Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
TESTING PROCEDURE FOR ZIVERCOM 6RTV RELAY Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 CONTENTS: 1) COMMUNICATION 2) CONFIGURATION 1. COMMUNICATION a. Click ‘ZIV’ icon in Desktop B. Then Give user name and password User name :zivercom Password :ziv Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 C.Click The IEDs and go to installations: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 D.Click sub_pruebas.sbs and goto Edit: E. Select communication port, Data bits and stop bits: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 F.Click sub_pruebas.sbs and go to communication: G.Select Address 0 and click OK: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 2) CONFIGURATION A. Click test: B. Click setting: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 C.Click Normal setting and change the voltage, frequency and current: D.click Voltage regulator Configuration and units in main display Set secondary: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 F.Click voltage Regulator control and change Dead band,Time delay type and T1,T2 Time: G.Click Compensations and change Line drop compensation Type selector,R parameter and X parameter: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 Line drop compensation LCD R/X Calculate Having one Formula: LCD R=Vnominal+ ( ILOCAL/ Inominal)*R*cosϕ LCD X=Vnominal-(ILOCAL/ Inominal)*R*sinϕ Example: LDC-R = 6 V ; LDC-X = 0V ; ϕ=0º ; Vn = 120 V ; In = 5 A ; ILOCAL = 2 A VCOM = 120 + (2/5) * 6*cos0º = 122.4 V So, Now our Nominal Voltage is 122.4V Our Dead band is 1% So, lower operate 123.6V Raise operate 121.2V H.Goto user’s setting and click ANALOGS and Set Under, over voltage and over current level: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 I.Click Time and Set Under, over voltage and over current time: J.Click configuration and open Edit: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 K. Click I/O logic and open output: L.Configure Digital Output: 1.Digital Output 1: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 2.Digital Output 2: 3.Digital Output 3: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 4.Digital Output 4: M. Click I/O logic and open LEDs: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 N.Configure Led: 1.LED 1: 2.LED 2: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 3.LED 3: 4.LED 4: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 5.LED P1 Red: 6.LED P1 Green: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 7.LED P2 Red: 8.LED P3 Red: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 O. Click I/O logic and open input: P.Configure Digital input: 1.Digital Input 1: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 2.Digital Input 2: 3.Digital Input 3: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 4.Digital Input 4: 5.Digital Input 5: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012 6.Digital Input 6: Q.Send the data to Relay: Prepared by: Karunamoorthy, Testing Engineer Date: 20.10.2012