Download Workshop Materials

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Mercury-arc valve wikipedia , lookup

Stepper motor wikipedia , lookup

Power inverter wikipedia , lookup

Relay wikipedia , lookup

Electrical ballast wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Ohm's law wikipedia , lookup

Transformer wikipedia , lookup

Power engineering wikipedia , lookup

Current source wikipedia , lookup

Schmitt trigger wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Power electronics wikipedia , lookup

Power MOSFET wikipedia , lookup

Rectifier wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Triode wikipedia , lookup

Ground (electricity) wikipedia , lookup

Three-phase electric power wikipedia , lookup

Transformer types wikipedia , lookup

History of electric power transmission wikipedia , lookup

Islanding wikipedia , lookup

Voltage regulator wikipedia , lookup

Buck converter wikipedia , lookup

Surge protector wikipedia , lookup

Voltage optimisation wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Distribution management system wikipedia , lookup

Fault tolerance wikipedia , lookup

Opto-isolator wikipedia , lookup

Stray voltage wikipedia , lookup

Mains electricity wikipedia , lookup

Protective relay wikipedia , lookup

Alternating current wikipedia , lookup

Earthing system wikipedia , lookup

Electrical substation wikipedia , lookup

Transcript
DISTRIBUTED GENERATION ISSUES
•Technical Issues
•Non-Technical Issues
Technical Issues
•DG Size
•The greater the DG size, the higher the
fault duty capacity
•Location and type of fault
•Contribution of DG to fault on the feeder
reduces expected current for substation
relays. They must be able to see faults at
the end of the circuit.
Technical Issues (continued)
•Configuration of interconnection
transformer
•Ungrounded windings greatly affect relay
performance during grounded faults
•If primary winding is delta and a phaseto-ground fault occurs on the grid, the
current relays of the DG will not be as
sensitive to it. DG voltage relays on the
primary side must see rise in voltage.
Technical Issues (continued)
•Lowest expected feeder load compared
to maximum generator output
•DG is preferred not to back feed
substation bus under minimal circuit
loading
•At all times of year, power must not be
pushed back to substation transformer
(generator could feed transmission fault)
Technical Issues (continued)
•Voltage issues near DG site
•Voltage on feeder must not be outside of
allowable range due to presence of DG
•Undesired voltage regulation on circuit
must not result during low circuit loading
Non-Technical Issues
•Customer’s system configuration and
operation with DG
•Understanding prints and scheme
involved
•Need generator data to model DG
•Increasing volume of DG applications