* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download FUNDAMENTAL THEORY OF LOAD COMPENSATION
Ground (electricity) wikipedia , lookup
Power over Ethernet wikipedia , lookup
Mercury-arc valve wikipedia , lookup
Audio power wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
Electrical ballast wikipedia , lookup
Power inverter wikipedia , lookup
Opto-isolator wikipedia , lookup
Electric power system wikipedia , lookup
Amtrak's 25 Hz traction power system wikipedia , lookup
Pulse-width modulation wikipedia , lookup
Electrical substation wikipedia , lookup
Electrification wikipedia , lookup
Power factor wikipedia , lookup
Power MOSFET wikipedia , lookup
Current source wikipedia , lookup
Voltage regulator wikipedia , lookup
Surge protector wikipedia , lookup
History of electric power transmission wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Stray voltage wikipedia , lookup
Power engineering wikipedia , lookup
Power electronics wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Buck converter wikipedia , lookup
Voltage optimisation wikipedia , lookup
Alternating current wikipedia , lookup
Chapter 3 FUNDAMENTAL THEORY OF LOAD COMPENSATION (Lectures 19-28) 3.1 Introduction In general, the loads which have poor power factor, unbalance, harmonics, and dc components require compensation. These loads are arc and induction furnaces, sugar plants, steel rolling mills (adjustable speed drives), power electronics based loads, large motors with frequent start and stop etc. All these loads can be classified into three basic categories. 1. Unbalanced ac load 2. Unbalanced ac + non linear load 3. Unbalanced ac + nonlinear ac + dc component of load. The dc component is generally caused by the usage of half-wave rectifiers. These loads, particularly nonlinear loads generate harmonics as well as fundamental frequency voltage variations. For example arc furnaces generate significant amount of harmonics at the load bus. Other serious loads which degrade power quality are adjustable speed drives which include power electronic circuitry, all power electronics based converters such as thyristor controlled drives, rectifiers, cyclo converters etc.. In general, following aspects are important, while we do provide the load compensation in order to improve the power quality [1]. 1. Types of load (unbalance , harmonics and dc component) 2. Real and Reactive power requirements 3. Rate of change of real and reactive power etc. In this unit, we however, discuss fundamental load compensation techniques for unbalanced linear loads such as combination of resistance, inductance and capacitance and their combinations. The objective here will be to maintain currents balanced and unity factor with their voltages. 69 3.2 Fundamental Theory of Load Compensation We shall find some fundamental relation ship between supply system the load and the compensator. We shall start with the principle of power factor correction, which in its simplest form, and can be studied without reference to supply system [2]–[5]. The supply system, the load and the compensator can be modeled in various ways. The supply system can be modeled as a Thevenin’s equivalent circuit with an open circuit voltage and a series impedance, (its current or power and reactive power) requirements. The compensator can be modeled as variable impedance or as a variable source (or sink) of reactive current. The choice of model varied according to the requirements. The modeling and analysis done here is on the basis of steady state and phasor quantities are used to note the various parameters in system. 3.2.1 Power Factor and its Correction Consider a single phase system shown in 3.1(a) shown below. The load admittance is represented Is V l IX IR V Il Il Fig. 3.1 (a) Single line diagram of electrical system (b) Phasor diagram by Yl = Gl + jBl supplied from a load bus at voltage V = V ∠0. The load current is I l is given as, I l = V (Gl + jBl ) = V Gl + jV Bl = IR + jIX (3.1) According to the above equation, the load current has a two components, i.e. the resistive or in phase component and reactive component or phase quadrature component and are represented by IR and IX respectively. The current, IX will lag 90o for inductive load and it will lead 90o for capacitive load with respect to the reference voltage phasor. This is shown in 3.1(b). The load apparent power can be expressed in terms of bus voltage V and load current Il as given below. Sl = = = = = = V (Il )∗ V (IR + j IX )∗ V (IR − j IX ) V (Il cos φl − j Il sin φl ) V Il cos φl − j V Il sin φl Sl cos φl − j Sl sin φl 70 (3.2) From (3.1), I l = V (Gl + jBl ) = V Gl + jV Bl , equation (3.2) can also be written as following. Sl = = = = = V (Il )∗ V (V Gl + jV Bl )∗ V (V Gl − jV Bl ) V 2 Gl − j V 2 Bl Pl + jQl (3.3) From equation (3.3), load active (Pl ) and reactive power (Ql ) are given as, Pl = V 2 Gl Ql = −V 2 Bl (3.4) Now suppose a compensator is connected across the load such that the compensator current, Iγ is equal to −IX , thus, I γ = V Yγ = V (Gγ + jBγ ) = −IX = −j V Bl (3.5) The above condition implies that Gγ = 0 and Bγ = −Bl . The source current Is , can therefore given by, I s = I l + Iγ = IR (3.6) Therefore due to compensator action, the source supplies only in phase component of the load current. The source power factor is unity. This reduces the rating of the power conductor and losses due to the feeder impedance. The rating of the compensator is given by the following expression. S γ = Pγ + j Qγ = V (I γ )∗ = V (−j V Bl )∗ = jV 2 Bl (3.7) Using (3.4), the above equation indicates the Pγ = 0 and Qγ = − Ql . This is an interesting inference that the compensator generates the reactive power which is equal and opposite to the load reactive and it has no effect on active power of the load. This is shown in Fig. 3.2. Using (3.2) and (3.7), the compensator rating can further be expressed as, Qγ = −Ql = −Sl sin φl = −Sl p 1 − cos2 φl VArs (3.8) From (3.8), |Qγ | = Sl p 1 − cos2 φl (3.9) If |Qγ | < |Ql | or |Bγ | < |Bl |, then load is partially compensated. The compensator of fixed admittance is incapable of following variations in the reactive power requirement of the load. In 71 I I X Is V Is IR l IX I Il Il Fig. 3.2 (a) Single line diagram of compensated system (b) Phasor diagram practical however a compensator such as a bank of capacitors can be divided into parallel sections, each of switched separately, so that discrete changes in the reactive power compensation can be made according to the load. Some sophisticated compensators can be used to provide smooth and dynamic control of reactive power. Here voltage of supply is being assumed to be constant. In general if supply voltage varies, the Qγ will not vary separately with the load and compensator error will be there. In the following discussion, voltage variations are examined and some additional features of the ideal compensator will be studied. 3.2.2 Voltage Regulation Voltage regulation can be defined as the proportional change in voltage magnitude at the load bus due to change in load current (say from no load to full load). The voltage drop is caused due to feeder impedance carrying the load current as illustrated in Fig. 3.3(a). If the supply voltage is represented by Thevenin’s equivalent, then the voltage regulation (VR) is given by, E − V E − |V | VR = (3.10) = V |V | for V being a reference phasor. In absence of compensator, the source and load currents are same and the voltage drop due to the feeder is given by, ∆V = E − V = Zs Il (3.11) The feeder impedance, Zs = Rs + jXs . The relationship between the load powers and its voltage and current is expressed below. S l = V (I l )∗ = Pl + jQl (3.12) Since V = V , the load current is expressed as following. Il = Pl − jQl V 72 (3.13) Substituting, Il from above equation into (3.11), we get Pl − jQl ∆V = E − V = (Rs + jXs ) V Rs Pl + Xs Ql Xs Pl − Rs Ql = +j V V = ∆VR + j∆VX (3.14) Thus, the voltage drop across the feeder has two components, one in phase (∆VR ) and another is in phase quadrature (∆VX ). This is illustrated in Fig. 3.3(b). Feeder E Z s Rs jX s E Is l Load V Il j VX VR V R Il Yl Gl jBl jX l I l Il Sl Pl jQl Fig. 3.3 (a) Single phase system with feeder impedance (b) Phasor diagram From the above it is evident that load bus voltage (V ) is dependent on the value of the feeder impedance, magnitude and phase angle of the load current. In other words, voltage change (∆V ) depends upon the real and reactive power flow of the load and the value of the feeder impedance. Now let us add compensator in parallel with the load as shown in Fig. 3.4(a). The question is: whether it is possible to make E = V , in order to achieve zero voltage regulation irrespective of change in the load. The answer is yes, if the compensator consisting of purely reactive components, has enough capacity to supply to required amount of the reactive power. This situation is shown using phasor diagram in Fig. 3.4(b). The net reactive at the load bus is now Qs = Qγ + Ql . The compensator reactive power (Qγ ) has to be adjusted in such a way as to rotate the phasor ∆V until E = V . From (3.14) and Fig. 3.3(b), Rs Pl + Xs Qs Xs Pl − Rs Qs E∠δ = V + +j V V (3.15) The above equation implies that, 2 2 Rs Pl + Xs Qs Xs Pl − Rs Qs 2 E = V + + V V (3.16) 73 Feeder E Z s Rs jX s I Il I V Load Q Comp. Is E Is l Yl Gl jBl Sl Pl jQl V V jX s I s Rs Is Il Fig. 3.4 (a) Voltage with compensator (b) Phasor diagram The above equation can be simplified to, E 2 V 2 = (V 2 + Rs Pl )2 + Xs2 Q2s + 2(V 2 + RsPl ) Xs Qs ( (( +Xs2 Pl2 + Rs2 Q2s − ( 2X P( (s( l Rs Qs (3.17) Above equation, rearranged in the powers of Qs , is written as following. (Rs2 + Xs2 ) Q2s + 2V 2 Xs Qs + (V 2 + Rs Pl )2 + (Xs Pl )2 − E 2 V 2 = 0 (3.18) Thus the above equation is quadratic in Qs and can be represented using coefficients of Qs as given below. a Q2s + b Qs + c = 0 (3.19) Where a = Rs2 + Xs2 , b = 2V 2 Xs and c = (V 2 + Rs Pl )2 + Xs2 Pl2 − E 2 V 2 . Thus the solution of above equation is as following. p −b ± (b2 − 4ac) Qs = (3.20) 2a In the actual compensator, this value would be determined automatically by control loop. The equation also indicates that, we can find the value of Qs by subjecting a condition such as E = V irrespective of the requirement of the load powers (Pl , Ql ). This leads to the following conclusion that a purely reactive compensator can eliminate supply voltage variation caused by changes in both the real and reactive power of the load, provided that there is sufficient range and rate of Qs both in lagging and leading pf. This compensator therefore acts as an ideal voltage regulator. It is mentioned here that we are regulating magnitude of voltage and not its phase angle. In fact its phase angle is continuously varying depending upon the load current. It is instructive to consider this principle from different point of view. We have seen that compensator can be made to supply all load reactive power and it acts as power factor correction device. If the compensator is designed to compensate power factor, then Qs = Ql + Qγ = 0. This implies that Qγ = −Ql . Substituting Qs = 0 for Ql in (3.14) to achieve this condition, we get the 74 following. ∆V = (Rs + jXs ) Pl V (3.21) From above equation, it is observed that ∆V is independent of Ql . Thus we conclude that a purely reactive compensator cannot maintain both constant voltage and unity power factor simultaneously. Of course the exception to this rule is a trivial case when Pl = 0. 3.2.3 An Approximation Expression for the Voltage Regulation Consider a supply system with short circuit capacity (Ssc ) at the load bus. This short circuit capacity can be expressed in terms of short circuit active and reactive powers as given below. ∗ E E2 ∗ S sc = Psc + jQsc = E I sc = E = ∗ (3.22) Zsc Zsc Where Zsc = Rs + jXs and I sc is the short circuit current. From the above equation |Zsc | = Therefore, Rs = Xs = tan φsc = E2 Ssc E2 cos φsc Ssc E2 sin φsc Ssc Xs Rs Substituting above values of Rs and Xs , (3.14) can be written in the following form. ∆V Pl cos φsc + Ql sin φsc Pl sin φsc − Ql cos φsc E 2 = +j V V2 V2 Ssc ∆V ∆VR ∆VX = +j V V V Using an approximation that E ≈ V , the above equation reduces to the following. ∆V Pl cos φsc + Ql sin φsc Pl sin φsc − Ql cos φsc = +j V Ssc Ssc The above implies that, ∆VR Pl cos φsc + Ql sin φsc ≈ V Ssc ∆VX Pl sin φsc − Ql cos φsc ≈ V Ssc 75 (3.23) (3.24) (3.25) Often (∆VX /V ) is ignored on the ground that the phase quadrature component contributes negligible to the magnitude of overall phasor. It mainly contributes to the phase angle. Therefore the equation (3.25) is simplified to the following. ∆VR Pl cos φsc + Ql sin φsc ∆V = = V V Ssc (3.26) Implying that the major change in voltage regulation occurs due to in phase component, ∆VR . Although approximate, the above expression is quite useful in terms of short circuit level (Ssc ), (Xs /Rs , active and reactive power of the load. On the basis of incremental changes in active and reactive powers of the load, i.e., ∆Pl and ∆Ql respectively, the above equation can further be written as, ∆V ∆VR ∆Pl cos φsc + ∆Ql sin φsc = = . V V Ssc (3.27) Further, feeder reactance (Xs ) is far greater than feeder resistance (Rs ), i.e., Xs >> Rs . This implies that, φsc → 90o , sin φsc → 1 and cos φsc → 0. Using this approximation the voltage regulation is given as following. ∆V ∆VR ∆Ql ∆Ql ≈ ≈ sin φsc ≈ . V V Ssc Ssc (3.28) That is, per unit voltage change is equal to the ratio of the reactive power swing to the short circuit level of the supply system. Representing ∆V approximately by E − V and assuming linear change in reactive power with the voltage, the equation (3.28) can be writtwn as, E−V Ql . ≈ V Ssc (3.29) The above leads to the following expression, V ' E Ql ' E(1 − ) Ql Ssc (1 + Ssc ) (3.30) with the assumption that, Ql /Ssc << 1. Although above relationship is obtained with approximations, however it is very useful in visualizing the action of compensator on the voltage. The above equation is graphically represented as Fig. 3.5. The nature of voltage variation is drooping with increase in inductive reactive power of the load. This is shown by negative slope −E/Ssc as indicated in the figure. The above characteristics also explain that when load is capacitive, Ql is negative. This makes V > E. This is similar to Ferranti effect due to lightly loaded electric lines. Example 3.1 Consider a supply at 10 kV line to neutral voltage with short circuit level of 250 MVA and Xs /Rs ratio of 5, supplying a star connected load inductive load whose mean power is 25 MW and whose reactive power varies from 0 to 50 MVAr, all quantities per phase. 76 V E E S sc 0 Ql Fig. 3.5 Voltage variation with reactive power of the load (a) Find the load bus voltage (V ) and the voltage drop (∆V ) in the supply feeder. Thus determine load current (I l ), power factor and system voltage (E ). (b) It is required to maintain the load bus voltage to be same as supply bus voltage i.e. V =10 kV. Calculate reactive power supplies by the compensator. (c) What should be the load bus voltage and compensator current if it is required to maintain the unity power factor at the supply? Solution: The feeder resistance and reactance are computed as following. Zs = Es2 /Ssc = (10 kV)2 /250 = 0.4 Ω/phase It is given that, Xs /Rs = tan φsc = 5, therefore φsc = tan−1 5 = 78.69o . From this, Rs = Zs cos φsc = 0.4 cos(78.69o ) = 0.0784 Ω Xs = Zs sin φsc = 0.4 sin(78.69o ) = 0.3922 Ω (a) Without compensation Qs = Ql , Qγ = 0 To know ∆V , first the voltage at the load bus has to be computed. This is done by rearranging (3.18) in powers of voltage V . This is given below. (Rs2 + Xs2 ) Q2l + 2 V 2 Xs Ql + (V 2 + Rs Pl )2 + Xs2 Pl2 − E 2 V 2 = 0 (R2 + X 2 ) Q2 + 2 V 2 X Q + V 4 + R2 P 2 + 2 V 2 R P + X 2 P 2 − E 2 V 2 = 0 | s {z s }l | {z s }l |{z} | s{z l} | {z s }l | s{z l} | {z } III II I III II III II Combining the I, II and III terms in the above equation, we get the following. V 4 + 2(Rs Pl + Xs Ql ) − E 2 V 2 + (Rs2 + Xs2 )(Q2l + Pl2 ) = 0 Now substituting values of Rs , Xs , Pl , Ql and E in above equation, we get, V 4 + 2 [0.0784 × 25 + 0.3922 × 50] − 102 V 2 + (0.07842 + 0.39222 )(252 + 502 ) = 0 77 (3.31) After simplifying the above, we have the following equation. V 4 − 56.86V 2 + 500 = 0 Therefore V 2 and V √ 56.86 − 4 × 500 = 2 = 45.985, 10.875 = ±6.78 kV, ±3.297 kV 56.86 ± Since rms value cannot be negative and maximum rms value must be a feasible solution, therefore V = 6.78 kV. Now we can compute ∆V using (3.14), as it is given below. ∆V R s Pl + X s Q l Xs Pl − Rs Ql +j V V 0.3922 25 − 0.0784 50 0.0784 25 + 0.392 50 +j = 6.78 6.78 = 3.1814 + j0.8677 kV = 3.2976∠15.25o kV = Now the line current can be found out as following. Pl − Ql 25 − j50 = V 6.782 = 3.86 − j7.3746 kA = 8.242∠ − 63.44o kA Il = The power factor of load is cos (tan−1 (Ql /Pl )) = 0.4472 lagging. The phasor diagram for this case is similar to what is shown in Fig. 3.3(b). (b) Compensator as a voltage regulator Now it is required to maintain V = E = 10.0 kV at the load bus. For this let their be reactive power Qγ supplied by the compensator at the load bus. Therefore the net reactive power at the load bus is equal to Qs , which is given below. Qs = Ql + Qγ Thus from (3.18), we get, (Rs2 + Xs2 )Q2s + 2V 2 Xs Qs + (V 2 + Rs Pl )2 + Xs2 Pl2 − E 2 V 2 = 0 (0.7842 + 0.39222 )2 Q2s + 2 × 102 × 0.3922 × Qs + (102 + 0.784 × 25)2 + 0.39222 × 252 − 104 = 0 From the above we have, 0.16 Q2s + 78.44 Qs + 491.98 = 0. 78 Solving the above equation we get, √ 78.442 − 4 × 0.16 × 491.98 2 × 0.16 = −6.35 or − 484 MVAr. Qs = −78.44 ± The feasible solution is Qs = −6.35 MVAr because it requires less rating of the compensator. Therefore the reactive power of the compensator (Qγ ) is, Qγ = Qs − Ql = −6.35 − 50 = −56.35 MVAr. With Qs = −6.35 MVAr, the ∆V is computed by replacing Qs for Ql in (3.14) as given below. ∆V Xs Pl − Rs Qs Rs Pl + Xs Qs +j V V 0.0784 × 25 + 0.39225 × −6.35 0.39225 × 25 − 0.0784 × (−6.35) = +j 10 10 1.96 − 2.4 9.805 + 0.4978 = +j 10 10 = −0.0532 + j1.030 kV = 1.03137∠92.95o kV = Now, we can find supply voltage E as given below. E = ∆V + V = 10 − 0.0532 + j1.030 = 9.9468 + j1.030 = 10∠5.91o kV The supply current is, Pl − jQs 25 − j(−6.35) = V 10 = 2.5 + j0.635 kA = 2.579∠14.25o kA. Is = This indicates that power factor is not unity for perfect voltage regulation i.e., E = V . For this case the compensator current is given below. −jQγ −j(−56.35) = V 10 = j5.635 kA Iγ = Iγ The load current is computed as below. Pl − jQl 25 − j50 = V 10 = 2.5 − j5.0 = IlR + jIlX = 5.59∠63.44o kA Il = The phasor diagram is similar to the one shown in Fig. 3.4(b). The phasor diagram shown has interesting features. The voltage at the load bus is maintained to 1.0 pu. It is observed that the reactive power of the compensator Qγ is not equal to load reactive power (Ql ). It exceeds by 6.35 79 MVAr. As a result of this compensation, the voltage regulation is perfect, however power factor is not unity. The phase angle between V and I s is cos−1 0.969 = 14.25o as computed above. Therefore the angle between E and I s is (14.25o − 5.91o = 8.34o ). Thus, source power factor (φs ) is cos(8.340 ) = 0.9956 leading. (c) Compensation for unity power factor To achieve unity power factor at the load bus, the condition Qγ = −Ql must be satisfied, which further implies that the net reactive power at the load bus is zero. Therefore substituting Ql = 0 in (3.31), we get the following. V 4 + 2(Rs Pl − E 2 ) V 2 + (Rs2 + Xs2 )(Pl2 + Q2l ) = 0 V 4 + (2 × 0.0784 × 25 − 102 )V 2 + (0.07842 + 0.39222 ) 252 = 0 From the above, V 4 + 96.08V 2 + 99.79 = 0 The solution of the above equation is, 96.08 ± 93.97 = 95.02, 1.052 2 = ±9.747 kV, ±1.0256 kV. V2 = V Since rms value cannot be negative and maximum rms value must be a feasible solution, therefore V = 9.747 kV. Thus it is seen that for obtaining unity power factor at the load bus does not ensure desired voltage regulation. Now the other quantities are computed as given below. Il = Pl − jQ 25 − j50 = = 2.5648 − j5.129 = 5.7345∠−63.43o kA V 9.747 Since Qγ = −Ql , this implies that Iγ = −jQγ /V = jQl /V = j5.129 kA. The voltage drop across the feeder is given as following. ∆V Rs Pl + Xs Ql Xs Pl − Rs Ql +j V V (0.784 × 25 + j0.3922 × 25) = 9.747 = 0.201 + j1.005 = 1.0249∠5.01o kV = The phasor diagram for the above case is shown in Fig. 3.6. The percentage voltage change = (10 − 9.748)/10 × 100 = 2.5. Thus we see that power factor improves voltage regulation enormously compared with uncompensated case. In many cases, degree of improvement is adequate and the compensator can be designed to provide reactive power requirement of load rather than as a ideal voltage regulator. 80 I j 5.13 kA E 10 kV 5.77 VX V = 9.75 kV VR I lR = 2.56 kA I lX j 5.13 kA Is I l 5.73 63.43 kA Fig. 3.6 Phasor diagram for system with compensator in voltage regulation mode 3.3 Some Practical Aspects of Compensator used as Voltage Regulator In this section, some practical aspects of the compensator in voltage regulation mode will be discussed. The important parameters of the compensator which play significant role in obtaining desired voltage regulation are: Knee point (V k ), maximum or rated reactive power Qγmax and the compensator gain Kγ . The compensator gain Kγ is defined as the rate of change of compensator reactive power Qγ with change in the voltage (V ), as given below. Kγ = dQr dV (3.32) For linear relationship between Qγ and V with incremental change, the above equation be written as the following. ∆Qγ = ∆V Kγ (3.33) Assuming compensator characteristics to be linear with Qγ ≤ Qγmax limit, the voltage can be represented as, Qγ V = Vk + (3.34) Kγ This is re-written as, Qγ = Kγ (V − Vk ) 81 (3.35) Flat V-Q characteristics imply that Kγ → ∞. That means the compensator which can absorb or generate exactly right amount of reactive power to maintain supply voltage constant as the load varies without any constraint. We shall now see the regulating properties of the compensator, when compensator has finite gain Kr operating on supply system with a finite short circuit level, Ssc . The further which are made in the following study are: high Xs /Rs ratio and negligible load power fluctuations. The net reactive power at the load bus is sum of the load and the compensator reactive power as given below. Ql + Qγ = Qs (3.36) Using earlier voltage and reactive power relationship from equation (3.30), it can be written as the following. V ' E(1 − Qs ) Ssc (3.37) The compensator voltage represented by (3.34) and system voltage represented by (3.37) are shown in Fig. 3.7(a) and (b) respectively. V V Vk Q K Vk E Q V E 1- s S SC Q Qs (a) (b) Fig. 3.7 (a) Voltage characterstics of compensator (b) System voltage characteristics Differentiating V with respect to Qs , we get, intrinsic sensitivity of the supply voltage with variation in Qs as given below. dV E =− (3.38) dQs Ssc It is seen from the above equation that high value of short circuit level Ssc reduces the voltage sensitivity, making voltage variation flat irrespective of Ql . With compensator replacing Qs = Qγ + Ql in (3.37), we have the following. Ql + Qγ V 'E 1− Ssc 82 (3.39) Substituting Qγ from (3.35), we get the following equation. Ql /Ssc 1 + Kγ Vk /Ssc − V 'E 1 + E Kγ /Ssc 1 + E Kγ /Ssc (3.40) Although approximate, above equation gives the effects of all the major parameters such as load reactive power, the compensator characteristics Vγ and Kγ and the system characteristics E and Ssc . As we discussed, V-Q characteristics is flat for high or infinite value Kγ . However the higher value of the gain Kγ means large rating and quick rate of change of the reactive power with variation in the system voltage. This makes cost of the compensator high. The compensator has two effects as seen from (3.40), i.e., it alters the no load supply voltage (E) and it modifies the sensitivity of supply point voltage to the variation in the load reactive power. Differentiating (3.40) with respect to Ql , we get, dV E/Ssc =− dQl 1 + Kr E/Ssc (3.41) which is voltage sensitivity of supply point voltage to the load reactive power. It can be seen that the voltage sensitivity is reduced as compared to the voltage sensitivity without compensator as indicated in (3.38). It is useful to express the slope (−E/Ssc ) by a term in a form similar to Kγ = dQγ /dV , as given below. Ssc E E = − Ssc Ks = − Thus, 1 Ks Substituting V from (3.39) into (3.35), the following is obtained. Ql + Qγ Qγ = Kγ E 1 − − Vk Ssc Collecting the coefficients of Qγ from both sides of the above equation, we get Kγ Ql Qγ = E 1− − Vk 1 + Kγ (E/Ssc ) Ssc (3.42) (3.43) (3.44) Setting knee voltage Vk of the compensator equal to system voltage E i.e., Vk = E, the above equation is simplified to, Kγ (E/Ssc ) Ql 1 + Kγ (E/Ssc ) Kγ /Ks = − Ql . 1 + Kγ /Ks Qγ = − 83 (3.45) From the above equation it is observed that, when compensator gain Kγ → ∞, Qγ → −Ql . This indicates perfect compensation of the load reactive power in order to regulate the load bus voltage. Example 3.2 Consider a three-phase system with line-line voltage 11 kV and short circuit capacity of 480 MVA. With compensator gain of 100 pu determine voltage sensitivity with and without compensator. For each case, if a load reactive power changes by 10 MVArs, find out the change in load bus voltage assuming linear relationship between V-Q characteristics. Also find relationship between compensator and load reactive powers. Solution: The voltage sensitivity can be computed using the following equation. dV E/Ssc =− dQl 1 + Kγ E/Ssc √ Without compensator Kγ = 0, E = (11/ 3) = 6.35 kV and Ssc = 480/3 = 160 MVA. Substituting these values in the above equation, the voltage sensitivity is given below. dV 6.35/160 =− = −0.039 dQl 1 + 0 × 6.35/160 The change in voltage due to variation of reactive power by 10 MVArs, ∆V = −0.039 × 10 = −0.39 kV. With compensator, Kγ = 100 dV 6.35/160 =− = −0.0078 dQl 1 + 100 × 6.35/160 The change in voltage due to variation of reactive power by 10 MVArs, ∆V = −0.0078 × 10 = −0.078 kV. Thus it is seen that, with finite compensator gain their is quite reduction in the voltage sensitivity, which means that the load bus is fairly constant for considerable change in the load reactive power. The compensator reactive power Qγ and load reactive power Ql are related by equation (3.45) and is given below. Kγ (E/Ssc ) 100 × (6.35/160) Ql = − Ql 1 + Kγ (E/Ssc ) 1 + 100 × (6.35/160) = −0.79 Ql Qγ = − It can be observed that when compensator gain, (Qγ ) is quite large, then compensator reactive power Qγ is equal and opposite to that of load reactive power i.e., Qγ = −Ql . It is further observed that due to finite compensator gain i.e., Kγ = 100, reactive power is partially compensated The compensator reactive power varies from 0 to 7.9 MVAr for 0 to 10 MVAr change in the load reactive power. 3.4 Phase Balancing and Power Factor Correction of Unbalanced Loads So far we have discussed voltage regulation and power factor correction for single phase systems. In this section we will focus on balancing of three-phase unbalanced loads. In considering unbalanced loads, both load and compensator are modeled in terms of their admittances and impedances. 84 3.4.1 Three-phase Unbalanced Loads Consider a three-phase three-wire system suppling unbalanced load as shown in Fig. 3.8. V V an bn Ia I1 Ib N V cn Za Zb n I2 Ic Zc Fig. 3.8 Three-phase unbalanced load Applying Kirchoff’s voltage law for the two loops shown in the figure, we have the following equations. −V an + Za I 1 + Zb (I 1 − I 2 ) + V bn = 0 −V bn + Zb I 2 + Zb (I 2 − I 1 ) + V cn = 0 (3.46) Rearranging above, we get the following. V an − V bn = (Za + Zb ) I 1 − Zb I 2 V bn − V cn = (Zb + Zc ) I 2 − Zb I 1 The above can be represented in matrix form as given below. V an − V bn I1 (Za + Zb ) −Zb = −Zb (Zb + Zc ) V bn − V cn I2 Therefore the currents are given as below. −1 I1 (Za + Zb ) −Zb V an − V bn = −Zb (Zb + Zc ) I2 V bn − V cn 1 (Zb + Zc ) Zb V an − V bn = Zb (Za + Zb ) V bn − V cn ∆Z 1 I1 (Zb + Zc ) Zb V an − V bn Therefore, = . Zb (Za + Zb ) I2 V bn − V cn ∆Z (3.47) (3.48) (3.49) Where, ∆Z = (Zb + Zc )(Za + Zb ) − Zb2 = Za Zb + Zb Zc + Zc Za . The current I 1 is given below. 1 I1 = (Zb + Zc )(V an − V bn ) + Zb (V bn − V cn ) ∆Z 1 = (Zb + Zc )V an − Zc V bn − Zb V cn (3.50) ∆Z 85 Similarly, 1 ∆Z 1 = ∆Z I2 = Zb (V an − V bn ) + (Za + Zb )(V bn − V cn ) Zb V an + Za V bn − (Za + Zb )V cn (3.51) Now, 1 (Zb + Zc )V an − Zc V bn − Zb V cn ∆Z I2 − I1 1 Zb V an + Za V bn − (Za + Zb )V cn − (Zb + Zc )V an + Zc V bn + Zb V cn ∆ Z (Zc + Za )V bn − Za V cn − Zc Van ∆Z (Zc + Za )V bn − Zc V an − Za V cn (3.52) ∆Z Ia = I1 = Ib = = = = and (Za + Zb )V cn − Zb V an − Za V bn ∆Z Alternatively phase currents can be expressed as following. I c = −I 2 = −I b − I a = V an − V N n Za V bn − V N n = Zb V cn − V N n = Zc (3.53) Ia = Ib Ic (3.54) Applying Kirchoff’s current law at node N , we get I a + I b + I c = 0. Therefore from the above equation, V an − V N n V bn − V N n V cn − V N n + + = 0. Za Zb Zc (3.55) Which implies that, V an V bn V cn 1 1 1 Za Zb + Zb Zc + Zc Za + + = + + V Nn = V Nn (3.56) Za Zb Zc Za Zb Zc Za Zb Zc From the above equation the voltage between the load and system neutral can be found. It is given below. Za Zb Zc V an V bn V cn V Nn = + + ∆Z Za Zb Zc 1 V an V bn V cn = 1 + + (3.57) Za Zb Zc + Z1b + Z1c Za 86 Some interesting points are observed from the above formulation. 1. If both source voltage and load impedances are balanced i.e., Za = Zb = Zc = Z, then 1 V N n = 3 V an + V bn + V cn = 0. Thus their will not be any voltage between two neutrals. 2. If supply voltage are balanced and load impedances are unbalanced, then V N n 6=0 and is given by the above equation. 3. If supply voltages are not balanced but load impedances are identical, then V N n = This equivalent to zero sequence voltage V 0 . 1 3 V an + V bn + V cn . It is interesting to note that if the two neutrals are connected together i.e., V N n = 0, then each phase become independent through neutral. Such configuration is called three-phase four-wire system. In general, three-phase four-wire system has following properties. ) V Nn = 0 (3.58) I a + I b + I c = I N n 6= 0 The current I N n is equivalent to zero sequence current (I 0 ) and it will flow in the neutral wire. For three-phase three-wire system, the zero sequence current is always zero and therefore following properties are satisfied. ) V N n 6= 0 (3.59) Ia + Ib + Ic = 0 Thus, it is interesting to observe that three-phase three-wire and three-phase four-wire system have dual properties in regard to neutral voltage and current. 3.4.2 Representation of Three-phase Delta Connected Unbalanced Load A three-phase delta connected unbalanced and its equivalent star connected load are shown in Fig. 3.9(a) and (b) respectively. The three-phase load is represented by line-line admittances as given below. c c Ic Ic Yl Z lc ca l bc Y Z lb Ib Ib a b Yl Ia n a b ab Z la Ia (a) (b) Fig. 3.9 (a) An unbalanced delta connected load (b) Its equivalent star connected load 87 ab Ylab = Gab + jB l l bc Ylbc = Gbc l + jBl ca Ylca = Gca l + jBl (3.60) The delta connected load can be equivalently converted to star connected load using following expressions. Zlab Zlca = ab Zl + Zlbc + Zlca bc ab Zl Zl b Zl = ab Zl + Zlbc + Zlca ca bc Z Z l l c Zl = ab bc ca Zl + Zl + Zl Zla (3.61) Where Zlab = 1/Ylab , Zlbc = 1/Ylbc and Zlca = 1/Ylca . The above equation can also be written in admittance form Ylab Ylbc + Ylbc Ylca + Ylca Ylab Yl = Ylbc ab bc bc ca ca ab Y Y + Y Y + Y Y l l l l Yl b = l l Ylca ab bc bc ca ca ab Y Y + Y Y + Y Y l l l l Yl c = l l Ylab a (3.62) Example 3.3 Consider three-phase system supply a delta connected unbalanced load with Zal = Ra = 10 Ω, Zbl = Rb = 15 Ω and Zcl = Rc = 30 Ω as shown in Fig. 3.8. Determine the voltage between neutrals and find the phase currents. Assume a balance supply voltage with rms value of 230 V. Find out the vector and arithmetic power factor. Comment upon the results. 88 Solution: The voltage between neutrals V N n is given as following. VN n = = = = = = VN n = V an V bn V cn Ra Rb Rc + + Ra Rb + Rb Rc + Rc Ra Ra Rb Rc o 10 × 15 × 30 V ∠0 V ∠−120o V ∠120o + + 10 × 15 + 15 × 30 + 30 × 10 10 15 30 o o o 4500 3V ∠0 + 2V ∠−120 + V ∠120 900 30 " √ ! √ !# 3 3 4500 1 1 1 V 3+2 − −j + − +j 900 30 2 2 2 2 " √ √ # V 1 3 3 3 − 1 − − j2 × +j 6 2 2 2 " √ # V 3 3 1 1 −j =V − j √ = V [0.25 − j0.1443] 6 2 2 4 4 3 V √ ∠−30o = 66.39∠−30o Volts 2 3 Knowing this voltage, we can find phase currents as following. Ia = = = = √ V an − V N n V ∠0o − V /(2 3)∠−30o = Ra 10 V [1 − 0.25 + j0.1443] 10 230 × [0.075 + j0.01443] 17.56∠10.89o Amps Similarly, Ib √ V bn − V N n V ∠ − 120o − V /(2 3)∠−30o = = Rb 15 = 230 × [−0.05 − j0.04811] = 15.94∠−136.1o Amps and Ic √ V ∠120o − V /(2 3)∠−30o V cn − V N n = = Zc 30 = 230 × [−0.025 + j0.03367] = 9.64 ∠126.58o Amps 89 It can been seen that I a + I b + I c = 0. The phase powers are computed as below. S a = V a (I a )∗ = Pa + jQa = 230 × 17.56∠ − 10.81o = 3976.12 − j757.48 VA S b = V b (I b )∗ = Pb + jQb = 230 × 15.94∠(−120o + 136.1o = 3522.4 + j1016.69 VA S c = V c (I c )∗ = Pc + jQc = 230 × 9.64∠(120o − 126.58o ) = 2202.59 − j254.06 VA From the apparent power S V = S a + S b + S c = 9692.11 + j0 VA. Therefore, above the total SV = S a + S b + S c = 9692.11 VA. The total arithmetic apparent power SA = S a + S b + S c == 9922.2 VA. Therefore, the arithmetic and vector apparent power factors are given by, P 9692.11 = = 0.9768 SA 9922.2 P 9622.11 = 1.00. = = SV 9622.11 p fA = p fV It is interesting to note that although the load in each phase is resistive but each phase has some reactive power. This is due to unbalance of the load currents. This apparently increases the rating of power conductors for given amount of power transfer. It is also to be noted that the net reactive power Q = Qa + Qb + Qc = 0 leading to the unity vector apparent power factor . However the arithmetic apparent power factor is less than unity showing the effect of the unbalance loads on the power factor. 3.4.3 An Alternate Approach to Determine Phase Currents and Powers In this section, an alternate approach will be discussed to solve phase currents and powers directly without computing the neutral voltage for the system shown in Fig.3.9(a). First we express threephase voltage in the following form. V a = V ∠0o V b = V ∠ − 120o = α2 V V c = V ∠1200 = αV (3.63) Where, in above equation, α is known as complex operator and value of α and α2 are given below. √ α = ej2π/3 = 1∠120o = −1/2 + j 3/2 √ α2 = ej4π/3 = 1∠240 = 1∠ − 120 = −1/2 − j 3/2 (3.64) Also note the following property, 1 + α + α2 = 0. Using the above, the line to line voltages can be expressed as following. 90 (3.65) V ab = V a − V b = (1 − α2 )V V bc = V b − V c = (α2 − α)V V ca = V c − V a = (α − 1)V (3.66) Therefore, currents in line ab, bc and ca are given as, ab 2 I abl = Y ab l V ab = Yl (1 − α )V I bcl = Ylbc V bc = Ylbc (α2 − α)V I cal = Ylca V ca = Ylca (α − 1)V (3.67) Hence line currents are given as, I al = I abl − I cal = [Ylab (1 − α2 ) − Ylca (α − 1)]V I bl = I bcl − I abl = [Ylbc (α2 − α) − Ylab (1 − α2 )]V I cl = I cal − I bcl = [Ylca (α − 1) − Ylbc (α2 − α)]V (3.68) Example 3.4 Compute line currents by using above expressions directly for the problem in Example 3.3. Solution: To compute line currents directly from the above expressions, we need to compute Ylab . These are given below 1 Zlc = Zlab Zla Zlb + Zlb Zlc + Zlc Zla Zla 1 = = Zlbc Zla Zlb + Zlb Zlc + Zlc Zla 1 Zlb = = Zlca Zla Zlb + Zlb Zlc + Zlc Zla Ylab = Ylbc Ylca (3.69) Substituting, Zal = Ra = 10 Ω, Zbl = Rb = 15 Ω and Zcl = Rc = 30 Ω into above equation, we get the following. 1 Ω 30 1 Ylbc = Gbc = Ω 90 1 Ylca = Gca = Ω 60 Ylab = Gab = Substituting above values of the admittances in (3.68) , line currents are computed as below. 91 " Ia = 1 30 ( )# √ ) √ 1 3 1 1 3 1 − (− − j ) − (− + j )−1 V 2 2 60 2 2 ( = V (0.075 + j0.0144) = 0.07637 V ∠10.89o = 17.56∠10.89o Amps, for V=230 V Similarly for Phase-b current, " ( ( √ √ ) √ )# 1 1 3 1 3 1 1 3 Ib = (− − j ) − (− + j ) − 1 − (− − j ) V 90 2 2 2 2 30 2 2 = V (−0.05 − j0.0481) = 0.06933 V ∠ − 136.1o = 15.94∠ − 136.91o Amps, for V=230 V Similarly for Phase-c current, " Ic = 1 60 ) ( √ √ √ )# 1 3 1 1 3 1 3 (− + j ) − 1) − (− − j ) − (− + j ) V 2 2 90 2 2 2 2 ( = V (−0.025 + j0.0336) = 0.04194 V ∠126.58o = 9.64∠126.58o Amps, for V=230 V Thus it is found that the above values are similar to what have been found in previous Example 3.3. The other quantities such as powers and power factors are same. 3.4.4 An Example of Balancing an Unbalanced Delta Connected Load An unbalanced delta connected load is shown in Fig. 3.10(a). As can be seen from the figure that between phase-a and b there is admittance Ylab = Gab l and other two branches are open. This is an example of extreme unbalanced load. Obviously for this load, line currents will be extremely unbalanced. Now we aim to make these line currents to be balanced and in phase with their phase voltages. So, let us assume that we add admittances Yγab , Yγbc and Yγca between phases ab, bc and ca respectively as shown in Fig. 3.10(b) and (c). Let values of compensator susceptances are given by, Yγab = 0 √ Yγbc = jGab l / 3 √ Yγca = −jGab l / 3 92 3 / j G ab l j G ab l / 3 Y / Yl bc 0 3 Y bc ab jG l / 0 0 Yl bc 0 ab jGl ca Yl ca Yl ca Y Ic ca Ic Y Ic c c bc c 3 Ib b Ia Yl G ab ab l a Ib a b Yl ab Glab Yab 0 Ia (a) Ib b Y ab Glab Ia (b) (c) Fig. 3.10 (a) An unbalanced three-phase load (b) With compensator (c) Compensated system Thus total admittances between lines are given by, ab Y ab = Ylab + Yγab = Gab l + 0 = Gl √ √ ab Y bc = Ylbc + Yγbc = 0 + jGab l / 3 = jGl / 3 √ √ ab Y ca = Ylca + Yγca = 0 − jGab l / 3 = −jGl / 3. Therefore the impedances between load lines are given by, 1 1 = Y ab Gab l √ −j 3 1 = = Y bc Gab √l 1 j 3 = = ab ca Y Gl Z ab = Z bc Z ca √ √ ab ab ab Note that Z ab + Z bc + Z ca = 1/Gab l − j 3/Gl + j 3/Gl = 1/Gl . The impedances, Za , Zb and Zc of equivalent star connected load are given as follows. Z ab × Z ca Z ab + Z bc√+ Z ca 1 j 3 1 = ( ab × ab )/( ab ) Gl Gl Gl √ j 3 = Gab l Za = 93 a Z bc × Z ab ca Z ab + Z bc + √Z −j 3 1 1 )/( ab ) = ( ab × ab Gl Gl Gl √ −j 3 = Gab l Zb = Z ca × Z bc Z ab √ + Z bc +√Z ca 1 −j 3 j 3 = ( ab × ab )/( ab ) Gl Gl Gl 3 = Gab l Zc = The above impedances seen from the load side are shown in Fig. 3.11(a) below. Using (3.57), c Ic Ic 3 Z ab Gl Load Zlb j c 1 Glab c l 3 Glab Ib b Zla j 1 Glab Source n 3 Glab Ib a b Ia N 1 Glab a Ia Fig. 3.11 Compensated system (a) Load side (b) Source side the voltage between load and system neutral of delta equivalent star load as shown in Fig. 3.11, is computed as below. 1 V an V bn V cn VN n = 1 + + Za Zb Zc + Z1b + Z1c Za 1 V ∠0o V ∠ − 120o V ∠120o √ √ + + = 1 3 √ 1 3/Gab + (−j √3/G j 3/Gab −j 3/Gab ab ) + Gab l l l (j 3/Gab ) l l l ab ab 3V Gl G = − j √l ab 3 Gl 3 √ ! 1 3 −j = 2V 2 2 = 2 V ∠ − 60o 94 Using above value of neutral voltage the line currents are computed as following. Ia = = V an − V N n Za [V ∠0o − 2 V ∠ − 60o ] √ j Gab3 l = Ib = = Gab l Gab l V = Va V bn − V N n Zb [V ∠ − 120o − 2 V ∠ − 60o ] √ −j Gab3 l = = Ic = = Gab l Gab l o V ∠240 Vb V cn − V N n Zc [V ∠120o − 2 V ∠ − 60o ] 3 Gab l o = Gab l V ∠120 = Gab l Vc From the above example, it is seen that the currents in each phase are balanced and in phase with their respective voltages. This is equivalently shown in Fig. 3.11(b). It is to be mentioned here that the two neutrals in Fig. 3.11 are not same. In Fig. 3.11(b), the neutral N is same as the system neutral as shown in Fig. 3.8, whereas in Fig. 3.11(a), V N n = 2 V ∠−60o .√However the reader √ ca may be curious to know why Yγab = 0, Yγbc = jGab = −jGab l / 3 and γ l / 3 have been chosen as compensator admittance values. The answer of the question can be found by going following sections. 3.5 A Generalized Approach for Load Compensation using Symmetrical Components In the previous section, we have expressed line currents I a , I b and I c , in terms load admittances and the voltage V for a delta connected unbalanced load as shown in Fig 3.12(a). For the sake of completeness, theses are reproduced below. 95 I al = I abl − I cal = [Ylab (1 − α2 ) − Ylca (α − 1)]V I bl = I bcl − I abl = [Ylbc (α2 − α) − Ylab (1 − α2 )]V I cl = I cal − I bcl = [Ylca (α − 1) − Ylbc (α2 − α)]V c c Ic I cl Yl Y Yl ab b ca ca l Ybc bc Yl ca l bc I bl I al (3.70) Ib a b Ia (a) Y Y Yl ab a Yab (b) Fig. 3.12 (a) An unbalanced delta connested load (b) Compensated system Since loads currents are unbalanced, these will have positive and negative currents. The zero sequence current will be zero as it is three-phase and three-wire system. These symmetrical components of the load currents are expressed as following. I 0l I al 1 1 1 I 1l = √1 1 a a2 I bl (3.71) 2 3 1 a a I 2l I cl √ In equation (3.71), a factor of 1/ 3 is considered to have unitary symmetrical transformation. From the above equation, zero sequence current is given below. √ I 0l = I al + I al + I al / 3 The positive sequence current is as follows. 1 I 1l = √ I al + αI bl + α2 I cl 3 1 = √ [ Ylab (1 − α2 ) − Ylca (α − 1) + α Ylbc (α2 − α) − Ylab (1 − α2 ) 3 +α2 Ylca (α − 1) − Ylbc (α − α2 ) ] V 1 = √ [ Ylab − α2 Ylab + Ylca − αYlca + α3 Ylbc − α2 Ylbc − αYlab − α3 Ylab + α3 Ylca − α2 Ylca 3 −α4 Ylbc + α3 Ylbc ] V √ = Ylab + Ylbc + Ylca V 3 96 Similarly negative sequence component of the current is, 1 I 2l = √ I al + α2 I bl + αI cl 3 1 = √ [Ylab (1 − α2 ) − Ylca (α − 1) + α2 Ylbc (α2 − α) − Ylab (1 − α2 ) 3 +α Ylca (α − 1) − Ylbc (α2 − α) ]V̄ 1 = √ [ Ylab − α2 Ylab − αYlca + Ylca + α4 Ylbc − α3 Ylbc − α2 Ylab 3 +α4 Ylab + α2 Ylca − αYlca − α3 Ylbc + α2 Ylbc ] V 1 = √ [ −3α2 Ylab − 3Ylbc − 3αYlca ] V 3 √ = −[α2 Ylab + Ylbc + αYlca ] 3V From the above, it can be written that, I 0l = 0 √ I 1l = Ylab + Ylbc + Ylca 3V I 2l = − α2 Ylab + Ylbc + αYl √ ca (3.72) 3V When compensator is used, three delta branches Yγab , Yγbc and Yγca are added as shown in Fig. 3.12(b). Using above analysis, the sequence components of the compensator currents can be given as below. I 0γ = 0 √ 3V √ = − α2 Yγab + Yγbc + αYγca 3V I 1γ = I 2γ Yγab + Yγbc + Yγca (3.73) bc ca Since, compensator currents are purely reactive, i.e., Gab γ = Gγ = Gγ = 0, ab ab Yγab = Gab γ + jBγ = jBγ bc bc Yγbc = Gbc γ + jBγ = jBγ ca ca Yγca = Gca γ + jBγ = jBγ . (3.74) Using above, the compensated sequence currents can be written as, I 0γ = 0 I 1γ = j Bγab + Bγbc + Bγca I 2γ √ 3V √ = −j(α2 Bγab + Bγbc + αBγca ) 3 V (3.75) Knowing nature of compensator and load currents, we can set compensation objectives as following. 1. All negative sequence component of the load current must be supplied from the compensator negative current, i.e., I 2l = −I 2γ 97 (3.76) The above further implies that, Re I 2l + j Im I 2l = −Re I 2γ − j Im I 2γ (3.77) 2. The total positive sequence current, which is source current should have desired power factor from the source, i.e., Im (I 1l + I 1γ ) = tan φ = β Re (I 1l + I 1γ ) (3.78) Where, φ is the desired phase angle between the line currents and the supply voltages. The above equation thus implies that, Im (I 1l + I 1γ ) = β Re (I 1l + I 1γ ) (3.79) Since Re (I 1γ ) = 0, the above equation is rewritten as following. Im (I 1l ) − β Re (I 1l ) = −Im (I 1γ ) (3.80) The equation (3.77) gives two conditions and equation (3.79) gives one condition. There are three unknown variables, i.e., Bγab , Bγbc and Bγca and three conditions. Therefore the unknown variables can be solved. This is described in the following section. Using (3.75), the current I 2γ is expressed as following. √ I 2γ = −j[α2 Bγab + Bγbc + αBγca ] 3 V " # √ ! √ ! √ 1 1 3 3 = −j − −j Bγab + Bγbc + − + j Bγca 3V 2 2 2 2 " ! √ √ # √ 3 ab 3 ca 1 ab 1 = − Bγ + Bγ − j − Bγ + Bγbc − Bγca 3V 2 2 2 2 = Re I 2γ − j Im I 2γ Thus the above equation implies that ! √ √ 1 3 ab 3 ca 1 Bγ − Bγ = − √ Re I 2γ = √ Re I 2l 2 2 3V 3V (3.81) (3.82) and, 1 1 − Bγab + Bγbc − Bγca 2 2 1 1 = − √ Im I 2γ = √ Im I 2l 3V 3V (3.83) Or 1 −Bγab + 2 Bγbc − Bγca = √ 2 Im I 2l 3V 98 (3.84) From (3.75), Im (I 1γ ) can be written as, Im (I 1γ ) = Bγab + Bγbc + Bγca √ 3 V. (3.85) Substituting Im (I 1γ ) from above equation into (3.85), we get the following. 1 1 Im (I 1l ) − β Re (I 1l ) −(Bγab + Bγbc + Bγca ) = − √ Im (I 1γ ) = √ 3V 3V (3.86) Subtracting (3.86) from (??), the following is obtained, Bγbc = −1 √ [Im (I 1l ) − 2 Im (I 2l ) − β Re (I 1l )]. 3 3V̄ (3.87) Now, from (3.82) we have 1 1 1 − Bγab − Bγca = √ Im (I 2l ) − Bγbc 2 2 3V −1 1 = √ Im (I 2l ) − √ Im (I 1l ) − β Re (I 1l ) − 2 Im (I 2l ) 3V 3 3V 1 = √ (3.88) Im (I 2l ) + Im (I 1l ) − β Re (I 1l ) 3 3V Reconsidering (3.88) and (3.83), we have 1 − Bγab − 2 1 ab B − 2 γ 1 ca 1 √ Bγ = Im (I 1l ) + Im (I 2l ) − β Re (I 1l ) 2 3 3V √ 1 ca 1 √ [ 3Re (I 2l )] Bγ = 2 3 3V Adding above equations, we get Bγca = √ −1 √ [Im (I 1l ) + Im (I 2l ) + 3 Re (I 2l ) − β Re (I 1l )]. 3 3V (3.89) Therefore, 2 √ Bγab = Bγca + √ [ 3 Re (I 2l )] 3 3V √ √ −1 √ [Im (I 1l ) + Im (I 2l ) + 3 Re (I 2l ) − β Re (I 1l ) − 2 3 Re (I 2l )] = 3 3V √ −1 = √ [Im (I 1l ) + Im (I 2l ) − 3 Re (I 2l ) − β Re (I 1l )] (3.90) 3 3V Similarly, Bγbc can be written as in the following. 1 Bγbc = − √ Im(I 1l ) − 2Im(I 2l ) − β Re(I 1l ) 3 3V (3.91) (3.92) 99 From the above, the compensator susceptances in terms of real and imaginary parts of the load current can be written as following. √ −1 √ [Im (I 1l ) + Im (I 2l ) − 3 Re (I 2l ) − β Re (I 1l )] 3 3V 1 = − √ [Im(I 1l ) − 2Im(I 2l ) − β Re(I 1l )] 3 3V √ −1 = √ [Im (I 1l ) + Im (I 2l ) + 3 Re (I 2l ) − β Re (I 1l )] 3 3V Bγab = Bγbc Bγca (3.93) In the above equation, the susceptances of the compensator are expressed in terms of real and imaginary parts of symmetrical components of load currents. It is however advantageous to express these susceptances in terms of instantaneous values of voltages and currents from implementation point of view. The first step to achieve this is to express these susceptances in terms of load currents, i.e., I al , I bl and I cl , which is described below. Using equation (3.71), the sequence components of the load currents are expressed as, 1 I¯0l = √ I¯al + I¯bl + I¯cl 3 1 I¯1l = √ I¯al + αI¯bl + α2 I¯cl 3 1 I¯2l = √ I¯al + α2 I¯1l + αI¯cl . 3 (3.94) Substituting these values of sequence components of load currents, in (3.93), we can obtain compensator susceptances in terms of real and inaginary components of the load currents. Let us start from the Bγbc , as obtained following. 1 Bγbc = − √ Im(I 1l ) − 2Im(I 2l ) − β Re(I 1l ) 3 3V 1 I al + αI bl + α2 I cl I al + α2 I bl + αI cl I al + αI bl + α2 I cl √ √ √ =− √ Im − 2 Im − β Re 3 3V 3 3 3 1 =− Im (−I al + (2 + 3α)I bl + (2 + 3α2 )I cl − β Re (I al + αI bl + α2 I cl ) 9V 1 Im −I al + 2I bl + 2I cl + 3αI bl + 3α2 I cl − β Re (I al + αI bl + α2 I cl ) =− 9V By adding and subracting I bl and I cl in the above equation we get, Bγbc = − 1 Im (−I al − I bl − I cl ) + 3I bl + 3I cl + 3α I bl + α2 I cl − β Re(I al + αI bl + α2 I cl ) 9V We know that I al +I bl +I cl =0, therefore I al + I bl = −I cl . Bγbc 1 =− 3V 2 −Im I al + Im αI bl + Im α I cl 100 β 2 − Re I al + αI bl + α I cl (3.95) 3 Similarly, it can be proved that, Bγca 1 =− 3V β 2 2 Im I al − Im αI bl + Im α I cl − Re I al + αI bl + α I cl 3 Bγab 1 =− 3V 2 Im I al + Im αI bl − Im α I cl β − Re I al + αI bl + α2 I cl 3 (3.96) (3.97) The above expressions for Bγca and Bγab are proved below. For convenience, the last term associated with β is not considered. For the sake simplicity in equations (3.96) and (3.97) are proved to those given in equations (3.93). −1 Im I al − Im αI bl + Im α2 I cl 3V " ( )# 2 I 0l + I 1l + I 2l I 0l + α2 I 1l + αI 2l I + αI + α I 1 0l 1l 2l √ √ √ =− Im −α + α2 3V 3 3 3 Bγca = Since I 0l =0 1 Bγca = − √ 3 3V 1 =− √ 3 3V 1 =− √ 3 3V 1 =− √ 3 3V Im I 1l − 2α2 I 2l " √ ! # 3 1 Im I 1l − 2 − − j I 2l 2 2 i h √ Im I 1l + I 2l + j 3I 2l h √ i Im I 1l + Im I 2l + 3Re I 2l Note that Im(jI 2l ) = Re(I 2l ). Adding β term, we get the following. i √ 1 h Bγca = − √ Im(I 1l ) + Im(I 2l ) + 3Re I 2l − βRe(I 1l ) 3 3V Similarly, 1 Im I al + Im αI bl − Im α2 I cl 3V " ( )# 2 I 0l + I 1l + I 2l I 0l + α2 I 1l + αI 2l 1 2 I 0l + αI 1l + α I 2l √ √ √ =− Im +α −α 3V 3 3 3 Bγab = − 101 1 Bγab = − √ Im I 1l − 2αI 2l 3 3V " √ ! # 3 1 1 = − √ Im I 1l − 2 − + j I 2l 2 2 3 3V i h √ 1 √ =− Im I 1l + I 2l − j 3I 2l 3 3V √ i 1 h =− √ Im I 1l + Im I 2l − 3Re I 2l 3 3V Thus, Compensator susceptances are expressed as following. 1 β 2 2 Im(I al ) + Im(αI bl ) − Im(α I cl ) − Re(I al + αI bl + α I cl ) =− 3V 3 1 β bc 2 2 Bγ = − −Im(I al ) + Im(αI bl ) + Im(α I cl ) − Re(I al + αI bl + α I cl ) (3.98) 3V 3 1 β Bγca = − Im(I al ) − Im(αI bl ) + Im(α2 I cl ) − Re(I al + αI bl + α2 I cl ) 3V 3 An unity power factor is desired from the source. For this cos φl = 1, implying tan φl = 0 hence β = 0. Thus we have, 1 Bγab = − Im I al + Im αI bl − Im α2 I cl 3V 1 −Im I al + Im αI bl + Im α2 I cl (3.99) Bγbc = − 3V 1 Bγca = − Im I al − Im αI bl + Im α2 I cl 3V The above equations are easy to realize in order to find compensator susceptances. As mentioned above, sampling and averaging techniques will be used to convert above equation into their time equivalents. These are described below. Bγab 3.5.1 Sampling Method Each current phasor in above equation can be expressed as, I al = Re(I al ) + jIm(I al ) = Ial,R + jIal,X An instantaneous phase current is written as follows. √ ial (t) = 2 Im (I al ejωt ) √ = 2 Im (Ial,R + jIal,X ) ejωt √ = 2 Im [(Ial,R + jIal,X )(cos ωt + j sin ωt)] √ = 2 Im [(Ial,R cos ωt − Ial,X sin ωt) + j(Ial,R sin ωt + Ial,X cos ωt)] √ = 2 [(Ial,R sin ωt + Ial,X cos ωt)] 102 (3.100) (3.101) ial (t) Im (I al ) = I al,X = √ 2 at sin ωt = 0, cos ωt = 1 (3.102) From equation (3.63), the phase voltages can be expressed as below. √ va (t) = 2 V sin ωt √ vb (t) = 2 V sin(ωt − 120o ) √ vc (t) = 2 V sin(ωt + 120o ) (3.103) From above voltage expressions, it is to be noted that, sin ωt = 0, cos ωt = 1 implies that the phase-a voltage, va (t) is going through a positive zero crossing, hence, va (t) = 0 and dtd va (t) = 0. Therefore, equation (3.102), can be expressed as following. ial (t) I a,l = √ when, va (t) = 0, dva /dt > 0 2 (3.104) I b,l = Ibl,R + jIbl,X (3.105) Similarly, Therefore, α (I b,l ) = α(Ibl,R + jIbl,X ) √ ! 1 3 = − +j (Ibl,R + jIbl,X ) 2 2 ! ! √ √ 1 3 3 1 = − Ibl,R − Ibl,X + j Ibl,R − Ibl,X 2 2 2 2 (3.106) From the above, √ Im {α (Ibl )} = 3 1 Ibl,R − Ibl,X 2 2 103 (3.107) Similar to equation, (3.101), we can express phase-b current in terms Im (α I bl ), as given below. √ ibl (t) = 2 Im (I bl ejωt ) √ = 2 Im (α I bl ejwt α−1 ) √ 0 = 2 Im (αI bl ej(wt−120 ) ) " # √ ! √ 1 3 0 (I bl,R + jI bl,X ) ej(wt−120 ) = 2 Im − +j 2 2 ! ! √ √ √ 1 3 3 1 = 2 Im [ − Ibl,R − Ibl,X + j Ibl,R − Ibl,X 2 2 2 2 (cos(wt − 1200 ) + j sin(wt − 1200 )) ] (3.108) " # √ √ √ 1 3 3 1 = 2 (− I bl,R − I bl,X ) sin(wt − 1200 ) + ( I bl,R − I bl,X ) cos(wt − 1200 ) 2 2 2 2 From the above equation, we get the following. ibl (t) Im (αI bl ) = √ 2 when, vb (t) = 0, dvb /dt > 0 (3.109) when, vc (t) = 0, dvc /dt > 0 (3.110) Similarly for phase-c, it can proved that, icl (t) Im (α2 I cl ) = √ 2 Substituting Im (I al ) , Im (αI bl ) and Im (α2 I cl ) from (3.104), (3.109) and (3.110) respectively, in (3.99), we get the following. 1 Brab = − √ 3 2V 1 Brbc = − √ 3 2V 1 Brca = − √ 3 2V h ia |(va =0, dva >0) + ib |(v dt h dvb b =0, dt >0) − ic |(vc =0, dvc >0) i dt −ia |(va =0, dva >0) + ib |(v + ic |(vc =0, dvc >0) dt dt h i ia |(va =0, dva >0) − ib |(v =0, dvb >0) + ic |(vc =0, dvc >0) dvb b =0, dt >0) b dt dt i (3.111) dt Thus the desired compensating susceptances are expressed in terms of the three line currents sampled at instants defined by positive-going zero crossings of the line-neutral voltages va , vb , vc . An artificial neutral at ground potential may be created measuring voltages va , vb and vc to implement above algorithm. 3.5.2 Averaging Method In this method, we express the compensator susceptances in terms of real and reactive power terms and finally expressed them in time domain through averaging process. The method is described 104 below. From equation (3.99), susceptance, Bγab , can be re-written as following. 1 Im I al + Im αI bl − Im α2 I cl 3V 1 = − 2 V Im I al + V Im αI bl − V Im α2 I cl 3V 1 = − 2 Im V I al + Im V αI bl − Im V α2 I cl 3V Bγab = − (3.112) Note the following property of phasors and applying it for the simplification of the above expression. ∗ Im V I = −Im V I ∗ (3.113) Using above equation (3.112) can be written as, 1 3V 2 1 = 3V 2 1 = 3V 2 Bγab = Im (V I al )∗ + Im (αV a I bl )∗ − Im (α2 V I cl )∗ i h ∗ ∗ ∗ ∗ ∗ 2 ∗ ∗ ∗ Im (V a I al ) + Im (α V a I bl ) − Im ((α ) V a I cl ) h i ∗ ∗ ∗ ∗ ∗ ∗ Im (V a I al ) + Im (α2 V a I bl ) − Im (αV a I cl ) ∗ ∗ ∗ Since V a = V ∠0o is a reference phasor, therefore V a = V a = V , α2 V a = V b and α V a = V c . Using this, the above equation can be written as following. 1 = 3V 2 1 Similarly, Bγbc = 3V 2 1 Bγca = 3V 2 Bγab h i ∗ ∗ ∗ Im (V a I al ) + Im (V b I bl ) − Im (V c I cl ) h i ∗ ∗ ∗ −Im (V a I al ) + Im (V b I bl ) + Im (V c I cl ) h i ∗ ∗ ∗ Im (V a I al ) − Im (V b I bl ) + Im (V c I cl ) (3.114) It can be further proved that, Z 1 T Im (V = va (t)∠(−π/2) ial (t) dt T 0 Z 1 T ∗ Im (V b I b ) = vb (t)∠(−π/2) ibl (t) dt T 0 Z 1 T ∗ Im (V c I c ) = vc (t)∠(−π/2) icl (t) dt T 0 ∗ a I a) 105 (3.115) In (3.115), the term va (t)∠(−π/2) denotes the voltage va (t) shifted by −π/2 radian in time domain. For balanced voltages, the following relationship between phase and line voltages are true. √ va (t)∠(−π/2) = vbc (t)/ 3 √ (3.116) vb (t)∠(−π/2) = vca (t)/ 3 √ vc (t)∠(−π/2) = vca (t)/ 3 From (3.115) and (3.116), the following can be written. Z T 1 ∗ Im (V a I a ) = √ vbc (t) ial (t) dt 3T 0 Z T 1 ∗ Im (V b I b ) = √ vca (t) ibl (t) dt 3T 0 Z T 1 ∗ Im (V c I c ) = √ vab (t) icl (t) dt 3T 0 ∗ ∗ (3.117) ∗ Substituting above values of Im (V a I a ), Im (V b I b ) and Im (V c I c ) into (3.114), we get the following. Bγab Bγbc Bγca Z 1 T 1 √ (vbc ial + vca ibl − vab icl ) dt = (3 3V 2 ) T 0 Z 1 1 T √ = (−vbc ial + vca ibl + vab icl ) dt (3 3V 2 ) T 0 Z 1 T 1 √ (vbc ial − vca ibl + vab icl ) dt = (3 3V 2 ) T 0 (3.118) The above equations can directly be used to know the the compensator susceptances by performing the R T averaging R t1 +T on line the product of the line to line voltages and phase load currents. The term = t1 can be implemented using moving average of one cycle. This improves transient 0 response by computing average value at each instant. But in this case the controller response which changes the susceptance value, should match to that of the above computing algorithm. 3.6 Compensator Admittance Represented as Positive and Negative Sequence Admittance Network Recalling the following relations from equation (3.93) for unity power factor operation i.e. β = 0, we get the following. √ −1 Bγab = √ [Im (I 1l ) + Im (I 2l ) − 3 Re (I 2l )] 3 3V −1 Bγbc = √ [Im (I 1l ) − β Re (I 1l ) − 2Im (I 2l )] (3.119) 3 3V √ −1 Bγca = √ [Im (I 1l ) + Im (I 2l ) + 3 Re (I 2l )] 3 3V 106 From these equations, it is evident the the first terms form the positive sequence suceptance as they involve I 1l terms. Similarly, the second and third terms in above equation form negative sequence susceptance of the compensator, as these involve I 2l terms. Thus, we can write, ab ab Bγab = Bγ1 + Bγ2 ab ab + Bγ2 Bγab = Bγ1 Bγab ab Bγ1 = + (3.120) ab Bγ2 Therefore, 1 ab bc ca Bγ1 = Bγ1 = Bγ1 =− √ Im(I¯1l ) 3 3V (3.121) And, ab Bγ2 bc Bγ2 ca Bγ2 √ 1 = − √ Im(I 2l ) − 3Re(I 2l ) 3 3V 1 = − √ −2 Im(I 2l ) 3 3V √ 1 = − √ Im(I 2l ) + 3Re(I 2l ) 3 3V (3.122) Earlier in equation, (3.123), it was established that, I 0l = 0 √ I 1l = Ylab + Ylbc + Ylca 3V I 2l = − α2 Ylab + Ylbc + αYlca √ 3V Noting that, ab Ylab = Gab l + jBl bc Ylbc = Gbc l + jBl ca Ylca = Gca l + jBl Therefore, √ Im (I 1l ) = Im ((Ylab + Ylbc + Ylca ) 3V ) √ = (Blab + Blbc + Blca ) 3V (3.123) Thus equation (3.121) is re-written as following. ab bc ca Bγ1 = Bγ1 = Bγ1 =− 1 Blab + Blab + Blca 3 107 (3.124) ca bc ab using equations (3.122) as following. Knowing that, and Bγ2 , Bγ2 Now we shall compute Bγ2 √ I¯2l = − α2 Ylab + Ylbc + αYlca 3V # " √ ! √ ! √ 3 −1 j −1 j 3 ab bc bc ca ca − Gab + jB + G + jB + + (G + jB ) 3V =− l l l l l l 2 2 2 2 " !# √ √ √ √ √ Gab 3 ab Gca 3 ca 3 ab Blab 3 ca Blca l l bc bc =− − + Bl + Gl − − Bl − j Gl + − Bl − Gl + 3V 2 2 2 2 2 2 2 2 !# " √ √ √ √ ca ab ca √ 3 G 3 3 B 3 B Gab l l l l − Blab − Gbc + Blca + j Gab − Blbc − Gca 3V = l + l + l + 2 2 2 2 2 2 2 2 (3.125) The above implies that, Im (I 2l ) = √ − 3 Re(I 2l ) = ! √ √ ca √ 3 ab Blab 3 B l Gl + − Blbc − Gca 3V l + 2 2 2 2 ! √ √ 3 ab 3 ab √ bc 3 ca 3 ca √ G + Bl + 3Gl − G − Bl − 3V 2 l 2 2 l 2 ab Thus, Bγ2 can be given as, √ √ ca i √ 1 h ab ab 2Bl − Blbc − Blca + 3 Gbc Bγ2 =− √ − 3 Gl 3V l 3 3V √ i 1h ca = − 2Blab − Blbc − Blca + 3 Gbc − G l l 3 1 1 bc = √ Gca Blbc + Blca − 2Blab + l − Gl 3 3 (3.126) Similarly, i √ 1 h ca Im(I¯2l ) + 3 Re(I¯2l ) Bγ2 =− √ 3 3V " # √ √ √ √ ab ca √ 1 3 ab Bl 3 ca Bl 3 ab 3 ab 3 ca 3 ca √ =− √ Gl + − Blbc − Gl + + Gl − Bl − 3Gbc G + Bl 3V l + 2 2 2 2 2 2 2 l 2 3 3V i 1 h√ ab √ bc =− 3Gl − 3Gl − Blab − Blbc + 2Blca 3 1 1 ab (3.127) = √ Gbc + Blab + Blbc − 2Blca l − Gl 3 3 bc And, Bγ2 is computed as below. 108 1 bc =− √ −2Im(I¯2l ) Bγ2 3 3V ! √ √ ca √ 2 3 ab Blab 3 B l = √ Gl + − Blbc − Gca V 3 l + 2 2 2 2 3 3V 1 1 ca + Blab + Blca − 2Blbc = √ Gab l − Gl 3 3 (3.128) Using (3.121), (3.126)-(3.128), We therefore can find the overall compensator susceptances as following. ab ab Bγab = Bγ1 + Bγ2 1 1 1 bc = − Bγab + Bγbc + Bγca + √ Gca + Blca + Blbc − 2Blab l − Gl 3 3 3 1 bc = −Blab + √ Gca l − Gl 3 Similarly, bc bc Bγbc = Bγ1 + Bγ2 1 1 1 ca ab ca bc − G B + B − 2B + = − Bγab + Bγbc + Bγca + √ Gab l l l l 3 3 l 3 1 ca = −Blbc + √ Gab l − Gl 3 And, ca ca Bγca = Bγ1 + Bγ2 1 1 1 ab Blbc + Blab − 2Blca = − Bγab + Bγbc + Bγca + √ Gbc + l − Gl 3 3 3 1 ab = −Blca + √ Gbc l − Gl 3 Thus, the compensator susceptances in terms of load parameters are given as in the following. 1 bc Bγab = −Blab + √ Gca l − Gl 3 1 ca Bγbc = −Blbc + √ Gab l − Gl 3 1 ca ca ab Bγ = −Bl + √ Gbc l − Gl 3 109 (3.129) It is interesting to observe above equations. The first parts of the equation nullifies the effect of the load susceptances and the second parts of the equations correspond to the unbalance in resistive load. The two terms together make source current balanced and in phase with the supply voltages. The compensator’s positive and negative sequence networks are shown in Fig. 3.13 . What happens if we just use the following values of the compensator susceptances as given below? Bγab = −Blab Bγbc = −Blbc Bγca = −Blca (3.130) In above case, load suceptance parts of the admittance are fully compensated. However the source currents after compensation remain unbalanced due to unbalance conductance parts of the load. isa ila ilb Source isb ilc isc I 1,abc Load I 2,abc Bab2 Bab1 Bbc1 Bca1 Bbc2 Bca2 Bab , Bbc , Bca Fig. 3.13 Sequence networks of the compensator Example 3.5 For a delta connected load shown in 3.14 , the load admittances are given as following, ab Ylab = Gab l + jBl bc Ylbc = Gbc l + jBl ca Ylca = Gca l + jBl Given the load parameters: Zlab = 1/Ylab = 5 + j12 Ω Zlbc = 1/Ylbc = 3 + j4 Ω Zlca = 1/Ylca = 9 − j12 Ω Determine compensator susceptances (Bγab , Bγbc , Bγca ) so that the supply sees the load as balanced and unity power factor. Also find the line currents and source active and reactive powers before and after compensation. 110 va a ia ab ca N B B vc ca ic Y Y ab vb ib c Y bc b bc B Fig. 3.14 A delta connected load Solution: Zlab = 5 + j12 Ω ⇒ Ylab = 0.03 − j0.0710 f Zlbc = 3 + j4 Ω ⇒ Ylbc = 0.12 − j0.16 f Zlca = 9 − j13 Ω ⇒ Ylca = 0.04 + j0.0533 f Once we know the admittances we know, ab Gab l = 0.03, Bl = −0.0710 bc Gbc l = 0.12, Bl = −0.16 ca Gca l = 0.04, Bl = 0.0533 1 bc Bγab = −Blab + √ (Gca l − Gl ) = 0.0248 f 3 1 ca Bγbc = −Blbc + √ (Gab l − Gl ) = 0.1540 f 3 1 ab Bγca = −Blca + √ (Gbc l − Gl ) = −0.0011 f 3 Total admittances are: Y ab = Ylab + Yγab = 0.03 − j0.0462 f Y bc = Ylbc + Yγbc = 0.12 − j0.006 f Y ca = Ylca + Yγca = 0.04 + j0.0522 f Knowing these total admittances, we can find line currents using following expressions. Current Before Compensation 111 I a = I abl − I cal = (1 − α2 )Ylab − (α − 1)Ylca V = 0.2150 V ∠−9.51o A I b = I bcl − I abl = (α2 − α)Ylbc − (1 − α2 )Ylab V = 0.4035 V ∠−161.66o A I c = I cal − I bcl = (α − 1)Ylca − (α2 − α)Ylbc V = 0.2358 V ∠43.54o A Powers Before Compensation Sa Sb Sc Total real power, P Total reactive power, Q Power factor in phase-a, pfa Power factor in phase-b, pfb Power factor in phase-c, pfc V a (I al )∗ = Pa + jQa = V (0.2121 + j0.0355) V b (I bl )∗ = Pb + jQb = V (0.3014 + j0.2682) V c (I cl )∗ = Pc + jQc = V (0.0552 + j0.2293) Pa + Pb + Pc = V 0.5688 W Qa + Qb + Qc = V 0.5330 VAr cos φa = cos(9.51o ) = 0.9863 lag cos φb = cos(41.63o ) = 0.7471 lag cos φc = cos(76.45o ) = 0.2334 lag = = = = = = = = Thus we observe that the phases draw reactive power from the lines and currents are unbalanced in magnitude and phase angles. After Compensation I a = I ab − I ca = (1 − α2 )Y ab − (α − 1)Y ca V = 0.1896 V ∠0o A I b = I bc − I ab = (α2 − α)Y bc − (1 − α2 )Y ab V = 0.1896 V ∠−120o A I a = I ca − I bc = (α − 1)Ylca − (α2 − α)Y bc V = 0.1896 V ∠120o A Powers After Compensation Sa Sb Sc Total real power, P Total reactive power, Q Power factor in phase-a, pfa Power factor in phase-b, pfb Power factor in phase-c, pfc = = = = = = = = V a (I al )∗ = Pa + jQa = V (0.1986 + j0.0) V b (I bl )∗ = Pb + jQb = V (0.1986 + j0.0) V c (I cl )∗ = Pc + jQc = V (0.1986 + j0.0) Pa + Pb + Pc = (V × 0.5688 )W Qa + Qb + Qc = 0 VAr cos φa = cos(0o ) = 1.0 cos φb = cos(0o ) = 1.0 cos φc = cos(0o ) = 1.0 From above results we observe that after placing compensator of suitable values as calculated above, the line currents become balanced and have unity power factor relationship with their voltages. 112 Example 3.6 Consider the following 3-phase, 3-wire system. The 3-phase voltages are balanced sinusoids with RMS value of 230 V at 50 Hz. The load impedances are Za = 3 + j 4 Ω, Zb = 5 + j 12 Ω, Zc = 12 − j 5 Ω. Compute the following. 1. The line currents I la , I lb , I lc . 2. The active (P ) and reactive (Q) powers of each phase. 3. The compensator susceptance ( Bγab , Bγbc , Bγca ), so that the supply sees the load balanced and unity power factor. 4. For case (3), compute the source, load, compensator active and reactive powers (after compensation). N Vsa I la Vsc I lc Vsb I lb a c Zb Fig. 3.15 An unbalanced three-phase three-wire star connected load Solution: Given that Za = 3 + j 4 Ω, Zb = 5 + j 12 Ω, Zc = 12 − j 5 Ω. 1. Line currents I la , I lb , andI lc are found by first computing neutral voltage as given below. V nN = 1 ( Z1a + 1 Zb + Va 1 ( ) Za Zc = = = Vb Vc + ) Zb Zc Va Vb Vc Za Zb Zc )( + + ) Za Zb + Zb Zc + Zc Za Za Zb Zc Zabc V a V b V c ( + + ) ∆Z Za Zb Zc 50∠97.82o (24.12∠−99.55o ) o 252.41∠55.5 43.79 − j 67.04 V 80.75∠−57.15o V = ( = + Now the line currents are computed as below. 113 V a − V nN Za 230∠0o − 80.75∠−57.15o = 3+j4 = 33.2 − j 21.65 = 39.63∠−33.11o A I la = V b − V nN Zb 230∠−120o − 80.75∠−57.15o = 5 + j 12 = 15.85∠152.21o A I lb = V c − V nN Zc 230∠120o − 80.75∠−57.15o = 12 − j 5 = 23.89∠143.35o A I lc = 2. Active and Reactive Powers For phase a Pa = Va Ia cos φa = 230 × 39.63 × cos(33.11o ) = 7635.9 W Qa = Va Ia sin φa = 230 × 39.63 × sin(33.11o ) = 4980 VAr For phase b Pb = Vb Ib cos φb = 230 × 15.85 × cos(−152.21o − 120o ) = 140.92 W Qb = Vb Ib sin φb = 230 × 15.85 × sin(−152.21o − 120o ) = 3643.2 VAr For phase c Pc = Vc Ic cos φc = 230 × 23.89 × cos(−143.35o + 120o ) = 5046.7 W 114 Qc = Vc Ic sin φc = 230 × 23.89 × sin(−143.35o + 120o ) = −2179.3 VAr Total three phase powers P = Pa + Pb + Pc = 12823 W Q = Qa + Qb + Qc = 6443.8 VAr 3. Compensator Susceptance First we convert star connected load to a delta load as given below. Zlab = Za Zb +Zb Zc +Zc Za Zc Zlbc = ∆Z Za = 50.44 + j 2.08 = 50.42∠2.36o Ω Zlca = ∆Z Zb = 19.0 − j 4.0 = 19.42∠ − 11.89o Ω = 4 + j 19 = 19.42∠77.11o Ω The above implies that, ab Ylab = 1/Zlab = Gab l + j Bl = 0.0106 − j0.050 f bc Ylbc = 1/Zlbc = Gbc l + j Bl = 0.0198 − j0.0008 f ca Ylca = 1/Zlca = Gca l + j Bl = 0.0504 + j0.0106 f From the above, the compensator susceptances are computed as following. Bγab = −Blab + −Gbc (Gca l ) l √ 3 = 0.0681 f Bγbc = −Blbc + (Gab −Gca l √ l ) 3 = −0.0222 f Bγca = −Blca + (Gbc −Gab l √ l ) 3 = −0.0053 f Zγab = −j 14.69 Ω (capacitance) Zγbc = j 45.13 Ω (inductance) Zγca = j 188.36 Ω (inductance) 115 4. After Compensation 0 Zlab = Zlab || Zγab = 24.97 − j 41.59 = 48.52∠ − 59.01o Ω 0 Zlbc = Zlbc || Zγbc = 21.52 − j 24.98 = 32.97∠49.25o Ω 0 Zlca = Zlca || Zγca = 24.97 − j 41.59 = 19.7332∠ − 6.0o Ω Let us convert delta connected impedances to star connected. Za = = = Zb = = = Zc = = = Zab0 × Zca0 Zab0 + Zbc0 + Zca0 9.0947 − j 10.55 13.93∠ − 49.25o Ω Zbc0 × Zab0 Zab0 + Zbc0 + Zca0 23.15 + j 2.43 23.28∠6.06o Ω Zca0 × Zbc0 Zab0 + Zbc0 + Zca0 4.8755 + j 8.12 9.47∠59.01o Ω The new voltage between the load and system neutral after compensation is given by, 1 0 V nN = ( Z1a 1 Zb Va 1 ( ) Za Zc o + + = 205.42∠−57.15 V + Vb Vc + ) Zb Zc Based on the above, the line currents are computed as following. 0 Ia = = Ib = = V a − V nN Za 18.58∠0o A 0 V b − V nN Zb 18.58∠ − 120o A 0 Ic V c − V nN = Zc = 18.58∠120o A 116 Thus, it is seen that after compensation, the source currents are balanced and have unity power factor with respective supply voltages. Source powers after compensation Pa = Pb = Pc = 230 × 18.58 = 4272.14 W P = 3Pa = 12820.2 W Qa = Qb = Qc = 0 Q = 0 VAr Compensator powers ab Sγ ab ∗ = V ab (I γ ) ∗ ∗ = V ab (V ab .Yγab ) 2 = V ab Yγab ∗ √ = (230 × 3)2 × (−j 0.0068) = −j 10802 VA bc Sγ ca Sγ = Vbc2 Yγbc ∗ √ = (230 × 3)2 × (j 0.0222) = j 3516 VA = Vca2 Yγca ∗ √ = (230 × 3)2 × (j 0.0053) = j 842 VA References [1] A. Ghosh and G. Ledwich, Power quality enhancement using custom power devices. Kluwer Academic Pub, 2002. [2] T. J. E. Miller, Reactive power control in electric systems. Wiley, 1982. [3] L. Gyugyi, “Reactive power generation and control by thyristor circuits,” IEEE Transactions on Industry Applications, no. 5, pp. 521–532, 1979. 117 [4] R. Otto, T. Putman, and L. Gyugyi, “Principles and applications of static, thyristor-controlled shunt compensators,” IEEE Transactions on Power Apparatus and Systems, no. 5, pp. 1935– 1945, 1978. [5] N. Hingorani and L. Gyugyi, Understanding FACTS: Concepts and Technology of Flexible AC Transmission Systems, 2000. Wiley-IEEE Press, 1999. 118