Download EXECUTIVE SUMMARY THE MAXIMUM INVERTER OUTPUT

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Operational amplifier wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

CMOS wikipedia , lookup

Power MOSFET wikipedia , lookup

Surge protector wikipedia , lookup

Valve RF amplifier wikipedia , lookup

Transistor–transistor logic wikipedia , lookup

Radio transmitter design wikipedia , lookup

Wilson current mirror wikipedia , lookup

Audio power wikipedia , lookup

Valve audio amplifier technical specification wikipedia , lookup

Opto-isolator wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Current mirror wikipedia , lookup

Power electronics wikipedia , lookup

Rectiverter wikipedia , lookup

Transcript
/ Perfect Welding / Solar Energy / Perfect Charging
THE BRIGHT IDEA BEHIND POWER CLASSES
TECHNICAL ARTICLE
Authored By:
Brian Lydic, Standards & Technology Integration Engineer, Fronius USA
[email protected]
Adam Gentner, Group Leader, National Technical Support, Fronius USA
[email protected]
EXECUTIVE SUMMARY
/ With the spread of residential PV power, more and more
companies are making and selling inverters in odd sizes, namely
3.8 kW, 7.6 kW and 11.4 kW. But why is that?
/ The answer to that question lies within the AC service panel. At
a 240 V grid, a 3.8 kW inverter is the largest inverter that is
allowed on a 100A service panel, a 7.6 kW inverter is the largest
allowed on a 200 A service panel and an 11.4 kW inverter on a
300 A panel. As the cost of upgrading a service panel can be very
high, it is useful to fit the largest system possible on the existing
panel. With most modern homes being supplied by a 200 A
service panel, the 7.6 kW inverter is the largest inverter allowed
on the home without updating the service panel.
/ To figure out why these odd sizes are the maximum for common
AC panel sizes, we have to have a look on the inverter’s output
current and how this is related to the AC panel size. First, we will
need to figure out the maximum inverter output current that
works for our panel and then check in which inverter power class
that would result. After picking the power class, we can easily
calculate the required breaker size for the inverter.
/ The Fronius Primo is available in power
classes ranging from 3.8 to 8.2 kW. Why
are these numbers so specific? Read on
to find out more!
THE MAXIMUM INVERTER OUTPUT CURRENT FOR YOUR AC PANEL
/ The National Electric Code (NEC) defines the relation between
the inverter’s output current, the AC panel’s current (Ipanel) and
the panel’s main breaker (Imain).
/ To size a breaker for a typical load panel, NEC 705.12* is used.
WHAT THE CODE SAYS
/ 705.12
(3) Busbars. One of the methods that follows shall be used to
determine the ratings of busbars in panelboards.
The busbar shall be sized for the loads connected in accordance
with Article 220. A permanent warning label shall be applied
to the distribution equipment adjacent to the back-fed breaker
from the inverter that displays the following or equivalent
wording:
WARNING:
INVERTER OUTPUT CONNECTION;
DO NOT RELOCATE THIS OVERCURRENT DEVICE.
The warning sign(s) or label(s) shall comply with 110.21(B).
(a) The sum of 125 percent of the inverter(s) output
circuit current and the rating of the overcurrent device
protecting the busbar shall not exceed the ampacity of the
busbar.
Informational Note: This general rule assumes no limitation in
the number of the loads or sources applied to busbars or their
locations.
(b) Where two sources, one a utility and the other an
inverter, are located at opposite ends of a busbar that contains
loads, the sum of 125 percent of the inverter(s) output circuit
current and the rating of the overcurrent device protecting the
busbar shall not exceed 120 percent of the ampacity of the
busbar.
SE_White_Paper_Power_Classes_Explained.indd 1
9/28/2015 3:32:42 PM
LET’S DO THE MATH
/ Following (b), we can calculate the largest inverter output
currents using the following formula:
Iinv x 125% + Imain = Ipanel x 120%
Therefore, Iinv = Ipanel x 120% - Imain
125%
/ With that we can easily calculate the maximum inverter
output current for different AC panel sizes:
For a 100 A panel with a 100 A main breaker
Iinv = 100 x 120% - 100
125%
maximum Iinv = 16 A
For a 200 A panel with a 200 A main breaker
Iinv = 200 x 120% - 200
125%
maximum Iinv = 32 A
For a 300 A panel with a 300 A main breaker
Iinv = 300 x 120% - 300
125%
maximum Iinv = 48 A
THE INVERTER‘S OUTPUT POWER
/ Once we know the maximum output current that the inverter
can have on our panel, we can easily calculate the inverter’s
output power. Given a grid voltage of 240 volts, we can use
principles of electrical engineering to calculate the largest
inverter allowed on these panels:
/ The main formula to calculate electric power is:
POWER = CURRENT X VOLTAGE
Maximum inverter output power = maximum Iinv x 240 V
16 A x 240 V = 3840 W
3.8 kW is the max. inverter power
allowed on a 100 A panel
32 A x 240 V = 7680 W allowed on a 200 A panel
7.6 kW is the max. inverter power
48 A x 240 V = 11520 W
11.5 kW is the max. inverter
power allowed on a 300 A panel
WHICH BREAKER SIZE IS
REQUIRED?
/ Now that we know our inverter size, we can calculate the
required breaker size. Breakers are Overcurrent Protection
Devices (OCPDs) that protect circuits and equipment from
currents that exceed their ratings. Breakers and fuses are the
most common type of OCPD.
/ They are common in electrical installations of all types, and
are sized according to Article 240 of the NEC*.
240.6 Standard Ampere Ratings.
(A) Fuses and Fixed-Trip Circuit Breakers. The standard ampere ratings for fuses and inverse time circuit breakers shall
be considered 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90,
100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450,
500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000,
4000, 5000, and 6000 amperes. Additional standard ampere
ratings for fuses shall be 1, 3, 6, 10, and 601. The use of fuses
and inverse time circuit breakers with nonstandard ampere
ratings shall be permitted.
(B) Adjustable-Trip Circuit Breakers. The rating of adjustabletrip circuit breakers having external means for adjusting the
current setting (long-time pickup setting), not meeting the
requirements of 240.6(C), shall be the maximum setting
possible.
SE_White_Paper_Power_Classes_Explained.indd 2
/ Article 690 of the NEC dictates the rules specific to PV
Systems.
690.8(A)
(3) Inverter Output Circuit Current. The maximum current
shall be the inverter continuous output current rating.
690.9(B)
Overcurrent Device Ratings. Overcurrent device ratings
shall be not less than 125 percent of the maximum currents
calculated in 690.8(A).
Exception: Circuits containing an assembly, together with
its overcurrent device(s), that is listed for continuous
operation at 100 percent of its rating shall be permitted to be
used at 100 percent of its rating.
/ For our use the important information is that the OCPD
will be sized off of the Continuous Output Current rating of
the inverter, multiplied by 125%. This number should be
rounded up to the next highest standard size listed above.
Calculation Examples
Example a)
If the continuous output current* of the inverter would be
16 A, we multiply by 1.25 and get a 20 A circuit breaker.
Example b)
If the continuous output current* of the inverter would be
28.9 A: 1.25 x 28.9 = 36.1 A. The next highest breaker is
used (40 A in this case).
*Continuous output current is listed as nominal output current in the manual ratings tables.
CONCLUSION
/ The maximum current on a given AC panel is the reason
for some odd looking inverter power classes. In order to avoid
costs for AC panel upgrades, it makes sense for inverter
manufacturers to provide power classes that get the most
solar power on an existing customer’s AC panel without
upgrading it. That’s why Fronius offers the Fronius Primo in
the power classes 3.8 kW and 7.6 kW, or the Fronius IG Plus
A with 11.4 kW.
/ The breaker size for the inverter is defined in the NEC and
can be calculated with the maximum continuous output
power of the inverter.
CONTACT US
/ If you have any questions about this or if you want to learn
more about our solar solutions, do not hesitate and contact
us at (219)734-5500 or [email protected]. We
are happy to help you!
REFERENCES
/ * For all references to the NEC, the 13th edition, 2014 version was used:
Earley, Mark W, Christopher D. Coache, Mark Cloutier, and Gil Moniz. National Electrical Code Handbook. Quincy, Mass: National Fire Protection Association, 2014. Print.
Fronius USA LLC