Download (HVDC) Power Lines

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Three-phase electric power wikipedia , lookup

Electromagnetic compatibility wikipedia , lookup

Opto-isolator wikipedia , lookup

Buck converter wikipedia , lookup

Electric power system wikipedia , lookup

War of the currents wikipedia , lookup

Islanding wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electric machine wikipedia , lookup

Voltage optimisation wikipedia , lookup

Stray voltage wikipedia , lookup

Surge protector wikipedia , lookup

Vehicle-to-grid wikipedia , lookup

Wireless power transfer wikipedia , lookup

Electrical substation wikipedia , lookup

General Electric wikipedia , lookup

Overhead power line wikipedia , lookup

Metadyne wikipedia , lookup

Mercury-arc valve wikipedia , lookup

Electric power transmission wikipedia , lookup

Transmission tower wikipedia , lookup

Distributed generation wikipedia , lookup

Electrification wikipedia , lookup

Life-cycle greenhouse-gas emissions of energy sources wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Rectiverter wikipedia , lookup

Mains electricity wikipedia , lookup

HVDC converter wikipedia , lookup

Power engineering wikipedia , lookup

High-voltage direct current wikipedia , lookup

Alternating current wikipedia , lookup

History of electric power transmission wikipedia , lookup

Transcript
Strahlenschutzkommission
Geschäftsstelle der
Strahlenschutzkommission
Postfach 12 06 29
D-53048 Bonn
http://www.ssk.de
Biological Effects of Emissions from High Voltage Direct
Current (HVDC) Power Lines
Recommendation by the German Commission on Radiological
Protection, with scientific reasoning
– Excerpt –
Adopted at the 263rd meeting of the German Commission on Radiological Protection, on
12 September 2013
Biological Effects of Emissions from High Voltage Direct Current (HVDC) Transmission Lines
2
Introduction
The governmentally encouraged use of renewable energy sources as a result of the
transformation of the energy system (energy turnaround - Energiewende) in Germany leads to
long distances between the points at which electric power is generated and consumed. This
presents a need to build new long-distance power transmission lines. High voltage direct
current (HVDC) power lines are to be employed as a part of this grid expansion.
The Federal Ministry for the Environment, Nature Conservation and Nuclear Safety (BMU)
requested the Commission on Radiological Protection (SSK) to supplement its previous
statement on alternating voltage energy supply systems (SSK 2008) by providing an
assessment of HVDC lines, especially of their constant electric and magnetic fields, in terms
of radiation protection aspects with regard to human exposure. The SSK subsequently
prepared the following recommendation. Deriving limit values is not a subject of this
recommendation.
Recommendations
In view of the anticipated ambient levels of electric and magnetic fields generated by HVDC
overhead power lines, and considering the prevailing regulatory gaps, the SSK makes the
following recommendations:
The SSK recommends that the constant electric fields of HVDC lines be limited with the
goal of preventing health impairment or substantial discomfort, and that a weighted
summation of the individual contributions be conducted in cases of simultaneous
exposure to constant and alternating electric fields.
Due to the limited data, notably with regard to the numbers of persons studied and the
influences of cofactors such as ion density, it is not possible at present to derive reliable
threshold values for perception, discomfort, pain and danger. The SSK therefore
recommends that further research be conducted on perception, mainly in the form of
human studies under well-controlled conditions.
The SSK recommends that grid operators be requested to prevent possible secondary
effects (such as electric shocks caused by discharges to or from conductive surfaces) by
taking suitable corrective action, primarily with a focus on constructive measures.
The SSK notes the need to protect individuals who carry magnetically activatable
implants. For instance, in order to definitely ensure that no interference with cardiac
pacemakers occurs, the SSK recommends that the magnetic flux density be limited to
500 µT.