Download Document 8888801

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Bacterial cell structure wikipedia , lookup

Trimeric autotransporter adhesin wikipedia , lookup

Disinfectant wikipedia , lookup

Transcript
CASE STUDY
ANGERS, France (49)
HEADWORKS
BIOLOGY
SEPARATION
MEMBRANE
DISINFECTION
BIOSOLIDS
SYSTEMS
Eco-Friendly
Safe
Economical
Energy Efficient
36 blocks of 24 modules AC1125
120,000 m3/day
Raw water origin : surface
ANGERS, France (49)
36 blocks of 24 modules AC1125 (2006)
Angers and surrounding towns are supplied from the waters of
the river Loire and the alluvial table.
These waters are loaded with particles (suspended and colloidal
matter, algae), organic matter, micro-organisms, kysts, bacteria
and metals (Fe, Mn).
To eliminate the bulk of this pollution, Aquasource membranes
are associated with Cristal® process of powdered activated
carbon.
• The water :
Turbidity : 5 to 100 NTU
Iron : < 0.05 to 2 mg/L
Manganese : 0.05 to 0.3 mg/L
T : 5 to 25°C
pH : 7 to 9.7
TOC : 3 to 8 mgC/L
KMnO 4 demand : 2.5 to 9.5 mgO2/L
• Treatment objectives :
OZONE
Distribution
Elimination of turbidity
microbiological retention.
and
• The system :
PAC
Cl2
The
AC1125
Ultrafiltration
module has a membrane area of
125 m² and is integrated in the
Ultrazur 450 unit.
Its average flow rate at 20°C is
12.5 m 3/hr.
Source
Partnership
AQUASOURCE
20 AV. DIDIER DAURAT - BP 64050 - 31029 TOULOUSE CEDEX 4 - FRANCE
33 (0) 5 61 36 30 36 (TEL) - 33 (0) 5 61 36 30 60 (FAX)
WWW.AQUASOURCE-MEMBRANE.COM
CS - VUS0025 - V0 - 2007