* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download ON LINE UPS 6-10kVA USER MANUAL
Survey
Document related concepts
History of electric power transmission wikipedia , lookup
Stray voltage wikipedia , lookup
Power engineering wikipedia , lookup
Pulse-width modulation wikipedia , lookup
Three-phase electric power wikipedia , lookup
Solar micro-inverter wikipedia , lookup
Voltage optimisation wikipedia , lookup
Power inverter wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Alternating current wikipedia , lookup
Mains electricity wikipedia , lookup
Buck converter wikipedia , lookup
Opto-isolator wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Electric battery wikipedia , lookup
Transcript
ON LINE UPS 6-10kVA USER MANUAL Thanks for choosing EATON products! All warnings and operation instructions in the manual and on the machine should be strictly followed, and this user manual should be kept for future reference. Do not attempt to operate the UPS until reading through all safety information and operating instructions of this manual carefully. Sol e m n S t a t e m e n t Copyright Statement EATON is dedicated to a continued effort of technological innovation and provision of improved products and services to satisfy customers' needs. Product design and technical specifications are subject to upgrading without notice. Safet y I n s t r uc t i o n s Operation Safety 1. Prior to the application, please read “Safety Instructions” carefully to ensure correct and safe application. Please keep the user manual. 2. During operation, attention should be paid to all warning symbols and operations should be followed strictly as required. 3. Equipment is not supposed to be used in environment that directly exposed to sunlight or rain or in a humid environment. 4. The equipment should not be installed close to area of thermal sources or any area where there is presence of devices such as electric heaters and furnaces. 5. Make sure the safety space should be left for proper ventilation and product maintenance when placing UPS. Refer to the instructions during installation. 6. Dry and non-conductive items should be used for cleaning. 7. In case of a fire hazard, dry powder extinguisher should be used properly. Using liquid fire extinguishers may result in electric shock hazard. Electrical Safety 1. Before electricity is switched on, make sure earthing is properly done and wire and battery polarity are correctly connected. 2. When UPS relocation or wire reconnection is necessary, AC and battery should be switched off and UPS should be completely turned off, otherwise there might be a danger of electric shock because output terminal might be still electrified. 3. Please use EATON specified appendix devices and accessories. 4. To meet the requirement of EMC, the length of the output should be less than 10m. Battery Safety 1. Battery service lifetime will be shortened as ambient temperature rises. Replace batteries periodically to guarantee normal UPS performance and sufficient back-up time. 2. Only personnel with proper expertise can carry out the maintenance of accumulator batteries. Replacement of accumulator batteries requires a match of same type and model with equal quantity. 3. As accumulator batteries may contain potential electric shock and short-circuit current danger, to avoid accidents that might be thus resulted, the following warnings should be observed during battery replacement: A. Do not wear watches, rings or similar metallic items; B. Use insulated tools; C. Put on rubber shoes and gloves; D. Do not place metallic tools or similar metallic parts on the batteries; E. Switch off load connected to the batteries before dismantling battery connection terminals. 4. Do not expose accumulator battery to fire in order to avoid possible explosion that might endanger physical safety. 5. Non-professionals are not allowed to open or destroy accumulator batteries for electrolytes in batteries contain strong acid and other dangerous substances which will cause damages to both human skins and eyes. Should electrolytes come into any contact with human body unintentionally, rinse with clean water and seek medical advice. 6. Do not cause battery positive and negative polarity short circuit, otherwise, electric shock or inflammation may occur. Maintenance 1. Working environment and storage means can affect the service term and reliability of this product to some extent. Therefore, the product is not suitable for performance in the following environment: A. Locations where temperature exceeds the maximum or goes below the minimum temperature as required by technical specifications or humidity is o improper (temperature range: 0-40 C ; relative humidity range: 20%-90%). B. Locations where vibration and impact are constant; C. Locations where metallic dust, corrosive substances as well as salts and inflammable gases are present. 2. For long-term inaction, UPS (without batteries) should be kept in dry o environment with temperature ranging from -25-55 C. Before start-up, ambient temperature should be brought back to 0 or above for a certain period of time (above 2 hours). Cont e nt s C h a p t e r 1. B r i e f i n t r o d u c t i o n……………………………………... …..1 1.1 Frequently used symbols..................................................................................2 1.2 Front view……………………………………………………………………………2 1.3 Rear view…………………………………………………………………………….3 1.4 Technical data…………………………………………………………….…………4 C h a p t e r 2. I n s t a l l a t i o n 2.1 Unpacking inspection........................................................................................6 2.2 Wiring table.......................................................................................................7 2.3 Connection........................................................................................................8 2.4 Installation of external battery of long backup time model................................9 2.5 Connecting to computer interface....................................................................10 2.6 Parallel operation (option)...............................................................................11 2.7 Communication card installation......................................................................15 2.8 EPO.................................................................................................................16 2.9 Maintenance switch.........................................................................................17 2.10 Dustproof net (option)....................................................................................17 2.11 Transformer (option)......................................................................................17 C h a p t e r 3. C o n t r o l P a n e l…………………………………………………18 C h a p t e r 4. O p e r a t i o n ……………………………………………………….19 4.1 Start up............................................................................................................19 4.2 Shut down........................................................................................................21 C h a p t e r 5. B a t t e r y m a i n t e n a n c e……………………………………..22 C h a p t e r 6. Troubleshooting……………………………………………………….23 C h a p t e r 7. Warranty……………………………………………………………….25 Ch apt e r 1 B r i ef i nt r oduc t i o n This On-Line-Series is an uninterruptible power supply incorporating doubleconverter technology. It provides perfect protection specifically for computers, communication equipment and so on. The double-converter principle eliminates all mains power disturbances. A rectifier converts the alternating current from the socket outlet to direct current. This direct current charges the batteries and powers the inverter. On the basis of this DC voltage, the inverter generates AC voltage, which permanently supplies the loads. When some overload, inverter fault or rectifier fault occurs, the UPS will transfer to Bypass mode. This manual is designed for the EATON DX series product, include: EDX6000H-LCD: 6kVA standard model with internal battery EDX6000HXL-LCD: 6kVA long back up time model with external battery EDX10KHXL-LCD: 10kVA long back up time model with external battery 1 1.1 Frequently used symbols Symbol & Description Symbol Description Caution Danger Alternating Current Direct current Earth protection Connection protection Cycle Do not place with sundries Overload Battery On/off 1.2 Front view EATON DX O N /O F F T EST / EATON DX ON/OFF EDX6000H-LCD TE S T/ EDX6000HXL-LCD & EDX10KHXL-LCD 1.3 Rear view EDX6000H-LCD 1. Computer interface 2. Intelligent slot 3. Fan (2 Fans on 10kVA) 4. Parallel card (optional) cover 5. Input switch 6. Maintenance switch (optional) cover 7. Terminal block cover 8. Cable clamp 9. EPO (optional) EDX6000HXL-LCD & EDX10KHXL-LCD NOTE: 1. For models with parallel card and maintenance switch, you should remove covers 4 and ⑥ to access the parallel card and maintenance switch. 3 Input protection rating (MCB) 32A ELECTRICAL OUTPUT CHARACTERISTICS – NORMAL MODE Rated apparent/active power Transfer–normal to stored energy Rated output voltage Output voltage variation Crest factor 1.4 Technical data 6000VA / 4800W No break 220V ±2% 3:1 Eaton E Series DX 1Ph 6-10kVA LCD UPS Technical Specification CONSTRUCTION Model Rating Technology Dimensions: W x D*x H mm EDX6000H-LCD EDX6000HXL-LCD EDX10KHXL-LCD 6000VA / 4800W 10000VA / 8000W 248 x 500 x 616 240 x 500 x 460 240 x 500 x 460 60kg 20kg 21kg 6000VA / 4800W VFI, on-line double conversion *Allow 150mm rear clearance for connections & air flow Weight ENVIRONMENTAL & SAFETY Ambient service temperature Ambient storage temp. Maximum service altitude Relative humidity Degree of protection Acoustic Noise Standards Power electronics part: 0 to 40C, Battery part: 5 to 25C without reducing battery life 0˚C to +45˚C 1000m above sea level 20 to 90%, no condensation allowed IP21 (EN60529) <55dB @ 1m, Normal mode, typical load, battery fully charged EMS & EMI: Complies with IEC61000-4-2 Level 4, IEC61000-4-3 Level 3, IEC61000-4-4 Level 4, IEC61000-4-4 Level 4, IEC62040-1, EN55022 Class B Safety: Complies with GB4943-2001/IEC62040-1 POWER CONNECTIONS Input Output Hardwired Hardwired USER INTERFACE Display Communication Ports Optional LED mimic diagram + LCD Display with measurements (Input/Output/Bypass V & Hz, Battery V & % capacity & remaining time and level indicator, Load % & level Indicator, Alarm codes) 1 off Intelligent-Slot (Empty), 1 x RS232 DB9 Serial Port Intelligent Slot cards; AS400 Relay, Web/SNMP, Modbus ELECTRICAL CHARACTERISTICS – INPUT Rated input voltage Input voltage tolerance (with linear load) Bypass Voltage Tolerance Operating Frequency Input current distortion Input power factor @ Pnom Input Current (at rated load with fully charged battery) Input protection rating (MCB) 220V 185±5V - 274±5V @ >90% load, 165±5V - 274±5V @ 70 - ≤90%, 150±5V - 274±5V @ 50 - ≤70%, 120±5V - 274±5V @ ≤50% load, 165 – 253V (Default 187-253V user adjustable) 50/60Hz auto sensing; Tolerance (46/56 ±0.5) Hz Low, (54/64±0.5) Hz High <10% THDi 0.99pf 25A 25A 41A 32A 32A 63A 6000VA / 4800W 10000VA / 8000W ELECTRICAL OUTPUT CHARACTERISTICS – NORMAL MODE Rated apparent/active power Transfer–normal to stored energy Rated output voltage Output voltage variation Crest factor 4 6000VA / 4800W No break 220V ±2% 3:1 Internal battery (H Models): Full Load / Half Load 4 / 12 mins NA NA NOTE: Battery times are approximate and vary depending on age, temperature and load configuration. BYPASS CHARACTERISTICS Type of bypass Transfer Time In-Built Automatic Relay Bypass Online mode: <4ms ECO Mode: ≤8ms Eaton E Series 1Ph 6-10kVA LCD UPS Technical Specification EDX6000H-LCD EDX6000HXL-LCD EDX10KHXL-LCD Rated output frequency 50Hz (default) or 60Hz Output frequency regulation On Line Mode: Follows bypass frequency Total output voltage distortion ≤2% Linear Load, ≤4% Non Linear Load Frequency Slew Rate 1Hz/sec Load power factor range 0.7 – 1.0 Number of output phases 1 Phase Overload (Normal Mode, Resistive Load) 125% for 1 minute, 150% 30 seconds Output voltage variation – dynamic load ±6% max from 20%-100%-20% load step or vice versa Recovery to nominal voltage ±10% within 60ms ELECTRICAL OUTPUT CHARACTERISTICS – STORED ENERGY Rated apparent/active power 6000VA / 4800W 6000VA / 4800W Waveform Sine Wave Rated output voltage 220V Output voltage variation ±2% Crest factor 3:1 Rated output frequency 50Hz (default) or 60Hz Output frequency regulation ±0.05Hz Total output voltage distortion ≤2% Linear Load, ≤4% Non Linear Load Load power factor range 0.7 – 1.0 Number of output phases 1 Phase Output Overload 125% for 1 minute, 150% 30 seconds 10000VA / 8000W EFFICIENCY (Input/Output) Efficiency at 100% linear load ≤90% (≤97% in ECO mode) BATTERY Internal Battery Type Valve Regulated Lead Acid, AGM, 3-5 year design life at 25oC Charging voltage 2.275V/Cell ± 1% Charger Capacity 220W ±5% 1000W ±5% 1000W ±5% End V/Cell, >23% Load 1.6V 1.67V 1.67V End V, ≤23% Load 1.83V 1.83V 1.83V Internal Battery Re-charge time Internal Battery: <7 hours (6kVA) to recover 90% of capacity External Battery: Dependant on battery capacity Battery Nominal Voltage 192V (96 Cells) *240V / 120 Cells optional on XL Models Internal Battery Configuration Battery Circuit Protection Rating 16 x 12V 7.2Ah NA NA 30A 30A 60A 4 / 12 mins NA NA Battery Run Times Internal battery Full / Half Load NOTE: Battery times are approximate and vary depending on age, temperature and load. BYPASS CHARACTERISTICS 5 Type of bypass In-Built Automatic Relay Bypass Transfer Time Online mode: <4ms, ECO Mode: ≤8ms Chapt e r 2 I ns t al l at i o n DANGER: Ensure supply power is disconnected and the battery supply is isolated. CAUTION: 1. The installation as described in this chapter may only be carried out by qualified personnel and must comply with the local regulations 2. The UPS is recommended for floor mounted installation only. 2.1 Unpacking inspection 1. Open the packing box of the UPS and take it out, check whether the UPS is damaged during the process of transportation. 2. Should any damage be observed or parts be found missing, do not start the machine. Contact the forwarder and distributor immediately. Accessories: 1) User manual RECYCLE: Please keep the packaging for future use. 2.2 Wiring table CAUTION: Choice of the diameter and cross section of conductors depend on the rated power of UPS, the installation and local regulations. 6 DX6K DX6K XL DX10K XL 10AW (6mm2) 10AWG (6mm2) 10AWG (6mm2) 10AWG (6mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 6AWG (25mm2) 6AWG (25mm2) 6AWG (25mm2) 6AWG (25mm2) L 10AWG (6mm2) 10AWG (6mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 6AWG (25mm2) 6AWG (25mm2) + 10AWG (6mm2) 10AWG (6mm2) 10AWG (6mm2) 10AWG (6mm2) 10AWG (6mm2) 10AWG (6mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 6AWG (25mm2) 6AWG (25mm2) 6AWG (25mm2) 6AWG (25mm2) 6AWG (25mm2) 6AWG (25mm2) L 10AWG (6mm2) 10AWG (6mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 6AWG (25mm2) 6AWG (25mm2) N 10AWG (6mm2) 10AWG (6mm2) 10AWG (6mm2) 10AWG (6mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 8AWG (10mm2) 6AWG (25mm2) 6AWG (25mm2) 6AWG (25mm2) 6AWG (25mm2) G N G G DX10 KXL DX10K XL31 DX15K XL31 DX20K XL31 2.3 Connection DANGER: The customer must install a suitably rated disconnection switch in the mains supply to the UPS. 1. Choose appropriate cables for input and output to reference “wiring table”. 2. Remove the terminal block cover in the rear panel. 3. Connect the load to the output of the terminal block. 4. Connect the input power cable to the input of the terminal block. On XL model connect the external battery cables. 5. Secure the cables to the cable clamps. 7 DANGER: Make sure the input and output cables are connected firmly. Terminal block: In put EDX6000H-LCD 8 Outp ut Inpu t Output EDX6000HXL-LCD EDX10KHXL-LCD 7. Put the cover board back to the UPS and tighten the screws. 8. Before the input protection switch is being set in the “ON” position, supply power source to the UPS. Input Protection Switch 2.4 Installation of external battery of long backup time model EATON DX has 16 batteries (20 batteries for special models) connected in series as a 192VDC bank, and multiple of battery banks can be connected in parallel; while 20 batteries for special models connected in series as a 240VDC block and multiples of battery can be connected in parallel. It is very important to follow the battery connecting procedures; otherwise, there may be electric shock hazard. Please perform the connecting procedure according to the following step strictly: 1. Make sure the battery switch in the “OFF” position and connect the 16 batteries in series. 2. Connect the battery cable to the battery blocks. A disconnect switch/protective device must be connected between the battery bank and the UPS, the current and voltage specification of the switch shall be as follows: - Standard 16 battery system: 192VDC, 34A - Optional 20 battery system: 240V DC, 27A 9 DANGER: Do not connect the battery cable to the UPS first; otherwise, there may be electric shock hazard. 3. Connect the battery cable to the battery terminal of UPS. Make the power supply to the UPS, then set the battery block switch in the “ON” position, the UPS will begin to charge the battery block. CAUTION: The battery grounding of the UPS is located on the right of the terminal block and marked with the icon " ". 2.5 Connecting to the Computer interface Computer interface: standard RS232 communication port, use a RS232 cable to connect the UPS with the computer. 1. Connect the RS232 communication cable to the serial port computer. 2. Connect the RS232 cable to the RS232 communication port of the UPS. Communication Port RS232 Cable 10 The PIN configuration of computer interface port on UPS is as follows: 2.6 Parallel operation (option) 1. Redundancy N+X is currently the most reliable structure in power protection. N represents the minimum number of the UPS modules of the UPS system that the total load needs; X represents the number of the redundant UPS blocks of the UPS system, i.e. the number of faulty UPS modules that the system can handle simultaneously. The bigger X is, the higher the system reliability is. For occasions where reliability is highly depended on, N+X is the optimal mode. The UPS system can be configured with up to three UPS modules. Use the parallel cables to connect the parallel UPS with each other to realise power redundancy. 2. Connection The parallel function is optional and customers should purchase the necessary accessories (including the parallel cables and parallel cards), then the customer service engineers will help install them. Up to three UPS modules can be paralleled; each must be supplied with a separate battery. 1) Remove the parallel card cover and connect the UPS parallel communications cables. 11 2) Connect each output breaker to a main output breaker and then to the loads. Utility Input Switchboard Output Switchboard Load Load Load Load CAUTION: Requirement of output wiring length: When the lead from the output terminal of each set of UPS to the output patch board is less than 20m, wire difference should be less than 20%; When the lead from the output terminal of each set of UPS to the output patch board is longer than 20m, wire difference should be less than 10%. 3) The wiring connection diagrams are as follows and the wiring requirements follow the requirements of single UPS. 4) The parallel UPSs have been designed for use with separate batteries. 12 Output ground Output neutral Output line Battery pack 3# Battery pack 2# Battery pack 1# Input line Input neutral Input ground 13 3. Advantages of parallel configuration This configuration improves the reliability of the power supply system through the redundancy frame structure. Two UPSs equally share the load, when one UPS fails, the other will take up full load itself. It is designed to isolate the UPS from the AC source for maintenance; each UPS has a manual maintenance bypass. 4. Operation 1) Please follow the single UPS operating guide to perform general operation. 2) Power on Power on under mains: After you make sure that the power supply connection is correct, press the “ON” button of any UPS continuously for more than 1 second, the units transfer to work under INV mode simultaneously as they start up sequentially in line mode. Power on under battery: Short press the "ON" button of each UPS to get power sources, then press the “ON” button of one's continuously for more than 1 second, the units work under battery mode simultaneously. 3) Power off Press the “OFF” button of one set of UPS continuously for more than 4 seconds, all the UPSs will be shut down; Press the “OFF” button of one set of UPS continuously for more than 1 second, no more than 4 seconds, this UPS will be shutdown alone. CAUTION: Long-press is more than 1 seconds, short-press is less than 0.5 second. 2.7 Communication card installation Intelligent slot is designed for the communication cards. You don’t need to stop the UPS during the installation of communication card. 1. Remove the cover board of intelligent slot. 2. Insert the communication card into the slot. 3. Use the screws to tighten the card. 14 Intelligent slot SNMP Card (option) The intelligent slot with installation of SNMP card supplies the SNMP compliant data on an RJ45 connector. AS400 card (option) This series UPS support AS400 card (an optional accessory) for intelligent slot. The following is the pin assignment and description of DB-9 connector in AS400 card. PIN Description PIN1 PIN2 UPS Fail Summary alarm PIN3 PIN4 GND (Ground) Remote shutdown PIN5 PIN6 Common Bypass PIN7 Battery low PIN8 PIN9 UPS on Line loss 15 2.8 EPO EPO (Emergency Power Off) is an optional green connector located on the rear panel of the UPS. It performs emergency power off when the UPS is under emergent condition. There are two connection methods as follows: EPO Switch performs Emergency Power Off EPO Switch 1-2 connect with short wire, always keep connected 3-4 open- UPS perform Emergency power off 16 2.9 Maintenance switch There are voltages present inside the UPS when it works under line mode, battery mode or bypass mode, so you separate the UPS electronics from the utility via closing the Maintenance switch to perform on-line maintenance. Maintenance switch Utility input Output Battery Maintenance switch cover 2.10 Dustproof net (option) Dustproof net is used to protect the UPS from dust and it is necessary to install a dustproof net for the device at an environment with heavy dust or smog. Dustproof net should be installed inside the UPS and at the back of the front panel. Please refer to the dustproof net quick installation guide for details. 2.11 Transformer (option) Please refer to the transformer quick installation guide for details. 17 Chap t e r 3 Contr o l p a n e l ①~④ LED: ① Utility power ② Battery ③ Bypass ④ Inverter ⑤ ON/OFF button ⑥ Function button ⑦ LCD The alarm silence of the function button is valid only in battery mode and bypass mode. It cannot silence other fault warning alarms of the UPS system. The LCD has five parts as follows: ① Numerical display: show voltage, frequency, battery capacity, load capacity and fault code. ② Configuration: show the connection configuration of part ① . ③ Load capacity icon: show the level of the load capacity. ④ Battery capacity icon: show the level of the battery capacity. ⑤ Alarm icon: when the UPS is abnormal, the icon will appear. 18 Chapt er 4 O per at i o n 4.1 Start up The battery is fully charged before delivery. However, storage and transportation will inevitably cause some charge loss. Therefore, it is advisable to charge the battery for 12 hours before using it, so as to ensure adequate battery autonomy. Start with the utility power: 1. Power on the UPS, the Utility Power LED is lit, then press the “ON” Button to start the UPS. 2. After few minutes, the normal operation begins, the utility power LED and the inverter LED are lit and the LCD shows the main menu under normal mode. EATON DX 3. UPS supplies power to the load. 4. Press the “Function” button to obtain the following information from LCD. 19 Hz VAC IN P UT L OA D 5. Turn on the UPS, it will perform a self-test automatically and all of the “ ” On the LCD are lit one by one from left to right. The inverter LED on and UPS is under normal mode. If the utility power is abnormal, the UPS runs in battery mode. Start without the utility power: 1. Press the “ON” button to start the UPS (connect the external battery first for the long backup time models). 2. UPS starts up in battery mode, the battery LED and the inverter LED are on, the LCD shows the main menu under battery mode. 20 3. UPS supplies power to the load 4. Press the “Function” button to obtain the following information from LCD. 5. Buzzer beeps once every 4 seconds, which indicates the UPS run under battery mode. Press the "Function” button for more than 2 seconds to silence the buzzer. 4.2 Shut down 1. Press the “OFF” button to turn off the UPS. 2. The terminal still has live voltage via bypass; the line LED and the bypass LED are on. The LCD shows the main menu under bypass mode. 3. The buzzer beeps once every 2 minutes, which indicates the UPS run under bypass mode. Press the “Function” button for more than 2 seconds to silence the buzzer. 4. Press the "Function" button to obtain the following information from LCD. Hz VAC LOAD IN P U T 5. To completely power down the UPS, disconnect the line input of the UPS. 21 Ch a p t e r 5 B a t t e r y m a i n t e n a n c e The battery is key component of the UPS. The battery life depends on the ambient temperature, charge and discharge times. High ambient temperature and deep discharge will shorten the battery life. 1. When being connected to the utility whether the UPS has been turned on or not, the UPS keeps charging the battery and also offers the protective function of charging and discharging. 2. If the UPS has not been used for a long period, charging is recommended every 4 to 6 months. Charging should begin after the UPS shout down automatically in the course of discharging. In the regions of hot climates, the battery should be charged and discharged every 2 months. Moreover, the standard charging time should be not less than 12 hours. 3. Under normal conditions, the battery life lasts 3 to 5 years. In case the battery is found not in good condition, earlier replacement should be made. The battery should only be replaced by qualified service personnel. 4. In replacement of battery, please use the same number and type of battery. 5. Batteries should not be replaced individually. All batteries should be replaced at the same time following the instruction of the battery supplier. 6. Normally, the battery should be charged and discharged every 4 to 6 months. The standard charging time should be not less than 12 hours. 22 Chapt er 6 Tr oubl es hoot i n g 6.1 Understanding the UPS in alarm condition If the Alarm icon is on and the LCD shows fault code, which indicates that the operation is abnormal. Please refer to the "troubleshooting table" for details. A. Fault code (fault menu) The following items are displayed by the LCD via pressing the function button: output voltage and frequency, input voltage and frequency, load level and battery capacity. And the fault menu is the main menu. B. Alarm code (alarm menu) The following items are displayed by the LCD via pressing the function button: parameters of output, input, load level, voltage, frequency and battery capacity. And the alarm menu is the main menu. 23 6.2 Troubleshooting table Fault code 001 002 003 005 006 007 008 010 017 021 022 023 025 026 029 032 034 035 036 042 055 056 057 059 100 103 104 106 107 109 110 111 113 114 115 117 118 119 125 126 131 200 201 219 227 24 Description FAULT CODE TABLE BUS soft start overtime BUS voltage high BUS voltage low BUS short circuit Inverter soft start overtime Inverter voltage high Inverter voltage low R phase inverter voltage short circuit R phase reverse power Current balance fault Overload Over-temperature INV Rly fault Line input SCR fault Rectifier fault Communication wire disconnected CAN communication wire fault Synchronous signal wire fault System power supply fault Line input fuse fault NTC fault Parallel line fault Battery fault Battery overcharged WARNING CODE TABLE EXTEND WARNING TABLE Internal alarm Line loss alarm Input N wire disconnected Reversed L, N connection Bypass loss alarm Battery disconnected Battery voltage low alarm Battery overcharged Overload pre-alarm Overload alarm Fan failure Charger failure Address fault Fail to meet power-on requirements Temperature is too low Temperature is too high Slave board fail alarm INTERNAL WARNING TABLE Eeprom alarm Address conflict Fail to identify model Parallel mode alarm Chapt er 7 W arrant y Our company promises: products to be offered free warranty service for one year from the date of purchase. The local office or distributor may grant a warranty period different to the above and refer to local terms of liability as defined in the supply contract. To obtain service under warranty via a valid guarantee offered by dealers; To obtain service under warranty via serial number. The cost of delivery shall be borne by the customer, please contact the service centre or distributor. This limited warranty does not apply to conditions as follows: Out of warranty; The finished product of which the serial number is changed or lost; Capacity dropped normally and external appearance damaged; Some damage occurred during delivery, move; Damage due to force disaster and man-made fault; Disobeying provisions of operating/using the unit; 614-04506-IN 25