Download Model 480 Universal Voltage Regulator

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Brushed DC electric motor wikipedia , lookup

Transistor wikipedia , lookup

Ground loop (electricity) wikipedia , lookup

Ground (electricity) wikipedia , lookup

Spark-gap transmitter wikipedia , lookup

Stepper motor wikipedia , lookup

Power engineering wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Decibel wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Power inverter wikipedia , lookup

Electrical ballast wikipedia , lookup

Integrating ADC wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Electrical substation wikipedia , lookup

Three-phase electric power wikipedia , lookup

History of electric power transmission wikipedia , lookup

Current source wikipedia , lookup

Islanding wikipedia , lookup

Ohm's law wikipedia , lookup

Potentiometer wikipedia , lookup

Rectifier wikipedia , lookup

Power MOSFET wikipedia , lookup

Triode wikipedia , lookup

Power electronics wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Schmitt trigger wikipedia , lookup

Distribution management system wikipedia , lookup

Opto-isolator wikipedia , lookup

Buck converter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Surge protector wikipedia , lookup

Alternating current wikipedia , lookup

Stray voltage wikipedia , lookup

Voltage regulator wikipedia , lookup

Voltage optimisation wikipedia , lookup

Mains electricity wikipedia , lookup

Transcript
Model 480
UNIVERSAL
VOLTAGE REGULATOR
Manufactured by
FLIGHT SYSTEMS
www.flightsystems.com
INSTALLATION and ADJUSTMENT INSTRUCTIONS
Description and Specifications
The Model 480 Universal Regulator is designed for OEM applications as well as an economical replacement for many hard to get or obsolete regulators found on older generator sets. It is easy to install and works
with all single and three phase systems from 100V to 480V, 50 or 60 Hz by connecting four or five wires. It
works with brushless exciters or conventional fields. Field excitation of up to 5 A is provided by means of a
phase-controlled SCR. The unit is internally fused and includes a heavy-duty EMI filter with voltage spike
suppression. Adjustments are provided for Voltage, Stability and Voltage/Frequency Ramp. Separate voltage
sensing and remote voltage adjustment are supported. Voltage regulation is typically +/- 1%. The output
voltage is automatically reduced during under-speed operation. An under-frequency LED indicator shows
when the engine speed is low. A soft start feature helps prevent a sudden load on the engine at startup. The
Model 480 is self-starting on a residual voltage of 5 volts or less and does not require field flash. Connection
is by means of a screw-terminal barrier strip for safety and reliability. The unit is encapsulated in a clear
urethane compound for protection and is fully repairable. Overall size is 3.5” [89] W x 5.75” [146] L x 2.30”
[58] H. (See Unit Dimensions Diagram, Pg. 6)
Application
The Model 480 may be used with almost any generator with a system voltage of 100 to 480 volts, 50 or 60
Hz, and a field current requirement of up to 5 Amps. The field or exciter field resistance must be between 15
and 500 ohms and be isolated from all other circuits. The maximum available field voltage (up to 90 VDC)
will depend on the voltage powering the regulator. The regulator powering voltage at terminals B-C must
be between 100V and 300V. The sensed voltage at terminals A-C must be between 100 and 480VAC. Sensing voltage range is selected by connecting a jumper (supplied) between the appropriate terminals of TB3
(see illustrations). After the voltage range is selected, the VOLTS adjustment pot is used to precisely set the
desired output voltage.
Installation
1.
If applicable, remove the old regulator and carefully mark the wires. Verify that the field circuit is isolated from all other circuits and that the field resistance is between 15 and 500 ohms.
2.
Mount (fix) the unit to a flat surface in a suitable location using the four #8 (0.177 [4.5mm]) clear holes provided. These holes may be enlarged to #10 (0.205 [5.2mm]) if necessary. Make sure that the location chosen provides adequate ventilation for cooling and access to the adjustments.
3.
Please refer to the wiring diagrams below and determine which one is appropriate for your generator. Ring or spade type terminals on wires are preferred as they make the most secure connection. The barrier strip can clamp wires without using terminals, however this method is not as secure.
4.
Observing polarity, connect the positive field terminal of the generator to F+ and the negative field terminal to F-. NOTE: Connecting the field backwards may require re-flashing of the field due to reversal/loss of residual magnetism.
1
5.
Place the voltage programming jumper in the proper position on TB3 for your system voltage. The voltage programming jumper is not used on 415/240V and 480/277V systems. See illustrations that follow.
6.
Connect terminals A, B, and C on TB1 to the proper points as shown in the wiring diagrams below. On 120V single phase systems, connect sensing terminal A to power terminal B using the link sup-
plied. In this configuration, only four wires are needed. All other configurations use five wires without the link.
7.
Refer to the illustration for TB2 connections and install the jumper (supplied) in the position that is appropriate for your generator. Note: The jumper must be installed for 50 Hz systems but is not needed at all for 60 Hz operation. The jumper position shown for 60Hz operation is merely for stor-
age of the jumper.
8.
If desired, an external remote voltage adjustment potentiometer may be added by connecting it in place of the jumper that is now connected on TB2 between the EXT VOLT terminals. See illustra-
tions and adjustment instructions on following pages.
CAUTION: Do not come in contact with any metal parts of the regulator, including the heat sink,
as dangerous voltages are present when the generator is running.
Adjustment
Verify the wiring before proceeding with adjustment. Make sure that the voltage programming jumper on
TB3 and the frequency jumper on TB2 are in the correct position for your system voltage and frequency.
Turn the STAB pot full CCW. Start the generator and bring it up to rated operating speed (use the Hz function on your DVM). Make sure that the V/F LED indicator is not on. If it is, turn the V/F pot CCW until
the LED just goes off. Adjust the VOLTS pot until the desired output voltage is obtained. The object of the
STABILITY adjustment is to obtain the best dynamic response to changes in load without instability. Under
no-load conditions, turn the STAB pot slowly CW until the output voltage starts to fluctuate, then CCW until
it becomes stable. Repeat if necessary. To adjust the V/F RAMP, reduce the speed of the generator to 58 Hz
(48 Hz for 50Hz systems). Turn the V/F pot CW until the V/F LED indicator just comes on. At rated speed,
this LED should not be on.
Optional Remote Voltage Adjustment
The output voltage of the generator can be remotely adjusted by adding a 1K potentiometer in place of the
jumper connected between the EXT VOLT terminals on TB2. Before connecting the remote potentiometer,
follow all of the steps above for installation and adjustment. The potentiometer should be wired so that its
resistance decreases with clockwise rotation. See illustration for TB2. Perform output voltage adjustment
as follows:
1.
Set the remote potentiometer at its mid point.
2.
Start the generator and set the VOLTS pot on the regulator for the desired output voltage (120, 230, etc.). The remote potentiometer will now have an adjustment range of approximately +/- 6%.
2
Field Flash
In order for the regulator to start up automatically and build voltage, the residual voltage of the generator
should be 5 VAC or higher. If a generator has not been used for a long period of time, has been apart or has
had its field inadvertently reversed, it may have lost some or all of its residual magnetism. In this case, it
may require field flashing. To flash the field, the generator must be stopped and the field leads disconnected. Momentarily connect the field leads to a 12 volt battery for 3-5 seconds, observing polarity (positive to
F+, negative to F-). Repeat a few times. CAUTION: Do not come in contact with the field circuit because
a high-voltage “kickback” will occur each time the circuit is interrupted.
TROUBLESHOOTING CHART
Warranty
The Model 480 Universal Regulator is warranted against defects in materials and workmanship for a period
of two years from the date of shipment. This warranty does not cover damage caused by operation outside
of ratings, misapplication or abuse. Flight Systems is not responsible for consequential damage to other
equipment, loss of use, spoilage of product, labor or travel costs, or injury to personnel as a result of its use.
Warranty service is limited to repair or replacement of product that we determine is defective, otherwise our
standard repair rates will apply.
3
4
5
MODEL 480 UNIT DIMENSIONS
FLIGHT SYSTEMS
207 Hempt Rd. Mechanicsburg PA, 17050
717-590-7330
Fax: 717-590-7327
www.flightsystems.com
Issued 8/24/10 - Printed in USA