Download Veris H600 - RSD Total Control

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power inverter wikipedia , lookup

Current source wikipedia , lookup

History of electric power transmission wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Rectifier wikipedia , lookup

Portable appliance testing wikipedia , lookup

Electrical substation wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Power engineering wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Ohm's law wikipedia , lookup

Three-phase electric power wikipedia , lookup

Voltage optimisation wikipedia , lookup

Power electronics wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Stray voltage wikipedia , lookup

Aluminium-conductor steel-reinforced cable wikipedia , lookup

Ground (electricity) wikipedia , lookup

Buck converter wikipedia , lookup

Overhead power line wikipedia , lookup

Skin effect wikipedia , lookup

Mains electricity wikipedia , lookup

Earthing system wikipedia , lookup

Electrical wiring wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Alternating current wikipedia , lookup

Opto-isolator wikipedia , lookup

Transcript
CURRENT MONITORING
VERIS INDUSTRIES
H600
INSTALLATION GUIDE
600
Split-Core Current Switch,
Fixed Trip Point
Installer’s Specifications
Sensor Power
Induced from monitored current
Insulation Class
600VAC RMS (UL), 300VAC RMS (CE)
Frequency Range
50/60 Hz
Temperature Range -15° to 40°C (5° to 104°F) (to 200A); -15° to 60°C (5° to 140°F) (to 150A)
Humidity Range
10-90% RH, non-condensing
Terminal Block Maximum Wire Size
14 AWG (16 AWG for H300)
Terminal Block Torque (nominal)
4 in-lbs (7 in-lbs for H300)
Agency Approvals
UL 508 open device listing
CE:EN61010-1:2001-02, CAT III, deg. 2, basic insulationI
The product design provides for basic insulation only.
RoHS
Compliant
quick install
DANGER
1. Disconnect and lock out power to the conductor to be monitored.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•
•
•
•
•
2. Plan the installation:
Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the iris, or “window” when it is installed
and keep the product at least 1/2” (13mm) from any uninsulated conductors (CE).
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.
Failure to follow these instructions will result in death or serious injury.
3. Install mounting bracket
Drill holes to mount the bracket to the chosen surface using the included screws.
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
4. Wire the output connections between the sensor and the controller.
NOTICE
•
•
•
•
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
5. Snap the sensor over the wire to be monitored and clip the assembly to the
mounting bracket.
Dimensions
Removable Mounting Bracket
Wiring Example
0.6"
(16 mm)
Insulated Conductor ONLY
CONTACTOR
0.5"
(13 mm)
DDC CONTROLLER
2.5" *
(64 mm)
2.1"
(54 mm)
DI
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
Fan
1.2"
(31 mm)
0.7"
(18 mm)
2.1"
(54 mm)
1.0" *
(26 mm)
2.9"
(74 mm)
3.5"
(89 mm)
Motor
Z201983-0J
PAGE 1
©2009 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / [email protected]
09091
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
VERIS INDUSTRIES
INSTALLATION GUIDE
H600
Operation
troubleshooting
The H600 is a current-sensitive switching device that monitors current (amperage) in
the conductor passing through it. A change in amperage in the monitored conductor
that crosses the switch (setpoint) threshold plus the hysteresis value will cause
the resistance of the FET status output to change state, similar to the action of a
mechanical switch. In this model, the setpoint is fixed at 150mA AC max. (200mA for
50Hz operation). The status output is suitable for connection to building controllers or
other appropriate data acquisition equipment operating at up to 30 volts. The H600
requires no external power supply to generate its output.
Problem
No Reading at Controller
Solution
• Check for control voltage at sensor (<30V)
• Check for amperage in monitored conductor (> 0.15A
@ 60Hz)
• Assure that sensor core mating surfaces are clean and
that the core clamp is completely closed
Notes
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown.
240A
> 200A (Sensor max.)
300A:5A
H68xx-5A CT
ES 23
USTRI 972 56
4-85
gon
IS INDOre 0-35
VER tland, 1-80
®
Por
keye
Haw
4A
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the "window." This increases the current measured
by the transducer.
Controller must be
programmed to account for the
extra turns. e.g., if four turns
pass through the sensor (as
shown) the normal controller
reading must be divided by 4.
Z201983-0J
PAGE 2
< 0.15 A (Sensor Min.)
4x
0.5A
0.1A
S
RIE 23
USTon 972 56
4-85
IS IND
, Oreg 0-35
VER land 1-80
®
keye
Port
Haw
©2009 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / [email protected]
09091