Download must be submitted to the authority having jurisdiction”. be used in a

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts
no text concepts found
Transcript
CITY OF MONTRÉAL
BY-LAW
97-068
BY-LAW AMENDING THE BUILDING BY-LAW (B-1)
At the Montréal city council meeting of April 14, 1997, it was enacted that:
1. The Building By-law (R.B.C.M., chapter B-1) is amended by adding the following after article 4:
“4.1. Article 1.1.4.1 of the Code is amended by adding the following abbreviation at the
top of the list:
“ACGIH ..... American Conference of Governmental Industrial Hygienists (6500 Glenway
Avenue, Bldg. D-7, Cincinnati, Ohio 45211, U.S.A.)”.”.
2. That by-law is amended by adding the following articles after Article 8:
“8.1. Subsection 2.3.3 of the Code is amended by adding the following after Article
2.3.3.2:
“2.3.3.3. Inspection Report. Before a fire alarm and detection system is
operated, an inspection report in accordance with the model in Appendix A to
CAN/ULC-S537-M, “Standard for the Verification of Fire Alarm Systems”,
must be submitted to the authority having jurisdiction”.
8.2. Subsection 2.4.1 of the Code is amended by adding the following after Article 2.4.1.3:
“2.4.1.4. Seal of Approval. The materials, appliances and systems that are part
of a fire protection assembly or system in a building must bear the seal of
approval of a laboratory or agency accredited by the Canadian Standards
Association as an accreditation agency or be covered by evaluation reports or
evaluation listings issued by the Canadian Construction Materials Centre, and
favorable to the use of products under the proposed conditions.”.”.
3. Article 9 of that by-law is amended by adding the following after Sentence 2:
“(3) by replacing document number “CAN/ULC-S524-M86” opposite the title “Standard
for the Installation of Fire Alarm Systems” by document number “CAN/ULC-S524M91”.”.
4. Article 10.1 of that by-law is repealed.
5. Article 10.2 of that by-law is replaced by the following:
“10.2. Article 3.1.5.15 of the Code is replaced by the following:
“3.1.5.15. Combustible Piping Materials
(1) Except as provided in Clause 3.1.5.2.(1)(e) and Sentences (2) and (3),
combustible totally enclosed raceways, piping and tubing and associated adhesives may
be used in a building required to be of noncombustible construction provided they
(a) have a flame-spread rating of no more than 25, except when concealed
97-068 / 1
in a wall or a concrete slab, and
(b) when used in buildings referred to in Subsection 3.2.6., have a smoke
developed classification of no more than 50.
(2) Combustible sprinkler piping may be used within a sprinklered floor area in a
building required to be of noncombustible construction. (See also Article 3.2.5.14.)
(3) Polypropylene pipes and fittings may be used for drain, waste and vent piping
for the conveyance of corrosive materials or for piping used to distribute distilled or
dialyzed water in laboratory or hospital facilities provided
(a) the building is sprinklered,
(b) the piping is not located in a vertical shaft,
(c) piping that penetrates a fire separation is sealed at the penetration by a
fire stop which, when subjected to the fire test method in CAN4-S115M, “Standard Method of Fire Tests of Firestop Systems”, has an FT
rating not less than the fire-resistance rating of the fire separation.”.”.
6. Article 10.3 of that by-law is replaced by the following:
“10.3. Article 3.1.8.8 of the Code is amended by replacing Sentence (6) by the following:
“(6) A duct serving commercial cooking equipment referred to in
Sentence (2) of Article 6.2.2.6. or used in a smoke control system or in the
ventilation system of a generator referred to in Article 3.5.2.11. and
penetrating a required fire separation
(a) may not be provided with a fire damper at right angles with
the fire separation,
(b) be in a service space from the fire compartment to the envelope of the
building.”.”.
7. That by-law is amended by adding the following after Article 14:
“14.1. Section 3.1 of the Code is amended by adding the following subsections after
Subsection 3.1.16:
“3.1.17. Access Ramps to Parking Areas
3.1.17.1. Difference in Ground Level and Counterslope. Access ramps to the
indoor and outdoor parking areas must conform to Subsection 9.8.11.
3.1.18. Exterior Doors
3.1.18.1. Exterior doors fronting on a public way. No exterior door may open,
even partly, above a city sidewalk along a building.
3.1.19. Guards
3.1.19.1. Location and Configuration
(1) A guard at least 1070 mm high must be installed
(a) around the roofs to which an access is provided other than
for maintenance work purposes,
(b) in front of openings made in the smoke venting shafts
referred to in Subsection 3.2.6. and that are located less
than 1070 mm above the floor,
97-068 / 2
at each raised floor, mezzanine, balcony, gallery and other
place where there is a difference in level of more than
600 mm.
(2) The guards of public stairways that are not part of an exit must be
at least 920 mm measured vertically from the nose of the step to the top of the
guard, and at least 1070 mm around the landings.
(3) Except as provided in Sentence 3.3.2.8.(4), the sizes of any
openings in a guard required for a room, stairway or space accessible to the
public, or for an exterior balcony, may not be such as to prevent the passage
of a spherical object of 100 mm diam., for residential occupancies, day care
centres, day nurseries or other occupancies, unless the size and position of
larger openings constitute a hazard.”.”.
(c)
8. That by-law is amended by adding the following after Article 21:
“21.1. Article 3.2.4.5 of the Code is amended by adding the following sentences after
Sentence (2):
“(3) The testing referred to in Sentence (2) must be carried out by a
person holding a contractor’s licence for the installation of alarm systems,
issued by the Régie du bâtiment du Québec, and who is a qualified contractor
as defined in CAN/ULC-S537-96, “Standard for the Verification of Fire Alarm
Systems”.
(4) The results of the testing referred to in Sentence (2) must be
submitted to the authority having jurisdiction on the form referred to in Article
2.3.3.3.”.”.
9. That by-law is amended by adding the following after Article 25:
“25.1. Article 3.2.4.19 of the Code is replaced by the following:
“3.2.4.19. Audibility of Alarm Systems
(See Appendix A.)
(1) Audible signal devices forming part of a fire alarm system must be
installed in a building so that alert signals and alarm signals can be clearly
heard throughout the floor area in which they are installed. (See Appendix A.)
(2) The temporal pattern of an alarm signal must be in accordance
with requirement 4.2 of ISO-8201, “Acoustics - Audible emergency evacuation
signal”. (See Appendix A.)
(3) The audible signals produced by smoke alarms and the alarm
patterns of alert signals must be different from the audible signals or alarm
patterns of alarm signals to avoid confusion.
(4) The sound pressure level of a fire alarm signal may not exceed 95
dBA in any normally occupied area. (See Appendix A.)
(5) In rooms of residential occupancies, the sound pressure level of
the audible signal device of a fire alarm system must be at least 75 dBA when
the doors between the device and the rooms are closed. (See Appendix A.)
97-068 / 3
(6) The sound pressure level of the audible signal device of a fire
alarm system serving a floor area used for occupancies other than residential
occupancies must exceed the level of ambient noise by 10 dBA or more, but
may not be less than 65 dBA.
(7) In addition to audible signal appliances, visual signal appliances
must be provided in each floor area
(a) where the level of ambient noise is more than 87 dBA, or
(b) where occupants
(i) wear ear protection,
(ii) are in audio booths, or
(iii) are in soundproof enclosures.
(8) Sentence (7) also applies to assembly occupancies where the
sound level produced by music or other sounds produced during shows is
likely to exceed 100 dBA.
(9) All audible signal devices within a dwelling unit must be provided
with a disconnect that will enable a person to silence the audible device for no
more than 10 min, and then reactivate it automatically. (See Appendix A.)
(10) Each audible signal device within a dwelling unit or a suite must
be connected to the fire alarm system so that, even if it were disconnected or
damaged, the devices in other dwelling units and those in public corridors
and suites may operate.
(11) The audible signal devices referred to in Sentence (10) need not
be under separate electrical control.
(12) Audible signal devices must be installed in the service space
referred to in Sentence 3.2.1.1.(7) and be connected to the fire alarm
system.”.”.
10. Article 26.1 of that by-law is amended by replacing Sentence 3.2.5.8.(3) of the Code by the following:
“(3) The design, construction and installation of fire pumps providing the water
supply for standpipe systems and automatic sprinkler systems in accordance with NFPA 13
or NFPA 13R must conform to NFPA 20, “Standard for the Installation of Centrifugal Fire
Pumps”.”.
11. Article 27 of that by-law is replaced by the following:
“27. Article 3.2.5.9 of the Code is amended by replacing, in the title of that article, the
words “Standpipe and Hose Systems” by the words “Standpipe Systems”, and by
replacing, in Sentence (1), the words “a standpipe and hose system” by the words “a
standpipe system”.”.
12. Article 28 of that by-law is amended:
(1)
by replacing Sentences (1) and (2) by the following:
“(1) by replacing Sentence (1) by the following:
“(1) Except as provided in Sentences (2) to (13) and Articles 3.2.5.11., 3.2.5.12. and
3.2.5.16., the design, construction, installation and testing of a standpipe system must
97-068 / 4
(2)
conform to NFPA 14, “Installation of Standpipe and Hose Systems”.”;
(2) by replacing Sentence (5) by the following:
“(5) Where a standpipe system is required, 64 mm diam hose connections must be
provided; however, 64 mm diam hose connections are not required in buildings 14 m or
less in height, measured between grade and the ceiling level of the top storey.”;”;
in Sentence (4), by adding the following after Sentence 3.2.5.10.(12) of the Code:
“(13) The pipes connecting the 64 mm diam hose connections to sprinkler risers must be
at least 64 mm diam where they do not exceed 2 m in length, and 100 mm in other
cases.”.
13. Article 29 of that by-law is amended:
(1)
(2)
by replacing Sentence (1) by the following:
“(1) by replacing Sentence (1) by the following:
“(1) The 64 mm diam hose connections must be placed in exits, in accordance with
NFPA 14, “Installation of Standpipe and Hose Systems”.”;”;
by adding, in Sentence (3), the following sentences after Sentence 3.2.5.11.(8) of the Code:
“(9) Where an automatic sprinkler system or part of it must be designed in
conformance with the design criteria of NFPA 13, “Standard for the Installation of Sprinkler
Systems”, paragraph 10-1.2, hose stations for 38 mm diam hoses no more than 30 m
long must be provided in the building or part of the building that is sprinklered, if such
hose stations are required under that standard, in addition to automatic sprinkler systems.
(10) Except as provided in Sentences (8) and (9) and Sentence 3.3.2.13.(6), a floor
area that is not fully sprinklered must be provided with hose stations for 38 mm diam
hoses.”.
14. Article 31 of that by-law is replaced by the following:
“31. Article 3.2.5.16 of the Code is amended by adding the following sentences after
Sentence (2):
“(3) The fire department connections referred to in Sentences (1) and (2) must be
located on a façade fronting on a street, no less than 460 mm and no more than 1500 mm
above adjacent grade and be visible at all times and easily accessible.
(4) Each high building referred to in Article 3.2.6.1. must be provided with at least 2
fire department connections installed in accordance with Sentence (3), the closest possible
to each other and located on 2 separate façades where those façades front on a street.”.”.
15. Article 32 of that by-law is replaced by the following:
“32. Article 3.2.6.2 of the Code is amended:
(1) by replacing Sentence (1) by the following:
“(1) Every building must be designed to limit the danger to occupants and
firefighters from exposure to smoke in a building fire, as provided:
(a) in Sentences (2) to (4) and Measure B (Open Corridor Access to
Stairs and Elevators) referred to in the
Supplement to NBC 1990, or
(b) in Sentences (2) to (4), in Article 3.2.6.4. and in Measure
A
(Fully Sprinklered Building) in that Supplement.”;
97-068 / 5
(2)
by adding the following after Sentence (4):
“(5) Every exit stair shaft that must be pressurized during a fire must be
equipped with a smoke control system separate from the one serving other
parts of the building, including other exit stair shafts.
(6) The air ducts of smoke control systems must be metallic.”.”.
16. Article 34 of that by-law is replaced by the following:
“34. Article 3.2.6.9 of the Code is amended:
(1) by replacing Clause 6(a) by the following:
“(a) installed in service spaces containing no combustible materials
and separated from the remainder of the building by a fire
separation having a fire-resistance rating of not less than 1 h, or”;
(2) by adding the following sentence after Sentence (6):
“(7) From elevators used by firefighters, a corridor or free access
to stair shafts with 64 mm diam stair shafts.”.”.
17. That by-law is amended by adding the following after Article 34:
“34.0.1. Article 3.2.6.14 of the Code is replaced by the following:
“3.2.6.14. Protection of Electrical Conductors
(1) Electrical conductors used in connection with fire alarm systems
and emergency equipment referred to in Articles 3.2.6.2. to 3.2.6.13. must be
protected against fire exposure from the source of power to the branch
circuits, in accordance with Sentence (3).
(2) Where the central alarm and control facility and the fire alarm
control unit are in different fire compartments, the electrical conductors
connecting the fire alarm control unit to the central alarm and control facility
must be protected against fire exposure in accordance with Sentence (3).
(3) The electrical conductors referred to in Sentences (1) and (2) must
(a) be installed in service spaces containing no combustible material
and separated from the remainder of the building by fire
separations having a fire-resistance rating of not less than 1 h, or
(b) be protected against fire exposure to ensure continued operation
for a period of not less than 1 h during testing in accordance with
CAN/ULC-S101-M, “Standard Methods of Fire Endurance Tests
of Building Construction and Materials”.
(4) For Clause 3(b), the joint around electrical conductors in fire
separations must be sealed in accordance with Clause 3.1.9.1.1(b).”.”.
18. That by-law is amended by adding the following after Article 35:
“35.0.1. Article 3.3.1.13 of the Code is amended by adding the following sentence after
Sentence (2):
“(3) Except as provided in Article 3.3.1.15., stairways that are neither required exits
nor required access to exits must conform to Subsections 9.8.3. and 9.8.4.”.”.
97-068 / 6
19. Article 35.1 of that by-law is replaced by the following:
“35.1. Article 3.3.1.15 of the Code is replaced by the following:
“3.3.1.15. Curved Stairs
(1) Except as provided in Sentence (2), a curved stair having treads
with a minimum run of not less than 150 mm, a minimum average run of not
less than 200 mm and having risers in conformance with Sentence 3.4.6.7.(2)
is permitted. (See also 3.4.6.8.(2) for curved stairs used as an exit.)
(2) In part of a floor area containing a group C, D, E, F2 or F3
occupancy, interior stairs not used as an exit may be curved in whole or in
one or several parts, under the following conditions:
(a) they are not accessible to the public,
(b) they only serve two consecutive storeys,
(c) they are not part of a means of egress serving more than 6
persons,
(d) they have a clear width of not less than 760 mm if covered and
860 mm if surrounded by contiguous walls, and a clear width of
not more than 860 mm if they end on the narrowest side at runs
less than 100 mm,
(e) have runs which, when measured at 500 mm from the narrowest
side, have a constant depth not less than 225 mm, equal to that of
straight parts, if any,
(f) the height of risers is uniform and no more than 200 mm,
(g) the rotation is always on the same side between 2 storeys.”.”.
20. That by-law is amended by adding the following after Article 35.1:
“35.2. Section 3.3.1 of the Code is amended by deleting Article 3.3.1.17.”.
21. That by-law is amended by adding the following after Article 36:
“36.1. Article 3.3.2.5 of the Code is amended by replacing Clause (1)(c) by the following :
“(c) no fire separation is required for corridors used by the public in the same
establishment or serving classrooms where the distance from any point in the
floor area to an exit measured along the path of exit travel does not exceed the
travel distances in Article 3.4.2.5.”.”.
22. Article 39.1 of the Code is repealed.
23. Article 43.2 of that by-law is amended by deleting Sentence 3.4.6.11.(4) of the Code.
24. Article 44 of that by-law is amended by replacing, in Sentence (3), in Clause 3.4.6.15. (4)(e) of the
Code, “25” by “15”.
25. Article 45 of that by-law is amended by adding, in Sentence 3.5.2.7.(4) of the Code, after the word
“ventilated”, the words “in conformance with Sentence 6.2.2.4.(2)”.
97-068 / 7
26. That by-law is amended by adding the following after Article 46:
“46.1. Article 3.5.3.4 of the Code is replaced by the following :
“3.5.3.4. Exhaust Duct Negative Pressure
(1) When a vertical service space contains an exhaust duct that serves
more than one fire compartment, the duct must have a fan located at or near
the exhaust outlet to ensure that the duct is under negative pressure, and the
individual fire compartments may not have individual fans that exhaust directly
into the duct in the vertical service space unless the individual ducts go up
500 mm into the exhaust duct and a back-draft damper is installed at the
exhaust outlet of each fan.”.”.
27. That by-law is amended by adding the following after Article 48 :
“48.1. Article 3.6.4.1 of the Code is amended by adding the following sentence after
Sentence (2) :
“(3) Plumbing systems in dwelling units and rooming houses must conform to Part
9.”.”.
28. Article 49 of that by-law is replaced by the following :
“49. Article 3.6.4.2 of the Code is amended :
(1) by replacing Sentence (8) by the following:
“(8) Except as provided in Sentence (11), the number of water closets
required for residential occupancies must be at least one fixture for each group
of 10 persons of both sexes.”;
(2) by replacing Sentence (11) by the following sentences :
“(11) Both sexes may be served by one water closet where
(a) the occupant load is no more than 25 in a restaurant, 25 in an
establishment where training courses are provided except an elementary
school, or a high school, 10 in a Group C, D or F occupancy, and 15 in
a day care centre,
(b) the total area of an art gallery or a Group E occupancy is no more than
250 m².
(12) No required water closet may be
(a) more than one storey above or below the one where the
occupancy for which it is required is located,
(b) more than 60 m from the area intended for consumption, in a
restaurant or a drinking establishment.
(13) Where a washroom contains more than one water closet, each
water closet must be in a stall no less than 900 mm wide by 1200 mm deep.
(14) Urinals must be installed so that
(a) their side walls are no less than 200 mm from a wall,
(b) the distance between centres of several fixtures is no less than
500 mm,
(c) there is a clearance of no less than 450 mm in front of each urinal
97-068 / 8
and no less than 900 mm between the front of a urinal and
another fixture on the opposite wall. ”.”.
29. Article 49.1 of that by-law is repealed.
30. That by-law is amended by adding the following after Article 57.3:
“57.4. Article 6.2.1.1 of the Code is amended by adding, after the words “SMACNA
Manuals”, the words “, NFPA standards”.”.
31. Article 58 of that by-law is replaced by the following :
“58. Article 6.2.2.1 of the Code is amended by adding the following sentences after
Sentence (2) :
“(3) Except for storage garages referred to in Article 6.2.2.3., the rates at which
outdoor air must be supplied to rooms and spaces in buildings by ventilation systems
must conform to ANSI/ASHRAE - 62, “Ventilation for Acceptable Indoor Air Quality”.
(4) Public corridors must be supplied with outdoor air at the rate of 1.3 L/s per
square metre of area.
(5) Ventilation systems having a capacity of more than 6000 L/s must be tested for
performance. Each owner must submit to the authority having jurisdiction a report
indicating the measured rate of air and the rate of exhaust air specified on the plans for
each louvre, diffuser, outdoor air intake, exhaust air outlet and fan. The difference between
the measured rate of air and the exhaust air specified on the plans may not be more than
10%.
(6) The required mechanical ventilation systems must be in continuous operation
during the period of occupancy of rooms and spaces in the building.”.”.
32. Article 58.1 of that by-law is replaced by the following articles :
“58.1. Article 6.2.2.2 of the Code is amended by replacing Sentence (1) by the following :
“(1) Except in bars, entertainment facilities, dance halls and music
studios and except as provided in the By-law concerning noise (R.B.C.M.,
chapter B-3), the natural ventilation provided by windows that open, doors or
other openings of each room or space with a total opening area no less than
5% of that of the floor is permitted instead of mechanical ventilation.”.
58.2. Article 6.2.2.3 of the Code is amended by adding the following, in Sentence (3), after
the word “occupancy.”:
“They must also be positioned so that the entire area of the storage garage is
ventilated.”.
58.3. Article 6.2.2.4 of the Code is amended by replacing, in Sentence (1), the words
“unsafe concentrations” by the words “concentrations greater than those permitted in the
Industrial Ventilation Manual published by the American Conference of Governmental
Industrial Hygienists”.
58.4. Article 6.2.2.6 of the Code is replaced by the following :
“6.2.2.6. Cooking Equipment
(1) Open-air cooking areas with a capacity of no more than 8 kW for
equipment running on electricity and no more than 14 kW for equipment
97-068 / 9
running on gas must be provided with a hood connected to an independent air
exhaust system.
(2) Except as provided in Sentence 3.5.3.1.(1) and Article 3.5.4.2.,
systems for the ventilation of commercial cooking equipment, except
microwave ovens, convection ovens, hot plates, toasters or other similar
equipment, must be designed, constructed and installed to conform to
NFPA 96, “Ventilation Control and Fire Protection of Commercial Cooking
Operations”, where the cooking equipment is
(a) listed, according to applicable standards, as commercial equipment,
(b) used in a restaurant or in a catering establishment,
(c) listed, according to applicable standards, as residential equipment and
has an open-air cooking area of a cumulative capacity of more than 14
kW when operating on gas.
(3) Except as provided in Sentence (5), the exhaust rate of systems for
the ventilation of commercial cooking equipment required under Sentence (2)
must be calculated according to one of the following methods :
(a) multiply the section of the lower opening of the hood by the air velocity
in Table 6.2.2.6.A.,
Table 6.2.2.6.A.
Exhaust Rate
Number of Open
Sides under Hood
Minimum
Average
Velocity
Allowed
Away from any wall
4
0.5 m/s
Standing against a wall
3
0.375 m/s
Standing against 2 walls
2
0.25 m/s
Location
of Hood
With aprons
0.25 m/s
(b) follow the method in ASHRAE, “Kitchen Ventilation”, Volume 5, No. 1.
(4) The make-up air may not be introduced directly into a kitchen hood.
(5) Where the cooking equipment in Sentence (2) is not solid-fuel-fired, the capacity of
the exhaust system must be calculated according to the following formula :
Q = 500 (P x H)
where
Q = capacity of hood in L/s,
P = perimeter of hood in metres,
H = height in metres, measured between the bottom of the hood and the
cooking area.
97-068 / 10
(6) For the purposes of Sentence (5), where the perimeter of the hood
is not fully cleared, the surface of aprons and walls along that perimeter may
be deducted from the product (P x H). For a fireplace, the capacity in L/s of
the exhaust system must be equal to 500 times the fireplace opening in square
metres.
(7) The lower opening of the hood required in Sentence (2) may not
be less than 460 mm from the cooking surface and no more than 2100 mm
from the floor.
(8) No drain may surround the interior perimeter of a kitchen hood
required in Sentence (2) unless it is the one required to drain grease from
filters.
(9) The power or gas supply of the cooking equipment referred to in
Sentence (2) must be designed so that it automatically interrupts when
(a) the automatic fire suppression system protecting the
ventilation system of the kitchen equipment is activated,
(b) a power failure occurs in the electric circuit supplying the
ventilation system of the cooking equipment.
(10) The power or gas supply of the cooking equipment referred to in
Sentence (9) may only be reactivated by a manual reset device.”.
58.5. Article 6.2.2.7 of the Code is amended by adding, after the word “means”, the words
“, as specified in Sections 9.18.3. and 9.19.1.”.”.
33. That by-law is amended by adding the following after Article 59:
“59.1. Article 6.2.3.10 of the Code is amended by adding the following sentences after
Sentence (9):
“(10) Where, in accordance with Articles 3.5.3.4. and 9.10.9.18. of the
Code, individual fans serve a fire compartment, the capacity of the fan at the
outlet of the main exhaust may be determined by applying the coincidence
factor in Table 6.2.3.10.A.
97-068 / 11
Table 6.2.3.10.A.
COINCIDENCE FACTOR
OPERATION OF FANS
(11) The minimum diameters of exhaust ducts of residential kitchen
hoods, washrooms and dryers must conform to Table 6.2.3.11.A.
Table 6.2.3.11.A.
Diameter of exhaust ducts
Volume (L/s)
Diameters
(mm)
Maximum Lengths
(m)
24 (in washrooms)
75
100
4.6
15
35 (in washrooms)
100
125
150
7.6
24.3
61
47 (in washrooms)
100
125
150
4.6
15
36.5
70 (for dryers, including 2 bends)
100
125
150
6
21.3
45.7
70 (for residential kitchen hoods)
125
150
200
6
15
76
(12) Systems must exhaust waste air directly to the outdoors.
(13) Despite Sentence (12), exhaust systems may discharge air into a
storage gagage provided the systems serve rooms
(a) that are accessible only by that storage garage,
(b) that are not served by an air duct system serving other parts of the
building,
(c) other than a boiler room, rooms housing generators referred to in
Article 3.5.2.11. and a temporary combustible waste storage
room,
(d) other than rooms containing materials referred to in Articles
6.2.2.4. and 6.2.2.5.”.”.
59.2. Article 6.2.3.12 of the Code is replaced by the following:
“6.2.3.12. Make-Up Air
(1) In ventilating systems that exhaust air to the outdoors, provision
must be made for the admission of a supply of make-up air in sufficient
quantity so that the operation of the exhaust system and other exhaust
equipment or combustion equipment is not adversely affected. (See Appendix
97-068 / 12
A.)
(2)
(3)
The make-up air must be drawn directly from outdoors.
Despite Sentence (2), the make-up air may be drawn from a
storage garage provided the storage garage serves rooms
(a) that are accessible only from the same storage garage,
(b) other than a boiler room, a room containing a generator referred
to in Article 3.5.2.11., or a temporary combustible waste storage
room.
(4) The admission of make-up air may not depend on the opening of
windows and doors for any hood whose capacity exceeds 420 L/s. The makeup air must be in sufficient quantity so that the operation of heat-producing
equipment in the same room is not adversely affected.”.
59.3. Article 6.2.3.13 of the Code is amended by replacing Sentences (3), (4) and (5) by
the following:
“(3) The lower end of an outdoor air intake must be no less than
(a) 2.1 m from the ground when located on a wall next to a public
way,
(b) 0.45 m above the roof when it is located on it,
(c) 0.9 m from the ground in other cases.
(4) Air exhaust systems must end
(a) at the envelope of the building, no less than 2.1 m from any
outside air intake and any window that opens in the same
building or neighboring buildings, where those systems are part
of the ventilation systems referred to in Article 6.2.2.1. and
Sentence 6.2.2.6.(1),
(b) at the roof of the building, no less than 7.6 m from any outside
air intake, and from any window that opens in the same building
or neighboring buildings, where those systems are part of the
ventilation systems referred to in Articles 6.2.2.4. and 6.2.2.5. and
Sentence 6.2.2.6.(2),
(c) at the envelope of the building, no less than 7.6 m from any
outside air intake and any window that opens in the same
building or neighboring buildings, where those systems are part
of the ventilation systems referred to in Article 6.2.2.3.
(5) The lower end of an outdoor exhaust outlet must end no less than
(a) 3.6 m from the ground if it is on a wall next to a public way,
(b) 0.45 m above the roof if it is located on it,
(c) 0.6 m from the ground in other cases.
(6) Exterior openings for outdoor air intakes and exhaust outlets must
be shielded from the entry of snow and rain and must be fitted with screens
accessible for maintenance and be corrosion-resistant, of mesh no larger than
15 mm, except where climate conditions require larger openings.
(7) No outdoor ventilation outlet may be in an areway.
97-068 / 13
(8) Except as provided in Sentence (4), an outdoor ventilation outlet,
whether it be on the roof or on the wall, must be 1.5 m from any lot line.”.
59.4. Article 6.2.3.16 is amended by adding the following after Sentence (2):
“(3) Fans, air washers, heating and cooling units or associated air
handling equipment must be provided with a visible and easily accessible
name plate, giving the specifications of the equipment.”.”.
34. That by-law is amended by adding the following after Article 68:
“68.1. Table 9.6.3.A of the Code is amended by replacing, in column 2, “760” by “610”.”.
35. Article 73 of that by-law is replaced by the following:
“73. Subsection 9.8.3 of the Code is amended:
(1) by replacing the title of that subsection by the following:
“Straight Stairs”;
(2) by adding the following sentence after Sentence 9.8.3.3.(2):
“(3) Exterior stairs serving only dwelling units that do no constitute their
only exit and that serve as an exit for no more than 2 dwelling units per storey
may have a width of not less than 760 mm.”.
73.1. Subsection 9.8.5 of the Code is replaced by the following:
“9.8.5. Curved Stairs
9.8.5.1. Exit Stairs
(1) Except as provided in Sentence (2), curved stairs in exits must
conform to Sentence 3.4.6.8.(2).
(2) Exit stairs serving only dwelling units, that do not constitute their
only exit and that serve as an exit for no more than 2 dwelling units may be
entirely curved or in one or more parts, under the following conditions:
(a) they have a clear width of no less than 760 mm, and a width of no
more than 860 mm provided they end on the narrowest side at
runs less than 100 mm,
(b) the height of winders is uniform and is no less than 125 mm and
no more than 200 mm,
(c) they have runs which, when measured at 500 mm from the
narrowest side, have a constant depth no less than 225 mm and
equal to that of straight parts, if any,
(d) the rotation is always on the same side between 2 storeys.
9.8.5.2. Curved Stairs not in Exits
(1) Stairs not in exits may be entirely curved or in one or more parts
under the conditions in Sentence 3.3.1.15.(1) or under the following
conditions:
(a) they conform to Clauses 9.8.5.1.(2)(a) to (d),
(b) they are not accessible to the public,
(c) they only serve 2 consecutive storeys,
97-068 / 14
they are not part of a means of egress serving more than 6
persons,
(e) they must, when surrounded by contiguous walls, have a width
no less than 860 mm.
9.8.5.3. Head Room. The head room for curved stairs must conforms to Article
9.8.3.4.
9.8.5.4. Nosing or Backslope. Risers with curved parts must form a nosing of
no less than 25 mm, or an equivalent back slope on the risers must be
provided.”.
73.2. Subsection 9.8.7 of the Code is amended by adding the following after Article
9.8.7.10:
“9.8.7.11. Curved Stairs. In curved stairs containing more than 3 winders that
converge to a central point, at least one handrail must extend vertically 150
mm or more on each run or its extension.”.”.
(d)
36. Article 74 of that by-law is replaced by the following:
“74. Article 9.8.8.1 of the Code is replaced by the following:
“9.8.8.1. Required Guards
(1) Every exterior landing, porch and every balcony, mezzanine,
exterior gallery, raised walkway, stair, terrace, areaway and roof to which
access is provided for other than maintenance purposes, and every other place
to which access is provided where there is a difference in level must be
protected by guards on all open sides where the difference in elevation
between adjacent levels exceeds 600 mm.
(2) When an interior stair has more than 2 risers, the sides of the stair
and the landing or floor level around the stairwell must be enclosed by walls
or be protected by guards, except that a stair to an unfinished basement in a
dwelling unit may have one unprotected side.”.
74.1. Section 9.8 of the Code is amended by adding the following subsection after
Subsection 9.8.10:
“9.8.11. Access Ramps to Parking Areas
9.8.11.1. Difference in Ground Level
(1) The entrance to a storage garage must, according to the horizontal
distance of the threshold from the sidewalk or concrete curb, as the case may
be, correspond to the maximum difference in ground level in Table 9.8.11.1.A.
(2) The access ramp to parking areas must have, at every place, in the
direction of vehicular traffic, and outside the centreline where the ramp is
curved, a gradient corresponding to the difference in level/distance ratio in
Table 9.8.11.1.A.
97-068 / 15
Table 9.8.11.1.A.1
Forming Part of Article 9.8.11.1.
Difference in Level / Distance Ratio
Horizontal Distance²
(in metres)
Maximum Difference in Level
(in metres)
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
7.0
7.5
8.0
8.5
9.0
9.5
10.0
0
0.06
0.12
0.22
0.32
0.42
0.52
0.62
0.72
0.82
0.92
1.02
1.12
1.22
1.32
1.42
1.52
1.62
1.72
1.82
1.92
Column 1
Column 2
1
Data not corresponding to one of the exact figures in this table must, for calculation purposes, be reduced to
the preceding smaller measure and, if the distance between the garage threshold and the
right of way line of the public domain is more than 10 m, the maximum difference in level
may not be more than 20% from that distance.
² For a storage garage, the horizontal distance in this table is measured between the property line providing
access to the garage, and the threshold point closest to that line.
9.8.11.2. Counterslope. Where there is no sidewalk, the owner must alter the
soil profile by means of a counterslope set up from the pavement or adjacent
concrete curb laid by the city. The top of the counterslope must be at least at
the level of the pavement or curb.”.”.
37. Article 76.2 of that by-law is amended:
(1)
(2)
(3)
by adding, in Sentence 9.9.6.5.(5) of the Code, after clause (b), the following clause:
“b.1) it has a panic bar, easily retractable and built in the door frame,”;
by replacing, in Sentence 9.9.6.5.(5)(c) of the Code, “725 mm” by “610 mm”;
by adding the following paragraph after Sentence 9.9.6.5.(6) of the Code:
“(7) In a building containing only one use in Group C and no more than 2 dwelling
units per storey, the exterior door of an exit stair shaft may swing inward if it serves no
more than 3 dwelling units or 9 rooms to let and is no more than 1.5 m from the exterior
soil or if it serves no more than 2 dwelling units.”.
97-068 / 16
38. Articles 83.1 to 83.4 of that by-law are repealed.
39. That by-law is amended by adding the following article after Article 84:
“84.1. Article 9.10.9.18 of the Code is replaced by the following:
“9.10.9.18. Exhaust Ducts Serving More Than One Fire Compartment. When a
vertical service space contains an exhaust duct that serves more than one fire
compartment, the duct must have a fan located at or near the exhaust outlet to
ensure that the duct is under negative pressure, and the individual fire
compartments may not have individual fans that exhaust directly into the duct
in the vertical service space, unless the individual ducts go up 500 mm into
the exhaust duct and a back-draft damper is installed at the exhaust outlet of
each fan.”.”.
40. That by-law is amended by adding the following after Article 100:
“100.1. Article 9.31.1.1 of the Code is replaced by the following:
“9.31.1.1. Application
(1) This section applies to the plumbing facilities and plumbing
systems within dwelling units and rooming houses.
(2) Plumbing facilities other than those required in dwelling units or
rooming houses must conform to Subsection 3.6.4. (See also Section 3.7
concerning barrier-free plumbing facilities.)”.”.
41. Article 101 of that by-law is replaced by the following:
“101. Article 9.31.4.1 of the Code is replaced by the following:
“9.31.4.1. Sanitary Facilities
(1) A kitchen sink, lavatory, bathtub or shower, and water closet must
be provided for each dwelling unit.
(2) The sanitary facility required in Sentence (1), except the lavatory,
may be omitted in rooms of a rooming house where the facility is available in
a common occupancy with one bathtub or shower and one water closet per
group of 5 rooms, provided the bathrooms and washrooms are in separate
premises. Where the number of rooms is not a multiple of 5 and the result of
the calculation of the required number of fixtures has a fraction of more than
5%, the result is rounded off to the next whole number.”.”.
42. Article 103 of that by-law is amended:
(1) by replacing Table 10.1.2.A by the following:
“Table 10.1.2.A.
Being an integral part of Subsection 10.1.2.
Alterations
Types of alterations
Requirements relating to parts of
the floor area that are added or altered
Requirements relating to other
parts of the building
97-068 / 17
1. Extension
area (1)
in
building
All provisions of this Code (16), (17),
(18) and (19).
2. Extension
in
building
For types 3 and 4: (6).
height
3. Construction
of
connected floor space
inter-
4. Change in occupancy thus
transforming the building into
a high building
The provisions of this Code re- lating
to:
(1) for the framework sup- porting the
part added or altered:
(a) structural strength,
(b) fire resistance (3),
(2) type of construction (6),
(3) fire alarm and detection system,
where required for the parts altered or
added (9),
(4) automatic
sprinkler
system, where required for the parts
altered or added (9),
(5) standpipe and hose system, where
required for the parts altered or added,
(6) for means of egress serv- ing the
part added or altered: means of
egress (10),
(7) for service spaces connect- ed
with the part added or altered: service
spaces.
Subsection 3.2.6. of this Code, if the
building becomes a high building
after alterations.
Subsection 3.2.8. of this Code, if the
building contains inter-connected
floor space after alterations.
Column 1
2
3
5. Extension in floor area (2)
The provisions of this Code relat- ing
to:
(1) structural strength,
(2) type of construction,
(3) combination of major occupancies,
(4) means of egress,
(5) fire compartments (4),
(6) for an extension in floor
area: exposing building
face,
(7) fire alarm and detection system,
(8) automatic sprinkler system,
(9) standpipe and hose system, if
any,
(10) building materials,
(11) emergency lighting,
(12) plumbing,
(13) ventilation (16),
(14) health safety (17) (18) (19).
The provisions of this Code re- lating
to:
(1) for the framework sup- porting the
part added: structural strength,
(2) fire alarm and detection system,
where required for the parts added,
(3) for storeys where alter- ations are
made, except if the part added or
altered is isolated from the rest of the
floor area by a fire separation having a
fire-resistance rating at least equal to
the one required for the floor
assembly above or, if it is higher, to
the rating determined in Table
3.1.3.A.: automatic sprinkler system
(11),
(4) for means of egress serving the
part added or altered: means of egress
(5).
Article 3.2.2.11. of this Code, for the
addition of an underground storey.
The provisions of this Code relat- ing
to:
The provisions of this Code re- lating
to:
6. Addition of a mezza- nine
not considered in calculating
the building height (2)
7. Addition of an underground storey (2)
8. Change in occupancy thus
creating a new occu-pancy in
97-068 / 18
9. Change in occupancy thus
creating a new occu-pancy in
Group B, another division in
Group B, Group C or Division
1 of Group F (13)
(1) type of construction (7),
(2) combination of major occupancies,
(3) means of egress,
(4) fire compartments (4),
(5) fire alarm and detection system,
(6) automatic sprinkler system,
where required after alterations,
(7) building materials,
(8) emergency lighting,
(9) plumbing,
(10) ventilation (16),
(11) health safety (17) (18) (19).
(1) for the framework sup- porting the
altered part: struc- tural strength,
(2) fire alarm and detection sys- tem,
where required for the altered parts,
(3) for means of egress serving the
altered part: means of egress (5).
Column 1
2
3
10. Change to all or part of a
floor area, thus in- creasing
the total occu- pant load on
the floor area
The provisions of this Code relat- ing
to:
(1) combination of major occupancies,
(2) means of egress,
(3) fire compartments (4),
(4) fire alarm and detection sys- tem,
where required after
alterations,
(5) building materials,
(6) emergency lighting,
(7) plumbing,
(8) ventilation (16),
(9) health safety (17) (18) (19).
The provisions of this Code re- lating
to:
(1) for the framework sup- porting the
altered part: struc- tural strength,
(2) fire alarm and detection system,
where required for the altered parts,
(3) for means of egress serving the
altered part: means of egress (5).
11. Change in occupan- cy
thus creating a new
occupancy in another group
or another divi-sion, without
increasing the occupant load
or in-creasing the fire load
12. Change to all or part of a
floor area without increasing
the total occupant load on the
The provisions of this Code relat- ing
to:
(1) combination of major occupancies (14),
(2) means of egress (8),
(3) fire compartments (4),
(4) building materials,
(5) emergency lighting,
(6) plumbing,
(7) ventilation (16),
(8) health safety (17) (18) (19).
The provisions of this Code re- lating
to:
(1) for the framework sup- porting the
altered part: struc- tural strength,
(2) for means of egress serving the
altered part: means of egress (5).
13. Alteration, replace- ment
or addition of a building unit
The provisions of this Code relating to
that unit, depending on the work (15).
14. Construction of an
enclosed outdoor café (12)
The provisions of this Code relat- ing
to:
(1) structural strength,
(2) type of construction,
(3) means of egress,
(4) fire compartments,
(5) exposing building face,
another group or another
division and increasing the
occupant load or increasing
the fire load
floor area
The provisions of this Code re- lating
to:
(1) for the part supporting the part
added or altered: struc- tural strength,
(2) fire alarm and detection system,
where required for the added parts,
(3) for means of egress serving the
part added or altered: means of egress
97-068 / 19
(6) fire alarm and detection system, if any, or where required
after alterations,
(7) automatic sprinkler system, if
any,
(8) building materials,
(9) emergency lighting,
(10) plumbing,
(11) ventilation (16),
(12) health safety (17) (18) (19).
Column 1
2
(5).
3
Supplementary Requirements
The addition of a stairway, an elevator, a dumbwaiter, a service room, a washroom, a landing stage, a
storage room or other similar unit or room does not constitute an extension in building area.
However, where a service room, a storage room or other similar room is added, its area may
not be more than 150 m² or 10% of the floor area in which it is located (See Alterations, Type
13).
(b)
An extension in building area that does not exceed 10% of the existing building area or 150 m²
may be carried out in accordance with the requirements applying to type 5 alterations referred
to in this table.
(2) The addition of a stairway, an elevator, a dumbwaiter, a service room, a washroom, a landing stage, a storage
room or other similar unit or room does not constitute an extension in floor area or the addition of a
mezzanine or underground storey. However, where a service room, a storage room or other similar
room is added, its area may not be more than 150 m² or 10% of the floor area in which it is located
(See Alterations, Type 13).
(3) In a building of no more than 6 storeys in building height, where the occupancy of the part added or altered is not
in group B or C, the floors of other parts of the building need only have a fire-resistance rating of 1 h
when a fire-resistance rating of more than 1 h is required.
(4) In a building of no more than 6 storeys in building height, where the occupancy of the part added or altered is not
in group B or C, the fire separation between the part added or altered and the storey immediately below
need only have a fire-resistance rating of more than 1 h when a fire-resistance rating of more than 1 h
is required.
(5) Existing means of egress serving the part added or altered and designed in accordance with the by-laws in force
before January 1, 1994, need not be upgraded if their capacity, as determined by the methods of
calculation in this Code, is sufficient.
(6) Except for a building of more than 4 storeys in building height or whose building area is more than 1000 m², or
that contains a Group F, Division 1 major occupancy, for which the Code requires that it be both of
noncombustible construction and equipped with an automatic sprinkler system, the provisions of this
Code requiring that it be of noncombustible construction do not apply to existing combustible
components where the building is equipped with a fire alarm and detection system and the part having
those components is equipped with an automatic sprinkler system.
(7)
Except for a building of more than 4 storeys in building height or whose building area is more than
1000 m², or that contains a Group F, Division 1 major occupancy, for which the Code requires that it
be both of noncombustible construction and equipped with an automatic sprinkler system, the
provisions of this Code requiring that it be of noncombustible construction do not apply to existing
combustible components in one of the following cases:
(a)
the building is equipped with a fire alarm and detection system and the altered part is equipped
with an automatic sprinkler system,
(b)
the alteration meets the following conditions:
(i)
it is not of type 9, as defined in this table,
(1) (a)
97-068 / 20
(ii)
(iii)
(iv)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
it is carried out on the first storey, on the storey immediately above or below the first storey,
on two of those storeys or on three storeys at a time,
it only involves an increase in the occupant load,
the total occupant load of the establishment undergoing alterations is less than 60.
Where the alteration does not consist in an increase in area, the existing means of egress, designed in
accordance with the by-laws in force before January 1, 1994, need not be upgraded if their capacity, as
determined by the methods of calculation in this Code, is sufficient.
The units of an existing system must conform to this Code.
Unless they serve a floor area or part of a floor area containing patient rooms, no existing means of egress
need be extended if their capacity, as determined by the methods of calculation in this Code, is
sufficient.
Where there is no higher floor, those requirements apply, taking into consideration the fire-resistance
rating required for the floor assembly below.
The enclosed outdoor café must be located at the first storey level and may not consist of more than one
storey; its area may not be more than 50% of that of the establishment to which it is attached.
Where the new occupancy consists in a habitable space authorized under the Urban Planning By-law
(R.B.C.M., chapter U-1) as a supplementary occupancy in a business,
(a)
the construction requirements relating to occupancies of a building must be determined in
accordance with Subsections 3.1.3. and 3.2.2., or Section 9.10, as the case may be,
(b)
the major occupancy of a suite containing a habitable space must be considered as being in
Group C,
(c)
the major occupancies authorized in the same building and consisting of activities, operations or
processes constituting an explosion or inflammation hazard or any other safety hazard may not
contain any habitable spaces and must be grouped in a fire compartment having the same
fire-resistance rating as the upper storey or, if it is higher, having the fire-resistance rating
according to Table 3.1.3.A., or Subsection 9.10.9., as the case may be,
(d)
the fire alarm and detection system, where required, must conform to the requirements applicable
to Group C major occupancies,
(e)
the health safety requirements applicable to Group C occupancies are those prescribed in the
following sections and articles of chapter II of the Housing By-law (R.B.C.M., chapter L-1):
(i)
articles 46, 48 and 49,
(ii)
section II,
(iii) section III,
(iv) articles 62 to 65,
(v)
articles 68 and 70 to 73,
(vi) articles 74, 75 and 77,
(vii) section VII,
(viii) section VIII,
(f)
the health safety requirements applicable to uses other than those of Group C are those in this
Code.
The alteration, in all or in part, of a floor area containing a major occupancy incompatible with another
major occupancy of the building but that was authorized under the by-laws in force before January 1,
1994, may be carried out if it involves type 12 alterations referred to in this article and does not involve
an increase in area.
Where the building unit is the exit of a building of no more than 4 storeys, Articles 3.2.3.13., 9.9.4.5. and
9.9.4.6. of this Code do not apply, provided the floor area or part of the floor area served by the exit
has a separate means of egress.
97-068 / 21
(16)
(17)
(18)
(19)
Subsection 3.6.3., Part 6 and Section 9.32 of this Code apply to:
(a)
the added parts of a building undergoing type 1, 2, 5, 6, 7 or 14 alterations,
(b)
the altered parts of a building undergoing type 8 alterations involving an increase in occupant load, or type
10 alterations,
(c)
the altered parts of a building undergoing type 3, 4, 9, 11 or 12 alterations or type 8 alterations involving an
increase in the fire load; however, the existing ventilation designed in accordance with the by-laws in force
before January 1, 1994, need not be upgraded to conform to this Code,
(d)
any new component added to an existing system,
(e)
any new system.
Subject to supplementary requirements (18) and (19), Sections 3.6, 9.5, 9.6, 9.7 and 9.32 relating to health safety
apply to all types of alterations, except type 3 alterations and type 12 alterations not involving an increase in area.
Subject to supplementary requirement (19) and Sentence 3.6.4.2.(8), Subsection 3.6.4. applies to floor areas or parts
of a floor area undergoing alterations involving an increase in occupant load of more than 25, provided the floor area
or part of the floor area is already served by at least one water closet for both sexes. It also applies to alterations
involving the establishment of a new occupancy for which the number of fixtures must be recalculated.
Where one or more washrooms serve both the part added or altered and the other parts of the building, the required
number of fixtures may
(a)
be determined under Subsection 3.6.4. for the total floor area, or
(b)
be equal to the number determined under Subsection 3.6.4. for the part added or altered and the number
determined under the by-laws in force before January 1, 1994, for the other parts of the building, where the
existing fixtures have already been determined under those by-laws.
”;
(2)
(3)
(4)
(5)
by replacing Sentence 10.1.3.2.(1) by the following:
“(1) Existing combustible projections such as exterior galleries, balconies,
stairways, ramps, cornices, eaves fronting on a street may be replaced without considering
the minimum distances required under this Code.”;
by adding the following article after Article 10.1.3.3:
“10.1.3.4. Fire Resistance of Firewalls
(1) Except as provided in Sentence (2), a firewall having a fire-resistance rating of
at least 2 h and separating 2 existing buildings may serve as the firewall for which the
Code requires a fire-resistance rating of more than 2 h if there is no extension in height.
(2) Where the alteration consists in a change of occupancy thus creating a new
Group F, Division 1 or 2 occupancy, the fire-resistance rating of the firewall section in the
altered part of the building must be increased to 4 h.”;
by replacing Article 10.2.1.1 of the Code by the following:
“10.2.1.1. Scope. This section applies to any building constructed before December 1,
1976, whose height is more than 22.85 m and whose distance between grade and the floor
of the last storey is more than 18 m.”;
by deleting Sentence 10.2.2.6.(2) of the Code.
43. Section IV of that by-law is amended by adding the following before Article 104:
“103.1. Schedule A to the Code is amended by adding the following articles after Article A3.2.4.17:
“A-3.2.4.19.(1) Alert and Alarm Signals. Alert signals are part of a 2 stage fire
alarm system. The intent of the first, alert, stage is to notify persons in
authority of a potential threat to building occupants. If a continuously staffed
location is available, the alert signal can be restricted to that location.
A-3.2.4.19.(2) Alarm Signal Temporal Pattern. The temporal pattern of an
97-068 / 22
alarm signal relates to the time during which the signal is produced and the
intervals between the individual signal pulses. The international standard ISO
8201, “Acoustics - Audible emergency evacuation signal,” includes a pattern
that is becoming widely used in different countries and it is appropriate for
this pattern to be adopted in Canada. The temporal pattern can be produced
on most signalling devices. Most existing fire alarm systems can be modified,
and this pattern could be phased in when the systems require modification.
The characteristic of the pattern is a 3-pulse phase followed by an off phase.
The 3 pulses each consist of an on phase lasting for 0.5 ± 0.05 s followed by
an off phase lasting for 0.5 ± 0.05 s sounded for 3 successive on periods and
then followed by an off phase lasting for 1.5 ± 0.15 s. Figure A-3.2.4.19.(2).A.
indicates the pattern that is intended.
Figure A-3.2.4.19.(2).A.
Temporal pattern for fire alarm signal
Although the diagram shows a square wave form, the wave can have other
shapes that produce a similar effect.
If single stroke bells are to be used, the temporal pattern can be produced by
having the bell struck three times at a rate of one stroke per second followed
by an interval of 2 s of silence. Figure A-3.2.4.19.(2).B. shows the pattern that
results.
97-068 / 23
Figure A-3.2.4.19.(2).B.
Temporal pattern imposed on a single stroke bell or chime
A-3.2.4.19.(4) Sound Pressure Level. For the purposes of this requirement, an
audible signalling device should not produce a sound pressure level more
than 95 dBA when measured at a distance of 3 m from each device or at a
height of 2 m above the floor.
A-3.2.4.19.(5) Residential Sound Level. In a building in which corridors or
hallways serve more than one suite or dwelling unit, there will be situations
where an audible signal device cannot be placed in the corridor or hallway to
alert persons sleeping in suites and dwelling units, because the sound level in
the vicinity of the device would exceed that permitted by Sentence
3.2.4.19.(4). In these situations it will be necessary to supplement the building
fire alarm system with an audible signal device in the suite or dwelling unit.
These devices could be piezoelectric devices similar to the sounding units in
many smoke alarms, subject to the device emitting the appropriate temporal
pattern required by Sentence 3.2.4.19.(2).
A-3.2.4.19.(9) Disconnect Device for Dwelling Units. To minimize the
annoyance caused by false and unwanted alarms, the disconnect will permit a
person to silence the local audible device within the dwelling unit. At that time
the person would be aware of sounds from devices in common spaces and
could plan appropriate action. The disconnect will reduce the possibility of
tampering with the audible devices.”.”.
44. Article 104 of that by-law is amended by replacing, in the title of Article A.3.2.5.10.8(c) and 8(d), the
words “Standpipe Systems and Hose Stations” by the words “Piping Systems”.
45. Article 107 of that by-law is amended:
(1)
(2)
by deleting, in paragraph 2, the word “alter,”;
by replacing paragraphs 3 to 9 by the following:
“(3) alter a building, as well as install or change any appliance or equipment covered by
a requirement under this by-law or the Code, in particular:
(a) a standpipe and hose system, a fire alarm system and an automatic
sprinkler system;
(b) a solid-fuel-burning appliance and an oil combustion appliance;
(c) an appliance intended for the storage of flammable substances,
combustible liquids and all other materials that may constitute a safety
hazard for the occupants of a building and the public;
(d) electromagnetic locks and generators;
(e) heating and air-conditioning systems serving more than one suite and
having a capacity of more than 560 L/S, and ventilating systems;
(f) smoke control or smoke venting systems;
(4) construct or extend a parking area;
(5) upgrade existing buildings referred to in Part 10 of the Code.”.
46. Article 123 of that by-law is amended by adding, after the word “owner”, the words “, contractor or any
97-068 / 24
other interested person”.
47. Article 136 of that by-law is amended by deleting paragraph 2 of the second paragraph.
48. The By-law concerning the ventilation of buildings in the city of Montréal (4936) is repealed.
____________________
BASIC INFORMATION
FILE : 97-0008640
RESOLUTION : CO97-00719
APPROVAL : N.A.
COMING INTO FORCE : April 21, 1997
AMENDMENTS : Nil
97-068 / 25