Коды ошибок кондиционеров Fujisu инвертор В режим диагностики. Когда на дисплее пульта показывает EE:EE, удерживая кнопку unit off, нажмите temp up и temp down одновременно и удерживайте 3 сек. Возврат в нормальный режим. Нажмите Temp Up и Temp Down и удерживайте 3 сек. Начать тестирование. Switch Unit Off & Press Master & Fan Buttons together for 3 seconds. Press Start/Stop to Initiate. Изменить позицию сенсора. The unit can sense the air temperature at the unit or controller Turn Unit Off To change press THERMOSENSOR button for 5 seconds to unlock Toggle the THERMOSENSOR button & controller is displayed Set to desired setting (unit or controller) Press THERMOSENSOR button for 5 seconds to lock Two Handsets/1 Unit - set on RC DIP SWs Single handset DIP SW1 is On & 2 is Off Dual Handset Master Both On & Slave both Off Group Control up to 16 Unit from 1 RC Handset Set DIP SW3 on RC to ON Set Each ID Unit Rotary SW to Unit Address (0-15) in series Auto Restart on Power Failure DIP SW2-3 on ID Unit. Off is autorestart (std)/On is manual Restart Auto Changeover DIP SW5 on RC. On is autochangeover (std)/Off is Manual Memory Retention on Power Failure Dip SW6 on RC. On is Memory/Off is no memory Wired Remote Control Models Code Consists of Indoor Unit Address Followed by the Fault Code Below. No E denotes no fault. OO ID to RC Comms Fail O1 ID to OD Comms Fail O2 ID Air Sensor Open O3 ID Air Sensor Close O4 ID Pipe Sensor Open O5 ID Pipe Sensor Close O6 OD Pipe Sensor Fail O8 Power Source Connection Failure O9 Drain Problem OA OD Air Sensor Fail OC Discharge sensor Fail OE Outdoor High Pressure 11 OD PCB Fail 12 ID Fan Fail 13 OD Signal Abnormal 14 OD EEPROM Fail 15 Compressor Temp Failure 16 Pressure Switch Error 17 IPM Error 18 CT Error 19 Active Filter Module Error 1A Compressor Failure 1B OD Fan Failure 1C Inverter to PCB Comms Fail 1D 2 Way Valve sensor Fail 1E Expansion Valve Error 1F Connection ID Unit Error Outdoor PCB Fault Codes Inverter OD Unit PCBs (1 red LED) OD PCB LED Pulses = 1 Models 9-30 = Comms Failure Models 36-54 = Comms Failure OD PCB LED Pulses = 2 Models 9-30 = Disch Sensor Fail Models 36-54 = Disch Sensor Fail OD PCB LED Pulses = 3 Models 9-30 = Pipe Sensor Fail Models 36-54 = Pipe Sensor Fail OD PCB LED Pulses = 4 Models 9-30 = Air Sensor Fail Models 36-54 = Air Sensor Fail OD PCB LED Pulses = 5 Models 9-30 = 2 Way Valve Sensor Models 36-54 = OD PCB LED Pulses = 6 Models 9-30 = 3 Way Valve Sensor Models 36-54 = OD PCB LED Pulses = 7 Models 9-30 = Compressor Thermistor Models 36-54 = Compressor Thermistor OD PCB LED Pulses = 8 Models 9-30 = Pressure Switch Models 36-54 = Heat Sink Sensor Fail OD PCB LED Pulses = 9 Models 9-30 = Indoor Comms Error Models 36-54 = Pressure Switch OD PCB LED Pulses = 10 Models 9-30 = Current Trip Models 36-54 = OD PCB LED Pulses = 11 Models 9-30 = CT Fail Models 36-54 = OD PCB LED Pulses = 12 Models 9-30 = Compressor Position Fail Models 36-54 = IPM Error OD PCB LED Pulses = 13 Models 9-30 = Compressor Start Fail Models 36-54 = Compressor Position Fail OD PCB LED Pulses = 14 Models 9-30 = Timer Failure Models 36-54 = Compressor Start Fail OD PCB LED Pulses = 15 Models 9-30 = Models 36-54 = OD Upper Fan Fail OD PCB LED Pulses = 16 Models 9-30 = Models 36-54 = OD Lower Fan Fail OD PCB LED Pulses = Slow Blink Models 9-30 = Models 36-54 = Protect Operation Non Inverter OD PCBs (2 red LEDs) LED1 = Blinks LED2 = Blinks OD PCB Fail LED1 = 1 Pulse LED2 = Lit Power Source Failure LED1 = 2 Pulse LED2 = Lit OD Disch Temp Sensor LED1 = 3 Pulse LED2 = Lit OD Pipe Sensor LED1 = 4 Pulse LED2 = Lit OD Air Sensor LED1 = 5 Pulse LED2 = Lit Comms Failure LED1 = 6 Pulse LED2 = Lit Indoor Unit Error LED1 = 7 Pulse LED2 = Lit High Discharge Temp LED1 = 8 Pulse LED2 = Lit High Pressure LED1 = 9 Pulse LED2 = Lit Compressor Temp Abnormal LED1 = 10 Pulse LED2 = Lit Compressor Temp Sensor Fail Inverter Multi AOY30 This has 4 LEDs A,B, C & D to denote which circuit has the fault Up to 8 flashes - faults are identical to above 9-30 Single System 9 Pressure Switch A 10 Pressure Switch B 11 Indoor Unit Indexing Problem 12 IPM Fail 13 Compressor Position Fail 14 Compressor Fail 15 OD Fan Upper Fail 16 OD Fan Lower Fail 17 PCB Fail Interconnecting Wiring CO Multis 2 (Live) 1 (Neutral) 3 (Comms) HP Multis 1 (Live) 2 (Neutral) 3 (Comms) AOY90T 3 (Live) 2 (Neutral) 1 (Comms) ALL OTHERS 1 or L 2 or N 3 We recommend external pumps have their own power supply. Taking Power for a pump from the unit is a major source of Errors (CLIMATE CENTRE) Pipework • Pipe sizes and lengths should be as the relevant Technical Guide • Both lines should be insulated • No line accessories or oil traps should be fitted • In cooling mode both pipes should be between 0 and 10C - the suction line should sweat, but not freeze • In heating moded both pipes should be between 30 an 60C • Pipework should be refrigeration quality • Refrigerant should be R22, unless stated on the outdoor unit • Look for restrictions. They could cause compressor failures. Outdoor Unit • Discharge temperature should be between 50 & 70C • Suction temperature should be between -3 & 4C • If fan switches off check for high discharge temperature • Check Suction Line is sweating – problem if not! • Hot Recip. Compressor = PROBLEM! • Sweating/Frost on expansion line – undercharged Indoor Unit • Is it level? Have we adequate drainage? • Smells are always due to site conditions or drains • Flashing lights? = Fault Diagnostics - see over • When were the filters last cleaned? • Is the unit too large/small (between 5/20 air circs / hr) • Is it on Timer/Test Mode Controller • EE:EE on LCD handset - fault diagnostics - see over • Is the handset too far away? • When were the batteries changed last? • Heat Pump models 7-14 – NOT auto changeover • Timer is one shot, unless it has ‘repeat’ mode • With wired handset, check for interference. Cable should be screened • Is it on Timer/Test Mode Wiring • In general interconnecting wiring is 240 Volt, but see chart for details • With LCD wired handset models, Terminal 3 is the Live Not Terminal 1 NEVER apply mains voltage to Terminal 1 on these models • With LCD wired handset models wiring should be screened • Check Voltage drops! Check it isn’t down to Earth! • Has it got a timeclock/BMS interface? • Interconnecting cables MUST be circular crimped What the separate Wires do in the interconnecting Cables Note – Wires are 240V Live except where marked neutral or Earth or signal Cables marked Signal are digital pulses and you should not attempt to measure these with a meter. Wired Controllers - Fault diagnostics A Fault Condition is signalled by EE:EE appearing on the LCD panel. The unit should be interrogated by switching it off on the handset then pressing either the down arrows on the SET TIME and TEMP/DAY buttons together for 3 seconds for 7 day models or the ENERGY SAVE & ZONE CONTROL buttons for other models. The Failure code is in 2 parts - Fault and Address. The Fault Code is an E code. The second is the unit address for multi linked systems - with single units this is always 00. 7 day models have the fault code as shown in the table below above the address. Other models have the codes below, minus the 0, followed by the address - e.g. E9:00 denoting Float Switch on Unit 0. Code = E:0 Fault = I/U - R/C Comms Diagnosis = Check R/C wiring. Interference? Code = E:01 Fault = I/U - O/U Comms Diagnosis = Check intercon. wiring. Interference Code = E:02 Fault = Room Sensor Open Diagnosis = Sensor Missing Code = E:03 Fault = Room Sensor Short Diagnosis = Sensor Faulty Code = E:04 Fault = I/U Pipe Sensor Open Diagnosis = Sensor Missing Code = E:05 Fault = I/U Pipe Sensor Short Diagnosis = Sensor Faulty Code = E:06 Fault = O/U Pipe Sensor Open Diagnosis = Sensor Missing Code = E:07 Fault = O/U Pipe Sensor Short Diagnosis = Sensor Faulty Code = E:08 Fault = Power Source Error Diagnosis = Incorrect Power Supply Code = E:09 Fault = Float Switch Diagnosis = Check Drains - High Water Level Code = E:0A Fault = O/U Air Sensor Open Diagnosis = Sensor Missing Code = E:0C Fault = Disch Sensor Open Diagnosis = Sensor Missing Code = E:0D Fault = Disch Sensor Short Diagnosis = Sensor Faulty Code = E:0F Fault = High Disch Temp Diagnosis = Contamination In Pipework/Gas Shortage Code = E:11 Fault = Model Abnormal Diagnosis = Check PCB compatability Code = E:12 Fault = Indoor Fan Failure Diagnosis = Check Fan and Motor Code = E:13 Fault = O/D Signal Abnormal Diagnosis = Communications? Code = E:14 Fault = Outdoor PCB Fail Diagnosis = PCB Failure Outdoor Unit with A fault condition is signified by flashing red LED’s on the the outdoor PCB if it is equipped with one. Except for multisplits and 2 LED models, the diagnostics are shown in the table on the right. For 2 LED models flashing signifies sensor failure and constantly lit indicates high discharge temperature. Fault = Signal Failure LED1 = LED2 = LED3 = LED4 = Flash LED5 = LED6 = Fault = Indoor Unit Failure LED1 = LED2 = LED3 = LED4 = Flash LED5 = LED6 = Fault = Discharge Sensor Fail LED1 = LED2 = LED3 = LED4 = LED5 = LED6 = Flash Fault = O/D Pipe Sensor Fail LED1 = LED2 = LED3 = LED4 = LED5 = Flash LED6 = Flash Fault = O/D Air Sensor Fail LED1 = LED2 = LED3 = Flash LED4 = LED5 = Flash LED6 = Fault = Power Source Error LED1 = LED2 = Flash LED3 = LED4 = LED5 = LED6 = Fault = PCB LED1 = Flash LED2 = Flash LED3 = Flash LED4 = Flash LED5 = Flash LED6 = Flash Fault = PCB Failure LED1 = * LED2 = * LED3 LED4 LED5 LED6 = = = = * * * * All Flashing Very Rapidly Fault = High Pressure Trip LED1 = Flash LED2 = LED3 = LED4 = LED5 = LED6 = Fault = Discharge Temp Trip LED1 = LED2 = Flash LED3 = LED4 = LED5 = LED6 = Unit = All Code Means:- = Power On Red = On Green = Off Yellow = Off Unit = All Code Means:- = Timer Mode Red = On Green = On Yellow = Off Unit = All Code Means:- = Louvre On Red = On Green = On or Off Yellow = On Unit = All Code Means:- = HP Defrost Cont. Red = Long pulses Green = Off Yellow = Off Unit = All Code Means:- = Test Red = Cont. Pulse Green = Cont. Pulse Yellow = Off Unit = D,E,F Code Means:- = Power Fail Red = On Green = Cont Long Yellow = Pulses Off Unit = All Code Means:- = PCB Failure Red = Cont. Short Pulse Green = Cont. Short Pulse Yellow = Off Unit = G Code Means:- = Room Sensor Fault Red = 1 Short Pulse Green = Rapid Pulse Yellow = Off Unit = A,B,G Code Means:- = Sensor Fault Red = 2 Short Pulses Green = Rapid Pulse Yellow = Off Unit = D,E,F Code Means:- = Room Sensor Open/Fail Red = 2 Short Pulses Green = Rapid Pulse Yellow = Off Unit = E,F Code Means:- = Room Sensor Short Red = 2 Short Pulses Green = Rapid Pulse Yellow = Rapid Pulse Unit = C Code Means:- = Room Sensor Fault Red = 3 Short Pulses Green = Long Pulse Yellow = Off Unit = D,E,F Code Means:- = Pipe Sensor Open Red = 3 Short Pulses Green = Rapid Pulse Yellow = Off Unit = E,F Code Means:- = Pipe Sensor Short Red = 3 Short Pulses Green = Rapid Pulse Yellow = Rapid Pulse Unit = D,E,F Code Means:- = High Water Red = 4 Short Pulse Green = Rapid Pulse Yellow = Off Unit = F Code Means:- = Comms Failure Red = 5 Short Pulses Green = Rapid Pulse Yellow = Off Unit = G Code Means:- = High Water Red = 6 Short Pulses Green = Rapid Pulse Yellow = Off Unit = B,E,F Code Means:- = Fan Failure Red = 6 Short Pulses Green = Rapid Pulse Yellow = Off Unit = F Code Means:- = 3ph Reversal Red = Rapid Pulse Green = 2 Short Pulses Yellow = Off Unit = C Code Means:- = Pipe Sensor Fault Red = Long Pulse Green = 3 Short Pulses Yellow = Off Unit = F OD Code Means:- = Pipe Sensor Open Red = Rapid Pulse Green = 3 Short Pulses Yellow = Off Unit = F OD Code Means:- = Pipe Sensor Short Red = Rapid Pulse Green = 3 Short Pulses Yellow = Rapid Pulse Unit = F OD Code Means:- = Temp Sensor Open Red = Rapid Pulse Green = 4 Short Yellow = Pulses Off Unit = F OD Code Means:- = Temp Sensor Short Red = Rapid Pulse Green = 4 Short Pulses Yellow = Rapid Pulse Unit = F Code Means:- = Discharge Sensor Open Red = Rapid Pulse Green = 5 Short Pulses Yellow = Off Unit = F Code Means:- = Discharge Sensor Short Red = Rapid Pulse Green = 5 Short Pulses Yellow = Rapid Pulse Unit = F Code Means:- = High/Low Pressure Red = Rapid Pulse Green = 6 Short Pulses Yellow = Off Unit = F Code Means:- = High Discharge Temp Red = Rapid Pulse 7 Green = Short Pulses Yellow = Off SENSOR RESISTANCES - Use to Check Thermistors across the range Sensor At 10C At 20C At 30C Air Temperature Sensors 20K Ohms 13K Ohms 8K Ohms Indoor Pipe Sensor 103K Ohms 63K Ohms 40K Ohms Outdoor Pipe Sensor 10K Ohms 6K Ohms 4K Ohms Discharge Sensor 646K Ohms 395K Ohms 250K Ohms