Download WECC-0107 VAR-501-WECC-2 Power System Stabilizers Posting 4

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Buck converter wikipedia , lookup

Wireless power transfer wikipedia , lookup

Decibel wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Audio power wikipedia , lookup

Transmission line loudspeaker wikipedia , lookup

Power over Ethernet wikipedia , lookup

Voltage optimisation wikipedia , lookup

Electrical substation wikipedia , lookup

Rectiverter wikipedia , lookup

Islanding wikipedia , lookup

Electrical grid wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Electric power transmission wikipedia , lookup

Utility frequency wikipedia , lookup

Electric power system wikipedia , lookup

Three-phase electric power wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Electrification wikipedia , lookup

Power engineering wikipedia , lookup

Distribution management system wikipedia , lookup

Mains electricity wikipedia , lookup

Alternating current wikipedia , lookup

History of electric power transmission wikipedia , lookup

Transcript
VAR-501-WECC-3 – Power System Stabilizers
Standard Development Timeline
This section is maintained by the drafting team during the development of the standard and will
be removed when the standard becomes effective.
Posting for Comment
This document is in its fourth posting.
Procedural Background
Standard Authorization Request (SAR) Consolidation
WECC-0094 VAR-501-WECC-“1” PSS and the ballot results of the WECC-0105 P81
redraft have been merged into WECC-0107 VAR-501-WECC-“3” resulting in a
document applicable to the BES.
This Standards Authorization Request (SAR) to review WECC’s PSS-related documents
is in response to a WECC Board of Director’s resolution.
On September 5, 2012, the WECC Board of Directors adopted the recommendation of
the Regional Criteria Work Group that a (SAR) should be filed to evaluate VAR-502WECC-RBP-11, WECC Power System Stabilizer (PSS) Design and Performance, a
Regional Business Practice (RBP), for development as a WECC Regional Reliability
Standard (RRS). Under WECC-0099, the WECC Control Work Group conducted the
review concluding that a RRS should be drafted.
On February 11, 2014 during the WECC Standards Committee (WSC) meeting:
“A motion was made by Mr. Joe Tarantino that was seconded by Ms. Dana
Cabbell to retire WECC-0099 having determined that the assigned project was
complete, and to approve the proposed iterative SAR [WECC-0107] to develop a
Power System Stabilizer RRS. The motion carried by Consensus. Mr. Warren
Rust abstained.” WSC Meeting Minutes
On June 25, 2014, the WSC changed the scope of the SAR directing that the proposed
document be structured so that PSS: 1) where installed, be operating unless specifically
exempted, 2) tuned as specified, and 3) where not installed, installation would be required
when a generator is newly interconnected to the Bulk-Electric System (BES) or when a
generator is updated. The WSC further approved merging WECC-0094 VAR-501-
1
In June 2014, the WECC Board of Directors resolved to eliminate the Regional Business Practice (RBP) category
defaulting to a WECC Criterion (CRT) category.
Draft #3: December 18, 2014 through January 19, 2015
Developed as WECC-0107
Page 1 of 20
VAR-501-WECC-3 – Power System Stabilizer
WECC-1 Power System Stabilizers into the document and incorporating the “P81”,
VAR-501-WECC-2, revisions resulting from WECC-0105 (ballot closed July 18, 2014).
Standard of Review
The Federal Energy Regulatory Commission (FERC) has stated that Regional Entity
Standards or Regional Variances to a NERC Reliability Standard (Standard) are
permissible if they set more stringent reliability requirements than the NERC Reliability
Standard; or cover matters not covered by an existing NERC Reliability Standard; or if
they are necessitated by a physical difference in the Bulk-Electric System (BES).2
Operational Background
Power System Stabilizers (PSS) are needed in the Western Interconnection to dampen
operational oscillation.
PSSs are part of the Automatic Voltage Regulation (AVR) system of a generator and are
designed to add or subtract torque to a generator with the goal of damping oscillations on
the WECC Interconnection’s Bulk-Electric System (BES) that otherwise would be
amplified if the AVR is operated by itself.
PSSs within WECC (originally called Supplementary Control Systems) were developed
in the 1960s in response to power system oscillations on the Pacific Intertie within the
Western Interconnection. These oscillations occur at very low frequencies (<1 hertz), are
very lightly dampened, and became known as “inter-area modes” (modes) of oscillation
because they occurred when real power was transferred from one Western
Interconnection geographic region to another (such as between the Pacific Northwest and
the Southwest).
These modal oscillations are the result of a combination of many machines on one part of
the Western Interconnection BES whose voltage support response to system fluctuations
is not in phase with the response of machines on another part of the Interconnection’s
BES. 3
2
Order No. 672 at P 291. See also NERC Functional Model, Version 5, “2. Reliability Standards”, page 36.
3
While some areas of other interconnections may experience this phenomenon, it is typically seen as only a
local issue, not an issue for the entire interconnection. In the Western Interconnection it is seen as both an
interconnection-wide issue and a local issue.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 2 of 20
VAR-501-WECC-3 – Power System Stabilizer
WECC Physical Characteristics
The Federal Energy Regulatory Commission (FERC) Order 740, Docket No. RM09-15000, P23, noted that “in the Western Interconnection a significant number of transmission
paths are voltage or frequency stability-limited, in contrast to other regions of the [BES]
where transmission paths more often are thermally-limited. Disturbances resulting in a
stability-limited transmission path overload, generally, must be responded to in a shorter
time frame than a disturbance that results in a thermally-limited transmission path
overload. [FERC has also noted] its understanding that this physical difference is one of
the reasons for the need for certain provisions of regional Reliability Standards in the
Western Interconnection.”
When coupled with generator operations within WECC these physical characteristics
create modal oscillation that when not corrected by the installation and accurate operation
of PSSs causes instability within the WECC Interconnection.
Description of the Draft
Existing Standard
WECC currently does not have a RRS that specifies the threshold at which a PSS must be
installed; however, WECC does have an existing policy that addresses that threshold.
(Under WECC’s current policy, a PSS is not installed on a station service generator.)
Under WECC’s current policy, a PSS is installed:
1)
On synchronous generators, regardless of ownership, that are connected to the
transmission system (by a generator step-up transformer to 60 kV or higher
voltage);
2)
On every existing synchronous generator that is larger than 75 MVA and is
equipped with a suitable excitation system as defined in the WECC report
“Criteria to Determine Excitation System Suitability for PSS”, (Report) dated
December 1992.
3)
On every existing synchronous generator that is larger than 30 MVA, or is part of
a complex that has an aggregate capacity larger than 75 MVA, if the excitation
system is updated so that it becomes a suitable excitation system as defined in the
above mentioned Report. This applies to all machines with excitation systems
updated after November 18, 1993.
4)
On every synchronous generator that is larger than 30 MVA, or is part of a
complex that has an aggregate capacity larger than 75 MVA, and is equipped with
suitable excitation systems commissioned after November 18, 1993.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 3 of 20
VAR-501-WECC-3 – Power System Stabilizer
Proposed Standard
To be updated once the document is more fully developed.
Applicable Entities
To be updated once the document is more fully developed.
Facilities
To be updated once the document is more fully developed.
Effective Date
The proposed Effective Date is the first day of the fourth quarter following final regulatory
approval.
Requirements and Measures
To be updated once the document is more fully developed.
Measures and Compliance
To be updated once the document is more fully developed.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 4 of 20
VAR-501-WECC-3 – Power System Stabilizer
Project Roadmap
Completed Actions
Completion Date
1.
SAR received
February 11, 2014
2.
SAR deemed Complete/Valid/Team Site created
February 11, 2014
3.
WSC approved the SAR
March 12, 2014
4.
WSC solicits / assigns a drafting team (DT)
March 12, 2014
5.
DT announced / notice sent to DT members
March 12, 2014
6.
First DT meeting
April 8, 2014
7.
WSC Changed scope of SAR to subsume VAR501-WECC-1. WSC approved posting for 45-day
comment.
June 25, 2014
8.
Posting 1 WECC open
July 1, 2014
9.
Posting 1 WECC closed
August 14, 2014
10. Posting 1 WECC Responses posted
September 26, 2014
11. Posting 2 WECC open
October 15, 2014
12. Posting 2 closed
November 14, 2014
13. WSC approved posting of responses and granted
permission for the late posting.
December 3, 2014
14. Posting 2 Responses posted
December 4, 20144
15. Posting 3 WECC open
December 18, 2014
16. FERC approved new WECC Reliability Standards
Development Procedures
December 23, 2014
4
On December 3, 2014, the WECC Standards Committee (WSC) granted the drafting team an extension of time for
posting of responses. The WSC agreed that a quality response was preferable to a timely response.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 5 of 20
VAR-501-WECC-3 – Power System Stabilizer
17. Posting 3 closed
January 19, 20155
18. Posting 3 Responses posted
19. WSC approves for ballot
20. Ballot Pool open
21. Ballot Pool closed
22. Joint Session noticed
23. Joint Session
24. Ballot open
25. Ballot closed
26. WSC approves forwarding to the WECC Board of
Directors
27. Posted for 30 days prior to WECC Board meeting
28. Board meets to approve
29. Sent to NERC
5
This document was posted for a 30-day public comment period from December 12, 2014 through January 12,
2015. Late comments were received until January 20, 2015, 10:00 a.m. (Mountain) when the drafting team met to
respond to comments. The window was extended because a closing date in the mandated notice did not match text
in the posted document.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 6 of 20
VAR-501-WECC-3 – Power System Stabilizer
Version History
Version
0.1
1
2
Date
Action
April 23, 2004 WECC Effective Date: VAR-502WECC-0.1
July 1, 2011
FERC Effective Date: VAR-501WECC-1
May 28, 2014 WECC Ballot Body Approved
3
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Change
Tracking
Paragraph 81
clean-up
This document
is designed to
replace / retire:
VAR-502WECC-RBP0.1, WECC
Power System
Stabilizer
Design and
Performance
and to replace
VAR-501WECC-1, Power
System
Stabilizer with a
“Version 2”
Page 7 of 20
VAR-501-WECC-3 – Power System Stabilizer
Implementation Plan
To Be Announced
Definitions of Terms Used in Criterion
This section includes all newly defined or revised terms used in the proposed criterion. Terms
already defined in the Reliability Standards Glossary of Terms are not repeated here. New or
revised definitions listed below become approved when the proposed criterion is approved.
When the criterion becomes effective, these definitions will be removed from the criterion and
added to the WECC Glossary.
There are no new definitions proposed.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 8 of 20
VAR-501-WECC-3 – Power System Stabilizer
A. Introduction
1. Title:
Power System Stabilizers (PSS)
2. Number:
VAR-501-WECC-2
3. Purpose:
To ensure the Western Interconnection is operated in a coordinated
manner under normal and abnormal conditions, by establishing the
performance criteria for WECC power system stabilizers
4. Applicability:
B.
4.1
Generator Operator
4.2
Generator Owner
5. Facilities:
This standard only applies to synchronous generators
6. Effective Date:
This standard becomes effective on the first day of the fourth
quarter following final regulatory approval.
Requirements and Measures
R1.
Each Generator Operator shall provide to its Transmission Planner, within 180
days of the PSS’s Commercial Operation date or any changes to the PSS
operating specifications, its written operating procedure describing those known
circumstances during which its PSS will not be providing an active signal to the
Automatic Voltage Regulator (AVR). [Violation Risk Factor: Low] [Time
Horizon: Planning Horizon]
M1.
Each Generator Operator will have documented evidence that it provided to its
Transmission Planner its written operating procedure describing those known
circumstances during which its PSS will not be providing an active signal to the
AVR, within the time allotted as described in requirement R1.
For auditing purposes, because the Requirement R1 conditions are intended to be
unchanged unless otherwise notified, the Generator Operator need only provide
the specifications to the Transmission Planner one time or whenever the operating
specifications change thereafter.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 9 of 20
VAR-501-WECC-3 – Power System Stabilizer
For auditing purposes, if a PSS is in service but is not providing an active signal
to the AVR as required in Requirement R1, the disabled period does not count
against the Requirement R2 mandate to be in service except as otherwise allowed.
R2.
Each Generator Operator shall have its PSS in service while synchronized,
except during any of the following: [Violation Risk Factor: Medium] [Time
Horizon: Operating Assessment]




M2.
Component failure;
Testing of a BES Element affecting or affected by the PSS;
Maintenance;
As agreed upon by the Generator Operator and the Transmission Operator.
Each Generator Operator will have documentation of each claimed exception as
allowed in Requirement R2. Documentation may include but is not limited to:


An explanation covering the bulleted exception describing the
circumstances of the exception as allowed in Requirement R2.
Where applicable, the Generator Operator will have documented evidence
that the Generator Operator and the Transmission Operator agreed that the
PSS should not be operating during a specified set of circumstances.
For auditing purposes, the presumption is that the PSS was in service unless
otherwise exempted in Requirement R1. Evidence need only be provided to
prove the circumstances when the PSS was not in service.
R3.
Each Generator Owner shall tune its PSS to meet the following inter-area mode
criteria: [Violation Risk Factor: Medium] [Time Horizon: Operating
Assessment]
1) PSS shall be set to provide a compensated minimum-load VT/Vref frequency
response of the excitation system and synchronous machine such that the
phase angle will not exceed ± 30 degrees through the frequency range
from 0.2 Hertz to 1.0 Hertz or the highest frequency at which the phase of the
minimum-load Vt/Vref frequency response does not exceed 90 degrees.
2) PSS output limits shall be set to provide at least ±5% of the synchronous
machine’s nominal terminal voltage.
3) PSS gain shall be set to between 1/3 and ½ of maximum practical gain.
4) PSS washout time constant shall be no greater than 30 seconds.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 10 of 20
VAR-501-WECC-3 – Power System Stabilizer
M3.
Each Generator Operator will have documented evidence that its PSS was tuned
to meet the specifications of Requirement R3. Evidence may include, but is not
limited to, a completed Attachment A for this standard that reports: 1) output
limits, 2) per unit gain, 3) washout-time constant, and 4) bode plots of the PSS.
R4.
Each Generator Owner shall install and commission on its generator a PSS, within
180 days of either of the following events: [Violation Risk Factor: Medium]
[Time Horizon: Operational Assessment]


M4.
The Generator Owner connects a generator to the BES, after achieving
Commercial Operation, and after the Effective Date of this standard; (or)
The Generator Owner replaces the voltage regulator on its existing excitation
system, after achieving Commercial Operation, and after the Effective Date of
this standard for its generator that is connected to the BES.
Each Generator Owner will have evidence that it installed and commissioned a
PSS on its generator, within 180 days of either connecting a generator to the BES
or replacing the voltage regulator on its existing excitation system, whenever
either event occurs after the Effective Date of this standard.
For auditing purposes, bullet one is intended to address newly connected
equipment; bullet two is intended to address equipment already connected to the
BES.
R5.
Each Generator Owner shall repair or replace a non-operating PSS within 24
months of that non-operating PSS becoming non-operational. [Violation Risk
Factor: Medium] [Time Horizon: Operational Assessment]
M5.
Each Generator Owner will have evidence that it repaired or replaced a nonoperational PSS within 24 months of that non-operating PSS becoming nonoperational. Evidence may include, but is not limited to, documentation of: 1) the
date the PSS became non-operational, and 2) the date the PSS was returned to
service, the span of time between the two events being within 24 months of one
another.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 11 of 20
VAR-501-WECC-3 – Power System Stabilizer
This section will be updated after the substance of the Requirements is established. The
DT requests that comments on this section not be submitted until the section is complete.
C. Compliance
1. Compliance Monitoring Process
1.1
Compliance Enforcement Authority
The Regional Entity shall serve as the Compliance Enforcement Authority.
For entities that do not work for the Regional Entity, the Regional Entity shall serve
as the Compliance Enforcement Authority.
For Reliability Coordinators and other functional entities that work for their
Regional Entity, the ERO or a Regional Entity approved by the ERO and FERC or
other applicable governmental authorities shall serve as the Compliance
Enforcement Authority.
For responsible entities that are also Regional Entities, the ERO or a Regional
Entity approved by the ERO and FERC or other applicable governmental
authorities shall serve as the Compliance Enforcement Authority.
1.2
Compliance Monitoring and Assessment Processes:
Compliance Audits
Self-Certifications
Spot Checking
Compliance Investigations
Self-Reporting
Complaints
1.3
Evidence Retention
The following evidence retention periods identify the period of time an entity is
required to retain specific evidence to demonstrate compliance. For instances
where the evidence retention period specified below is shorter than the time since
the last audit, the Compliance Enforcement Authority may ask an entity to provide
other evidence to show that it was compliant for the full time period since the last
audit.
Each Generator Operator shall keep evidence for all Requirements of the document
for a period of three years plus calendar current.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 12 of 20
VAR-501-WECC-3 – Power System Stabilizer
1.4
Additional Compliance Information
None
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 13 of 20
VAR-501-WECC-3 – Power System Stabilizer
Table of Compliance Elements
R
6
7
Time
Horizon
VRF
NA
Violation Severity Levels
Moderate
High VSL
VSL
NA
NA
NA
NA
Lower VSL
R1
Planning
Horizon
Low
R2
Operations Mediu
Assessment m
NA
Severe VSL
There shall be
a Severe6
Level of noncompliance
on any
occasion that
the Generator
Operator is
found to have
failed to
provide its
PSS operating
specifications
to the
Transmission
Planner as
required in
Requirement
R1.
(Requirement
R1 is binary.)
There shall be
a Severe7
Level of noncompliance
on any
occasion that
the Generator
Operator fails
to have its
PSS in
service, except
where allowed
in
Requirement
R2.
(Guidance VSL) For R1, Severe was chosen because the violation is binary.
(Guidance VSL) For R1, Severe was chosen because the violation is binary.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 14 of 20
VAR-501-WECC-3 – Power System Stabilizer
R
9
VRF
R3
Operations Mediu
Assessment m
R4
Operational Mediu
Assessment m
R5
8
Time
Horizon
Operational Mediu
Assessment m
Lower VSL
Occurs when
the Generator
Operator’s
PSS fails to
meet any of
the required
performances
in
Requirement
R3, two times
or less during
the audit
period.
NA
NA
Violation Severity Levels
Moderate
High VSL
VSL
Occurs when
the Generator
Operator’s
PSS fails to
meet any of
the required
performances
in
Requirement
R3, three
times during
the audit
period.
NA
NA
Occurs when
the Generator
Operator’s
PSS fails to
meet any of
the required
performances
in
Requirement
R3, four times
during the
audit period.
NA
NA
Severe VSL
(Requirement
R2 is binary.)
Occurs when
the Generator
Operator’s
PSS fails to
meet any of
the required
performances
in
Requirement
R3, five times
or more
during the
audit period.
There shall be
a Severe8
Level of noncompliance
on any
occasion that
the Generator
Owner is
found to have
failed to
install on its
generator a
PSS, as
required n
Requirement
R4.
(Requirement
R4 is binary.)
There shall be
a Severe9
Level of noncompliance
(Guidance VSL) For R1, Severe was chosen because the violation is binary.
(Guidance VSL) For R1, Severe was chosen because the violation is binary.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 15 of 20
VAR-501-WECC-3 – Power System Stabilizer
R
Time
Horizon
VRF
Lower VSL
Violation Severity Levels
Moderate
High VSL
VSL
Severe VSL
on any
occasion that
the Generator
Owner is
found to have
failed to repair
or replace a
nonoperational
PSS as
required in
Requirement
R5.
(Requirement
R5 is binary.)
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 16 of 20
VAR-501-WECC-3 – Power System Stabilizer
Attachment A
Output Limit Settings
Gain
Washout Time Constant
Voltage Step Test (greater than or equal to 80% load)
Response with PSS at
maximum Practical gain
Response with PSS at
nominal or as-commissioned
gain
Bode Plots
Excitation response with unit
connected to electrical
system without PSS in
service. (This is a VT/Vref
measured response.)
Excitation response with PSS
in service and unit connected
to electrical system. This plot
can be either via test or
calculated based on PSS
settings and measured
response of the first plot.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 17 of 20
VAR-501-WECC-3 – Power System Stabilizer
Guideline and Technical Basis
To be updated once the document is more fully developed.
PSS systems are used to minimize real power oscillations by rapidly adjusting the field of the
generator to dampen the low frequency oscillations.
It is necessary for large numbers of PSS devices to be in operation in the Western
Interconnection in order to provide the required system damping while still allowing for some of
these units to be out-of-service whenever necessary.
Facilities
The drafting team considered numerous approaches to setting the Facilities applicability
threshold. The drafting team noted that in the approved Version 2 of this standard the 80%
facilities applicability threshold was not based on a discrete technical study; rather, the 80% was
derived based on sound engineering judgment designed to include 80% of the units located
within the Western Interconnection.
Subsequent to approval of Version 2, the Bulk Electric System (BES) proceeding queried the
industry as to the most appropriate definition of the BES, with the final decision becoming the
threshold at which NERC standards would apply. When compared to the Version 2 proceedings
the BES proceedings were much more in-depth, represented a greater diversity of industry
viewpoints, and engaged a substantial array of subject matter experts not otherwise represented
in the Version 2 filing.
Noting the additional depth and breadth of the BES when juxtaposed to the Version 2
participation the drafting team concluded that the industry has already opined on the adequate
threshold at which NERC Reliability Standards should apply. As such, the drafting team opted to
use the default BES threshold as it more broadly represents the consensus of the industry.
Requirement R1
Requirement R1 recognizes that PSS systems have varying states such as on, off, active, and
non-active. So long as the PSS is operating in accordance with the documentation provided to
the Transmission Planner, this is not considered a status change for purposes of this standard. If
the PSS is not operating in accordance with the documentation provided to the Transmission
Planner, this could be considered a status change for purposes of NERC VAR-002-3,
Requirement R3.
This Requirement eliminates the requirement to count hours as required in the previous version
of this standard while also allowing the Generator Operator to create a unit-specific operating
plan.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 18 of 20
VAR-501-WECC-3 – Power System Stabilizer
The intent of the Requirement R1 is to provide the Transmission Planner the PSS operating zone
in which the PSS is, “active”, i.e., providing damping to the power system. Some PSS may be
programmed to become “active” at a specified MW loading level and above while others may be
programmed to be “active” in a particular band of MW loading levels and are “non-active” only
when passing through the “rough zone” or some other band. A “rough zone” is a MW loading
band in which the generator-turbine system could contribute to system instability.
Requirement R2
The intent of Requirement R2 is to remove the previous requirement to log hours for PSS inservice. In this standard’s previous version, the logged hours were totaled quarterly to meet the
98% in-service requirement. Instead of documenting the number of hours excluded, this
Requirement simplifies the process by allowing the Generator Operator to communicate to the
Transmission Operator the circumstances that render the PSS unavailable to the Transmission
Operator (such as component failure, maintenance, and testing). Unlike Requirement R1, the
circumstances listed in Requirement R2 are not considered normal operation of the PSS.
Requirement R3
The intent of Requirement R3 is to clarify the requirements associated with the tuning of the
parameters in the PSS.
The PSS transfer function should compensate the phase characteristics of the generator excitation
power system (GEP) transfer function so the compensated transfer function ((PSS(s) X GEP(s))
has a phase characteristic of +/- 30 degrees in the frequency range.
The GEP(s) transfer function is a theoretical transfer function and its phase characteristic cannot
be directly measured during field tests (only via simulation). Thus, the Requirement recognizes
the practical approach of measuring the frequency response between voltage reference set-point
and terminal voltage (Et/Vref) and using the phase characteristic of such frequency response as
being the phase characteristic of GEP(s). The phase characteristic of Et/Vref is a better
approximation to the phase characteristic of GEP(s) when the frequency response Et/Vref is
obtained with the generator synchronized to the grid at its minimum stable power output.
In an effort to allow for reasonable wash-out time constants the Requirement specifies 0.2 Hz as
the applicable threshold. The 0.2 Hz threshold more closely aligns with the observed oscillation
frequencies.
A properly tuned PSS should provide positive damping to the local mode of oscillation, which
typically has a frequency higher than 1.0 Hz.
The drafting team considers that providing damping to the local mode is for the Generator
Owner and, in particular, for the PSS commissioning engineer to address and does not require a
WECC standard to be accomplished.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 19 of 20
VAR-501-WECC-3 – Power System Stabilizer
This Requirement modifies the requirement associated with the adjustment of the PSS gain. The
standard no longer defines the PSS gain in terms of gain margin but instead requires that the final
PSS gain should be between 1/3 and 1/2 of the maximum practical gain that could be achieved
during PSS commissioning. The maximum practical gain might be associated with the excessive
noise or the raise of higher frequency oscillations in the closed loop response (exciter mode) or
any other form if inadequate closed-loop performance, as determined during PSS
commissioning. It is now part of Measure M3 to show the field test results that led to the
determination of the maximum practical gain.
Requirement R4
Requirement R4 requires a Generator Owner to install PSS on new applicable units or when
excitation systems are retrofitted on existing applicable units. This Requirement applies to new
excitation systems, not existing systems without PSS. The Requirement also allows a reasonable
amount of time for commissioning of new PSS.
Requirement R5
The intent of Requirement R5 is to remove the "tiered" approach to PSS repair / replacement
following a failure. A simple, streamlined approach to allow the Generator Owner sufficient
time to repair or replace a broken PSS has been written. Consideration has been given for the
need to procure parts or new equipment, schedule an equipment/unit outage, and install and test
the repaired or replaced PSS. It is recognized that in some instances, the automatic voltage
regulator may require replacement as well as the PSS to achieve a functioning system.
The 24 month timeframe is sufficient to return a functional, operating PSS to service.
Draft #4 Posted for Comment DATE through DATE
Developed as WECC-0107
Page 20 of 20