M,2S 2A,B,M,P,2S ELEV. E1.1 PUBLIC MEN'S RESTROOM 126 A,M,S OFFICE 112 C 1/2W TICKETS/ CONCESSIONS 124 2A,B,M,P,2S AOM AOM AOM OPEN TO ABOVE M1-12 A1:1-18(1) S1-19 M1-5 AIM AOM 75 PUBLIC WOMEN'S RESTROOM 122 M B M RISER 123 A,M,S 75 OFFICE 113 PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING M1-3 P 3A,B,M,P,3S 2A,M,2S C A1:1-11(1) S1-11 1 1/2W Mb,Sb,Vb LIM TELECOM 125 SAN JOSE CITY COLLEGE SAN JOSE, CALIFORNIA M1-31 3A,B,M,P,3S 3 C C TO FACP 30 A,M,S S3-10 A,M,S 2W WG EOL WG 2W C A1:1-9(1) S1-9 15 A1:1-10(1) S1-10 NO. ISSUE DATE VEST. 128 A1:2-1(1) S2-1 C WP WP 1/2W WOMEN'S STUDENT RESTROOM 130 WOMEN'S STUDENT LOCKERS 3A,B,M,P,3S 129 S3-1 30 A,2S 1/2W 1/4W A,M,S MEN'S STUDENT LOCKERS 132 A,M,S 30 MEN'S STUDENT RESTROOM 131 A1:1-7(1) S1-7 1/2W WP 30 A,2S A,M,S C D A1:1-8(1) S1-8 WP 1/2W D 4 135 WG WG 2W S3-2 135 WG WG M1-22 WG P 2W S2-2 C A,M,S FACP OFFICE 135 S3-9 3A,B,M,P,3S 3A,B,M,P,3S P 1/4W M1-1 110 A,M,S A,M,S ELEC. 136 M M1-2 A1:1-1(1) S1-1 1/2W C EQUIPMENT STORAGE 133 A,M,2S 2A,M,P,2S E 2W 5 S3-8 2W SPECTATOR GYMNASIUM 160 WG E UP TO 2ND FLOOR WG S3-3 15 GYM EQUIPMENT 134 A1:2-2(1) S2-3 C 1/4W A,M,S A1:1-2(1) S1-2 A,M,S 1/4W 15 C TRAINING STAFF ROOM 139 S3-7 F M1-21 6 A,M,S 30 S3-4 WG 2W 135 P WG WG TRAINING ROOM 138 2W WG 135 WG A,M,2S C 1/2W A1:1-3(1) S1-3 A,M,2S 30 1/2W C A1:1-4(1) S1-4 F M P A,M,2S M1-19 2 S2-4 A,M,S C A,M,S 1/4W A,M,S 2W G 2W WG WG EAST CORRIDOR 137 S3-5 S3-6 30 1/2W MULTIPURPOSE CLASSROOM 141 A1:1-6(1) S1-6 A,2S C A,M,S G 30 C 1/2W A1:1-5(1) S1-5 7 ARCHITECT'S STAMP 15 M 1/4W 1/4W A1:2-17(1) S2-18 C SOUTH CORRIDOR 150 A,M,S C M1-16 A,M,S S2-13 A1:2-9(1) S2-11 C A,M,S C A,M,2S S2-6 M 1/4W M THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. A1:2-3(1) S2-5 C A,M,S 1/4W A,2S P 8 15 15 1/4W JAN. 140 M1-14 APPROVAL M1-20 P P THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. A,2S LAUNDRY 159 A,2S WP C A1:2-15(1) S2-16 15 1/2W VEST. 149 A1:2-4(1) A,2S 15 A1:2-13(1) S2-14 C VEST. 144 H FOOTBALL LOCKER ROOM 146 1/2W A1:2-5(1) S2-7 A,M,2S PROJECT 30 A,2S A,2S WP 30 A1:2-16(1) S2-17 WP 1/2W 1/2W C EOL J A1:2-19(1) S2-20 C 1/2W C A1:2-8(1) S2-10 INTERFACE E N G I N E E R I N G P 1/2W A1:2-11(1) S2-12 MEN'S TEAM SHOWER 147 30 WP M M1-15 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com A1:2-6(1) S2-8 A1:2-14(1) S2-15 TEAM DRESSING ROOM 155 C TEAM DRESSING ROOM 148 WP 1/2W A,M,2S J 9 D PRO F E S S I ON ON LA AS AL No. E16806 ST HYDRONICS 157 15 A,M,2S 1/2W 2014-0174 Joe Ripp I NE ER A,S 30 A1:2-7(1) S2-9 CONTACT U A,2S 30 1/2W ENG C 15 CONSULTANT AT EL E CT RICA N E O OR F CAL I F L C A,2S 15 IA A1:2-18(1) S2-19 A1:2-10(1) MEN'S TEAM TOILETS 145 J 1/2W 15 15 RE C 15 15 R EG I S T E 1/2W H ELEC. 151 A1:2-12(1) WOMEN'S TEAM TOILETS 153 A,M,S 1ST FLOOR PLAN PHYSICAL EDUCATION BUILDING - FIRE ALARM PROJECT NO: 1089-0001 DATE: 1.12.2015 1 1ST FLOOR PLAN - PHYSICAL EDUCATION BUILDING - FIRE ALARM 0' 4' 8' 16' 1/8" = 1'-0" K K SHEET NO: FA2.01 12 11 10 9 8 7 6 5 4 3 2 1 DSA SUBMITTAL 12 11 10 A 9 B A.5 8 C 7 6 D 5 E F F.2 4 G 3 2 H 1 J A A 1 2 B B JANITOR 203 75 C 1/2W EOL 75 A2:1-8(1) S4-1 A,S C 1/2W A2:1-7(1) S4-2 SAN JOSE CITY COLLEGE P OPEN TO BELOW M1-28 M PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING ELEV. E1.1 M1-27 15 C SAN JOSE, CALIFORNIA A,S M 1/4W A2:2-1(1) S5-1 C C 3 NO. FITNESS CENTER 202 A,M,2S 75 1/2W 1/4W C 75 A2:1-5(1) S4-4 1/2W A,S ISSUE DATE A2:1-6(1) S4-3 A,S S5-2 M1-26 D D 1 AHU-2 FA7.01 4 ON ROOF A,M,2S A,M,P,S 15 110 1/2W 110 C SPECTATOR GYMNASIUM 160 1/4W A2:1-4(1) S4-5 C A2:2-2(1) S5-3 C A,2S 1/2W A2:1-1(1) S4-6 DOWN TO 1ST FLOOR A,M,2S E E A,M,P,S A,M,P,S OPEN TO BELOW 5 CORRIDOR 201 A,M,P,S A,M,P,S 1 FA7.01 M1-25 AHU-3 A,2S ON ROOF S5-4 C 1/4W F F A,M,P,S 6 15 C 1/4W A2:2-3(1) S5-5 A,2S 75 C C 1/2W A2:1-2(1) S4-7 A2:1-3(1) S4-8 A,M,P,S G 75 M1-29 1/2W G EXERCISE LAB 205 P ARCHITECT'S STAMP APPROVAL 7 M,P 1 FA7.01 8 75 AHU-1 A2:2-4(1) S5-6 THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. A,M,P,S 2W WP EOL THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. M1-30 H H CONSULTANT 2014-0174 Joe Ripp J J 9 4' 8' J AL EL L E CT RICA N E O OR F CAL I F IA AT 2ND FLOOR PLAN PHYSICAL EDUCATION BUILDING - FIRE ALARM PROJECT NO: 1089-0001 1 2ND FLOOR PLAN - PHYSICAL EDUCATION BUILDING - FIRE ALARM 0' ON LA AS No. E16806 ST 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com F E S S I ON I NE ER E N G I N E E R I N G PRO U INTERFACE D ENG TERRACE T1 RE CONTACT R EG I S T E PROJECT DATE: 1.12.2015 16' 1/8" = 1'-0" K K SHEET NO: FA2.02 12 11 10 9 8 7 6 5 4 3 2 1 DSA SUBMITTAL 12 11 10 9 8 7 6 5 4 3 2 1 GENERAL SHEET NOTES A A. A ONE-LINE DIAGRAM IS DIAGRAMMATIC. REFER TO FLOOR PLANS FOR EXACT NUMBER AND LOCATION OF DEVICES AND APPLIANCES. SHEET KEYNOTES 1 IF WELLNESS CENTER IS NOT CONSTRUCTED, WIRING AND CONDUIT IS TO STOP AT THE RESTROOM BUILDING. B B 10K 10K 10K P P P R K R K R K M1-25 M1-26 PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING M1-30 M ROOF PE BUILDING 2W 1/4W 1/4W 1/4W 1/4W SAN JOSE CITY COLLEGE ROOF PE BUILDING SAN JOSE, CALIFORNIA 1/4W SPEAKER CIRCUIT(S5) C C WP S5-6 1/2W 1/2W S5-5 1/2W S5-4 1/2W S5-3 1/2W S5-2 1/2W S5-1 1/2W S NO. 1/2W ISSUE DATE SPEAKER CIRCUIT(S3) C 10K C S3-8 C S3-7 C S3-6 C S3-5 C S3-4 S3-3 C S3-1 S3-2 S 75 15 C WP A2:2-4 A2:2-3 15 15 P CHANNEL 2 (A2:2) C A2:2-2 A2:2-1 A M D 75 75 C C A2:1-8 75 75 75 C C A2:1-7 75 A2:1-6 A2:1-5 75 C A2:1-4 A2:1-3 75 CHANNEL 1 (A2:1) C M1-27 A2:1-1 A2:1-2 D P P M1-28 M1-29 A 2ND FLOOR PE BUILDING 2ND FLOOR PE BUILDING P 2W 2W 2W 2W 2W 2W 2W 2W 2W 2W SPEAKER CIRCUIT(S4) M 10K S4-10 S4-9 S4-8 S4-7 S4-6 S4-5 S4-4 S4-3 S4-2 S4-1 S 1/2W 1/2W 1/4W 1/2W 1/2W 1/2W 1/2W 1/2W 1/4W 1/2W 1/2W 1/4W 1/2W 1/2W 1/4W 1/4W 1/4W 1/4W 6.8K 1/4W 1/4W SPEAKER CIRCUIT(S2) E 10K S2-20 S2-19 S2-18 1/2W 1/2W C 10K S1-19 S2-17 1/4W C S1-18 S2-16 S2-15 1/4W 1/4W C S1-17 S2-14 S2-13 1/2W 1/2W C S1-16 S1-15 S2-12 1/2W C S1-14 S1-13 S2-11 1/2W C S1-12 S2-10 S2-9 S2-8 1/2W 1/2W S2-7 1/2W 1/2W C C S1-11 S1-10 S2-6 1/2W C S1-9 S1-8 S2-5 1/2W C S1-7 S1-6 S2-4 S2-3 1/2W C 1/2W C S1-5 S2-2 S1-3 135 C WG S 135 WG WG A1:3-2 P P P M1-22 M1-21 M1-20 M1-19 C 135 A1:3-3 A1:3-4 P WF VS AIM AIM M1-18 M1-17 E P P P P M1-16 M1-15 M1-14 M1-13 M1-12 M SPEAKER CIRCUIT(S1) S1-1 S1-2 135 S 1/2W 1/2W C S1-4 S2-1 6.8K M1-1 P P P M1-2 M1-3 M1-4 AIM M1-5 M1-6 AOM M1-7 POWER MONITOR CHANNEL 3 (A1:3) AOM M1-8 M1-9 PRIMARY RECALL ALTERN RECALL AOM AOM M1-10 M1-11 HAT FLASH SHUNT TRIP WG A1:3-1 A 15 F 15 C A1:2-19 15 C A1:2-18 A1:2-9 75 C A1:2-17 30 15 C C WP A1:2-14 A1:2-15 A1:2-16 30 C 30 15 JB JB C A1:2-12 A1:2-13 15 15 A1:2-11 30 C A1:2-10 A1:2-9 C A1:2-8 75 30 C JB C WP A1:2-6 A1:2-7 15 A1:2-4 A1:2-5 15 15 15 C C C A1:2-3 CHANNEL 2 (A1:2) F A,S A1:2-1 A1:2-2 CHANNEL 3 (A2:3) A A1:1-18 30 30 75 30 C C C C A1:1-17 A1:1-16 A1:1-15 75 A1:1-14 A1:1-13 75 30 75 C C C A1:1-12 A1:1-11 75 30 75 WP A1:1-10 WP A1:1-9 A1:1-8 A1:1-7 30 30 30 30 30 15 110 C C C C C C C A1:1-6 A1:1-5 A1:1-4 A1:1-3 A1:1-2 CHANNEL 1 (A1:1) M A1:1-1 LIM A 1 M1-31 FIBER DATA JACK 4100ES TRANSMITTER G TO EXISTING CAMPUS NETWORK FIBER Y FUTURE TO WELLNESS CENTER VIA PULL BOX AT RESTROOM BUILDING TO/FROM CAMPUS FA NETWORK G FROM EXISTING CAMPUS NETWORK Y ARCHITECT'S STAMP 120 VOLT AC APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. CAT5 CABLE ETHERNET DROP TERMINATE W/RJ-45 FEMALE JACK THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. 1ST FLOOR PE BUILDING 1ST FLOOR PE BUILDING H H CONSULTANT 2014-0174 Joe Ripp J J J AL AT EL L E CT RICA N E O OR F CAL I F IA NO SCALE ON LA AS No. E16806 ST 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com F E S S I ON I NE ER E N G I N E E R I N G PRO U 1 ONE-LINE DIAGRAM - FIRE ALARM D ENG INTERFACE RE CONTACT R EG I S T E PROJECT ONE-LINE DIAGRAM - FIRE ALARM PROJECT NO: 1089-0001 DATE: 1.12.2015 K K SHEET NO: FA4.01 12 11 10 9 8 7 6 5 4 3 2 1 DSA SUBMITTAL 12 11 10 9 8 7 6 FROM EXISTING CAMPUS NETWORK 5 J2 U1 3 2 1 SYSTEM CONDUIT, 3/4" MIN. (2" SHOWN) REFER TO MOUNTING DETAIL FOR TYP. CONDUIT PENETRATION LOCATIONS TO EXISTING CAMPUS NETWORK J2 4 U1 A A U3 U4 U3 DO NOT LOCATE POWER-LIMITED WIRING IN THE SHADED AREAS OF THE BACKBOX, THIS AREA IS RESERVED FOR NON-POWER LIMITED CIRCUITRY SUCH AS AC POWER, BATTERIES AND CITY CONNECTION. U4 24 4100-6057 FIBER OPTION BD. J1 1 2 39 40 RCV 4100-6057 FIBER OPTION BD. 1 2 J1 39 40 XMIT TO LCD ANNUNCIATOR LOBBY 101 4100-6078 DAUGHTER CARD INSTALLED IN SLOT J1 FOR NETWORK INTERFACE CA A FERRITE BEAD TB3 SHLD RUI A+ RUI A- RTS RCV RUI B- XMIT R- GND OV-1 R+ RSRVD B+ B+ BIDNAC 3 B- AUX POWER +24 OV A TO 1ST FLOOR GYM (A1:3) CLICK HERE TO ADJUST CH3 CKTS CLICK HERE TO ADJUST CH2 CKTS SAN JOSE CITY COLLEGE NETWORK/RS232 DAUGHTER CARD CPU DAUGHTER CARD 1 2 4 6 8 5 16 4 32 3 64 2 9600/OFF 1 P7 ENHANCED TA POWER SUPPLY 120VAC 60Hz 7 P6 C SAN JOSE, CALIFORNIA CA SW1 SW4 8/OFF 7 6 5 4 3 2 1 PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING P 8 Lamp Test CLICK HERE TO ADJUST CH1 CKTS B- 7 Auto B+ BIDNAC 2 6 Off Disarm Next B+ 5 Disable P4 OV P5 RUI B- 4 On Arm 24V B+ BIDNAC 1 B TB4 3 Menu Enable MOUNTS ON BRACKET P3 Previous TB3 TB2 TO 1ST FLOOR (A1:2) 2 More Info TB1 8 P8 COMM P2 Event Time 5 1 P1 4 CPU MOTHERBOARD 4100-6052 EVENT REPORTING DACT System Reset 3 ON Alarm Silence 2 NETWORK 1 2 3 RING RING2 HOUSE 2 Trouble Ack 1 B+ P6 TIP2 Supv Ack 5 RS232 TIP HOUSE 2 Priority 2 Ack Alarm Silenced AC Power 4 RUI B+ 3 CTS 2 GND 1 + RING RING1 HOUSE 1 Fire Alarm Ack SYSTEM WARNINGS Supervisory Trouble A TB2 - TIP HOUSE 1 TIP1 B ALARMS Fire Alarm Priority 2 Alarm TO 1ST FLOOR (A1:1) P7 POWER C IDNet+ 250 DEVICES SW3 P4 OV-2 GND L- RSRVD 24C PIEZO GND RCV RTS XMIT CTS RUI CONNECTOR RUI CONNECTOR 4100 COMM P3 5 4 3 2 RECT (+) NO. IDNet B+ P2 SW1 SHLD R RS232 IDNet B- P5 P5 1 2 3 RECT (-) SHIELD JUMPER P1 IDNet A- CLICK HERE TO ADJUST IDNet CKT IDNet A+ L+ P4 RSRVD NETWORK SW2 P6 EARTH FAULT JUMPER 1 ISSUE DATE BTRY (+) TB1 BTRY (-) TB1 P1 M FERRITE BEAD TO IDNET (M1) A TO 2ND FLOOR (A2:1) A TO 2ND FLOOR (A2:2) 4 3 A+ A- + - 2 1 B- 5 D PRIMARY2 STYLE 4 DAR DAR PRIMARY ONLY SECONDARY 4100-9621/-1311 DIGITAL AUDIO CONTROLLER 5 6 7 CA 8 TO WELLNESS CENTER (A2:3) P4 8 32 64 9600/OFF INPUT OPTION CARD PORT 2 16 SW1 MESSAGE MEMORY EXPANSION 4100-1241 8 MINUTE MESSAGE EXPANSION MODULE 4 1 G 3 4 Label Label Label 2 2 E G 1 2 P7 R Label Label Label A CLICK HERE TO ADJUST CH3 CKTS 1 3 G ON SW1 1 P6 8 R AUX POWER +24 OV 4100-5311 ENHANCED TA POWER SUPPLY 120VAC 60Hz 7 Label Label Label P4 P5 B- P 6 OV INPUT OPTION CARD PORT 1 5 24V B+ BIDNAC 3 CLICK HERE TO ADJUST CH2 CKTS 4 P3 G B+ 3 R B- 2 P2 Label Label Label B+ BIDNAC 2 P6 1 P1 G B+ TB4 ON R 5 R 4 G 6 Label Label Label B- CLICK HERE TO ADJUST CH1 CKTS 7 G B+ BIDNAC 1 8 R Label Label Label TB3 TB2 B+ Label Label Label Label Label TB1 + D 6 - TB2 B+ P11 CA IDNet+ 250 DEVICES R E P1 Label Label Label R LOCAL SPEAKER/MIC RECT (-) SHIELD JUMPER P1 G SHLD PTT (RED) MIC (WHT) RTN (BLK) MIC (WHT) 2 1 IDNet B+ 3 4 SHLD 4 5 IDNet B- TP SPEAKER CIRCUIT S3 TO SPEAKER CIRCUIT S2 TO SPEAKER CIRCUIT S1 5 IDNet A- 56 IDNet A+ REMOTE MICROPHONE 3 2 1 RECT (+) EARTH FAULT JUMPER BTRY (+) TB1 BTRY (-) TB1 S 10K S 10K 10K TO SPEAKER CIRCUIT S4 TO SPEAKER CIRCUIT S5 TO SPEAKER CIRCUIT S6 F F B- SHLD B+ B- SHLD B+ B- NAC NAC NAC CLICK HERE TO ADJUST CKT SHIELDS 1 CLICK HERE TO ADJUST 510X CKTS 2 3 4 NAC 5 6 7 NAC NAC CLICK HERE TO ADJUST CKT SHIELDS CLICK HERE TO ADJUST CKT WIRING 8 B- 8 B+ 7 B- 6 SHLD 5 B+ 4 B- 3 TB1 SHLD 2 1 2 3 4 5 6 7 8 9 10 11 12 B+ B- A+ A- B+ B- A+ A- B+ B- A+ ANAC 1 NAC 2 NAC 3 B+ 1 B+ TB1 CLICK HERE TO ADJUST CKT WIRING P1 P2 P3 24V OV P4 P5 P6 SW1 P7 1 CA P1 2 3 4 5 6 G 4100-1327 FLEX 50 WATT DIGITAL AMP 70V RMS 8 DIGITAL AUDIO DECODER DIGITAL AUDIO DECODER 7 4100-5101 XPS POWER SUPPLY 120VAC 60Hz AUX POWER CA OV - G 4100-1327 FLEX 50 WATT DIGITAL AMP 70V RMS +24 + ARCHITECT'S STAMP CA APPROVAL TB2 CONNECT TO 120VAC 60HZ THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. NEUTRAL MOUNTS TO BACKBOX BATTERY P4 P3 P2 - P1 + AC - + THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT J J J ON LA AS AL No. E16806 AT EL L E CT RICA N E O OR F CAL I F IA ST 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com F E S S I ON I NE ER E N G I N E E R I N G PRO U INTERFACE 50 Ah BATTERY 2081-9296 D ENG 50 Ah BATTERY 2081-9296 2014-0174 Joe Ripp RE CONTACT R EG I S T E PROJECT CONTROL PANEL DIAGRAM - FIRE ALARM PROJECT NO: 1089-0001 DATE: 1.12.2015 K K SHEET NO: FIRE ALARM CONTROL PANEL FA5.01 CABINET # 1 - FIRST FLOOR RECEPTION AREA B230 SCALE: NTS 12 11 10 9 8 7 6 5 4 3 2 1 DSA SUBMITTAL 12 11 10 9 8 7 6 5 4 3 2 1 A A 4100 FACP 1ST FLOOR ELECTRICAL ROOM 136 - EPS-1 CIRCUIT SUMMARY & VOLTAGE DROP 4100 FACP 1ST FLOOR ELECTRICAL ROOM 136 4100es FACP Standby B Module Qty Description Total Standby Current Alarm Current Total Alarm Channel C 4100-9311 1 4100 CONFIG. DOMESTIC 120V 0.4250 0.4250 0.7350 0.7350 4100-1327 2 DIGITAL FLEX 50W AMP W/3 NACS - 70V 0.0850 0.1700 2.2700 4.5400 4100-5101 1 EXPANSION PWR SUPPLY (XPS) - 120VAC 60HZ 0.0500 0.0500 0.0500 0.0500 4100-6057 2 NETWORK MEDIA CARD FIBER OPTIC 0.0250 0.0500 0.0250 0.0500 4100-5311 1 ENHANCED POWER SUPPLY, 3 CHANNELS, IDNet1+, 120V 0.2250 0.2250 0.4900 0.4900 4100-6078 1 NETWORK IF CARD, MODULAR 0.0460 0.0460 0.0460 0.0460 4100-9621 1 BASIC AUDIO WITH MICROPHONE - DIGITAL 0.0750 0.0750 0.0820 0.0820 4100-6052 1 EVENT REPORTING DACT 0.0300 0.0300 0.0400 0.0400 4100-1241 1 MESSAGE EXPANSION BOARD - 8 MINUTES 0.0020 0.0020 0.0170 0.0170 4100-1288 1 64/64 LED/SWITCH CONTROLLER 0.0200 0.0200 0.0200 0.0200 4100-1279 13 2" BLANK DISPLAY MODULE 0.0000 0.0000 0.0000 0.0000 * 4100-0634 1 POWER DISTRIBUTION MODULE 120V 0.0000 0.0000 0.0000 0.0000 4100-2320 1 AUDIO EXPANSION BAY KIT 0.0000 0.0000 0.0000 0.0000 4100-0636 1 BOX TO BOX HARNESS KIT 0.0000 0.0000 0.0000 0.0000 4100-1284 1 8 SW, 16 RED/GREEN LED MODULE 0.0000 0.0000 0.0240 0.0240 Panel Totals 1.0930 D 13 ADDRESSABLE SINGLE ACTION MANUAL STATION * 4090-9001 3 IDNET SUPERVISED IAM * 4090-9002 4 IDNET RELAY IAM * 4098-9714 24 TRUEALARM PHOTO SMOKE SENSOR 4098-9733 2 TRUEALARM HEAT SENSOR 4098-9756 3 TRUEALARM DUCT SMOKE SENSOR W/ RELAY OUTPUT * 4098-9792 26 TRUEALARM SENSOR BASE * Branch 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 Device Current Draw on the IDNet Addressable Channel(s) is included in the Battery Selection Set below. Device # A1:1-1 A1:1-2 A1:1-3 A1:1-4 A1:1-5 A1:1-6 A1:1-7 A1:1-8 A1:1-9 A1:1-10 A1:1-11 A1:1-12 A1:1-13 A1:1-14 A1:1-15 A1:1-16 A1:1-17 A1:1-18 From PANEL A1:1-1 A1:1-2 A1:1-3 A1:1-4 A1:1-5 A1:1-1 A1:1-7 A1:1-7 A1:1-9 A1:1-9 A1:1-11 A1:1-12 A1:1-13 A1:1-14 A1:1-15 A1:1-16 A1:1-17 Totals: ENCAPSULATED RELAY PAM-SD 0.0000 0.0000 0.0150 0.0450 4098-9756 3 TRUEALARM DUCT SMOKE SENSOR W/ RELAY OUTPUT 0.0030 0.0090 0.0150 0.0450 4906-9204 3 ADDRESSABLE CEILING MNT MC V/O, WHITE 15 0.0002 0.0006 0.0600 0.1800 4906-9253 1 ADDRESSABLE WALL MNT MC S/V, WHITE 75 0.0002 0.0002 0.1370 0.1370 4906-9254 3 ADDRESSABLE CEILING MNT S/V 25V/70VRMS WHITE 110 0.0002 0.0006 0.2400 0.7200 4906-9254 15 ADDRESSABLE CEILING MNT S/V 25V/70VRMS WHITE 15 0.0002 0.0030 0.0600 0.9000 4906-9254 13 ADDRESSABLE CEILING MNT S/V 25V/70VRMS WHITE 30 0.0002 0.0026 0.0920 1.1960 4906-9254 17 ADDRESSABLE CEILING MNT S/V 25V/70VRMS WHITE 75 0.0002 0.0034 0.1800 3.0600 49VO-WWFO-BA 6 VO, WALL MT, WHITE, FIRE LABEL, WEATHERPROOF WP75 0.0008 0.0048 0.2120 1.2720 49VO-WWF 4 VO, WALL MT, WHITE, FIRE LABEL 135 0.0008 0.0032 0.0290 0.1600 0.6400 8.2890 Distance (Feet) 30 37 18 24 27 25 30 46 17 46 21 117 17 39 25 39 25 21 604 Ft. Peripheral Totals Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices RUI Totals 0 Address Totals 49 Addresses Total Standby * Device Address current draw included below (See Additional Current Draws): 0.0000 3.0336 0.0000 0.0000 0.0392 0.0490 1.1612 Total Alarm Standby Standby Alarm Alarm Current Total Current Total Branch 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 17.4656 F EPS-1 EPS-2 0.7040 0.2320 5.6300 4.1880 XPS-3 0.1950 4.5650 1.1310 14.3830 0.0000 3.0336 Sub Total Additional Current Draws: Current for Conversion of Battery Voltage to 29 volt EPS IDNAC Devices MAPNET/IDNet Device Address Communication Current Spare addressable point capacity Standby Time = Alarm Time = 49 0% 24 15 0 Hrs Min x 0.000800 = 0.0392 Sub Total 1.1702 Total = 0.0000 1.1702 x 0.0008 0% + 20% + Minimum Battery Required 2081-9296 50AH (2x) Battery Supplied 2081-9296 50AH (2x) From PANEL A1:2-1 A1:2-2 A1:2-3 TAP1 A1:2-4 A1:2-4 A1:2-6 A1:2-7 TAP1 A1:2-9 A1:2-10 A1:2-9 TAP2 A1:2-12 TAP3 A1:2-13 TAP3 TAP3 TAP2 A1:2-17 A1:2-18 Totals: = 0.0490 Spare Capacity 604 663 394 23% 49% 79% B SAN JOSE CITY COLLEGE PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING Wire Res. Per Ft. Min. Device Voltage: 0.0019 23.vdc @ 75° Celsius Voltage Drop Voltage SAN JOSE, CALIFORNIA 29vdc Device Draw 0.2400 0.0600 0.0920 0.0920 0.0920 0.0920 0.0920 0.2120 0.0920 0.2120 0.1800 0.0920 0.1800 0.1370 0.0920 0.1800 0.0920 0.0920 Class B Calculations Current at Device 2.321 0.428 0.368 0.276 0.184 0.092 1.653 0.212 1.349 0.212 1.045 0.865 0.773 0.593 0.456 0.364 0.184 0.092 0.269 0.061 0.026 0.026 0.019 0.009 0.191 0.038 0.089 0.038 0.085 0.391 0.051 0.089 0.044 0.055 0.018 0.007 at Device 28.731 28.670 28.645 28.619 28.600 28.591 28.540 28.502 28.451 28.414 28.367 27.976 27.925 27.836 27.792 27.737 27.719 27.712 C Branch % Drop Branch 1: 4.44% NO. ISSUE DATE D Distance (Feet) 239 42 48 26 25 14 18 15 20 34 12 16 31 14 4 12 9 9 14 26 16 19 663 Ft. 20.7% 12ga 0.0019 23.vdc @ 75° Celsius Voltage Drop Voltage 29vdc Candela 15cd 15cd 15cd PID 4906-9254 4906-9254 4906-9254 JBOX 4906-9204 4906-9254 49VO-WWFO-BA 4906-9254 4906-9254 4906-9254 4906-9204 4906-9254 JBOX 4906-9204 JBOX 4906-9254 4906-9254 4906-9254 49VO-WWFO-BA 4906-9254 4906-9254 4906-9254 Wire Res. Per Ft. Min. Device Voltage: 15cd 15cd WP75 30cd 30cd 15cd 15cd 30cd 15cd 15cd 15cd 15cd WP75 15cd 15cd 15cd Device Draw 0.0600 0.0600 0.0600 0.0000 0.0600 0.0600 0.2120 0.0920 0.0920 0.0600 0.0600 0.0920 0.0000 0.0600 0.0000 0.0600 0.0600 0.0600 0.2120 0.0600 0.0600 0.0600 Class B Calculations Current at Device 1.540 1.480 1.420 1.360 0.516 0.060 0.396 0.184 0.092 0.844 0.152 0.092 0.632 0.452 0.392 0.120 0.060 0.060 0.212 0.180 0.120 0.060 1.421 0.240 0.263 0.136 0.050 0.003 0.028 0.011 0.007 0.111 0.007 0.006 0.076 0.024 0.006 0.006 0.002 0.002 0.011 0.018 0.007 0.004 at Device 27.579 27.339 27.076 26.940 26.890 26.887 26.862 26.852 26.845 26.829 26.822 26.816 26.753 26.729 26.723 26.717 26.715 26.721 26.711 26.735 26.728 26.723 Branch % Drop E Branch 1: 7.89% F 17.4656 x 0.001 A1:3 = 0.0000 17.4656 Distributed Load Voltage Drop Allowable % Drop: Wire Gauge: Starting Voltage: 0.0000 Branch 1 1 1 1 32.4512 Battery Discharge Factor = Wire Length Distributed Load Voltage Drop = 28.0848 Standby Ah = 4.3664 Alarm Ah 32.4512 x 1.1702 0.25 x 17.4656 G Additional Spare Battery Capacity = x 0.001000 Device # A1:2-1 A1:2-2 A1:2-3 TAP1 A1:2-4 A1:2-5 A1:2-6 A1:2-7 A1:2-8 A1:2-9 A1:2-10 A1:2-11 TAP2 A1:2-12 TAP3 A1:2-13 A1:2-14 A1:2-15 A1:2-16 A1:2-17 A1:2-18 A1:2-19 20.7% 12ga Candela 110cd 15cd 30cd 30cd 30cd 30cd 30cd WP75 30cd WP75 75cd 30cd 75cd 75cd 30cd 75cd 30cd 30cd Allowable % Drop: Wire Gauge: Starting Voltage: 2. Backup Amplifier assumes Main Amplifier alarm current on failure. Battery Set #1 (Cabinet/Charger #1) Select ALL Power Supplies on this battery set: PID 4906-9254 4906-9254 4906-9254 4906-9254 4906-9254 4906-9254 4906-9254 49VO-WWFO-BA 4906-9254 49VO-WWFO-BA 4906-9254 4906-9254 4906-9254 4906-9253 4906-9254 4906-9254 4906-9254 4906-9254 A1:2 Notification Appliances E Unit Load* 18 19 4 Notification SLC Distributed Load Voltage Drop Miscellaneous Peripheral Devices That May Require System Power 3 4.44% 7.89% 2.13% Allowable % Drop: Wire Gauge: Starting Voltage: 6.0940 4098-9843 % Drop A1:1 IDNet Addressable Devices (SLC) 4099-9004 1ST FLOOR 1ST FLOOR 1ST FLOOR GYM A1:1 A1:2 A1:3 Panel Equipment Alarm Current 2.321A 1.540A 0.640A Description 6.4902 38.9414 Device # A1:3-1 A1:3-2 A1:3-3 A1:3-4 From PANEL A1:3-1 A1:3-2 A1:3-3 Totals: Distance (Feet) 105 55 180 54 394 Ft. 20.7% 12ga 0.0019 23.vdc @ 75° Celsius 29vdc Candela 135cd 135cd 135cd 135cd PID 49VO-WWF 49VO-WWF 49VO-WWF 49VO-WWF Wire Res. Per Ft. Min. Device Voltage: Device Draw 0.1600 0.1600 0.1600 0.1600 Class B Calculations Current at Device 0.640 0.480 0.320 0.160 G Voltage Drop 0.259 0.102 0.222 0.033 Voltage at Device 28.741 28.639 28.416 28.383 Branch % Drop Branch 1: 2.13% ARCHITECT'S STAMP APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT 2014-0174 Joe Ripp J ON LA AS AL I NE ER J J F E S S I ON No. E16806 AT EL L E CT RICA N E O OR F CAL I F IA ST 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com PRO U E N G I N E E R I N G D ENG INTERFACE RE CONTACT R EG I S T E PROJECT CALCULATIONS - FIRE ALARM PROJECT NO: 1089-0001 DATE: 1.12.2015 K K SHEET NO: FA6.01 12 11 10 9 8 7 6 5 4 3 2 1 DSA SUBMITTAL 12 11 10 9 8 7 6 5 4 3 2 1 A A IDNET CHANNEL M1 Address Device Type 4100 FACP 1ST FLOOR ELECTRICAL ROOM 136 - EPS-2 CIRCUIT SUMMARY & VOLTAGE DROP Alarm Current 1.592A 0.392A 1.714A Description Channel 2ND FLOOR 2ND FLOOR WELLNESS CENTER A2:1 A2:2 A2:3 % Drop 3.15% 0.67% 7.12% A2:1 B Device # A2:1-1 A2:1-2 A2:1-3 A2:1-4 A2:1-5 A2:1-6 A2:1-7 A2:1-8 From PANEL A2:1-1 A2:1-2 A2:1-3 A2:1-1 A2:1-5 A2:1-6 A2:1-7 Totals: C Distance (Feet) 103 26 51 24 51 29 30 29 343 Ft. 20.7% 12ga Spare Capacity 343 215 479 47% 87% 43% Wire Res. Per Ft. Min. Device Voltage: 0.0019 23.vdc @ 75° Celsius Device Draw 0.2400 0.2400 0.1800 0.1800 0.1800 0.1800 0.1800 0.2120 Class B Calculations Current at Device 1.592 0.600 0.360 0.180 0.752 0.572 0.392 0.212 Voltage Drop Voltage Branch % Drop at Device 28.367 28.307 28.236 28.219 28.219 28.155 28.110 28.086 0.633 0.060 0.071 0.017 0.148 0.064 0.045 0.024 Branch 1: 3.15% Device # TAP1 A2:2-1 A2:2-2 A2:2-3 A2:2-4 From PANEL TAP1 A2:2-1 TAP1 A2:2-3 Totals: Distance (Feet) 84 18 41 41 31 215 Ft. PID JBOX 4906-9254 4906-9254 4906-9254 49VO-WWFO-BA 20.7% 12ga 0.0019 23.vdc @ 75° Celsius 29vdc Candela 15cd 15cd 15cd WP75 Device Draw 0.0000 0.0600 0.0600 0.0600 0.2120 Class B Calculations Current at Device 0.392 0.120 0.060 0.272 0.212 Voltage Drop Voltage Branch % Drop at Device 28.873 28.865 28.855 28.830 28.804 0.127 0.008 0.009 0.043 0.025 Branch 1: 0.67% D A2:3 Distributed Load Voltage Drop Allowable % Drop: Wire Gauge: Starting Voltage: 20.7% 12ga Wire Res. Per Ft. Min. Device Voltage: 0.0019 23.vdc 1 2 3 4 5 6 7 8 PHOTO SMOKE 1ST FLR ELEC 136 X M1-2 ADRPUL PULL 1ST FLR ELEC 136 X M1-3 ADRPUL PULL 1ST FLR TICKETS/CONCESSION 124 X X M1-4 ADRPUL PULL 1ST FLR MACH RM 120 X X M1-5 HEAT HEAT 1ST FLR MACH RM 120 X M1-6 PHOTO SMOKE 1ST FLR MACH RM 120 X M1-7 IAM SUPERV 1ST FLR MACH RM 120 POWER MONITOR M1-8 RIAM PRIMARY M1-9 RIAM M1-10 RIAM RIAM @ 75° Celsius X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X 1ST FLR MACH RM 120 PRIMARY RECALL X X X ALTERN 1ST FLR MACH RM 120 ALTERN RECALL X X X RELAY 1ST FLR MACH RM 120 HAT FLASH X 1ST FLR MACH RM 120 SHUNT TRIP X RELAY PHOTO SMOKE M1-13 ADRPUL M1-14 X X X X X X X X X X X X X X X 1ST FLR ELEV E1.1 LOBBY X PULL 1ST FLR HALL 137 X ADRPUL PULL 1ST FLR EAST CORRIDOR 137 X M1-15 ADRPUL PULL 1ST FLR FOOTBALL LOCKER RM 146 X X X X M1-16 ADRPUL PULL 1ST FLR SOUTH CORRIDOR 150 X X X X X X M1-17 IAM SO 1ST FLR LAUNDRY 159 X M1-18 IAM WATER 1ST FLR LAUNDRY 159 X M1-19 ADRPUL PULL 1ST FLOOR TRAINING ROOM138 X X M1-20 ADRPUL PULL 1ST FLOOR MULTIPURPOSE 141 X X X M1-26 RPHOTO DUCT M1-27 PHOTO SMOKE X X X X X X X X X X X X X M1-24 X 2ND FLR FITNESS CENTER 202 AHU-3 X X X X DUCT X X X M1-23 RPHOTO X X M1-22 2ND FLR FITNESS CENTER 202 AHU-2 X 2ND FLR ELEV E1.1 LOBBY X M1-28 ADRPUL PULL 2ND FLR CORRIDOR 201 X M1-29 ADRPUL PULL 2ND FLR CORRIDOR 201 X M1-30 RPHOTO DUCT 2ND FLR AHU-1 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X M1-31 X X X X X M1-32 X X X X X M1-33 X X X X X X M1-34 X M1-35 X X M1-36 X X M1-37 X M1-38 X M1-39 X X X X X X X X X X X X X X X X X X X X X X M1-40 X X X M1-248 X X X X X M1-249 THRU X SPARE M1-250 29vdc X X M1-12 M1-25 Wire Res. Per Ft. Min. Device Voltage: Location Description M1-21 Distributed Load Voltage Drop Allowable % Drop: Wire Gauge: Starting Voltage: Point Type M1-1 M1-11 29vdc Candela 110cd 110cd 75cd 75cd 75cd 75cd 75cd WP75 PID 4906-9254 4906-9254 4906-9254 4906-9254 4906-9254 4906-9254 4906-9254 49VO-WWFO-BA A2:2 Branch 1 1 1 1 1 Wire Length Notification SLC Distributed Load Voltage Drop Allowable % Drop: Wire Gauge: Starting Voltage: Branch 1 1 1 1 1 1 1 1 Unit Load* 8 4 11 SWITCH SETTINGS X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X ON ON ON ON ON ON ON ON ON ON ON B ON ON ON ON ON SAN JOSE CITY COLLEGE ON PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING ON ON ON ON SAN JOSE, CALIFORNIA ON ON ON ON C ON ON ON NO. ISSUE DATE ON ON ON ON ON ON ON ON ON ON D ON ON X X X X X ON X X X X X ON X X X X X ON NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES. THE LABELS ARE BASED UPON INFORMATION SHOWN ON THE ARCHITECTURAL DRAWINGS. ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING. Branch % Drop at Device 27.677 27.576 27.425 27.293 27.247 27.156 27.088 27.027 26.983 26.955 26.934 27.059 POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES. Branch 1: 7.12% E 4100 FACP 1ST FLOOR ELECTRICAL ROOM 136 4100es FACP Speaker Db Loss Calculations *Circuit Voltage = 70vrms [Et] SPEAKER CIRCUIT DESCRIPTION Amp # Amp-1 Amp-1 Amp-1 Amp-2 Amp-2 Amp-2 F 1ST FLOOR 1ST FLOOR 2ND FLOOR 1ST FLOOR GYM 2ND FLOOR WELLNESS CENTER Amplifier Wattage Amp-1 Amp-2 50 50 IDNET CHANNEL M2 Address Device Type MAXIMUM -3 dB DROP Watts Used 20.W 27.75W Alarm Expansion 2.270A 2.270A Card? Yes Yes Avail. Ckts. 6 6 Plan Circuit Number S1 S2 S3 S4 S5 S6 Used Ckts. 4 3 Speaker Tap .25 Watt 5 9 5 2 Speaker Tap .5 Watt 14 11 8 Speaker Tap 1. Watt Speaker Tap 2. Watt 10 1 6 1 SWITCH SETTINGS Point Type Location Description 1 2 3 4 5 6 7 8 Total Total Wire Est. Ckt. Wire Res. Circuit Speaker Speaker Voltage Watts Actual Max Allowable M2-1 ADRPUL PULL 1ST FLR WELLNESS CNTR VEST 10 X Spkrs per Circuit 19 20 8 10 6 9 Watts [P] Gauge Length [D] in Feet Per Foot [Rw] Resistance [Rl=2D*Rw] Current [I=P/Et] Resistance [Rs=Et/I] At End At End dB Loss [dB=Log10 Ckt. Length M2-2 PHOTO SMOKE 1ST FLR WELLNESS CNTR VEST 10 X 1ST FLR WELLNESS CNTR VEST 115 X 8.25 Watts 7.75 Watts 4. Watts 20. Watts 3.25 Watts 4.5 Watts 16ga 16ga 16ga 16ga 16ga 16ga 620 680 447 410 158 500 0.0049 0.0049 0.0049 0.0049 0.0049 0.0049 6.064 6.650 4.372 4.010 1.545 4.890 0.118 0.111 0.057 0.286 0.046 0.064 593.939 632.258 1225.000 245.000 1507.692 1088.889 [Es=(Et*Rs) [Pe=(Es) [ML=(0.414*Rs) *2/Rs] /(Rs+Rl)] (Pe/P)*10] /(2*Rw)] 69.293 8.084 -.09 db 25142 69.271 7.590 -.09 db 26764 69.751 3.972 -.03 db 51856 68.873 19.361 -.14 db 10371 69.928 3.243 -.01 db 63823 69.687 4.460 -.04 db 46094 M2-3 Ft. Ft. Ft. Ft. Ft. Ft. PHOTO SMOKE 1ST FLR WELLNESS CNTR VEST 115 X M2-5 PHOTO SMOKE 1ST FLR WELLNESS CNTR TOILET 14 X M2-6 PHOTO SMOKE 1ST FLR WELLNESS CNTR TOILET 13 X M2-7 HEAT HEAT 1ST FLR WELLNESS CNTR JANITOR 12 X H PHOTO SMOKE MEZZANINE WELLNESS CNTR STORAGE 22 X X X X X X X X X X X X X X X X X X X X X PHOTO SMOKE MEZZANINE WELLNESS CNTR MECH 24 M2-10 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 16 X M2-11 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 16 X X M2-12 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 16 X X M2-13 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 16 X SMOKE X X M2-9 PHOTO X X X M2-14 G PULL M2-4 M2-8 % Used 40.00% 55.50% ADRPUL X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X MEZZANINE WELLNESS CNTR EXERCISE LAB 16 X X X X X X X X X X X X X X M2-15 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 16 X M2-16 PHOTO SMOKE MEZZANINE WELLNESS CNTR STORAGE 22 X M2-17 PHOTO SMOKE MEZZANINE WELLNESS CNTR MECH 27 X M2-18 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 X M2-19 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 X M2-20 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 X M2-21 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 X M2-22 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 X M2-23 PHOTO SMOKE MEZZANINE WELLNESS CNTR EXERCISE LAB 11 X X X X X X X X X X X M2-24 X X X M2-25 X X X M2-26 X M2-27 X M2-28 X M2-29 X M2-30 X M2-249 X THRU X SPARE M2-250 X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X ON ON ON F ON ON ON ON ON ON ON ON ON ON ON ON ON ON G ON ON ON ARCHITECT'S STAMP ON APPROVAL ON ON THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. ON ON ON THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. ON X X X X X X X X X X X X X X X X ON X X X X ON ON ON ON H CONSULTANT NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES. THE LABELS ARE BASED UPON INFORMATION SHOWN ON THE ARCHITECTURAL DRAWINGS. ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING. PROJECT CONTACT 2014-0174 Joe Ripp J J AL No. E16806 ST 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com ON LA AS I NE ER E N G I N E E R I N G F E S S I ON U INTERFACE PRO ENG POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES. D AT EL E CT RICA N E O OR F CAL I F L Totals: 15cd 75cd 75cd 75cd 75cd 1.323 0.101 0.152 0.131 0.046 0.091 0.068 0.061 0.044 0.028 0.021 0.029 Voltage IA PANEL A2:3-1 A2:3-2 A2:3-3 A2:3-4 A2:3-5 A2:3-6 TAP1 A2:3-7 A2:3-8 A2:3-9 TAP1 Candela 75cd 75cd 75cd 75cd 75cd 15cd PID 4906-9254 4906-9254 4906-9254 4906-9254 4906-9254 49VO-WWF JBOX 49VO-WWF 4906-9254 4906-9254 4906-9254 4906-9254 Voltage Drop J From Class B Calculations Current at Device 1.714 1.534 1.354 1.174 0.994 0.814 0.767 0.587 0.540 0.360 0.180 0.180 RE E Device # A2:3-1 A2:3-2 A2:3-3 A2:3-4 A2:3-5 A2:3-6 TAP1 A2:3-7 A2:3-8 A2:3-9 A2:3-10 A2:3-11 Device Draw 0.1800 0.1800 0.1800 0.1800 0.1800 0.0470 0.0000 0.0470 0.1800 0.1800 0.1800 0.1800 R EG I S T E Branch 1 1 1 1 1 1 1 1 1 1 1 1 Distance (Feet) 200 17 29 29 12 29 23 27 21 20 30 42 479 Ft. CALCULATIONS - FIRE ALARM PROJECT NO: 1089-0001 DATE: 1.12.2015 K K SHEET NO: FA6.02 12 11 10 9 8 7 6 5 4 3 2 1 DSA SUBMITTAL 12 11 10 9 8 7 6 5 PRODUCT INFORMATION FEATURES: DETAIL 1 KEYNOTES 1 AIR HANDLING UNIT (AHU) STARTER/VFD. 1 AIR HANDLING UNIT (AHU) STARTER/VFD. 2 FIRE ALARM ADDRESSABLE RELAY. CONNECT TO EMERGENCY STOP INPUT ON FAN CONTROLLER. PROGRAM TO STOP FAN ON ACTIVATION OF ASSOCIATED SMOKE DETECTION. PROVIDE RELAY FOR EACH FAN CONTROLLER. 2 FIRE ALARM ADDRESSABLE RELAY. CONNECT TO EMERGENCY STOP INPUT ON FAN CONTROLLER. PROGRAM TO STOP FAN ON ACTIVATION OF ASSOCIATED SMOKE DETECTION. PROVIDE RELAY FOR EACH FAN CONTROLLER. 3 FIRE ALARM ADDRESSABLE DUCT SMOKE DETECTOR. 3 FIRE ALARM ADDRESSABLE AREA SMOKE DETECTION SYSTEM. 4 FIRE ALARM ADDRESSABLE RELAY. DIGITAL INPUT TO BAS TO INITIATE ADDITIONAL AHU SHUT DOWN SEQUENCE. 4 FIRE ALARM ADDRESSABLE RELAY. DIGITAL INPUT TO BAS TO INITIATE ADDITIONAL AHU SHUT DOWN SEQUENCE. BAS CONNECTION TO FAN UNIT CONTROLLER. 5 B 5 FACP TrueAlert 2-WIRE ADDRESSABLE CONTROL OF VISIBLE AND AUDIBLE NOTIFICATION ACTIVATES APPLIANCES WITH: HORNS SOUNDED AS TEMPORAL OR MARCH TIME PATTERN, OR ON CONTINUOUSLY, CONTROLLED SEPARATELY FROM VISIBLE APPLIANCES ON THE SAME TWO-WIRE CIRCUIT TrueAlert NOTIFICATION APPLIANCE DESIGN PROVIDES FLEXIBLE, EASY, AND CONVENIENT FLUSH OR SURFACE WALL BOX MOUNTING FACP SPECIFICATIONS: 5 STROBE: RATED VOLTAGE RANGE: 23 TO 31 VRMS SUPERVISORY REQUIREMENTS: 1 UNIT LOAD STROBE FLASH RATE: 1 Hz 5 2 2 4 3 4 3 MODEL NUMBER 1 C 49VO-WRFO(-BA) 49VO-WWFO-BA 49VO-APPLW-O 1 PHYSICAL EDUCATION BUILDING WELLNESS CENTER BUILDING 49VO-APPLW-CO 49VO-WRFO-C HOUSING LETTERING VOLTAGE COLOR COLOR RED WHITE WHITE RED WP BACKBOX AND COVER ORDERED SEPARATELY RED 2 POSITION 1: CONFIGURATION CONTROL - LOCAL (OFF), PANEL (ON) POSITION 2: AUDIBLE VOLUME - HIGH (OFF), LOW (ON) POSITION 3: CANADIAN HORN MODE - SET TO OFF POSITION 4: LEGACY NAC MODE - SET TO OFF POSITION 5,6,7: UNUSED - SET TO OFF POSITION 8: CLEAR/COLOR LENS - ALARM (OFF), ALERT (ON) WHITE 23 VRMS 23 VRMS 23 VRMS VOLTAGE 23 VRMS 23 VRMS UL 1971 0°-49° C 75cd 0.160 0.160 0.160 ULC RATINGS 20cd 30cd 0.143 0.150 0.143 0.150 15cd 0.060 0.060 0.060 HOUSING DIMENSIONS (INCLUDING LENS): 5 1/8" H X 5" W X 2 5/8" D TEMPERATURE RANGE: -31° TO 120° F (-35° TO 49° C) HUMIDITY RANGE: 10% TO 93% NON-CONDENSING AT 104° F (40° C) CONNECTIONS: TERMINAL BLOCKS FOR 18 TO 12 AWG NO SCALE A IMPORTANT! WALL MOUNT INSTALLATION HEIGHT REFERENCE BOTTOM OF LENS IS EITHER EVEN WITH OR SLIGHTLY ABOVE BOTTOM OF COMPATABLE BOXES ELECTRICAL BOX OUTLINE WEATHER PROOF BOX 1-5/8" DEEP SIMPLEX 49WPBB-AVVOWR SIMPLEX 4905-9899 CONDUIT CUTOUTS ARE PROVIDED ON ALL FOUR SIDES. NFPA 72 REQUIRES THAT THE ENTIRE LENS BE NOT LESS THAN 80" AND NOT GREATER THAN 96" ABOVE THE FINISHED FLOOR. 80" MIN. MAGNETIC TEST LOCATION LSB RESERVED FOR FUTURE USE 1 2 3 4 5 6 7 8 B STROBE INTENSITY SETTING SAN JOSE CITY COLLEGE MOUNTING INSTRUCTIONS: DIP SWITCHES 5 & 6 0000 1000 0100 NOT 0=OFF 1=ON DIP SWITCHES 1100 USED 0010 1 THRU 4 1010 UL 1638 UL 1638 0110 1110 TO 0° C TO -35° C 0001 WP 75cd WP 185cd WP 75cd WP 185cd 1001 0.239 0.160 0.212 0.185 0101 0.239 0.160 0.212 0.185 1101 0.239 0.160 0.212 0.185 0011 1011 75cd 0111 0.168 1111 0.168 0000 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 1000 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 0100 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 1. SET THE APPLIANCE ADDRESS AND CONFIGURATION SETTINGS. 2. BRING THE BUILDING WIRING THROUGH THE RECTANGULAR OPENING IN THE APPLIANCE. 1100 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 3. ASSEMBLE THE HOUSING ONTO THE WEATHERPROOF BACKBOX ASSURING EVEN CONTACT WITH THE GASKET AROUND THE PERIPHERY. PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING 4. USING THE MOUNTING HOLES INDICATED IN THE FIGURE ABOVE, ASSEMBLE THE HOUSING TO THE BACKBOX. TIGHTEN THE SCREWS TO RECOMMENDED TORQUE SAN JOSE, CALIFORNIA 5. ASSEMBLE THE COVER TO THE WEATHERPROOF BACKBOX USING THE SCREWS PROVIDED. TIGHTEN THE SCREWS TO RECOMMENDED TORQUE. 49VO CKT + 49VO 2 1 FROM TrueAlert COMPATIBLE SLC CONTROLLER (SEE NOTES) CKT 49VO C 2 1 - (130 mm X 127 mm X 67 mm) WIRING NOTES: PCAF 51 57 57PW 581PW SURFACE MOUNTING TrueAlert V/O UNITS- DIP SWITCH ADDRESS CHART MSB INTENSITY SELECTION PLUG, ACCESSIBLE ONLY FROM REAR OF HOUSING; FACTORY SETTING IS FACP. CONTROLLED BY PANEL. ADDRESS SETTING DIP SWITCH GENERAL SPECIFICATIONS: 1 HVAC FAN SHUT DOWN DIAGRAM 1 DIP SWITCH ACCESSABLE FROM REAR APPLIANCE CONFIGURATION SETTINGS LED INDICATOR AND MAGNETIC TEST FEATURE: LED INDICTOR CAN BE ELECTED TO DISPLAY EACH POLLING CYCLE TO INDICICATE APPLIANCE SUPERVISION WHEN THE TrueAlert CONTROLLER IS IN DIAGNOSTIC MODE, THE MAGNETIC TEST PULSES THE LED TO INDICATE APPLIANCE ADDRESS AND IS SELECTABLE TO ALSO BRIEFLY FLASH THE STROBE TO CONFIRM OPERATION BAS CONNECTION TO FAN UNIT CONTROLLER. 3 TM TrueAlert ES (STYLE 4 SLC) VISIBLE ONLY NOTIFICATION APPLIANCES 49VO SERIES WEATHERPROOF CONFIGURATION INDIVIDUALLY ADDRESSED WALL MOUNT VISIBLE NOTIFICATION APPLIANCES WITH EFFICIENT ELECTRONIC HIGH INTENSITY XENON STROBE PROVIDES: SUPERVISION OF EACH INDIVIDUAL APPLIANCE'S WIRING AND CONNECTIONS ABILITY TO CONNECT USING "T" TAPPING FOR CLASS B/STYLE 4 CIRCUITS TO SIMPLIFY WIRING HORNS CONTROLLED SEPARATELY FROM STROBES ON THE SAME 2-WIRE CIRCUIT ALLOWING "ON-UNTIL-SILENCED" AND "ON-UNTIL RESET". XENON STROBE OUTPUT IS MANUALLY SELECTABLE FOR 15, 30, 75, 110, 135 AND 185 CANDELA OR "FACP". THE "FACP" SETTING ALLOWS THE 4100 TO PROGRAM THE CANDELA SETTING. IN/OUT WIRING ACCESSIBILITY FROM FRONT OF HOUSING PROVIDES EASY ACCESS FOR INSTALLATION, INSPECTION, AND TESTING MAGNETIC TEST DIAGNOSTICS TO ASSIST CHECKOUT AND TESTING OF APPLIANCES AND WIRING UL LISTED TO STANDARD 1971 A DETAIL 1 KEYNOTES 4 2 1 + SLC - SLC SLC + SLC + 49VO CKT 1 + - NO. 49VO 1 2 CKT + - SLC - SLC - SLC + SLC + ISSUE DATE 2 CKT + 1. REFER TO FIELD WIRING DIAGRAMS OF THE DRIVING TrueAlert COMPATIBLE CONTROLLER FOR ADDITIONAL SLC WIRING INFORMATION. 2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. 3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS. 4. ALL TrueAlert SLC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED. 5. POWERING THE V/O FROM AN APPLIANCE POWER SOURCE LESS THAN 17 VDC OR GREATER THAN 32 VDC MAY CAUSE PERMANENT DAMAGE. TO THE V/O UNIT. 6. THE TrueAlert V/O CAN ONLY BE OPERATED THROUGH A 4009 TrueAlert ADDRESSABLE CONTROLLER OR TrueAlert COMPATIBLE FACP. D D 4603-9101 REMOTE ANNUNCIATOR ET-1010/ET-1011 SPEAKER ASSEMBLY PRODUCT INFORMATION FEATURES: UL LISTED FM APPROVED FLUSH MOUNT ON STANDARD ELECTRICAL BOXES 4.09 4.29 SPECIFICATIONS: VOLTAGE: 24VDC NOMINAL CURRENT: ALARM 140mA SUPERVISORY 65mA OPERATING TEMPERATURE: 32° F TO 120° F HUMIDITY RANGE: 10% TO 90% RH FROM 32° F TO 104° F STANDARD TRIM: BEIGE (SUPPLIED WITH BOTH SLOTTED AND TAMPERPROOF SCREWS) E E OPTIONS 4.29 BRUSHED ALUMINUM TRIM: 4603-9111 SURFACE BOX: 2975-9206 DIMENSIONS 11 31/32"L X 4 5/8" W X 2 3/4"D FINISH: LIGHT BROWN ENAMEL TO FLUSH-MOUNT IN MASONRY WALLS, USE A A RAYCO 965 (3-1/2" DEEP) MASONRY BOX OR ITS EQUIVALENT. TO FLUSH-MOUNT IN PLASTERBOARD WALLS, USE A STEEL CITY GW-635-G OR A RAYCO EQUIVALENT. TO SURFACE-MOUNT, USE A SIMPLEX 2975-9206 BACK BOX NOTES: TO ADDITIONAL 24VDC POWERED DEVICES IF USED FROM 24 VDC POWER SOURCE 4.29 + TB1 - + - - TB2 - + TO NEXT SPEAKER OR END OR LINE RESISTOR (EOLR) F + F FROM PRECEDING SPEAKER OR FIRE ALARM CONTROL PANEL (FACP) FLUSH MOUNTING 1. ALL WIRING TO BE No. 18 AWG OR TO LOCAL CODE. 2. ALL WIRING SUPERVISED 3. WIRE TO BE 18 AWG TWISTED SHIELDED PAIR RECOMMENDED CONSULT SALES ENGINEERING FOR EXCEPTIONS. 2500 FT ONE WAY MAX COMMUNICATION LINE POWER 32 VDC MAX 130 mA MAX 1200 OR 9600 BAUD 4. WHEN WIRING LEAVES THE BUILDING, OVER VOLTAGE PROTECTORS ARE REQUIRED; USE 2081-9044 ONE IS INSTALLED WHERE IT LEAVE THE BUILDING AND ONE WHERE IT ENTERS THE NEXT BUILDING. TWO 2081-9044 (MAX) 4.29 S S FROM PREVIOUS RUI DEVICE OR FIRE ALARM CONTROL PANEL OF F COM + TO NEXT RUI DEVICE OR RETURN TO FIRE ALARM CONTROL PANEL IN STYLE 6 SYSTEM ON G G FOR RUI ADDRESSABLE SETUP SEE INSTALLATION INSTRUCTIONS 579- ARCHITECT'S STAMP APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. H H CONSULTANT 2014-0174 Joe Ripp J ON LA AS AL I NE ER J J F E S S I ON No. E16806 AT EL L E CT RICA N E O OR F CAL I F IA ST 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com PRO U E N G I N E E R I N G D ENG INTERFACE RE CONTACT R EG I S T E PROJECT DETAILS - FIRE ALARM PROJECT NO: 1089-0001 DATE: 1.12.2015 K K SHEET NO: FA7.01 12 11 10 9 8 7 6 5 4 3 2 1 DSA SUBMITTAL 12 11 10 9 UL LISTED, FM APPROVED TRUEALARM ANALOG SENSING PROVIDES DIGITAL TRANSMISSION OF ANALOG SENSOR VALUES VIA MAPNETII, OR IDNet SLC TWO WIRE COMMUNICATIONS FIRE ALARM CONTROL PANEL PROVIDES: -INDIVIDUAL SENSITIVITY SELECTION FOR EACH SENSOR -PEAK VALUE LOGGING ALLOWING ACCURATE ANALYSIS FOR SENSITIVITY SELECTION -AUTOMATIC ENVIRONMENTAL COMPENSATION -DISPLAY OF SENSITIVITY IN PERCENT PER FOOT -MULTISTAGE ALARM OPERATION -ABILITY TO DISPLAY AND PRINT DETAILED SENSOR INFORMATION IN PLAIN ENGLISH LANGUAGE PHOTOELECTRIC SMOKE SENSOR 4098-9714: SEVEN LEVELS OF SENSITIVITY FROM 0.2% TO 3.7% IONIZATION SMOKE SENSOR 4098-9717: FOUR LEVELS OF SENSITIVITY FROM 0.5% TO 1.7%. HEAT SENSOR 4098-9733: -RATE-OF-RISE TEMPERATURE DETECTION IS SELECTABLE AT THE CONTROL PANEL FOR EITHER 15°F OR 20°F PER MINUTE -FIXED TEMPERATURE SENSING IS INDEPENDENT OF RATE-OF-RISE AND PROGRAMMABLE TO OPERATE AT 135°F OR 155°F -TRUEALARM HEAT SENSORS CAN BE PROGRAMMED AS A UTILITY DEVICE TO MONITOR FOR TEMPERATURE EXTREMES IN THE RANGE FROM 32° F TO 120° F. UL STANDARD SPACING: -60 FT SPACING FOR 135° F -40 FT SPACING FOR 155° F INTEGRAL RED LED FOR POWER-ON (PULSING), OR ALARM OR TROUBLE (STEADY ON) BASE MOUNTED ADDRESS SELECTION: -ACCESSIBLE FROM FRONT (DIP SWITCH UNDER SENSOR) -ADDRESS REMAINS WITH ITS PROGRAMMED LOCATION FOR USE WITH SIMPLEX 4010, 4100, 4020, AND 4120 SERIES CONTROL PANELS. MAXIMUM QUANTITY OF DEVICES: -127 FOR 4020, 4100, 4120 -250 FOR 4010, 4100 MOUNTING: CEILING OR WALL COLOR : FROST WHITE BASE DIMENSIONS: 15/16" X 4-7/8" B 7 4098-9792 STANDARD SENSOR BASE PRODUCT INFORMATION FEATURES: A 8 4" X 1 1/2" DEEP OCTAGONAL OR 4" SQUARE X 1 1/2" DEEP, WHICH REQUIRES A 4098-9832 ADAPTER PLATE (6-3/8" X 1/4") BOX SUPPLIED BY CONTRACTOR MAPNETII/IDNet ADDRESS DIP SWITCHES SEE BASE INSTALLATION INSTRUCTIONS 574-709 FOR SETTINGS 4098-9714 PHOTOELECTRIC SMOKE SENSOR 4098-9717 IONIZATION SMOKE SENSOR (BOX TO BE FLUSH OR RECESSED 1/4" MAXIMUM) + + TO ADDITIONAL MAPNETII/IDNet DEVICES OR RETURN TO FIRE ALARM CONTROL PANEL FOR A STYLE 6 APPLICATION OPTIONAL SHIELD - - 4090-9002 IDNet SLC, INDIVIDUAL ADDRESSABLE OUTPUT MODULE RELAY (AOM) RELAY IAM BACK BOX COVER OPTIONS; SEMI-FLUSH TRIM PLATE 4090-9801 (SHOWN) WITH LIGHT PIPE FOR LED VIEWING SURFACE TRIM PLATE 4090-9802 WITH LIGHT PIPE FOR LED VIEWING 2-GANG BACK BOX COVER SUPPLIED BY CONTRACTOR MODEL 4098-9756 MODEL 2098-9808 2098-9806 NOT USED ADDRESS SETTING UNDER RE-SEALABLE LABEL S R + R - 2 3 11 B + FROM PREVIOUS SLC DEVICE 3 OR F.A.C.P. - IDNet SLC TO F.A.C.P. 3 4 4 4 NO. 733-984 (1.8K 1/2W) 3 ISSUE DATE 3 733-886 (6.8K 1/2W) 733-896 (4.7K 1/2W) WIRING FOR CURRENT LIMITED OPERATION 3 D EXHAUST TUBE CUT TO 1/2 OF DUCT WHEN < 24" DO NOT INSERT RUBBER PLUG TEST E R R 2098-9808 REMOTE STATUS/ALARM INDICATOR FOR DUCT WIDTHS 3' TO 95" 2098-9806 TEST STATION FOR DUCT WIDTHS 8" TO 3' (OPTIONAL) (OPTIONAL) 4098-9756 4-WIRE DUCT SENSOR 2098-9808 ALARM INDICATOR 2098-9806 REMOTE ALARM INDICATOR/KEY SWITCH SW2 1 2 3 4 5 6 7 8 RED ALARM LED SEE NOTES 3, 4 4098-9756 4-WIRE DUCT SENSOR 2098-9806 REMOTE ALARM INDICATOR/ KEYSWITCH RED ALARM LED SW2 1 2 3 4 5 6 7 8 ADDRESS SWITCH TB1 1 + 2 - LED 3 ADDRESS SWITCH 4 5 6 7 8 TEST 9 10 11 12 13 14 15 16 TEST MAP + MAP - +24V + 24C - TB1 1 + SEE NOTES 3,4 ALM 2 3 - TEST MAP + MAP - LED 4 5 6 7 8 9 10 11 12 13 14 15 16 +24V BLK UL LISTED CONTROL PANEL SIMPLEX 4010, 4020 4008, 4100+ OR 4120 F TO OTHER MAPNETII/ IDNET SLC DEVICES SEE NOTE 2 OR RETURN TO FACP FOR STYLE 6 SLC + + - SHIELD (OPTIONAL) POWER CIRCUIT 24 VDC - ALM RED BLK RED MAPNET II/IDNet + 24C WHT SHIELD WHT - SEE NOTE 1 5 + BLU YEL 4098-9843 PAM-SD RELAY - RED 1. DUCT SENSOR WIRING IS 12 TO 18 AWG. 2. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT IS 127 FOR 4020, 4100+, OR 4120, AND 250 FOR THE 4010 PANEL 3. THE 2098-9806 AND 2098-9808 ARE POLARIZED, OBSERVE COLOR-CODED WIRING. 4. MAXIMUM WIRE LENGTH TO TEST TERMINALS AND REMOTE LED IS 250 FEET. 5 4098-9843 PAM-SD RELAY (AIR PRODUCTS & CONTROL LIMITED) ARE RATED AT 7 AMPS 28 VDC/10 AMPS @ 115 VAC. MAXIMUM WIRE LENGTH TO PAM-SD RELAYS IS 500 FT. (15 PAM-SD RELAYS MAX.). WIRING FROM THE RELAY TO THE DEVICE IT IS CONTROLLING SHOULD BE NO MORE THAN 3 FT. (PER NFPA 72). SHIELD 1/2 W 10K EOL RESISTOR 4081-9008 ORG N.O. + WIRING NOTES: C N.C. RED WHT 1/2 W 10K EOL RESISTOR 4081-9008 C N.C. BLU YEL N.O. ORG 4098-9843 PAM-SD RELAY 5 + RED FIRE SMOKE DAMPER WHT - RED AIR HANDLING UNIT FSD POWER (BY OTHERS) AHU POWER (BY OTHERS) G AIR PRODUCTS PAM-SD 24VDC POLARIZED RELAY MODULE (SIMPLEX 4098-9843) SPECIFICATIONS: FEATURES: UL LISTED CALIFORNIA STATE FIRE MARSHAL LISTING NUMBERS: 2908-9806 ALARM INDICATOR 7300-0026:150 MOUNTING: FLUSH FINISH: CHROME OR STAINLESS STEEL 4 3 NORMAL MAPNETII OR IDNET SLC COMMUNICATION, AUTO-SELECT 1 ADDRESS PER HOUSING, PROVIDES OPERATING POWER TO MODEL 4098-9755 MODEL 4098-9756 WITH SUPERVISED MULTIPLE RELAY CONTROL, REQUIRES SEPARATE FUSED 24 VDC FROM FIRE ALARM POWER SUPPLY INPUT VOLTAGE 17-32 VDC (24 VDC NOMINAL) STANDBY CURRENT 3 mA @ 24 VDC 15 mA @ 24 VDC, ADD 15 mA ADDITIONAL FOR EACH ALARM CURRENT 4098-9843 RELAY 4098-9843 RELAY OUTPUT RATINGS, SINGLE FORM C 15 mA @ 24 VDC UP TO 15 MAX. PER RELAY CONTROL COIL CURRENT OUTPUT RELAY CONTACTS, RESISTIVE RATINGS 7 A @ 28 VDC & 120 VAC; 250 uA @ 5 VDC 500 FT. (152m) MAX. TO RELAY COILS, RELAY MUST BE LOCATION DISTANCE WITHIN 3 FT. (1m) OF DEVICE BEING CONTROLLED PER NFPA 72, SECTION 3-9.2.1 S B 2 SECONDARY IDNet/MAPNET SLC LINES 5 8 9 10 C R ADDRESSABLE OPERATION SECONDARY IDNet SLC LINES 1 2 R DATA COMMUNICATIONS 7 I ON 574-184 REV A OPTIONAL SHIELD 2 ALARM 300 TO 4000 FT/min (91 TO 1220 m/min) 0.2% TO 3.7% PER FOOT OF OBSCURATION, SELECTABLE AT HOST CONTROL PANEL 32° F TO 100° F (0° C TO 38° C) UL LISTED TEMPERATURE RANGE 32° F TO 122° F (0° C TO 50° C) OPERATING TEMPERATURE RANGE 0° F TO 140° F (-18° C TO 60° C) STORAGE TEMPERATURE RANGE 10% TO 95% RH, NON-CONDENSING HUMIDITY RANGE BLACK BASE WITH CLEAR COVER HOUSING COLOR WIRING CONNECTIONS TERMINAL BLOCKS, 18 TO 12 AWG REMOTE STATUS/ALARM LED AND TEST STATION WITH REMOTE STATUS/ALARM LED 1.2 mA, NO IMPACT TO ALARM CURRENT (2098-9808 REMOTE ALARM LED CURRENT OR 2098-9806) TEST STATION KEYSWITCH CURRENT 3.3 mA, NO IMPACT TO ALARM CURRENT (2098-9806) REMOTE ALARM LED AND TEST 250 FT. (76m) MAXIMUM STATION DISTANCE NORMALLY OPEN (N.O.) 4090-9002 RELAY IAM NOT USED PRIMARY IDNet SLC LINES 1 2 11 I SAN JOSE, CALIFORNIA ALARM SENSOR SENSITIVITY RANGE COMMON COMMON NORMALLY OPEN (N.O.) B B TUBE SUPPORT HOLE SHALL BE USED FOR DUCTS MORE THAN 3 FEET WIDE INSERT RUBBER PLUG GENERAL SPECIFICATIONS AIR VELOCITY RANGE (LINEAR FT/MIN) 4 5 8 9 NORMALLY CLOSED (N.C.) 574-184 REV A RR ON 4 5 8 9 NORMALLY CLOSED (N.C.) 4090-9002 RELAY IAM B B DUCT SMOKE SENSOR HOUSING WITH PHOTOELECTRIC SENSOR COMPATIBILITY DESCRIPTION DUCT HOUSING WITH SUPERVISED MULTIPLE RELAY CONTROL FOR UP SIMPLEX FIRE ALARM CONTROL MODELS TO 15, 4098-9843 RELAYS (ORDERED SEPARATELY), REQUIRES 4008, 4010, 4020, 4100, AND 4120. SEPARATE 24 VDC FIRE ALARM POWER AND RELAY END-OF-LINE RESISTOR REMOTE LED INDICATOR AND TEST STATION, SELECT ONE IF REQUIRED MOUNTING DESCRIPTION USE SINGLE GANG BOX, RED LED STATUS INDICATOR 3" H X 2" W X 2" D TEST STATION WITH KEYSWITCH AND RED LED STATUS (TURNING (76 mm X 51 mm X 51 mm) SWITCH TO TEST INITIATES ALARM FOR SYSTEM TESTING SPECIFICATIONS: WIRING NOTES: RR SHIELD + IDNet/MAPNET - IDNet/MAPNET DUCT DETECTOR SELECTION CHART DUCT SENSOR HOUSING WITH SUPERVISED OUTPUT FOR MULTIPLE REMOTE RELAYS, REQUIRES SEPARATE 24 VDC (RELAYS ARE UNDER PANEL CONTROL AND CAN BE ACTIVATED MANUALLY OR BY A SEPARATE ALARM/INPUT) GENERAL FEATURES: UL LISTED TO STANDARD 268A CLEAR COVER ALLOWS VISUAL INSPECTION TEST PORTS PROVIDE FUNCTIONAL SMOKE TESTING ACCESS WITH COVER IN PLACE MOUNTS TO RECTANGULAR DUCTS OR ROUND DUCTS (MINIMUM SIZE 8" SQUARE OR 18" DIAMETER) MAGNETIC TEST FEATURE FOR ALARM INITIATION AT HOUSING OPTIONAL WEATHERPROOF ENCLOSURE IS AVAILABLE SEPARATELY (REFER TO DATA SHEET S4098-0032) DIAGNOSTIC LEDS (ON INTERFACE BOARD): RED ALARM/TROUBLE LED FOR SENSOR STATUS AND COMMUNICATIONS POLLING DISPLAY YELLOW LED FOR OPEN OR SHORTED TROUBLE INDICATION OF SUPERVISED RELAY CONTROL SAMPLING TUBES (ORDERED SEPARATELY): AVAILABLE IN MULTIPLE LENGTHS TO MATCH DUCT SIZE INSTALLED AND SERVICED WITH HOUSING IN PLACE REMOTE MODULE OPTIONS (ORDERED SEPARATELY): RED STATUS/ALARM LED (2098-9808) TEST STATION WITH LED (2098-9806) RELAYS USED (4098-9843) 4" SQUARE X 2 1/8" DEEP BOX SUPPLIED BY CONTRACTOR IDNet SLC RELAY MODULES ALLOW THE SIMPLEX FIRE ALARM CONTROL PANEL TO CONTROL A REMOTELY LOCATED FORM "C" CONTACT USING IDNet ADDRESSABLE COMMUNICATIONS FOR BOTH DATA AND POWER. TYPICAL APPLICATIONS WOULD BE FOR SWITCHING LOCAL POWER FOR CONTROL FUNCTIONS SUCH AS ELEVATOR CAPTURE, OR CONTROL OF HVAC COMPONENTS, PRESSURIZATION FANS, DAMPERS, ETC. RELAY STATUS IS ALSO COMMUNICATED REQUIRING ONLY ONE DEVICE ADDRESS. 1 PRIMARY IDNet/MAPNET SLC LINES 8 9 10 S R B SAN JOSE CITY COLLEGE PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING TO ADDITIONAL DEVICES OR RETURN TO FIRE ALARM CONTROL PANEL FOR STYLE 6 SYSTEM APPLICATION 6 OPTIONAL SHIELD S R B SUPERVISED INPUT: - 4090-9001 AIM WITH T-SENSE CAPABILITY HAS A SUPERVISED INPUT THAT MONITORS FOR CONTINUITY TO AN END-OF-LINE RESISTOR AND CAN DIFFERENTIATE BETWEEN A SHORT CIRCUIT CONTACT CLOSURE AND A CURRENT LIMITED CONTACT CLOSURE. FOUR STATE OPERATION: - NORMAL IS WHEN ALL CONTACTS ARE OPEN AND THERE IS CONTINUITY TO THE END-OF-LINE RESISTOR. - OPEN IS WHEN CONTINUITY DOES NOT EXIST TO THE END-OF-LINE RESISTOR, CAUSING A TROUBLE CONDITION. - SHORT, INDICATES THAT A CONTACT HAS CLOSED THAT IS DIRECTLY CONNECTED TO THE INPUT CIRCUIT. - CURRENT LIMITED INDICATES THAT A CONTACT HAS CLOSED BEYOND A SERIES CONNECTED CURRENT LIMITING RESISTOR. THIS OPERATION ALLOWS DIFFERENTIATION BETWEEN TWO DIFFERENT CONTACT TYPES DUE TO THEIR WIRING LOCATION, AND REPORTING AS A SINGLE IDNET ADDRESSABLE POINT TO A 4100U FIRE ALARM CONTROL PANEL. MODEL: SPECIFICATIONS: PRODUCT INFORMATION B 4098-9756 ADDRESSABLE ANALOG 4-WIRE DUCT SENSOR MAPNET II/IDNet SLC WITH 24VDC RELAY COMPACT AIR DUCT SENSOR HOUSING WITH CLEAR COVER TO MONITOR FOR THE PRESENCE OF SMOKE INCLUDES FACTORY INSTALL TRUEALARM PHOTOELECTRIC SMOKE DETECTOR AND FEATURES: INDIVIDUAL SENSOR INFORMATION PROCESSED BY THE HOST CONTROL PANEL T0 DETERMINE SENSOR STATUS DIGITAL TRANSMISSION OF ANALOG SENSOR VALUES VIA MAPNET II OR IDNET SLC 2-WIRE COMMUNICATIONS PROGRAMMABLE SENSITIVITY, CONSISTENT ACCURACY, ENVIRONMENTAL COMPENSATION, STATUS TESTING, AND MONITORING OF SENSOR DIRT ACCUMULATION DESCRIPTION: SHIELD IDNet/MAPNET + IDNet/MAPNET - T-SENSING OPERATION: PRODUCT INFORMATION FEATURES: RELAY IAM POWER: SUPPLIED BY IDNet COMMUNICATIONS RELAY IAM CONTACTS (FORM "C", SPDT) POWER LIMITED RATING: 2A @ 24VDC, TRANSIENT SUPPRESSED LOADS, 1A @ 24VDC FOR INDUCTIVE LOADS NON POWER LIMITED RATING: 1/2A @ 24VAC, TRANSIENT SUPPRESSED LOADS, 1A @ 24 VDC FOR INDUCTIVE LOADS WIRE CONNECTIONS: SCREW TERMINALS FOR IN/OUT WIRING, #18 TO #14 AWG WIRE COMPATIBLE WITH SIMPLEX 2081-9044 OVER VOLTAGE PROTECTORS DIMENSIONS: 4 1/8"H x 4 1/8"W x 1 3/8"D (105mm x 105mm x 35mm) HOUSING MATERIAL: BLACK THERMOPLASTIC MOUNTING PLATE MATERIAL: SHEET METAL, GALVANIZED TEMPERATURE RANGE: 32° F TO 120° F (0° C TO 49° C) INTENDED FOR INDOOR OPERATION HUMIDITY RANGE UP TO 93% RH AT 100° F (38° C) 6 FROM UL-LISTED F.A.C.P. OR PREVIOUS SLC DEVICE 1. ALL WIRING TO COMPLY WITH LOCAL CODE. 2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS. 3. ONLY N.O. DRY CONTACTS ARE ALLOWED. 4. MAXIMUM WIRE LENGTH (NO. 18 AWG) IS 400 FT. W/2081-9044 OVER VOLTAGE PROTECTORS OR 400 FT. W/O PROTECTORS. 5. A MAXIMUM QUANTITY OF DEVICES PER CIRCUIT: CONTROL PANEL MODULE DEPENDENT 6. IF SHIELD IS PRESENT, CONNECT TO THE OUTGOING IDNet SHIELD TO PROVIDE A CONTINUOUS SHIELD OVER THE LENGTH OF THE IDNet CHANNEL. METHOD OF SPLICE DETERMINED BY AHJ. 7. REFER TO INSTALLATION INSTRUCTIONS 574-331. 8. MAXIMUM ALLOWABLE LINE RUN FROM THE F.A.C.P. TO THE FARTHEST DEVICE, NOT TO EXCEED 2500 FEET. 9. MAXIMUM TOTAL WIRE (INCLUDING ALL T-TAPS) FROM THE FIRE ALARM CONTROL PANEL 10. FOR STYLE 6 CIRCUIT WIRING IT IS RECOMMENDED THAT THE PRIMARY 1 AND THE BACK-UP 2 LINES BE IN SEPARATE WIRE RUNS AND IN COMPLIANCE WITH LOCAL REQUIREMENTS. 11. REFER TO FIELD WIRING DIAGRAM 842-073 UL LISTED A SINGLE ADDRESSABLE POINT BOTH CONTROLS A 2A FORM "C" CONTACT AND TRACKS ITS STATUS COMPATIBLE WITH SIMPLEX MODEL 4010 AND 4100 ADDRESSABLE FIRE ALARM CONTROL PANEL LATCHING RELAY DESIGN ALLOWS DATA AND POWER TO BE BOTH SUPPLIED BY IDNet COMMUNICATIONS COMPACT, SEALED CONSTRUCTION: - SCREW TERMINALS FOR WIRING CONNECTIONS - REDUCES DUST INFILTRATION G ADDRESS DIP SWITCHES UNDER RE-SEALABLE LABEL SEE INSTALLATION INSTRUCTIONS (574-331) FOR SETTINGS WIRING NOTES: FEATURES: F BACK BOX COVER OPTIONS; SEMI-FLUSH TRIM PLATE 4090-9806 (SHOWN) WITH LIGHT PIPE FOR LED VIEWING SURFACE TRIM PLATE 4090-9807 WITH LIGHT PIPE FOR LED VIEWING SINGLE GANG COVER W/ 2 6/32 FLATHEAD SCREWS (SUPPLIED BY CONTRACTOR) THE 4090-9001 IS AN ADDRESSABLE INPUT MODULE (AIM) WITH POWER AND COMMUNICATIONS SUPPLIED BY A TWO WIRE ADDRESSABLE CIRCUIT. IT PROVIDES LOCATION SPECIFIC ADDRESSABILITY TO A SINGLE INITIATING DEVICE (SUCH AS SINGLE STATION SMOKE DETECTOR ALARM CONTACTS OR HEAT DETECTOR CONTACTS) OR MULTIPLE DEVICES AT THE SAME LOCATION BY MONITORING NORMALLY OPEN, DRY CONTACTS AND THE WIRING TO AN END-OF-LINE RESISTOR. CLOSURE OF THE MONITORED CONTACTS INITIATES AN ALARM OR OTHER RESPONSE AS PROGRAMMED AT THE FIRE ALARM CONTROL PANEL. AN OPEN IN THE MONITORED CIRCUIT WIRING WILL CAUSE A TROUBLE TO BE REPORTED. IF THE INITIATING DEVICE CONTACTS ARE MOMENTARY, SUCH AS FROM A RATE-OF-RISE HEAT DETECTOR, ENABLING THE LATCH FEATURE WILL MAINTAIN THE ALARM CONDITION UNTIL THE SYSTEM IS RESET. FOR APPLICATIONS WHERE THE CONTACT CLOSURE LATCHES, OR IF ITS CONDITION NEEDS TO BE TRACKED AT THE CONTROL PANEL NON-LATCHING OPERATION MAY BE ENABLED. FROM PREVIOUS MAPNETII/IDNet DEVICE OR FIRE ALARM CONTROL PANEL 1. IDNet LINES ARE TO BE #18 AWG TWISTED PAIR (CONSULT SG SALES ENGINEERING FOR EXCEPTIONS). 2. MAXIMUM ALLOWABLE LINE RUN, FROM THE F.A.C.P. TO THE FARTHEST DEVICE, NOT TO EXCEED 2500 FEET. 3. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT: CONTROL PANEL MODULE DEPENDENT 4. CONTRACTOR WIRING TO RELAY CONTACTS IS UNSUPERVISED. USE #14 AWG WIRE TO LOCAL CODE. 5. RELAY CONTACTS RATED 2A, 24VDC (1A FOR INDUCTIVE LOAD) RELAY CONTACTS RATED 0.5A 120VAC (NON POWER LIMITED) FOR POWER-LIMITED OPERATION, POWER MUST BE PROVIDED FROM FACP OR POWER-LIMITED POWER SUPPLY LISTED FOR FIRE PROTECTIVE SIGNALING USE. 6. SEE INSTALLATION INSTRUCTIONS 574-184. 7. IF SHIELD IS PRESENT, CONNECT TO THE OUTGOING IDNet SHIELD TO PROVIDE A CONTINUOUS SHIELD OVER THE LENGTH OF THE IDNet CHANNEL. METHOD OF SPLICE DETERMINED BY AHJ. 8. WHEN CONNECTED TO A NON POWER-LIMITED SOURCE, THE WIRING MUST MAINTAIN A MINIMUM 1/4 INCH SEPARATION FROM IDNet WIRING. 9. WHEN USED WITH NON POWER-LIMITED SOURCE, THE "POWER LIMITED WIRING" INDICATION ON THE DEVICE LABEL MUST BE OBLITERATED. 10. WHEN BOTH POWER-LIMITED AND NON POWER-LIMITED SOURCES ARE PRESENT, USE TYPE FPL, FPLR OR FPLP POWER LIMITED CABLE FOR POWER-LIMITED CIRCUITS. 11. MAXIMUM TOTAL WIRE (INCLUDING ALL T-TAPS) ON CIRCUIT, FROM THE F.A.C.P. NOT TO EXCEED 10,000 FEET OR .58uF. (CLASS B ONLY) 12. REFER TO FIELD WIRING DIAGRAM 842-073 4090-9810 BRACKET REQUIRED WHEN USING THE SIMPLEX TRIM PLATES OPTIONAL WHEN USING A CONTRACTOR SUPPLIED SINGLE GANG COVER DESCRIPTION: TRUEALARM SENSOR BASES CONTAIN INTEGRAL ADDRESSABLE ELECTRONICS THAT CONSTANTLY MONITOR THE STATUS OF THE DETACHABLE PHOTOELECTRIC, IONIZATION, OR HEAT SENSORS. EACH SENSOR'S OUTPUT IS DIGITIZED AND TRANSMITTED TO THE SYSTEM FIRE ALARM CONTROL PANEL EVERY FOUR SECONDS. SINCE TRUEALARM SENSORS USE THE SAME BASE, DIFFERENT SENSOR TYPES CAN BE EASILY INTERCHANGED TO MEET SPECIFIC LOCATION REQUIREMENTS. THIS FEATURE ALLOWS INTENTIONAL SENSOR SUBSTITUTION DURING BUILDING CONSTRUCTION. WHEN CONDITIONS ARE TEMPORARILY DUSTY, INSTEAD OF COVERING THE SMOKE SENSORS. HEAT SENSORS MAY BE INSTALLED WITHOUT REPROGRAMMING THE CONTROL PANEL, ALTHOUGH THE CONTROL PANEL WILL INDICATE AN INCORRECT SENSOR TYPE, THE HEAT SENSOR WILL OPERATE AS A DEFAULT SENSITIVITY PROVIDING HEAT DETECTION FOR BUILDING PROTECTION AT THAT LOCATION. E 1 A SUPERVISION RESISTOR: 6.8k 1/2W, (SUPPLIED) SIMPLEX PART NO. 733-886 RESISTOR FOR CURRENT LIMITED OPERATION: 4.7k 1/2W, WITH A 1.8k 1/2W INPUT REQUIREMENTS: NORMALLY OPEN, DRY CONTACTS HOUSING MATERIAL: BLACK THERMOPLASTIC FLUSH MOUNTING WIRING: D 2 UL LISTED SINGLE GANG ELECTRICAL BOX (2 1/8" MIN. DEPTH) (SUPPLIED BY CONTRACTOR) WIRE CONNECTIONS: SCREW TERMINALS FOR IN/OUT WIRING FOR WIRE FROM #18 TO #14 AWG. DIMENSIONS: 1 9/16" X 1 3/4" X 1 1/4" TEMPERATURE RANGE: 32° F TO 158° F (0° C TO 70° C) HUMIDITY: UP TO 93% RH AT 100° F 4098-9733 HEAT SENSOR 3 4090-9001 IDNET SLC, SUPERVISED ADDRESSABLE INPUT MODULE (AIM) SPECIFICATIONS: DESCRIPTION: PRODUCT INFORMATION 4 UL LISTED ADDRESSABLE COMMUNICATIONS SUPPLY BOTH DATA AND POWER TO PROVIDE: - SUPERVISED STYLE B MONITORING OF NORMALLY OPEN DRY CONTACTS. - COMMUNICATIONS WIRING USING ONE TWISTED, SHIELDED WIRE PAIR. COMPATIBLE WITH SIMPLEX ADDRESSABLE FIRE ALARM CONTROL PANELS. COMPACT, SEALED CONSTRUCTION: - ALLOWS MOUNTING IN A SINGLE GANG BOX - REDUCES DUST INFILTRATION PROVIDES CURRENT LIMITED MONITORING - TO MONITOR TAMPER SWITCH (SUPERVISORY) AND WATER FLOW SWITCH (ALARM) ON SAME CIRCUIT - REQUIRES ONLY ONE ADDRESSABLE POINT SELECTABLE LATCHING OPERATION - MONITORS MOMENTARY CONTACT CLOSURES SUCH AS RATE-OF RISE HEAT DETECTORS UL LISTED TEMPERATURE RANGE: 32°F TO 100°F OPERATING TEMPERATURE RANGE: 32°F TO 120°F HUMIDITY RANGE: 10% TO 95% RH PHOTOELECTRIC SENSOR AIR VELOCITY RANGE: 0-2000 FT/MIN IONIZATION SENSOR AIR VELOCITY RANGE: 0-300 FT/MIN WIRING CONNECTIONS: SCREW TERMINALS FOR IN/OUT WIRING, #18 TO #14 AWG COMMUNICATIONS MAPNETII/IDNet SLC: 1 ADDRESS PER BASE VOLTAGE (MAPNETII/IDNet SLC): 24-40VDC CURRENT: 400uA TYPICAL 1. ALL WIRING TO COMPLY WITH LOCAL CODE. 2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS. 3. MAINTAIN CORRECT POLARITY 4. MAPNETII/IDNet SLC WIRING TO BE #18 AWG TWISTED SHIELDED PAIR 5. IF SHIELD IS PRESENT, CONNECT TO THE OUTGOING IDNet SLC SHIELD TO PROVIDE A CONTINUOUS SHIELD OVER THE LENGTH OF THE IDNet SLC CHANNEL. METHOD OF SPLICE DETERMINED BY AHJ. 6. REFER TO INSTALLATION INSTRUCTIONS (574-707) 7. REFER TO APPLICATION MANUAL (574-709) 5 PRODUCT INFORMATION FEATURES: SPECIFICATIONS: C 6 ARCHITECT'S STAMP APPROVAL POWER REQUIREMENTS: 0.015 AMP @ 24VDC (17 VDC TO 32 VDC) STANDARD SINGLE GANG BOX 2" X 3" MINIMUM DEPTH 2" SUPPLIED BY CONTRACTOR ANY SINGLE GANG BOX SUPPLIED BY CONTRACTOR RELAY: U.L. RECOGNIZED SPDT THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. CONTACT RATING: 7 AMPS @ 120VAC & 28 VDC 250 MICRO AMPS @ 5 VDC AMBIENT TEMPERATURE: -50° F TO 85 °F (-50°C TO 85°C) SPECIFICATIONS: THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. APPROVALS: UNDERWRITERS LABORATORIES LISTED ALARM CURRENT: 2.8 mA DIMENSIONS OF BOX: 2 "W X 3"H X 2"D COVER PLATE SUPPLIED BY CONTRACTOR 12" 18 AWG WIRE LEADS DIMENSIONS: 1-1/2"H X 1 7/8" W X 13/16" D (38.1mm H X 47.625mm W X 20.638mm D) DESCRIPTION: H FEATURES: 2098-9806 REMOTE TEST STATION, PROVIDES A REMOTE RED ALARM LED STATUS INDICATOR AND A REMOTE TEST KEY ACTIVATED SWITCH MOUNTED ON A SINGLE GANG STAINLESS STEEL PLATE. THE LED WILL PULSE TO INDICATE NORMAL OPERATION OF THE DUCT DETECTOR AND WILL ENERGIZE CONTINUOUS WHEN IN ALARM OR IN TROUBLE. (THE EXACT STATUS OF THE SENSOR WILL BE DISPLAYED AT THE FIRE ALARM CONTROL PANEL.) TURNING THE TEST SWITCH TO "TEST" WILL INITIATE AN ALARM AND ALLOW THE RESULTING SYSTEM RESPONSES TO BE VERIFIED. CONSULTANT SINGLE SPDT RELAY DOUBLE-SIDED ADHESIVE TAPE 2014-0174 Joe Ripp 10.0 AMP CONTACTS 2098-9806 YEL ORG BLU J C N/C J N/O ON LA AS AL I NE ER No. E16806 AT EL E CT RICA N E O OR F CAL I F L 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com FLUSH MOUNTING ST MINIMUM 18 AWG OR TO LOCAL CODE. CONDUCTORS MUST TEST FREE OF ALL GROUNDS. REMOTE ALARM LED IS POLARIZED, OBSERVE COLOR CODED WIRING. ONE INDICATOR MAY BE INSTALLED PER DETECTOR. F E S S I ON U E N G I N E E R I N G WIRING: PRO ENG INTERFACE D IA 5 WIRE NUTS CONTACT J PROJECT RE MOUNTING SCREW R EG I S T E H DETAILS - FIRE ALARM RED (+) CONNECT TO REMOTE ALARM LED OUTPUT OF APPROPRIATE INITIATING DEVICES BLACK (-) PROJECT NO: 1089-0001 CONNECT TO REMOTE TEST SWITCH INPUT ON APPROPRIATE INITIATING DEVICES (-) WHT RED WHT K DATE: 1.12.2015 (+) RED 24VDC @ 0.015A (18 VDC TO 32 VDC) BACK VIEW K SHEET NO: FA7.02 12 11 10 9 8 7 6 5 4 3 2 1 DSA SUBMITTAL 9 8 7 6 5 TM 4906 S/V END-OF-LINE RESISTOR (VALUE DEPENDANT ON FACP) 4906 S/V SPKR + SPKR + SPKR + SPKR - SPKR - SPKR - JUMPER POSITION J1 TO TAP A J1 TO TAP B J1 TO TAP C J1 TO TAP D J1 TO TAP D J1 TO TAP E J1 TO TAP F J1 TO TAP G WATTAGE VOLTAGE SETTING 1/4 1/2 70.7VRMS 1 2 1/4 1/2 25VRMS 1 2 SLC - STROBE + STROBE + STROBE + STROBE - STROBE - STROBE - SLC - WIRING NOTES: 1. REFER TO FIELD WIRING DIAGRAMS OF THE DRIVING TrueAlert COMPATIBLE CONTROLLER FOR ADDITIONAL SLC WIRING INFORMATION. REFER TO THE FIELD WIRING DIAGRAMS SUPPLIED WITH THE 4100/4003 FOR ADDITIONAL NAC WIRING INFORMATION. 2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. 3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS. 4. ALL TrueAlert SLC AND NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED. 5. POWERING THE S/V FROM AN APPLIANCE POWER SOURCE LESS THAN 17 VDC OR GREATER THAN 32 VDC MAY CAUSE PERMANENT DAMAGE TO THE S/V UNIT. 6. THE TrueAlert S/V CAN ONLY BE OPERATED THROUGH A 4009 TrueAlert ADDRESSABLE CONTROLLER OR TrueAlert COMPATIBLE FACP. 7. WHEN CONTROLLED FROM A 4009 TrueAlert ADDRESSABLE CONTROLLER, THE FACP SETTINGS ARE NOT SUPPORTED. 8. MAXIMUM T-TAPPING LENGTH IS 100 FEET. CLEAR WHITE RED AMBER/ BLUE GREEN RED APPLIANCE CONFIGURATION CONTROL DIP SWITCH ACCESSABLE FROM REAR MAGNETIC TEST LOCATION NFPA 72 REQUIRES THAT THE ENTIRE LENS BE NOT LESS THAN 80" AND NOT GREATER THAN 96" ABOVE THE FINISHED FLOOR. 80" MIN. ADDRESS SETTING DIP SWITCH ACCESSABLE FROM REAR SEMI-FLUSH MOUNTING RESERVED FOR FUTURE USE LSB MSB 0000 1000 0100 1 2 3 4 6 7 8 1100 DIP SWITCHES 0=OFF 0010 1=ON 1 THRU 4 1010 NOT USED 0110 1110 0001 CURRENT VALUES ARE UL 1971 MAX RATING FOR THE GIVEN VOLTAGE LEVEL 1001 30cd 75cd 15cd 135cd 185cd VOLTAGE 110cd 0101 0.047 23 VRMS 0.208 0.057 0.100 0.160 0.132 1101 0.062 0.075 0.133 0.178 17 VRMS **0.281 **0.214 0011 0.054 23 VRMS 0.211 0.078 0.128 0.184 1011 0.067 **0.282 0.103 0.171 17 VRMS 0.250 0111 NOT *10cd *20cd *45cd *95cd *75cd 1111 SUPPORTED 23 VRMS 0.054 0.211 0.078 0.128 0.184 **0.282 17 VRMS 0.067 0.103 0.171 0.250 *3cd *7cd *15cd *37cd *30cd 23 VRMS 0.054 0.078 0.128 0.211 0.184 **0.282 0.067 17 VRMS 0.103 0.171 0.250 5 1000 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 0100 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 4" SQUARE x 1 1/2" DEEP BOX (RACO NO. 231 OR 232) SUPPLIED BY CONTRACTOR NOTE: NO CONDUIT ENTRY IN THE REAR OF THE BACK BOX 1. BRING THE BUILDING WIRING THROUGH THE RECTANGULAR OPENING IN THE BACKPLATE. 2. CONNECT THE BUILDING WIRES TO THE BACKPLATE. 3. SECURE THE BACKPLATE TO THE ELECTRICAL BOX BY USING THE PROVIDED HARDWARE. INSTALLED WITH THE WRITING "INSTALL THIS SIDE UP" AT THE TOP. G WHITE FIRE 5. SET THE APPLIANCE ADDRESS AND CONFIGURATION SETTINGS. 6. ATTACH THE ASSEMBLED APPLIANCE ONTO THE BACKPLATE. 49VO 2 1 CKT - 1 - 49VO 2 CKT 1 + - 49VO 2 CKT SLC - SLC SLC + SLC + FEATURES: 1 + - 49VO 2 CKT 1 + - SLC - SLC - SLC + SLC + CKT + B C D E 70.7V F G 25V TB1 SPKR+ A SPKR- SPKR - SLC - STROBE + STROBE + STROBE + STROBE - STROBE - STROBE - 2W MODEL NUMBER COVER COLOR 4906-9202 RED 4906-9204 WHITE RESERVED FOR FUTURE USE DIP SWITCHES 5 & 6 MSB LSB 0000 1000 0100 1100 0010 1010 DIP SWITCHES 0110 1 THRU 4 1110 0001 1001 0101 1101 0011 1011 0111 1111 1000 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 0000 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0100 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 1100 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 1 2 3 4 5 6 7 8 NOT USED 0=OFF 1=ON (RACO NO. 650) 3 1/2" X 1 1/2 " OR EQUAL (88.9 mm x 38.1 mm) HANDY BOX SUPPLIED BY CONTRACTOR NOTE: DO NOT BRING CONDUIT THROUGH THE REAR OF THE ELECTRICAL BOX MAGNETIC TEST LOCATION 011 57 03 51 PCAF - STROBE LED + CEILING MOUNT MOUNTING NOTES: 1. THE TrueAlert CEILING STROBE UNIT ATTACHES DIRECTLY TO A STANDARD SINGLE-GANG, ELECTRICAL BOX (NOT SUPPLIED), SEMI-FLUSH OR SURFACE MOUNTED. 2. THERE ARE TWO HOLES FOR ELECTRICAL BOX MOUNTING. SECURE THE HOUSING TO SINGLE-GANG BOX USING 2 MOUNTING SCREWS (#6/32-INCH x 1 1/8-INCH LONG SUPPLIED) LINE THE MOUNTING TABS OF THE STROBE UNIT TO THE HOUSING SLOTS AND SNAP INTO PLACE. 3. IT IS RECOMMENDED THAT THE STROBE ADDRESS BE SET BEFORE THE APPLIANCE IS SNAPPED TO THE HOUSING. 4. ADDRESS SWITCH SW2 IS ACCESSIBLE WITH THE CEILING-MOUNT STROBE REMOVED. 4906 STROBE TrueAlert STROBE UNIT REAR VIEW FROM TrueAlert COMPATIBLE SLC CONTROLLER (SEE WIRING NOTES) SLC SLC + 4905-9989 WHITE SPEAKER COVER WITH RED "FIRE" LETTERING DIMENSIONS 5 1/8"" H x 5" W x 1 1/2"D (130 mm X 127 mm X 38 mm) 2 CKT 1 + - 2 CKT 2 1 + - SLC - SLC - SLC - SLC + SLC + SLC + CKT + WIRING NOTES: 1. REFER TO FIELD WIRING DIAGRAMS OF THE DRIVING TRUEALERT COMPATIBLE CONTROLLER FOR ADDITIONAL SLC WIRING INFORMATION. 2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. 3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS. 4. ALL TrueAlert SLC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED. 5. POWERING THE STROBE FROM AN APPLIANCE POWER SOURCE LESS THAN 17 VDC OR GREATER THAN 32 VDC MAY CAUSE PERMANENT DAMAGE TO THE STROBE. 6. THE TrueAlert STROBE CAN ONLY BE OPERATED THROUGH A 4009 TrueAlert ADDRESSABLE CONTROLLER OR TrueAlert COMPATIBLE FACP. 7. WHEN CONTROLLED FROM A 4009 TrueAlert ADDRESSABLE CONTROLLER, THE FACP SETTINGS ARE NOT SUPPORTED. 8. MAXIMUM T-TAPPING LENGTH IS 100 FEET. G TrueAlert (STYLE Y) SPEAKER NOTIFICATION APPLIANCES 4902 SERIES ARCHITECT'S STAMP 4" SQ. x 1 1/2" DEEP BOX (101.6 mm x 38.1 mm) (RACO NO. 191 OR EQUAL) SUPPLIED BY CONTRACTOR FIRE ALARM SPEAKERS WITH MODELS FOR WALL MOUNTING UL LISTED TO STANDARD 1480 ULC LISTED MODEL (CA SUFFIX FOLLOWING THE MODEL NUMBER) JUMPER POSITION J1 TO TAP A J1 TO TAP B J1 TO TAP C J1 TO TAP D J1 TO TAP D J1 TO TAP E J1 TO TAP F J1 TO TAP G CAPACITOR INPUT FOR CONNECTION TO SUPERVISED NOTIFICATION APPLIANCE CIRCUIT RUGGED , HIGH IMPACT, FLAME RETARDANT THERMOPLASTIC HOUSING OFF-WHITE COLOR (NO LETTERING) FLUSH MOUNT ON CEILING OR WALL COMPATIBLE WITH OPTIONAL TILE BRIDGE 2905-9946 SPKR- TB1 SPKR+ WATTAGE SETTING 1/4 1/2 70.7VRMS 1 2 1/4 1/2 25VRMS 1 2 PROJECT CONTACT SPKR + IF LAST APPLIANCE ON CIRCUIT, CONNECT EOLR (SEE WINING NOTES) 2. ENSURE CORRECT ORIENTATION OF BOX WITH EXTENSION IN RELATION TO LOCATION OF MOUNTING SCREWS. 3. FOR INSTALLATION IN PLASTER OR CONCRETE CEILING, MOUNT BOX WITH EXTENSION FLUSH OR WITH MAXIMUM 1/4 INCH RECESS; FOR SUSPENDED CEILING, USE A SUITABLE BRIDGE THAT RESTS ON TILE SUPPORT BOX WITH EXTENSION. SOUND OUTPUT RATINGS @ 10 FT. (3m) SELECTED TAP 1/4W 1/2W 1W J 2W PRODUCT SELECTION SPEAKER MOUNTING ADAPTERS AND BOXES MODEL DESCRIPTION NUMBER ROUND HOUSING SPEAKER, CEILING 4902-9721(CA) OFF-WHITE (NO LETTERING) OR WALL MOUNT MOUNTING ADAPTERS MODEL DESCRIPTION NUMBER TILE BRIDGE 2905-9946 1. REFER TO FIELD WIRING DIAGRAMS SUPPLIED WITH THE 4100/4003 FOR ADDITIONAL NAC WIRING INFORMATION. 2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. 3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS. 4. ALL NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED. 5. END-OF-LINE RESISTOR VALUE DEPENDENT ON CONTROL PANEL. 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com MOUNTING NOTES: 1. THE TrueAlert CEILING-MOUNT SPEAKER ATTACHES DIRECTLY TO A STANDARD 4-INCH SQUARE ELECTRICAL BOX WITH EXTENSION RING (NOT SUPPLIED) SEMI-FLUSH MOUNTED OR SURFACE MOUNTED. BLACK D PRO F E S S I ON ON LA AS AL No. E16806 AT EL E CT RICA N E O OR F CAL I F DETAILS - FIRE ALARM BLACK SPKR - SPKR - SPKR + SPKR + 25 VRMS OR 70.7 VRMS AUDIO INPUT FROM 4100/4003 WIRING NOTES: E N G I N E E R I N G SEMI-FLUSH MOUNTING CEILING OR WALL NOTE: ULC LISTED MODELS ARE DESIGNATED WITH A "CA" SUFFIX. RED 2014-0174 Joe Ripp INTERFACE TrueAlert CEILING MOUNTED SPEAKER REAR VIEW (SHOWN TAPPED AT 1/2 WATT @ 25VRMS) REVERBERANT CHAMBER, UL 1480 TEST 79 dBA 82 dBA 85 dBA 88 dBA 4902-9721(CA) ROUND HOUSING ANECHOIC CHAMBER, ON-AXIS, ULC S541 79 dBA 82 dBA 85 dBA 88 dBA SPKR + H CONSULTANT DEPTH INTO BOX: 2 3/4" (70 MM) INPUT VOLTAGE: 25 OR 70.7 VRMS POWER TAPS: 1/4, 1/2, 1 AND 2W INPUT TERMINAL RATINGS: 18 TO 12 AWG FREQUENCY (FIRE ALARM): 400 TO 4000 Hz RESPONSE (GENERAL SIGNALING): 125 TO 12 kHz TEMPERATURE RANGE: 32° TO 100 ° F ( 0° TO 38° C) HUMIDITY RANGE: 10% TO 95% RH FROM 32° TO 122° F (0 ° TO 50° C) BLACK SPKR - THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. VOLTAGE SPECIFICATIONS: MOUNTING NOTES: SPKR - THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. (38.1 mm) 1 1/2" EXTENSION RING (RACO NO. 203 OR EQUAL) SUPPLIED BY CONTRACTOR TrueAlert SPEAKER JUMPER SETTINGS APPROVAL I NE ER COVERS (FOR REPLACEMENT OR COLOR CONVERSION) MODEL DESCRIPTION NUMBER RED SPEAKER COVER WITH WHITE "FIRE" LETTERING 4905-9988 - U WHITE USE TO COVER SURFACE MOUNTED 1 1/2" DEEP WITH 1 1/2" DEEP EXTENSION, ALL EXTERNAL TO WALL 1 + 4906 STROBE 4906 STROBE ST K RED DIMENSIONS 5 3/8" H x 5 1/4" W x 3 3/16" D (136 mm x 133 mm x 81 mm) TOTAL SURFACE DEPTH WITH SPEAKER = 4 5/8" (117 mm) CKT FEATURES: 4" SQ. X 1 1/2" DEEP BOX (101.6mm X 38.1mm) (RACO NO. 191) SUPPLIED BY CONTRACTOR 25 VRMS OR 70.7 VRMS AUDIO INPUT FROM 4100/4003 (SEE WIRING NOTES) 4906 STROBE 2 1 - IN/OUT WIRING TERMINALS FOR 18 AWG TO 12 AWG RED DESCRIPTION E F MOUNTS TO 4" SQUARE OUTLET BOX, 1 1/2' DEEP WITH 1 1/2" DEEP BOX EXTENSION NOTE: ULC LISTED MODELS ARE DESIGNATED WITH A "CA" SUFFIX. MOUNTING ADAPTERS MODEL NUMBER 4905-9941 SURFACE MOUNT ADAPTER SKIRTS (DEEP) 4905-9942 INTENSITY SELECTION PLUG, ACCESSIBLE ONLY FROM REAR OF HOUSING; FACTORY SETTING IS FACP STROBE INTENSITY SETTING VIEWABLE THROUGH THE LENS CKT CKT INPUT INPUT LETTERING CURRENT VALUES ARE UL 1971 MAX RATING COLOR 15cd 30cd 75cd VOLTAGE 110cd 0.060 0.092 0.180 0.240 23 VRMS WHITE 17 VRMS 0.076 0.128 0.242 0.328 23 VRMS 0.060 0.092 0.180 0.240 RED 17 VRMS 0.076 0.328 0.128 0.242 PRODUCT INFORMATION MODEL 5 1/8" H x 5 " W x 1 1/2" D (130 mm X 127 mm X 38 mm) DATE (ERICO NO. 512), T-BAR WITH CLIPS AND SCREWS SUPPLIED BY CONTRACTOR TrueAlert STROBE UNITS- DIP SWITCH ADDRESS CHART FOUR INCH CONE (102mm) PROVIDES HIGH QUALITY TONE AND VOICE REPRODUCTION MULTI-TAPPED DESIGN PROVIDES OUTPUT POWER OF 1/4, 1/2, 1, OR 2 W WITH EITHER 25 OR 70.7 VRMS INPUT BLACK DIMENSIONS ISSUE D 3. VOLTAGE DROPS AND STANDBY BATTERY CALCULATIONS SHOULD BE MADE USING ANTICIPATED OPERATING CONDITIONS. OPERATION ABOVE 24VRMS DRAWS LESS CURRENT. 1. THE TrueAlert WALL-MOUNT SPEAKER ATTACHES DIRECTLY TO A STANDARD 4-INCH ELECTRICAL BOX WITH EXTENSION RING (NOT SUPPLIED) FLUSH MOUNTED OR SURFACE MOUNTED. MOUNTING THE SPEAKER TO THE 4-INCH SQUARE ELECTRICAL BOX IS SHOWN. ATTACH THE SPEAKER TO THE ELECTRICAL BOX USING TWO SCREWS (SUPPLIED) MOUNTED CROSS CORNER. 2. TO REMOVE THE COVER PRESS THE SNAP RELEASE IN THE BOTTOM OF THE SPEAKER WITH A FLAT TIP SCREWDRIVER WHILE PULLING THE COVER UP WITH THE OTHER HAND. 3. NAC TERMINALS (CKT+, CKT-) ARE NOT ACCESSIBLE THROUGH THE FRONT AFTER MOUNTING. PRODUCT SELECTION SPEAKER MOUNTING ADAPTERS AND BOXES MODEL DESCRIPTION NUMBER 4902-9716(CA) RED WITH WHITE "FIRE" LETTERING RECTANGULAR HOUSING, WALL MOUNT SPEAKER 4902-9717(CA) WHITE WITH RED "FIRE" LETTERING NO. TM TrueAlert (STYLE 4) VISIBLE NOTIFICATION APPLIANCES 4906 SERIES 1. TrueAlert APPLIANCES ARE REQUIRED TO BE CONNECTED TO A TrueAlert ADDRESSABLE CHANNEL WHERE BOTH POWER AND ADDRESSED COMMUNICATIONS ARE SUPPLIED. REFER TO DATA SHEET S4009-0003, (TrueAlert ADDRESSABLE CONTROLLER) FOR ADDITIONAL INFORMATION ABOUT WIRING RULES AND DISTANCE LIMITATIONS. 2. THE RATED RANGE LISTED IS THE ABSOLUTE OPERATING VOLTAGE RANGE. OPERATION OUTSIDE OF THIS RANGE MAY CAUSE PERMANENT DAMAGE TO THE APPLIANCE. PLEASE NOTE THAT 17 VRMS IS THE LOWEST OPERATING VOLTAGE THAT IS ALLOWED AT THE LAST APPLIANCE ON THE TRUEAlert NOTIFICATION APPLIANCE CIRCUIT UNDER WORST CASE CONDITIONS. VOLTAGE DROP AND STANDBY BATTERY CALCULATIONS SHOULD BE MADE USING ANTICIPATED OPERATING CONDITIONS. "LOW" HORN SETTING DRAWS APPROXIMATELY 5 mA LESS CURRENT AT EACH VOLTAGE LISTED. SEMI-FLUSH MOUNTING SELECTED TAP 1/4W 1/2W 1W 2W MODEL 4902-9716(CA), REVERBERANT CHAMBER, UL 1480 TEST 78 dBA 81 dBA 84 dBA 87 dBA 4902-9717(CA) RECT. HOUSING ANECHOIC CHAMBER, ON-AXIS, 1kHz INPUT 87 dBA 90 dBA 93 dBA 96 dBA SLC SLC + 1. REFER TO FIELD WIRING DIAGRAMS OF THE DRIVING TrueAlert COMPATIBLE CONTROLLER FOR ADDITIONAL SLC WIRING INFORMATION. REFER TO THE FIELD WIRING DIAGRAMS SUPPLIED WITH THE 4100/4003 FOR ADDITIONAL NAC WIRING INFORMATION. 2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. 3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS. 4. ALL TrueAlert SLC AND NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED. 5. POWERING THE S/V FROM AN APPLIANCE POWER SOURCE LESS THAN 17 VDC OR GREATER THAN 32 VDC MAY CAUSE PERMANENT DAMAGE TO THE S/V UNIT. 6. THE TrueAlert S/V CAN ONLY BE OPERATED THROUGH A 4009 TrueAlert ADDRESSABLE CONTROLLER OR TrueAlert COMPATIBLE FACP. 7. WHEN CONTROLLED FROM A 4009 TrueAlert ADDRESSABLE CONTROLLER, THE FACP SETTING IS NOT SUPPORTED. 8. MAXIMUM T-TAPPING LENGTH IS 100 FEET. SOUND OUTPUT RATINGS @ 10 FT. (3m) J C TM WATTAGE SETTING 1/4 1/2 70.7VRMS 1 2 1/4 1/2 25VRMS 1 2 HUMIDITY RANGE: 10% TO 95% RH FROM 32° TO 122° F (0 ° TO 50° C) SPKR - WIRING NOTES: SPECIFICATION NOTES: VOLTAGE DEPTH INTO BOX: 2 3/4" (70 MM) INPUT VOLTAGE: 25 OR 70.7 VRMS POWER TAPS: 1/4, 1/2, 1 AND 2W INPUT TERMINAL RATINGS: 18 TO 12 AWG FREQUENCY (FIRE ALARM): 400 TO 4000 Hz RESPONSE (GENERAL SIGNALING): 125 TO 12 k Hz TEMPERATURE RANGE: 32° TO 100 ° F ( 0° TO 38° C) SPKR - ENG SPECIFICATIONS: SPKR + SLC + TEMPERATURE RANGE: 32° TO 122° F (O° TO 50° C) HUMIDITY RANGE: 10% TO 93% NON-CONDENSING AT 100° F (38° C) CONNECTIONS: TERMINAL BLOCKS FOR 18 TO 12 AWG 2 TrueAlert SPEAKER JUMPER SETTINGS TrueAlert WALL MOUNTED SPEAKER BACK VIEW (SHOWN TAPPED AT 1/2 WATT @ 25 VRMS) SPKR + HOUSING DIMENSIONS (INCLUDING LENS): 4 3/4" x 2 5/16" x 2 5/8" D (121 mm x 75 mm x 67 mm) 1 1/2" DEEP EXTENSION (38.1mm) (RACO NO. 203) SUPPLIED BY CONTRACTOR J1 H 4906 S/V SPKR + SLC - 84.3 87.1* 89.7* TM JUMPER POSITION J1 TO TAP A J1 TO TAP B J1 TO TAP C J1 TO TAP D J1 TO TAP D J1 TO TAP E J1 TO TAP F J1 TO TAP G 4906 S/V SAN JOSE, CALIFORNIA END-OF-LINE RESISTOR (VALUE DEPENDANT ON FACP) 4906 S/V GENERAL SPECIFICATIONS: TrueAlert (STYLE Y) SPEAKER NOTIFICATION APPLIANCES 4902 SERIES FIRE ALARM SPEAKERS WITH MODELS FOR WALL MOUNTING UL LISTED TO STANDARD 1480 ULC LISTED MODELS (CA SUFFIX FOLLOWING THE MODEL NUMBER) FOUR INCH CONE (102mm) PROVIDES HIGH QUALITY TONE AND VOICE REPRODUCTION MULTI-TAPPED DESIGN PROVIDES OUTPUT POWER OF 1/4, 1/2, 1, 2 W WITH EITHER 25 OR 70.7 VRMS INPUT IN/OUT WIRING TERMINALS FOR 18 AWG TO 12 AWG MOUNTS TO 4" SQUARE OUTLET BOX, 1 1/2' DEEP WITH 1 1/2" DEEP BOX EXTENSION CAPACITOR INPUT FOR CONNECTION TO SUPERVISED NOTIFICATION APPLIANCE CIRCUIT RUGGED, HIGH IMPACT, FLAME RETARDANT THERMOPLASTIC HOUSING APPEARANCE THAT COMPLEMENTS TrueAlert STROBES AND SPEAKER/STROBES RED OR WHITE HOUSING WITH "FIRE" LETTERING SURFACE OR SEMI-FLUSH WALL MOUNT OPTIONAL MATCHING ADAPTER SKIRTS FOR COVERING SURFACE MOUNTED ELECTRICAL BOXES SPKR + * PERFORMANCE REFERENCE, NOMINAL AVERAGE CURRENTS WITH STROBES FLASHING + 6. THE TrueAlert V/O CAN ONLY BE OPERATED THROUGH A 4009 TrueAlert ADDRESSABLE CONTROLLER OR TrueAlert COMPATIBLE FACP. PRODUCT INFORMATION SPKR - SPKR + SPKR + SPKR - FROM TRUEALERT-COMPATIBLE SLC CONTROLLER (SEE WIRING NOTES) 4. ATTACH THE COVER TO THE APPLIANCE. 1. REFER TO FIELD WIRING DIAGRAMS OF THE DRIVING TrueAlert COMPATIBLE CONTROLLER FOR ADDITIONAL SLC WIRING INFORMATION. 2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. 3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS. 4. ALL TrueAlert SLC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED. 5. POWERING THE V/O FROM AN APPLIANCE POWER SOURCE LESS THAN 17 VDC OR GREATER THAN 32 VDC MAY CAUSE PERMANENT DAMAGE. TO THE V/O UNIT. (130 mm X 127 mm X 67 mm) 4906-9257 SPKR - SLC + *CURRENT DRAWS REFLECT STROBE FLASHING WIRING NOTES: HOUSING DIMENSIONS (INCLUDING LENS): 5 1/8" H X 5" W X 2 5/8" D TEMPERATURE RANGE: 32° TO 120° F (O° TO 49° C) HUMIDITY RANGE: 10% TO 93% NON-CONDENSING AT 104° F (40° C) CONNECTIONS: TERMINAL BLOCKS FOR 18 TO 12 AWG ALERT NOT USED 0=OFF FROM AUDIO NAC CHANNEL (4100/4003) (SEE WIRING NOTES) STROBE: CANDELA SELECTION PLUG RATED VOLTAGE RANGE: 17 TO 31 VDC SUPERVISORY REQUIREMENTS: 1 UNIT LOAD STROBE FLASH RATE: 1 Hz SYNCHRONIZED SLC LOADING: UP TO 43 TRUEAlert ADDRESSABLE SYNCHRONIZED STROBES MAXIMUM PER SLC MOUNTING INSTRUCTIONS: 1100 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 * VISIBLE OUTPUT RATING FOR THE GIVEN LENS COVER COLOR AT THE APPLIANCE SETTING. ** 17 VOLT CURRENT SHOWN AT THE HIGH CANDELA SETTINGS IS FOR USE WITH 4009T ONLY. GENERAL SPECIFICATIONS: WHITE PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING SPECIFICATIONS: 49VO FROM TrueAlert COMPATIBLE SLC CONTROLLER (SEE NOTES) 4906-9256 INDIVIDUALLY ADDRESSED HIGH INTENSITY VISIBLE NOTIFICATION APPLIANCE (STROBE) PROVIDES: SUPERVISION OF EACH INDIVIDUAL APPLIANCE'S WIRING AND CONNECTIONS ABILITY TO CONNECT USING "T" TAPPING FOR CLASS B/STYLE 4 CIRCUITS TO SIMPLIFY WIRING. COMPATIBILITY WITH ADA REQUIREMENTS MAGNETIC TEST DIAGNOSTICS TO ASSIST CHECKOUT AND TESTING OF APPLIANCES AND WIRING XENON STROBE OUTPUT IS MANUALLY SELECTABLE FOR 15, 30, 75, 110 CANDELA OR "FACP". THE "FACP" SETTING ALLOWS THE 4100U TO PROGRAM THE CANDELA SETTING. UL LISTED TO STANDARD 1971 LED INDICATOR AND MAGNETIC TEST FEATURE: LED INDICTOR CAN BE SELECTED TO DISPLAY EACH POLLING CYCLE TO INDICATE APPLIANCE SUPERVISION WHEN THE TrueAlert CONTROLLER IS IN DIAGNOSTIC MODE, THE MAGNETIC TEST PULSES THE LED TO INDICATE APPLIANCE ADDRESS AND IS SELECTABLE TO ALSO BRIEFLY FLASH THE STROBE TO CONFIRM OPERATION TrueAlert NOTIFICATION APPLIANCE DESIGN PROVIDES FLEXIBLE, EASY, AND CONVENIENT FLUSH OF SURFACE WALL BOX MOUNTING: REAR OF HOUSING DOES NOT EXTEND INTO BOX AND EASILY MOUNTS TO SINGLE GANG ELECTRICAL BOX DIP SWITCHES 5 & 6 0000 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 BLANK 1=ON SAN JOSE CITY COLLEGE STROBE INTENSITY SETTING VIEWABLE THROUGH THE LENS FEATURES: STROBE INTENSITY SETTING VIEWABLE THROUGH THE RIGHT SIDE OF THE COVER TrueAlert V/O UNITS- DIP SWITCH ADDRESS CHART WHITE - ANECHOIC CHAMBER, ULC-S541 TESTING, 25 VRMS 81.6 WHEN SURFACE MOUNTING USE RED SKIRT NO. 4905-9937 OR WHITE SKIRT NO. 4905-9940 INTENSITY SELECTION PLUG, ACCESSIBLE ONLY FROM REAR OF HOUSING; FACTORY SETTING IS FACP. CONTROLLED BY PANEL. 581 531 PCAF 51 03 57 011 4906-9255 PRODUCT INFORMATION BACKPLATE BOTTOM OF LENS IS EITHER EVEN WITH OR SLIGHTLY ABOVE BOTTOM OF COMPATABLE BOXES FIRE 011 57 03 51 PCAF MSB - ANECHOIC CHAMBER, ULC-S541 TESTING, 70.7 VRMS 80.9 84.1 87.3* 90.2* - UL STANDARD 1480 SPEAKER OUTPUT RATING CATEGORIES ARE BASED UPON 3 dBA INCREMENTS. - SELECT TAPS AS INDICATED TO SATISFY FOR ULC FIRE ALARM APPLICATION REQUIREMENT OF 85 dBA MINIMUM. - SPEAKERS ARE NOT ADDRESSABLE AND ARE FOR CONNECTION TO CONVENTIONAL FIRE ALARM AUDIO CIRCUITS. IMPORTANT! WALL MOUNT INSTALLATION HEIGHT REFERENCE ELECTRICAL BOX OUTLINE WHITE CURRENT VALUES ARE UL 1971 MAX RATING LETTERING COLOR 15cd 30cd 75cd VOLTAGE 110cd 0.060 0.092 0.180 0.240 23 VRMS RED 17 VRMS 0.076 0.128 0.242 0.328 23 VRMS 0.060 0.092 0.180 0.240 17 VRMS 0.076 0.128 0.242 0.328 23 VRMS 0.060 0.092 0.180 0.240 RED 17 VRMS 0.076 0.128 0.242 0.328 23 VRMS 0.060 0.092 0.180 0.240 RED 17 VRMS 0.076 0.128 0.242 0.328 - WATTAGE TAP (25 VRMS OR 70.7 VRMS INPUT) 1/4W 1/2W 1W - REVERBERANT CHAMBER, UL 1480 TEST 76 79 82 85 OPTIONAL LENS COVER FOR COLORED LENS COVER 4906-9254 B INTENSITY SELECTION PLUG, ACCESSIBLE ONLY FROM REAR OF HOUSING; FACTORY SETTING IS FACP 1 2 3 4 5 6 7 8 SPEAKER - INPUT VOLTAGE: 25 OR 70.7 VRMS, SEE NOTE 4 - POWER TAPS: 1/4, 1/2, 1W, AND 2W - FREQUENCY RESPONSE: FIRE ALARM: 400 TO 4000 Hz SPEAKER OUTPUT RATINGS (dBA @ 10 FT. (3m) SLC SLC + SLC + LETTERING ADDRESS SETTING DIP SWITCH IS BEHIND STROBE ASSEMBLY; SELECT ADDRESS BEFORE INSERTING INTO HOUSING. DIP SWITCHES 1 ~ 6 ARE USED TO SET ADDRESS. DIP SWITCHES 7 AND 8 ARE NOT USED AND SHOULD BE SET TO "OFF". L SPKR + SPKR - MODEL NUMBER SPKR + SPKR + COVER COLOR MAGNETIC TEST LOCATION IA LETTERING LENS COLOR COLOR WHITE SPKR - SPKR - NOT USED LSB 1100 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 J STROBE: RATED VOLTAGE RANGE: 17 TO 31 VRMS SUPERVISORY REQUIREMENTS: 1 UNIT LOAD STROBE FLASH RATE: 1 Hz 49VO-WWF(-BA) 1. THE TrueAlert S/V ATTACHES DIRECTLY TO A STANDARD 4-INCH ELECTRICAL BOX (NOT SUPPLIED), FLUSH MOUNTED OR SURFACE MOUNTED. 2. THERE ARE FOUR HOLES FOR 4-INCH SQUARE ELECTRICAL BOX MOUNTING. SECURE THE HOUSING TO THE BOX USING TWO MOUNTING SCREWS. THE TWO MOUNTING SCREWS ARE PLACED CROSS CORNER (OPPOSITE TOP AND BOTTOM HOLES) 3. TO REMOVE THE COVER, PRESS THE SNAP RELEASE IN (ONE AT A TIME) WITH A FLAT TIP SCREWDRIVER WHILE PULLING UP THE COVER WITH THE OTHER HAND. ADDRESS SWITCH (SW1 IS ACCESSIBLE WITH THE COVER REMOVED). 0100 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 1 2 3 4 5 6 7 8 SPECIFICATIONS: RED STROBE INTENSITY SETTING VIEWABLE THROUGH THE LENS SEMI-FLUSH MOUNTING MOUNTING NOTES: APPLIANCE CONFIGURATION SETTINGS POSITION 1: CONFIGURATION CONTROL - LOCAL (OFF), PANEL (ON) POSITION 2: AUDIBLE VOLUME - HIGH (OFF), LOW (ON) POSITION 3: CANADIAN HORN MODE - SET TO OFF POSITION 4: LEGACY NAC MODE - SET TO OFF POSITION 5,6,7: UNUSED - SET TO OFF POSITION 8: CLEAR/COLOR LENS - ALARM (OFF), ALERT (ON) LED INDICATOR AND MAGNETIC TEST FEATURE: LED INDICTOR CAN BE ELECTED TO DISPLAY EACH POLLING CYCLE TO INDICICATE APPLIANCE SUPERVISION WHEN THE TrueAlert CONTROLLER IS IN DIAGNOSTIC MODE, THE MAGNETIC TEST PULSES THE LED TO INDICATE APPLIANCE ADDRESS AND IS SELECTABLE TO ALSO BRIEFLY FLASH THE STROBE TO CONFIRM OPERATION 49VO-WRF(-BA) SPEAKER HOUSING DIMENSIONS : 7 1/2" DIA. X 1/2"D (191MM X 13MM) STROBE LENS PROTRUSION DIMENSIONS : 2 5/8" (67MM) ABOVE SPEAKER HOUSING TEMPERATURE RANGE: 32° F TO 122° F (0° TO 50° C) HUMIDITY RANGE: 10% TO 93% NON-CONDENSING AT 100° F (38° C) DEPTH INTO BOX 2 3/4" (70MM) SPEAKER TAP SELECTION: SINGLE JUMPER WIRE WITH PRESSURE CONNECTOR ATTACHES TO ONE OF 8 TERMINALS CONNECTIONS: TERMINALS FOR 18 TO 12 AWG, SEPARATE TERMINALS FOR SPEAKER AND TrueAlert STROBE CONNECTION STROBE - RATED VOLTAGE: 17 TO 31 VRMS - SUPERVISORY REQUIREMENTS: 1 UNIT LOAD - STROBE FLASH RATE: 1Hz - SYNCHRONIZED SLC LOADING: UP TO 43 TrueAlert ADDRESSABLE SYNCHRONIZED STROBES MAXIMUM PER SLC TM TrueAlert ES (STYLE 4 SLC) VISIBLE ONLY NOTIFICATION APPLIANCES 49VO SERIES TrueAlert 2-WIRE ADDRESSABLE CONTROL OF VISIBLE AND AUDIBLE NOTIFICATION ACTIVATES APPLIANCES WITH: HORNS SOUNDED AS TEMPORAL OR MARCH TIME PATTERN, OR ON CONTINUOUSLY, CONTROLLED SEPARATELY FROM VISIBLE APPLIANCES ON THE SAME TWO-WIRE CIRCUIT F GENERAL SPECIFICATIONS: SLC + TrueAlert SPEAKER JUMPER SETTINGS INDIVIDUALLY ADDRESSED WALL MOUNT VISIBLE NOTIFICATION APPLIANCES WITH EFFICIENT ELECTRONIC HIGH INTENSITY XENON STROBE PROVIDES: SUPERVISION OF EACH INDIVIDUAL APPLIANCE'S WIRING AND CONNECTIONS ABILITY TO CONNECT USING "T" TAPPING FOR CLASS B/STYLE 4 CIRCUITS TO SIMPLIFY WIRING HORNS CONTROLLED SEPARATELY FROM STROBES ON THE SAME 2-WIRE CIRCUIT ALLOWING "ON-UNTIL-SILENCED" AND "ON-UNTIL RESET". XENON STROBE OUTPUT IS MANUALLY SELECTABLE FOR 15, 30, 75, 110, 135 AND 185 CANDELA OR "FACP". THE "FACP" SETTING ALLOWS THE 4100 TO PROGRAM THE CANDELA SETTING. IN/OUT WIRING ACCESSIBILITY FROM FRONT OF HOUSING PROVIDES EASY ACCESS FOR INSTALLATION, INSPECTION, AND TESTING MAGNETIC TEST DIAGNOSTICS TO ASSIST CHECKOUT AND TESTING OF APPLIANCES AND WIRING UL LISTED TO STANDARD 1971 COVER COLOR DIP SWITCHES (SW1) MAGNETIC TEST LOCATION FROM TRUEALERT-COMPATIBLE SLC CONTROLLER (SEE WIRING NOTES) - UL STANDARD 1480 SPEAKER OUTPUT RATING CATEGORIES ARE BASED UPON 3 dBA INCREMENTS. - SPEAKERS ARE NOT ADDRESSABLE AND ARE FOR CONNECTION TO CONVENTIONAL FIRE ALARM AUDIO CIRCUITS. MODEL NUMBER 82" MIN. FROM AUDIO NAC CHANNEL (4100/4003) (SEE WIRING NOTES) - WATTAGE TAP (25 VRMS OR 70.7 VRMS INPUT) 1/4W 1/2W 1W 2W - REVERBERANT CHAMBER, UL 1480 TEST 76 79 82 85 - ANECHOIC CHAMBER, ON-AXIS, 1kHz INPUT 87 90 93 96 E 011 57 03 51 PCAF NFPA 72 REQUIRES THAT THE ENTIRE LENS BE NOT LESS THAN 80" AND NOT GREATER THAN 96" ABOVE THE FINISHED FLOOR. 4906 S/V GENERAL SIGNALING: 125 TO 12 kHz SPEAKER OUTPUT RATINGS (dBA @ 10 FT. (3m) D 78-1/2" MIN. 1 2 3 4 5 6 7 8 0=OFF INTENSITY SELECTION PLUG, ACCESSIBLE ONLY FROM REAR OF HOUSING; FACTORY SETTING IS FACP 1-1/2" MSB 1=ON JUMPER LOCATED ON BACK OF APPLIANCE CL 1000 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 0000 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 0000 1000 0100 1100 0010 1010 DIP SWITCHES 0110 1 THRU 4 1110 0001 1001 0101 1101 0011 1011 0111 1111 ADDRESS SWITCH SW2 LSB 4" SQUARE BOX OUTLINE 4" 2975-9145 BOX OUTLINE 1100 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 G 0000 1000 0100 1100 0010 1010 DIP SWITCHES 0110 1 THRU 4 1110 0001 1001 0101 1101 0011 1011 0111 1111 0100 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 DIP SWITCHES 5 & 6 F 1000 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 0000 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 RESERVED FOR FUTURE USE 25V DIP SWITCHES 5 & 6 WIRING INPUT TERMINALS AND SPEAKER TAP SELECTION ARE ACCESSIBLE FROM REAR OF SPEAKER HOUSING. TrueAlert S/V UNITS- DIP SWITCH ADDRESS CHART E TrueAlert S/V UNITS- DIP SWITCH ADDRESS CHART STROBE - RATED VOLTAGE: 17 TO 31 VRMS - SUPERVISORY REQUIREMENTS: 1 UNIT LOAD - STROBE FLASH RATE: 1Hz - SYNCHRONIZED SLC LOADING: UP TO 43 TrueAlert ADDRESSABLE SYNCHRONIZED STROBES MAXIMUM PER SLC *CURRENT DRAWS REFLECT STROBE FLASHING COVER LETTERING CURRENT VALUES ARE UL 1971 MAX RATING MODEL NUMBER COLOR COLOR 15cd 30cd 75cd VOLTAGE 110cd 0.060 0.240 0.092 0.180 23 VRMS 4906-9251 RED WHITE 17 VRMS 0.076 0.328 0.128 0.242 23 VRMS 0.060 0.092 0.180 0.240 WHITE RED 4906-9253 17 VRMS 0.076 0.328 0.128 0.242 PRODUCT INFORMATION FEATURES: IMPORTANT! WALL MOUNT INSTALLATION HEIGHT REFERENCE A 1 1/2" DEEP EXTENSION (38.1mm) (RACO NO. 203) SUPPLIED BY CONTRACTOR CAUTION: DO NOT BRING CONDUIT THROUGH BACK OF ELECTRICAL BOX. RE WHITE S/V COVER WITH RED "FIRE" LETTERING GENERAL SPECIFICATIONS: SPEAKER - INPUT VOLTAGE: 25 OR 70.7 VRMS, SEE NOTE 4 - POWER TAPS: 1/4, 1/2, 1W, AND 2W - FREQUENCY RESPONSE: FIRE ALARM: 400 TO 4000 Hz 7 1/4" H X 5" W X 1 3/8"D (184 mm X 127 mm X 35 mm) WATTAGE SETTING 1/4 1/2 70.7VRMS 1 2 1/4 1/2 25VRMS 1 2 VOLTAGE R EG I S T E RED S/V COVER WITH WHITE "FIRE" LETTERING DIMENSIONS (INCLUDING LENS) : 7 1/4" (184mm) H X 5" (127mm) W X 2 5/8" (67mm) D TEMPERATURE RANGE: 32° F TO 122° F (0° TO 50° C) HUMIDITY RANGE: 10% TO 93% NON-CONDENSING AT 100° F (38° C) DEPTH INTO BOX: 2 1/2" (64mm) SPEAKER TAP SELECTION: SINGLE JUMPER WIRE WITH PRESSURE CONNECTOR ATTACHES TO ONE OF 8 TERMINALS CONNECTIONS: TERMINALS FOR 18 TO 12 AWG, SEPARATE TERMINALS FOR SPEAKER AND TrueAlert STROBE CONNECTION FOR VISIBLE LENS MOUNTING HIEGHT TO MEET "ADA" 80" MINIMUM, THE 4" SQUARE BACKBOX IS TO BE INSTALLED AT A HIEGHT OF 82" FROM THE FLOOR TO THE BOTTOM OF THE BOX. C DIMENSIONS COVERS (FOR REPLACEMENT OR COLOR CONVERSION) JUMPER POSITION J1 TO TAP A J1 TO TAP B J1 TO TAP C J1 TO TAP D J1 TO TAP D J1 TO TAP E J1 TO TAP F J1 TO TAP G TB1 MOUNTING BOX, RED FOR SURFACE OR FLUSH MOUNT REQUIRES ADAPTER PLATE 4905-9903 (THIS BOX MAY BE AVAILABLE FOR RETROFIT APPLICATIONS) RESERVED FOR FUTURE USE 1 1/2" DEEP EXTENSION (38.1mm) (RACO NO. 203) SUPPLIED BY CONTRACTOR CAUTION: DO NOT BRING CONDUIT THROUGH BACK OF ELECTRICAL BOX. 8 5/16" H X 5 3/4" W X 0.060" THICK (211 mm X 146 mm X 1.5 mm) 7 7/8" H X 5 1/8" W X 2 3/4"D (200 mm X 130 mm X 70 mm) ADAPTER PLATE, RED, REQUIRED TO MOUNT S/V ON 2975-9145 1 4" SQ. X 1 1/2" DEEP BOX (101.6mm X 38.1mm) (RACO NO. 191) SUPPLIED BY CONTRACTOR TrueAlert SPEAKER JUMPER SETTINGS AUDIBLE NOTIFICATION APPLIANCE (SPEAKER) HIGH QUALITY VOICE AND TONE REPRODUCTION WITH TAPS FOR 1/4, 1/2, 1W, OR 2W AT 25 OR 70.7 VRMS UL LISTED TO STANDARD 1480 SPEAKERS ARE WIRED SEPARATELY FROM TRUEALERT STROBE WIRING TrueAlert VISIBLE NOTIFICATION APPLIANCE (STROBE) XENON STROBE OUTPUT IS MANUALLY SELECTABLE FOR 15, 30, 75, 110 CANDELA OR "FACP". THE "FACP" SETTING ALLOWS THE 4100U TO PROGRAM THE CANDELA SETTING. UL LISTED TO STANDARD 1971 SUPERVISION OF EACH INDIVIDUAL STROBE'S WIRING AND CONNECTIONS WITH ACTIVATION AT A SYNCHRONIZED 1 Hz FLASH RATE MAGNETIC TEST DIAGNOSTICS TO ASSIST CHECKOUT AND TESTING OF TRUEALERT STROBE AND WIRING RUGGED, HIGH IMPACT, FLAME RETARTANT THERMOPLASTIC HOUSING AVAILABLE IN RED OR WHITE (COVERS ARE AVAILABLE SEPARATELY TO CONVERT COLORS) LED INDICATOR CAN BE SELECTED TO DISPLAY EACH POLLING CYCLE TO INDICATE APPLIANCE SUPERVISION WHEN THE TRUEALERT CONTROLLER IS IN DIAGNOSTIC MODE, THE MAGNETIC TEST PULSES THE LED TO INDICATE APPLIANCE ADDRESS AND IS SELECTABLE TO ALSO BRIEFLY FLASH THE STROBE TO CONFIRM OPERATION D B SURFACE MOUNT WHITE ADAPTER SKIRT 7 3/4" H X 5 3/8" W X 3 3/16"D (197 mm X 137 mm X 81 mm) DEPTH WITH S/V=5 7/8" (149mm) C A REQUIRED WHEN MOUNTING TO SURFACE MOUNTED ELECTRICAL BOX 4" SQUARE, 1 1/2" DEEP WITH 1 1/2" DEEP EXTENSION SURFACE MOUNT RED ADAPTER SKIRT 4905-9946 AUDIBLE NOTIFICATION APPLIANCE (SPEAKER) 4905-9947 HIGH QUALITY VOICE AND TONE REPRODUCTION WITH TAPS FOR 1/4, 1/2, 1W, OR 2W AT 25 OR 70.7 VRMS 4905-9903 UL LISTED TO STANDARD 1480 SPEAKERS ARE WIRED SEPARATELY FROM TRUEALERT 2975-9145 STROBE WIRING TrueAlert VISIBLE NOTIFICATION APPLIANCE (STROBE) MODEL XENON STROBE OUTPUT IS MANUALLY SELECTABLE FOR 15, 30, NUMBER 75, 110 CANDELA OR "FACP". THE "FACP" SETTING ALLOWS THE 4905-9996 4100 TO PROGRAM THE CANDELA SETTING. 4905-9997 UL LISTED TO STANDARD 1971 SUPERVISION OF EACH INDIVIDUAL STROBE'S WIRING AND CONNECTIONS WITH ACTIVATION AT A SYNCHRONIZED 1 Hz FLASH RATE MAGNETIC TEST DIAGNOSTICS TO ASSIST CHECKOUT AND TESTING OF TRUEALERT STROBE AND WIRING RUGGED, HIGH IMPACT, FLAME RETARTANT THERMOPLASTIC HOUSING AVAILABLE IN RED OR WHITE (COVERS ARE AVAILABLE SEPARATELY TO CONVERT COLORS) LED INDICATOR CAN BE SELECTED TO DISPLAY EACH POLLING CYCLE TO INDICATE APPLIANCE SUPERVISION WHEN THE TRUEALERT CONTROLLER IS IN DIAGNOSTIC MODE, THE MAGNETIC TEST PULSES THE LED TO INDICATE APPLIANCE ADDRESS AND IS SELECTABLE TO ALSO BRIEFLY FLASH THE STROBE TO CONFIRM OPERATION 4" SQ. X 1 1/2" DEEP BOX (101.6mm X 38.1mm) (RACO NO. 191) SUPPLIED BY CONTRACTOR DIMENSIONS MOUNTING ADAPTERS AND BOXES 2 TrueAlert SLC (STYLE 4) SPEAKER/VISIBLE NOTIFICATION APPLIANCES 4906 SERIES PRODUCT INFORMATION FEATURES: 70.7V MODEL NUMBER 3 TM TrueAlert ADDRESSABLE (STYLE 4) SPEAKER/VISIBLE NOTIFICATION APPLIANCES 4906 SERIES PRODUCT INFORMATION FEATURES: 4 B 10 A 11 J1 12 IF LAST APPLIANCE ON CIRCUIT, CONNECT EOLR (SEE WIRING NOTES) DIMENSIONS 7 1/2" DIA x 1/2"D (191mm x 13mm) DIMENSIONS 23 11/16" L x 13 3/8" W x .024" THK (602 mm x 340 mm x .508 mm) RED RED PROJECT NO: 1089-0001 DATE: 1.12.2015 WIRING NOTES 1. REFER TO FIELD WIRING DIAGRAMS SUPPLIED WITH THE 4100/4003 FOR ADDITIONAL NAC WIRING INFORMATION. 2. NOTIFICATION APPLIANCES ARE RATED PER INDIVIDUAL NAMEPLATE LABEL. 3. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. DO NOT LOOP WIRES UNDER TERMINALS. 4. ALL NAC WIRING CONNECTIONS ARE SUPERVISED AND POWER-LIMITED. 5. END-OF-LINE RESISTOR VALUE DEPENDENT ON CONTROL PANEL. K SHEET NO: FA7.03 12 11 10 9 8 7 6 5 4 3 2 1 DSA SUBMITTAL 9 8 7 DEVICE MOUNTING HEIGHT REFERENCE (PER NFPA 72) FIRE FIRE 3' (MIN) (914mm MIN) NFPA 72 AUDIBLE APPLIANCE 6" MIN (152.4mm MIN) BELOW FINISHED CEILING REF. 80" MIN (IBC) (2032mm MIN) C 4" (102mm) TO BOTTOM OF LENS 48" MAX (NFPA, ADA) 42" MIN (NFPA) CLASS 'A' + - WIRING TECHNIQUES FOR SHIELDED CABLE: EXAMPLE: #18-2 AWG SHIELDED TWISTED-PAIR CABLE A SHIELDS AND DRAINS MUST NEVER TOUCH GROUND. MOST GROUNDS ARE DUE TO SHIELDING ISSUES. BY CREATING A PROPER PROCEDURE FOR WIRE HANDLING WITH ADDRESSABLE CIRCUITS MOST GROUNDS AND SHORTS CAN BE ELIMINATED. ALL UNSHIELDED WIRE MUST BE ENTIRELY IN GROUND CONDUIT. PIGTAILS, (T-TAP) WIRING IS PERMITTED TO ADDRESSABLE DEVICES FOR CLASS B CIRCUIT WIRING. 12" (MAX) DRAIN WIRE PREPARE THE CABLE BY REMOVING 2" TO 4" OF JACKET AS NEEDED. EXAMPLE FOR WIRING LABELING 4 WIRE TAG DISCARD SHIELD REUSE INSULATION WALL MOUNTED SMOKE/HEAT DETECTOR DOOR WIDTH LESS 3" (76mm) SIDE WALL (1219mm) (1219mm MAX) (1067mm MIN) MEASUREMENTS SHOWN ARE TO TOP OF PULL HANDLE 9 2 N1:M 1. ALL WIRING IS TO BE COPPER CONDUCTOR. ALL EQUIPMENT MUST BE INSTALLED IN ACCORDANCE WITH THE MANUFACTURERS RECOMMENDATIONS AND THE SPECIFICATIONS AND STANDARDS DRAIN WIRE OF THE AUTHORITY HAVING JURISDICTION. THE INSTALLATION OF ALL WIRING, CABLE AND EQUIPMENT MUST BE IN ACCORDANCE WITH NFPA 70, NATIONAL ELECTRICAL CODE NEC), AND SPECIFICALLY WITH ARTICLE 760, FIRE ALARM PROTECTIVE SIGNALING SYSTEMS; ARTICLE 800, COMMUNICATION CIRCUITS, WHERE APPLICABLE. 5 2. IF SHIELDED WIRE IS USED, THE FOLLOWING MUST BE OBSERVED: (+) A. METALLIC CONTINUITY OF THE SHIELD MUST BE MAINTAINED AND RED INSULATED THROUGHOUT THE ENTIRE LENGTH OF THE CABLE. STRIP OFF APPROX. B. SHIELDS SHALL ONLY BE CONNECTED AT THE CONTROL UNIT. 1-2 INCHES OF SHIELD MUST NOT BE CONNECTED TO, OR TOUCH CONDUIT, ELECTRICAL BLACK INSULATION TO SLIDE ONTO DRAIN WIRE. BOXES, OR ASSOCIATED HARDWARE AT ANY POINT. C. THE ENTIRE LENGTH OF THE CABLE MUST HAVE A RESISTANCE GREATER THAN 1 MEGOHM TO EARTH. (-) D. ALL CONDUCTORS ARE TO BE FREE OF SHORTS AND GROUNDS. BLACK 3. UNDERGROUND WIRING MUST BE LISTED FOR APPLICATION AND FREE OF ALL WATER. 4. WIRING OTHER THAN THAT CONNECTED TO ELEVATOR CABS MUST NOT BE RUN REDUCE EXPOSED WIRES TO IN ELEVATOR SHAFTS (REF.NFPA 70, ARTICLE 620). ABOUT 5/16" TO 3/8" FOR 5. WIRING IN DUCTS, PLENUMS AND OTHER AIR HANDLING SPACES MUST BE LISTED INSERTION INTO BOX-TYPE FOR PLENUM USE AND INSTALLED IN ACCORDANCE WITH NFPA 70, ARTICLE 300. OR SCREW-CLAMP TERMINALS. 6. SPLICING IS PERMITTED IN ACCORDANCE WITH NFPA 70. ALL JUNCTIONS MUST BE INSULATED AS SOUNDLY AS THE ORIGINAL JACKET. CONTINUITY OF ANY SHIELD (WHERE USED) MUST BE MAINTAINED. 7. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT. 8. THE COMMUNICATION CIRCUIT MEETS THE OPERATIONAL CHARACTERISTICS DEFINED FOR A STYLE 4 AND STYLE 6 SIGNALING LINE CIRCUIT. MAXIMUM WIRE RUN NOT TO EXCEED 2500 FT. 9. ALL CIRCUITS ARE SUPERVISED AND POWER-LIMITED UNLESS OTHERWISE INDICATED. SHIELD WIRES ARE NOT SUPERVISED. 10. OPERATING POWER, FOR IDNet DEVICES, MUST ORIGINATE FROM A POWER-LIMITED POWER SUPPLY LISTED FOR FIRE PROTECTIVE SIGNALING USE OR, FROM THE F.A. CONTROL PANEL POWER SUPPLIES INDICATED IN THE APPROPRIATE DIAGRAM. MAXIMUM WIRE NOT TO EXCEED 1KM (3270 FT). 11. WHEN COMMUNICATION WIRING OR OPERATING WIRING LEAVES THE BUILDING, OVERVOLTAGE PROTECTORS ARE REQUIRED; USE 2081-9044, INSTALL ONE WHERE IT LEAVES THE BUILDING AND ONE WHERE IT ENTERS THE NEXT BUILDING. 12. TO PREVENT CONFUSION AND POSSIBLE ERRORS, TAG ALL CONDUCTORS, CODE AT INSTALLATION, TO IDENTIFY CIRCUIT ASSIGNMENT, POLARITY AND IN OR OUT DIRECTION OF THE WIRING. LOG ON AS-BUILTS. 13. LEAVE ADEQUATE SLACK IN THE WIRING TO ALLOW FOR TROUBLE SHOOTING. SIMPLEXGRINNELL IS NOT RESPONSIBLE FOR ELECTRICAL CONTRACTOR'S WIRE CONDITIONS. 14. IDNet COMMUNICATION LINE SPECS.: 15. IDNET MAXIMUM NUMBER OF DEVICES: MAX. 36 VDC @ .5A NON-CODED 250 3333 BAUD CODED PIEZO BASES 43 MAX. 33 MAX. LINE RESISTANCE 217 ADDRESSES STILL AVAILABLE FOR OTHER DEVICES. FINISHED WALL FINISHED FLOOR + PRODUCT INFORMATION SHIELD MAGNETIC DOOR HOLDER 48" MAX (ADA) 9.A UL LISTED FIRE PROTECTIVE SIGNALING CABLES MAY BE SELECTED FROM THE SIMPLEXGRINNELL WIRE & CABLE TABLE, #WIRE TABLE GENERAL WIRING GUIDELINES SIMPLEX NOTE: REFER TO THE PROPER DEVICE INSTALLATION INSTRUCTIONS FOR BACKBOX MOUNTING HEIGHT. 1 SIGNALING LINE (ADDRESSABLE) CIRCUITS SHIELDING EXAMPLE TRIM AWAY ONLY THE SHIELD AND KEEP THE DRAIN 3 WIRE UNDAMAGED. MANUAL PULL STATION FIRE PHONE JACK 2 MOST SHORTS ARE SHIELD TO CONDUCTOR. (305mm MAX) HEAT DETECTORS NEVER HERE 5" (127mm) 80" MIN (ADA) (2032mm MIN) 80" MIN (NFPA) (2032mm MIN) 3 CONDUIT SYSTEM MUST HAVE A GOOD REFERENCE TO EARTH GROUND ACCEPTED HERE TO EXIT DOOR 5' (MAX.) (1524mm) 96" MAX (NFPA, ADA) (2440mm MAX) ABOVE FINISHED FLOOR TO TOP OF LENS REF. 96" MAX (IBC) (2440mm MAX) ABOVE FINISHED FLOOR CEILING CEILING MOUNTED SMOKE/HEAT DETECTOR SYNCHRONIZE MORE THAN TWO APPLIANCES IN ANY FIELD OF VIEW. NOTE: MEASUREMENTS SHOWN ARE TO THE CLOSEST EDGE OF THE DETECTOR. 4" (102mm) 90" MIN (2286mm MIN) ABOVE FINISHED FLOOR (OTHER MOUNTING HEIGHTS SHALL BE PERMITTED BY THE AHJ PROVIDING IT MEETS THE SOUND LEVEL OUTPUT REQUIRED.) AUDIBLE/VISUAL & VISUAL ONLY APPLIANCES B 2 AUDIBLE ONLY FIRE THE 4" REQUIREMENT FOR SMOKE DETECTORS HAS BEEN REMOVED FROM THE 2010 EDITION OF NFPA 72 USE ONLY UL LISTED FIRE ALARM TWISTED SHIELDED PAIR CABLE (TSP) FOR IDNETS, DATA COMM. LINES, AUDIO, PHONE & SPEAKER WIRING IN A FIRE ALARM SYSTEM. MIN. SIZE IS 18-2 AWG SOLID STP. CUT 4 + CLASS 'B' + - B TO PREVENT CONFUSION AND POSSIBLE ERRORS, ALL WIRES MUST BE TAGGED. SEE WIRE LEGEND FOR TYPES. WIRES MUST BE CONNECTED SEPARATELY UNDER TERMINALS. A CONTINUOUS WIRE LOOP IS NOT ALLOWED. DRAIN WIRE ONLY CLASS B IDNET, MAPNET OR DATA COMM. CABLE MAY BE T-TAPPED. IT MUST BE DONE IN A JUNCTION BOX WITH CABLE STRAIN RELIEF I.E. CORD CLAMP/BUSHING, AND TAPE WRAPPED AS SHOWN HERE. PUSH REUSED INSULATION CAREFULLY DOWN INTO JACKET. SECURE WITH ELECTRICAL TAPE. 6 PHYSICAL EDUCATION BUILDING AND RENOVATED LAB BUILDING SAN JOSE, CALIFORNIA DRAIN WIRE ELECTRICAL TAPE. 7 STRIP THE INSULATED WIRES ABOUT 5/16" TO 3/8" FOR INSERTION INTO BOX-TYPE OR SCREW-CLAMP TERMINALS ON THE ADDRESSABLE DEVICE. C SECURE THE DRAIN WIRES INTO THE CONNECTOR APPROVED FOR THE PURPOSE. WIRES MUST BE TIGHT ENOUGH TO HOLD SECURELY AND NOT SLIP OUT OF THE CONNECTION. ENSURE BARE DRAINS ARE SECURED AND UNABLE TO MAKE EXTERNAL CONTACT. SEE NOTE 2 8 THE SHIELD/DRAIN IS NEVER CONNECTED TO THE DEVICE. TRIM THE BARE DRAIN TO ABOUT 1-1/2". JOIN THEM WITH AN ELECTRICAL CONNECTOR LISTED AND APPROVED FOR WIRE SPLICING. NO. INSTRUCTIONS D 4081-9001 4081-9002 4081-9003 2.2K 733-893 3.3K 733-896 4.7K 1ST BAND RED 2ND BAND RED ORANGE YELLOW 4TH BAND 3RD BAND GOLD RED ORANGE VIOLET 5TH BAND RED CIRCUIT TYPE 1/2 ANNUNCIATOR (4300) 4004, 4010 (TROUBLE) N.O. INITIATING PULL, SMOKE, HEAT, WATERFLOW, TAMPER, ETC. 24 PT. I/O SWITCH SUPV. CURRENT LIMITED N.O. INITIATING NOTIFICATION (DACT) N.O. INITIATING PULL, SMOKE, HEAT, WATERFLOW, TAMPER, ETC. 4004*, 4004R, 4005*, 4006, 4100, 4120, 4100U, ZAM'S N/A GOLD RED WATTS 1 N/A 1/2 N/A GOLD E 4081-9004 733-886 6.8K BLUE GREY RED 1/2 N/A GOLD CURRENT LIMITED N.O. INITIATING (IN LINE) 733-984 1.8K BROWN GREY RED GOLD N/A 1/2 4081-9006 733-890 560 GREEN BLUE BROWN GOLD N/A 1 N.C. INITIATING (EOLR) 4081-9007 733-891 1.2K BROWN RED RED GOLD N/A 1 N.C. INITIATING (EOLR) 4081-9008 733-894 10K BROWN BLACK ORANGE GOLD N/A 1/2 4081-9009 4081-9010 733-912 20 733-973 1K RED BLACK BROWN BLACK BLACK RED 1 N/A GOLD TO MR-101 RELAY COIL N.C. INITIATING (ACROSS CONTACTS) 24 PT. I/O (ACROSS CONTACTS) CURRENT LIMITED N.O. INITIATING (IN SERIES WITH CONTACT) 1 N/A GOLD F G 4081-9011 4081-9012 4081-9013 733-974 733-985 734-086 100 22K 4.99K BROWN RED YELLOW BLACK RED WHITE BROWN ORANGE WHITE GOLD GOLD BROWN N/A N/A BROWN 1/2 1/2 1/2 4081-9014 734-092 2.4K RED YELLOW RED GOLD N/A 1/2 4081-9015 734-093 1.5K BROWN GREEN RED GOLD N/A 1/2 4081-9016 4081-9017 4081-9018 734-149 734-171 734-168 378-090 378-046 378-069 150K 3.9K 10K 8.2K 5.6K 12K BROWN ORANGE BROWN GRAY GREEN BROWN GREEN WHITE BLACK RED BLUE RED YELLOW RED ORANGE RED RED ORANGE GOLD GOLD GOLD GOLD GOLD GOLD N/A N/A N/A N/A N/A N/A 1/2 1 1 1/2 1/2 1/2 4 3/4" 7. DO NOT LOCATE POWER-LIMITED WIRING IN THE SHADED AREAS OF THE BACKBOX, THIS AREA IS RESERVED FOR NON-POWER LIMITED CIRCUITRY SUCH AS AC POWER, BATTERIES AND CITY CONNECTION. WALL STUD GUIDES (SEE NOTE 3.) 4005 4004, 4005, 4006, 4008, 4009, 4010, 4100, 4100U 4005 8 POINT I/O 4005*, 4090-9001 IDNET IAM 4605-7401, 4100 SERIES PKG. SIZE 1 BAY 4090-9001 IDNET IAM 4006, 4008, 4010 4003 PID NUMBER BOX HEIGHT 2975-9407 22" N.C. INITIATING (SECURITY MONITORING EOLR) 4090-9001 IDNET IAM CURRENT LIMITED N.O. INITIATING (SECURITY MONITORING EOLR) 4090-9001 IDNET IAM ON H 16 32 64 2 BAY 2975-9408 40" 3 BAY 2975-9409 56" 1 BAY 2975-9410 22" 2 BAY 2975-9411 40" 5 17/32" 3 BAY 2975-9412 56" 3 17/32" 1 BAY 2975-9438 22" 2 BAY 2975-9439 40" 3 BAY 2975-9440 56" 4 5 6 7 12" BOX LENGTH 26 1/2" BOX DEPTH 12" 4081-9306 13 1/2" 27 7/8" 14 5/8" 4081-9308 13 1/2" 27 7/8" 14 5/8" FLOOR G PRODUCT INFORMATION 4099-9020 SINGLE ACTION NO GRIP IDNet SLC ADDRESSABLE MANUAL STATION MOUNTING INSTRUCTIONS: 1. COVER & BACKPLATE COME ASSEMBLED. 2. UNLOCK STATION, DROP COVER FORWARD TO EXPOSE MOUNTING SCREWS. UL LISTED SINGLE ACTION, NO GRIP, IDNet SLC ADDRESSABLE PULL LEVEL PROTRUDES WHEN ALARMED TAMPER RESISTANT RESET KEY LOCK MOUNTING: SEMI-FLUSH, SURFACE OPERATING TEMPERATURE RANGE: 32 - 120° F OPERATING HUMIDITY RANGE: 0 - 93% RH ADAPTER PLATES 2099-9813 OR 2099-9814 CAN BE USE FOR RETROFIT APPLICATIONS. 5" HIGH X 3 3/4" WIDE X 1' DEEP SCREW TERMINALS FOR 18 TO 14 AWG WIRE ADDRESSED BY MEANS OF AN 8 POSITION DIP SWITCH COMPATIBLE WITH IDNet SLC/MAPNET 128 1=ON BOX HEIGHT 2081-9280 4100-1260 4100, 4100U 4100, 4100U 4100, 4100U 70VRMS CONSTANT SUPV. NACS SECURITY MONITORING (EOLR) N.O. SECURITY MON. (SERIES) N.C. SECURITY MON. (SHUNT) 8 PID NUMBER 0=OFF MOUNTING INSTRUCTIONS: 1. COVER & BACKPLATE COME ASSEMBLED. 2. UNLOCK STATION, DROP COVER FORWARD ARCHITECT'S STAMP THIS DRAWING IS NOT FINAL OR TO BE USED FOR CONSTRUCTION UNTIL IT IS SIGNED BY THE ARCHITECT AND ENGINEER. 2975-9178 OR 2975-9022 BOXES FROM SIMPLEX OR WIREMOLD BOX NO. 5747 SUPPLIED BY CONTRACTOR H ADDRESS DIP SWITCHES UNDER RE-SEALABLE LABEL SEE INSTALLATION INSTRUCTIONS (574-332 FOR SETTINGS SURFACE MOUNTING 2099-9819 (BLACK) OR 2099-9820 (BEIGE) FLUSH ADAPTOR AVAILABLE FROM SIMPLEX 4 11/16" SQUARE x 2 1/8" DEEP BOX SUPPLIED BY CONTRACTOR CONSULTANT SEMI-FLUSH MOUNTING PROJECT CONTACT INTERFACE E N G I N E E R I N G 717 Market Street Suite 500 San Francisco, CA 94103 TEL 415.489.7240 FAX 415.489.7289 www.interfaceengineering.com STATION HOUSING AND PULL LEVER ARE CONSTRUCTED OF CHIP RESISTANT AND DIRT RESISTANT, HIGH IMPACT LEXAN. HOUSING IS RED WITH RAISED WHITE LETTERING AND PULL LEVER IS WHITE WITH RED RAISED LETTERING. * LEXAN IS A REGISTERED TRADEMARK OF THE GENERAL ELECTRIC CO. J DIP SWITCHES 1 THRU 4 1000 0100 1100 0010 1010 0110 1110 0001 1001 0101 1101 0011 1011 0111 1111 0 16 32 48 64 80 96 112 128 144 160 176 192 208 224 240 1000 1 17 33 49 65 81 97 113 129 145 161 177 193 209 225 241 0100 2 18 34 50 66 82 98 114 130 146 162 178 194 210 226 242 1100 3 19 35 51 67 83 99 115 131 147 163 179 195 211 227 243 0010 4 20 36 52 68 84 100 116 132 148 164 180 196 212 228 244 1010 5 21 37 53 69 85 101 117 133 149 165 181 197 213 229 245 0110 6 22 38 54 70 86 102 118 134 150 166 182 198 214 230 246 1110 7 23 39 55 71 87 103 119 135 151 167 183 199 215 231 247 0001 8 24 40 56 72 88 104 120 136 152 168 184 200 216 232 248 1001 9 25 41 57 73 89 105 121 137 153 169 185 201 217 233 249 0101 10 26 42 58 74 90 106 122 138 154 170 186 202 218 234 250 1101 11 27 43 59 75 91 107 123 139 155 171 187 203 219 235 251 0011 12 28 44 60 76 92 108 124 140 156 172 188 204 220 236 252 1011 13 29 45 61 77 93 109 125 141 157 173 189 205 221 237 253 0111 14 30 46 62 78 94 110 126 142 158 174 190 206 222 238 254 1111 15 31 47 63 79 95 111 127 143 159 175 191 207 223 239 255 PULL STATIONS SHALL BE INSTALLED IN ACCORDANCE WITH NFPA 72 AND ADA GUIDE LINES. J CUTOUT MUST BE A MINIMUM FLUSH MOUNTING INTRODUCTION: THE 4099-9020 ADDRESSABLE PULL STATION PROVIDES TWO-STATE STATUS INFORMATION (NORMAL AND SHORT) TO THE IDNet SLC COMPATIBLE FIRE ALARM CONTROL PANEL (FACP) VIA THE IDNet SLC CHANNEL. THE IDNet SLC CHANNEL PROVIDES THE COMMUNICATION LINK BETWEEN PULL STATION AND THE FACP AND POWERS THE ENTIRE CIRCUITRY. WIRING: 1. ALL WIRING TO COMPLY WITH LOCAL CODE. 2. CONDUCTORS MUST TEST FREE OF ALL GROUNDS. 3. MAINTAIN CORRECT POLARITY IDNet SLC FROM FIRE ALARM CONTROL PANEL OR OTHER IDNet SLC DEVICES ON CIRCUIT 7 1 2 3 4 SHIELD + - 6" HIGH BY 5" WIDE 9 SHIELD SHIELD + - 11 10 9 7. MAXIMUM QUANTITY OF DEVICES PER CIRCUIT: 250 6 AL AT EL E CT RICA N E O OR F CAL I F DETAILS - FIRE ALARM DATE: 1.12.2015 5 6 1 2 1 2 3 4 3 4 5 6 8. TERMINALS 1 AND 2 FOR FIELD WIRING. TERMINALS 3 AND 4 ARE FACTORY WIRING. 9. WIRE NUT, SPLICE, OR SOLDER THE SHIELD WIRES. 7 ON LA AS PROJECT NO: 1089-0001 4. IDNet SLC LINES ARE TO BE 18 AWG TWISTED SHIELDED PAIR 5. MAXIMUM LINE RUN FROM PANEL TO FARTHEST DEVICE NOT TO EXCEED 2500 FEET. 6. MAXIMUM TOTAL WIRE (INCLUDING ALL T-TAPS) FROM PANEL NOT TO EXCEED 10,000 FEET. 8 F E S S I ON TO ADDITIONAL IDNet SLC DEVICES OR RETURN TO FIRE ALARM CONTROL PANEL FOR STYLE 6 APPLICATION. K 10. IF SHIELD IS PRESENT, IT SHOULD BE CONNECTED TO THE OUTGOING IDNet SLC SHIELD TO PROVIDE A CONTINUOUS SHIELD OVER THE LENGTH OF THE IDNet SLC CHANNEL. SHIELD SHOULD BE INSULATED FROM THE ELECTRICAL BOX. 11. SEE INSTALLATION INSTRUCTIONS 574-332 12 PRO NOTE: BOX MUST BE RECESSED INTO WALL 1" TO 1 1/8". APPLICATION: K D No. E16806 ST 0000 0000 2014-0174 Joe Ripp I NE ER MOUNTING INSTRUCTIONS: 1. COVER & BACKPLATE COME ASSEMBLED. 2. UNLOCK STATION, DROP COVER FORWARD TO EXPOSE MOUNTING SCREWS. CONSTRUCTION: DIP SWITCHES 5 THRU 8 APPROVAL THIS DOCUMENT CONTAINS INFORMATION THAT IS PROPRIETARY TO LPAS, INC. AND IS FURNISHED FOR THE PURPOSES OF REVIEW, BIDDING OR CONSTRUCTION OF THE PROJECT LISTED IN THE JOB TITLE BOX ABOVE AND SHALL NOT BE USED FOR ANY OTHER PURPOSE OR RELEASED TO ANY OTHER PARTY WITHOUT THE WRITTEN CONSENT OF LPAS, INC. INFOMATION CONTAINED HEREIN IS AN INSTRUMENT OF PROFESSIONAL SERVICES AND SHALL REMAIN THE PROPERTY OF LPAS, INC. ALL RIGHTS RESERVED COPYRIGHT © 2009. TO EXPOSE MOUNTING SCREWS. RESETTING 4099-9020 SINGLE ACTION STATION REQUIRES A KEY TO RESET THE ACTIVATION LEVER AND DEACTIVATE THE ALARM SWITCH. (IF OPTIONAL PLASTIC BREAK ROD WAS USED IT MUST BE REPLACED) ADDRESS SHOWN ABOVE IS 120 SINGLE GANG EXTENSION RING 3/4" (RACO NO. 773) SUPPLIED BY CONTRACTOR KNOCKOUTS FOR 3/4" CONDUIT TOP AND BOTTOM OF BOX 4" SQUARE x 2 1/8" DEEP BOX (RACO NO. 231 OR 232) OR (RACO NO. 500) SINGLE GANG SWITCH BOX 2 1/2" DEEP SUPPLIED BY CONTRACTOR U 3 F ENG 2 BATTERY AREA (IF APPLICABLE) OPERATION: 1 CONDUIT FOR INTERNAL PANEL HARNESSES OR NPL WIRING. NO CONDUIT ENTRY OR WIRING IN THIS AREA FIG. 1 ACTIVATION: 4099-9020 NO GRIP SINGLE ACTION STATION PROVIDES A MORE EASILY ACTIVATED PULL LEVER FOR ANTICIPATED USERS MAY FIND THE STANDARD STATION LEVER DIFFICULT TO ACTIVATE. COMPLETING THIS ACTION BREAKS AN INTERNAL PLASTIC BREAK-ROD THAT IS VISIBLE BELOW THE PULL LEVER (USE OF PLASTIC ROD IS OPTIONAL). THE PULL LEVEL LATCHES INTO THE ALARM POSITION AND REMAINS EXTENDED OUT OF THE HOUSING TO PROVIDE A VISIBLE INDICATION. OFF 66" (TYPICAL, FOR 5 FOOT HEIGHT TO LCD DISPLAY CENTERLINE) WALL DO NOT USE ADDRESS 0 FOR AN IDNET ADDRESS 8 FOR SURFACE MOUNT USE 4 HOLES TO SECURE BACKBOX TO WALL SEE CHART TYPICAL CONDUIT LOCATION FOR PWR. LIMITED FIELD WIRING IDNET ADDRESSING 4 E NOTE: ADA REQUIREMENTS LIMIT THE ALLOWABLE PROTRUSION OF OBJECTS MOUNTED IN PUBLIC ACCESSIBLE WALKS, HALLS, CORRIDORS, PASSAGEWAYS OR AISLES. THE 4 INCH (100mm) RESTRICTION APPLIES TO ANY ITEM IN WHICH THE MEASUREMENT FROM THE FLOOR TO THE BOTTOM OF THE UNIT IS MORE THAN 27 INCHES. FEATURES: 2 EXAMPLE OF ADDITIONAL CABINET MOUNTING LOCATION 8. REFER TO SIMPLEX BACKBOX INSTALLATION DOCUMENT 579-117 FOR DETAILED INSTRUCTIONS. IDNET DIP SWITCH SETTINGS 1 16" KNOCKOUT SCREW/NAIL HOLES FOR SEMI-FLUSH MOUNT (SEE NOTE 3.) 6. NEMA RATING: NEMA 1 - GENERAL PURPOSE. 4090-9001 IDNET IAM ANNUNCIATOR (N2) SPEAKER CIRCUIT 3 1/4" MIN. 10" MAX. 24" 1 7/16" 5. IF PRESENT, USE WIRE MANAGEMENT BRACKETS ON BOX SIDES TO SECURE WIRE RUNS. 4005*, 4090-9001 IDNET IAM 4100, 4100U NOTIFICATION 6 29/32" 4. MINIMUM DISTANCE BETWEEN ANY TWO BOXES IS 3 1/4" (6" MAXIMUM). 4605-7401, 4100 SERIES 4090-9001 IDNET IAM (EOLR) 2080-9024 4004, 4005, 4090-9001 IDNET IAM 2190-9173 MAPNETII 2 PT I/O 4-20MA ZAM (TROUBLE) REFER TO FIG.1 FOR TYP. CONDUIT PENETRATION LOCATIONS 11 11/16" 3. MOUNT BOX TO WALL: BOX MUST BE LEVEL AND PLUMB. FOR SURFACE MOUNT USE TEAR DROP AND CLEARANCE HOLES ON BACK SURFACE. FOR SEMI-FLUSH MOUNT: USE WALL STUD GUIDES FOR MAXIMUM ALLOWABLE BOX DEPTH TO PROVIDE OPEN DOOR CLEARANCE. USE KNOCKOUTS ON SIDE WALL, SCREW OR NAIL BOX TO WALL STUDS. FIRE ALARM PANEL/MODULE 4081-9005 D 2. NO KNOCKOUTS PROVIDED. CUT CONDUIT/SERVICE ENTRANCE OPENINGS. REFER TO FIG.1 FOR PROPER LOCATIONS. CONDUIT PROTRUSION INTO BOX 1/2" MAX. * USE WITH RETROFIT OR HIGH CURRENT MODULE OHMS DATE 1. REMOVE ELECTRONIC CARD CAGE (IF PRESENT) AND STORE IT IN A SAFE DRY AREA. NOTE: REFER TO PANEL/MODULE AND DEVICE INSTALLATION INSTRUCTIONS FOR PROPER TERMINATIONS. REFERENCE NUMBER 733-892 ISSUE 4100ES BACKBOX INSTALLATION END-OF-LINE RESISTOR CODES MODEL SAN JOSE CITY COLLEGE L FOR CEILING HEIGHTS LESS THAN 86" (2180mm), THE VISUAL LENS MOUNTING HEIGHT SHALL BE WITHIN 6" (150mm) OF THE CEILING. 1 5 IA A A/C SUPPLY OR RETURN DIFFUSER VISUAL APPLIANCE MOUNTING HEIGHT CONSIDERATIONS IN SLEEPING ROOMS 1. MIN DISTANCE IN SLEEPING ROOMS IS 24" (610mm) FROM CEILING TO TOP OF LENS FOR 110CD STROBES WITHIN 16' OF THE PILLOW 2. 177CD STROBES, USED IN SLEEPING ROOMS, CAN BE WITHIN THE 24" (610mm) MINIMUM DISTANCE FROM THE CEILING. THE HIGHER INTENSITY IS TO COMPENSATE FOR A POSSIBLE SMOKE LAYER. 6 J 10 RE 11 R EG I S T E 12 5 SHEET NO: FA7.04 4 3 2 1 DSA SUBMITTAL