Download 2 - National Grid

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electronic engineering wikipedia , lookup

Opto-isolator wikipedia , lookup

Stray voltage wikipedia , lookup

Ground (electricity) wikipedia , lookup

Transmission line loudspeaker wikipedia , lookup

Mains electricity wikipedia , lookup

Electrical grid wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Electric power transmission wikipedia , lookup

Electrician wikipedia , lookup

Electrical engineering wikipedia , lookup

Alternating current wikipedia , lookup

Electrification wikipedia , lookup

Power engineering wikipedia , lookup

Electrical wiring in the United Kingdom wikipedia , lookup

Electrical substation wikipedia , lookup

History of electric power transmission wikipedia , lookup

Transcript
Amends to CUSC Section 2 Paragraph 2.12
2.12
PRINCIPLES OF OWNERSHIP
2.12.1
Subject to the Transfer Scheme or any contrary agreement in any Bilateral
Agreement or any other agreement the division of ownership of Plant and
Apparatus shall be at the electrical boundary, such boundary to be
determined in accordance with the following principles:
(a)
in relation to Plant and Apparatus located between the
National Electricity Transmission System and a Power
Station, the electrical boundary is at the busbar clamp on the
busbar side of the busbar isolators on Generators and Power
Station transformer circuits;
(b)
save as specified in Paragraph 2.12.1(c) below, in relation to
Plant and Apparatus located between the National Electricity
Transmission System and a Distribution System, the
electrical boundary is at the busbar clamp on the busbar side of
the Distribution System voltage busbar selector isolator(s) of
the National Electricity Transmission System circuit or if a
conventional busbar does not exist, an equivalent isolator. If no
isolator exists an agreed bolted connection at or adjacent to the
tee point shall be deemed to be an isolator for these purposes;
(c)
in relation to Transmission Plant and Transmission
Apparatus located between the National Electricity
Transmission System and a Distribution System but
designed for a voltage of 132KV or below in England and Wales
and below 132kV in Scotland, the electrical boundary is at the
busbar clamp on the busbar side of the busbar selector isolator
on the Distribution System circuit or, if a conventional busbar
does not exist, an equivalent isolator. If no isolator exists, an
agreed bolted connection at or adjacent to the tee point shall be
deemed to be an isolator for these purposes;
(d)
in relation to Plant and Apparatus located between the
National Electricity Transmission System and the system of a
Non-Embedded Customer, the electrical boundary is at the
clamp on the circuit breaker side of the cable disconnections at
the Non-Embedded Customer’s sub-station; and
(e)
in the case of a metal clad enclosed switchgear bay the electrical
boundary will be the equivalent of those specified in this
Paragraph 2.12.1 save that the electrical boundary will be at the
busbar shutters.
(f)
(g)
in the case of SF6 Gas Insulated Switchgear at other than Post
CAP 189 Sites, the electrical boundary will be the equivalent of
those specified in this Paragraph 2.12.1 save that the electrical
boundary will be at the gas zone separators on the busbar side
of the busbar selection devices.
in the case of Gas Insulated Switchgear at Post CAP 189
Sites, the electrical boundary will be the equivalent of those
specified in this Paragraph 2.12.1 save that the electrical
boundary will be at:
(i)
the connection lug on the Transmission side of the
cable sealing end connected to the Gas Insulated
Switchgear Transmission Side; or
(ii)
the next gas zone separators on the busbar side of the
busbar selection devices, and in such case the busbar
selection devices’ gas zone may contain a section of
the busbar.
2.12.2
If a User wants to use transformers of specialised design for unusual load
characteristics at the electrical boundary, these shall not be owned by the
User and shall form part of the National Electricity Transmission System
but the User shall pay The Company for the proper and reasonable
additional cost thereof as identified by The Company in the Offer covering
such transformers. In this Paragraph 2.12.2 “unusual load characteristics”
means loads which have characteristics which are significantly different from
those of the normal range of domestic, commercial and industrial loads
(including loads which vary considerably in duration or magnitude).
2.12.3
For the avoidance of doubt nothing in this Paragraph 2.12 shall effect any
transfer of ownership in any Plant or Apparatus.
AMENDS TO CUSC SECTION 11
Add New Definition as follows
“CAP 189 Modification Proposal”
shall mean CUSC Modification Proposal
189;
“CAP 189 Implementation Date”
shall mean the Implementation Date for the
CAP 189 Modification Proposal;
“Gas Insulated Switchgear”
SF switchgear where the substation busbars
and the interfacing switchgear between those
busbars and any connecting circuits are of an
integrated metal enclosed, gas insulated
construction.
“Post CAP 189 Sites”
shall mean New Connection Sites where
the connection application is submitted after
the CAP 189 Implementation Date or
Connection Sites where a Modification
Application is submitted after the CAP 189
Implementation Date;