Download Sepam 2000 Retrofit - Schneider Electric

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Variable-frequency drive wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Voltage optimisation wikipedia , lookup

Three-phase electric power wikipedia , lookup

War of the currents wikipedia , lookup

Electrification wikipedia , lookup

Islanding wikipedia , lookup

Mercury-arc valve wikipedia , lookup

History of electromagnetic theory wikipedia , lookup

Rectifier wikipedia , lookup

General Electric wikipedia , lookup

Electric machine wikipedia , lookup

TRIAC wikipedia , lookup

Stray voltage wikipedia , lookup

Current source wikipedia , lookup

Earthing system wikipedia , lookup

Electric motorsport wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power electronics wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Ohm's law wikipedia , lookup

History of electric power transmission wikipedia , lookup

Automation wikipedia , lookup

Mains electricity wikipedia , lookup

Buck converter wikipedia , lookup

Automation bias wikipedia , lookup

Current mirror wikipedia , lookup

Opto-isolator wikipedia , lookup

Alternating current wikipedia , lookup

Transcript
LPCT
How can a single sensor cover such a large
range ?
What is a LPCT ?
● LPCT stands for Low Power Current Transformer, also called electronic
CT in 60044-8 standard and the CT catalog AMTED305031
● It’s a matter of “classical” magnetic CT and not based on the Rogowski
principle
● Contrary to standard CT which burden is the wiring and the input
impedance of the relay, The LPCT has it’s burden integrated under the
form of a resistor:
● It’s output signal is then a
voltage proportional to the primary current.
For Schneider models we have
22.5mV at the nominal current In
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
2
The characteristics of a =S= LPCT
● The rated primary current: This is the primary side current for which the
output voltage is equal to 22.5mv
● The extended primary current: “metering” class of precision is
maintained until this current value.
● The accuracy limit primary current or the accuracy limit factor (ALF):
Multiplier of the primary side nominal current for which the rated error
value is reached. The CT saturation will occur after this level. The
“protection” class of precision is warranted until this point. Noticeable
difference, the ALF is from 400 to 500 instead of the usual 10 to 30.
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
3
The characteristics of a =S= LPCT
● Ex: CLP2
Ipn = 100A
Ipe = 1250A
FLP = 400
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
4
Connection to Sepam
● One CCA670 or CCA671 has to be used instead of one
CCA630/634 in order to connect the RJ45 cords coming
from the LPCT.
● CCA670 : lateral connectors for Sepam series 20 & 40
● CCA671 : radial connectors, for Sepam series 60 & 80.
● The LPCT can be used with every Sepam
Except the models integrating the transformer differential
(T87, M88, G88).
● With machine differential (M87, G87) CT & LPCT can
Be mixed up.
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
5
Connection to Sepam
● Connecting only one or two LPCT sensors is not allowed and lead to a
fall back position (same as if the CCA630 is not present).
● The cable is terminated by a RJ45 connector. It directly comes out of
the CT and it’s length is 6,5 meters. It cannot be modified (neither
shorter nor longer, no extension)
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
6
Sepam : Modifying the rated current
● For the CLP range the plated rated current is 100A for all models.
● With Sepam it is possible to modify the operational rated current in
order to adapt the measurement range (0.05 or 0.1 à 24In) to the need
among these values: In (A) = 25, 50, 100, 125, 133, 200, 250, 320, 400,
500, 630, 666, 1000, 1600, 2000*, 3150*. * Take care to ALP value of 40 et 50kA
● 2 operations are needed to make the change:
● Select the desired In with
SFT2841 (or through front panel use)
● Change the micro switches on CCA67x accordingly.
Each combination of switches allows 2 In values, The setting
done with SFT2841 will determine which one is used
(by selection of x1 or x5 gain level in input stage)
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
7
How does it work?
● The output signal of LPCT is adapted by a voltage to bring it back to
25mV pour In
● Ex for In = 500 A
● ULPCT = 5X22.5 = 112.5mV,
A the output of the (1+9)/R3 divisor the voltage is 25mV
● Ex for In = 100 A
● ULPCT = 1X22.5 = 22.5mV,
A the output of the (1+9)/R3 divisor the voltage is 5mV
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
8
Selection of the gain
● According to the set In, the selected gain is x1 ou x5
● For In=100A g = 5
5mV x 5 = 25mV
● For In=500A g = 1 25mV x 1 = 25mV
● In both case we have 25mV for In at the input of the A/D converter.
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
9
Secondary side injection
● It is possible to test the system by
secondary injection by using some
accessories:
4: remote test plug connection CCA613,
flush mounted on cubicle front face,
equipped with a 3 m cable to be
connected to the test plug of
CCA670/ CCA671 (sub-D 9 broches).
(this accessory is optional , the ACE917 can be
Directly connected on the CCA670/1)
5 ACE917 injection adapter,
6 Standard injection box.
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
10
Secondary side injection: ACE917
● It allows to inject currents into the 3 phases.
● The injection is done on the 1A or 5A nominal
current basis according to selected rated current
(do not take care of this mention:
)
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
11
Secondary side injection: ACE917
● The “output calibrator” selector has to be positioned on the same
position as the CCA670/1 switches.
● Ex: In=100A, 3rd switch ON on CCA670 and “output calibrator” selector
on position 3
● Nota: the positions 8 to 12 are equivalent
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
12
Secondary side injection: ACE917
Example :
3rd switch ON on CCA670 and selector on position 3
● In set as 100A :
By injecting 1A Sepam displays 100A
By injecting 3A Sepam displays 300A
● In set as 500A :
By injecting 1A Sepam displays 100A
By injecting 3A Sepam displays 300A
By injecting 5A Sepam displays 500A
It is really needed to inject 5 times more current for
The In listed in the right hand side column
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
13
Secondary side injection: ACE917
● The maximum current the ACE917 can sustain is theoretically the same
as what the embedded CCA630 it contains (20A permanently 100A/1s)
● However the banana plugs and their welded wires oblige to limit the
high currents to the shortest possible time
● On another side the voltage excursion being limited to 9V, the
maximum current that can be injected/1s in position 8 and above is
limited to 70A :
(100A in position 8 will not cause any failure but the signal isn’t scaled anymore)
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014
14
Secondary side injection: ACE917
● For rated current below 630/3150A the injection current may be
reduced by changing the position of the selector.
● The injected current will then generate a signal multiplied by the ratio:
In new position / In normal position
Example :
3rd switch ON on CCA670 and selector on position 5
The ratio is 200/100 = 2
● In set as 100A :
By injecting 1A Sepam displays 200A
By injecting 3A Sepam displays 600A
Schneider Electric - Infra/Automation/AED – D Mougin – 20/05/2014