Survey
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Table of Reportable Event Types in NERC EOP-004-2 Attachment 1 and Equivalent Alberta Requirements 1 NERC EOP-004-2 Event Type Threshold for reporting Equivalent Alberta Requirements Administrative Amendments / Alberta Variances Damage or destruction of a Facility Damage or destruction of an element within its Reliability Coordinator Area, Balancing Authority Area or Transmission Operator Area that results in actions to avoid a bulk electric system emergency. Section 304.7, Appendix 1: Events Reportable by the Operator of a Transmission Facility: Administrative amendment: The AESO has changed the wording of this event type to clarify its understanding that a bulk electric system emergency is a sustained outage of any combination of three (3) or more of the following: Damage to or destruction of a transmission facility that results in an unexpected sustained outage of any combination of three (3) or more of the following: (i) transmission lines energized at greater than 25 kV; or (ii) transformers with at least two terminals energized at greater than 25 kV; (i) transmission lines energized at greater than 25 kV; or (ii) transformers with at least two terminals energized at greater than 25 kV. Section 304.7, Appendix 4: Events Reportable by the ISO: Damage to or destruction of a transmission facility that results in an unexpected sustained outage of any combination of three (3) or more of the following: (i) transmission lines energized at greater than 25 kV; or Alberta variance: The AESO has included all transmission facilities within this event type, rather than only those facilities at the bulk electric system level, as this is required to ensure the reliability of the Alberta interconnected electric system. (ii) transformers with at least two (2) terminals energized at greater than 25 kV. 2 Damage or destruction of a Facility Damage or destruction of its Facility that results from actual or suspected intentional human action. Section 304.7, Appendix 3: Events Reportable by a Responsible Entity: Damage to or destruction of a transmission facility, generating unit, or aggregated generating facility that is part of or is directly connected to the bulk electric system that results from actual or suspected intentional human action. Section 304.7, Appendix 4: Events Reportable by the ISO: Damage to or destruction of a transmission facility, generating unit, or aggregated generating facility that is part of or is directly connected to the bulk electric system that results from actual or suspected intentional human action. Page 1 of 7 Public NERC EOP-004-2 Event Type 3 Physical threats to a Facility Threshold for reporting Physical threat to its Facility excluding weather or natural disaster related threats, which has the potential to degrade the normal operation of the Facility; Or suspicious device or activity at an Facility. Equivalent Alberta Requirements Administrative Amendments / Alberta Variances Section 304.7, Appendix 3: Events Reportable by a Responsible Entity: A physical threat to a transmission facility, generating unit, or aggregated generating facility that is part of or directly connected to the bulk electric system, excluding weather or natural disaster related threats, which has the potential to degrade the normal operation of the transmission facility, generating unit, or aggregated generating facility. Section 304.7, Appendix 4: Events Reportable by the ISO: A suspicious device or activity at a transmission facility, generating unit, or aggregated generating facility that is part of or directly connected to the bulk electric system. 4 Physical threats to a bulk electric system control center Physical threat to its control center, excluding weather or natural disaster related threats, which has the potential to degrade the normal operation of the control centre; or suspicious device or activity at a BES control centre. EOP-004-AB-2, Appendix 1: Reportable Events: 1. a physical threat to a control centre of the ISO, excluding weather or natural disaster related threat, which has the potential to degrade the normal operation of the control centre of the ISO; 2. a suspicious device or activity at a control centre of the ISO Section 304.7, Appendix 1: Events Reportable by the Operator of a Transmission Facility: A physical threat to a control centre for the bulk electric system, excluding a weather or natural disaster related threat, which has the potential to degrade the normal operation of the control centre. Section 304.7, Appendix 4: Events Reportable by the ISO: A suspicious device or activity at a control centre for the bulk electric system. 5 Bulk electric system emergency requiring public appeal for load reduction Public appeal for load reduction event. EOP-004-AB-2, Appendix 1: Reportable Events: 3. a situation on the bulk electric system requiring a public appeal for load reduction. Page 2 of 7 Public NERC EOP-004-2 Event Type 6 7 8 Threshold for reporting Equivalent Alberta Requirements Bulk electric system emergency requiring system-wide voltage reduction System wide voltage reduction of 3% or more. EOP-004-AB-2, Appendix 1: Reportable Events: Bulk electric system emergency requiring manual firm load shedding Manual firm load shedding ≥ 100 MW. EOP-004-AB-2, Appendix 1: Reportable Events: Bulk electric system emergency resulting in automatic firm load shedding Automatic firm load shedding ≥ 100 MW (via automatic undervoltage or underfrequency load shedding schemes, or remedial action scheme). Include in the rule Section 304.7, Appendix 1: Events Reportable by the Operator of a Transmission Facility: Administrative Amendments / Alberta Variances 4. a situation on the bulk electric system emergency requiring a system-wide voltage reduction greater than or equal to 3%. 5. a situation on the bulk electric system requiring manual firm load shedding greater than or equal to 100 MW. Automatic firm load shedding (via an automatic undervoltage or underfrequency load shedding scheme, or a remedial action scheme). Section 304.7 Appendix 4: Events Reportable by the ISO: Administrative amendment: All automatic firm load shedding is required to be reported to the AESO so the AESO can make a determination as to whether an amount equal to or greater than 100 MW has been shed from the Alberta interconnected electric system, in accordance with the corresponding NERC requirement. Automatic firm load shedding of greater than or equal to 100 MW (via an automatic undervoltage or underfrequency load shedding scheme, or a remedial action scheme). 9 Voltage deviation on a facility Observed within its area a voltage deviation of ± 10% of nominal voltage sustained for ≥ 15 continuous minutes. 10 IROL violation (all Interconnections) or SOL violation for Major WECC Transfer Paths (WECC only) Operate outside the IROL for time greater than IROL Tv (all Interconnections) or Operate outside the SOL for more than 30 minutes for Major WECC Transfer Paths (WECC only). Alberta Variance: The AESO is of the view that event reports regarding observed voltage deviations on a transmission facility are of little value for reliability purposes. The AESO will report observed voltage deviations of ±10% of nominal voltage sustained for greater than or equal to fifteen (15) continuous minutes for voltages of 500 kV or higher (i.e. the interconnection voltage level) to WECC and NERC through its existing reporting processes, but will not will not require such information be reported through an authoritative provision. EOP-004-AB-2, Appendix 1: Reportable Events: exceeding an interconnection reliability operating limit within the interconnected electric system for an amount of time that is greater than interconnection reliability operating limit Tv, or exceeding a system operating limit for a major transmission path Page 3 of 7 Public NERC EOP-004-2 Event Type Threshold for reporting Equivalent Alberta Requirements Administrative Amendments / Alberta Variances identified in the table “Major WECC Transfer Paths in the Bulk Electric System”, as provided by the WECC, for more than thirty (30) minutes. 11 12 Loss of firm load System separation (islanding) Loss of firm load for ≥ 15 minutes: ≥ 300 MW for entities with previous year’s demand ≥ 3,000 MW; or ≥ 200 MW for all other entities EOP-004-AB-2, Appendix 1: Reportable Events: Each separation resulting in an island ≥ 100 MW. EOP-004-AB-2, Appendix 1: Reportable Events: 6. a loss of firm load greater than or equal to 300 MW for 15 minutes or more; 7. an unintended transmission system separation within the interconnected electric system that results in an island of greater than or equal to 100 MW, excluding an island created by the loss of: Administrative amendment: The AESO has not included the reference to the previous years’ demand being greater than or equal to 3,000 MW, as demand on the Alberta interconnected electric system is greater than 3,000 MW. Alberta variance: The loss of the interconnection is not considered a reportable event. NERC has removed Alberta separation from Event Analysis as the event happens regularly and the implications are well understood. a) a transmission system radial connection; b) non-transmission system facilities (distribution level); or c) the interconnection. 13 14 Generation loss Transmission loss Total generation loss, within one minute, of : ≥ 2,000 MW for entities in the Western Interconnection EOP-004-AB-2, Appendix 1: Reportable Events: Unexpected loss within its area, contrary to design, of three or more bulk electric system elements caused by a common disturbance (excluding successful automatic reclosing). Section 304.7, Appendix 1: Events Reportable by the Operator of a Transmission Facility: 8. total generation loss, within one (1) minute, of greater than or equal to 2000 MW. Unexpected loss contrary to design, of any combination of three (3) or more of the following: (i) transmission lines energized at greater than 25 kV; or (ii) transformers with at least two terminals energized at greater than 25 kV Alberta variance: The AESO has changed the wording of this requirement to limit reporting to the identified facilities Alberta variance: The AESO has included the indicated transmission facilities, rather than only those facilities at the bulk electric system level, as this is required to ensure the reliability of the Alberta interconnected electric system. caused by a common disturbance (excluding successful automatic reclosing). Page 4 of 7 Public NERC EOP-004-2 Event Type Threshold for reporting Equivalent Alberta Requirements Administrative Amendments / Alberta Variances Section 304.7, Appendix 2: Events Reportable by the ISO: An unexpected outage impacting two (2) or more generating units or aggregated generating facilities with an aggregate gross generation exceeding 500 MW at the time of the outage, which is caused by a common disturbance and contrary to the design of the generating unit(s). Section 304.7, Appendix 4: Events Reportable by the ISO: Unexpected loss contrary to design, of any combination of three (3) or more of the following: (i) transmission lines energized at greater than 25 kV; or (ii) transformers with at least two (2) terminals energized at greater than 25 kV caused by a common disturbance (excluding successful automatic reclosing). 15 Unplanned control centre evacuation Unplanned evacuation from a bulk electric system control centre for 30 continuous minutes or more. EOP-004-AB-2, Appendix 1: Reportable Events: 9. an unplanned evacuation of the control centre of the ISO for thirty (30) continuous minutes or more. Section 304.7, Appendix 1: Events Reportable by the Operator of a Transmission Facility: An unplanned evacuation of a control centre of a transmission facility for thirty (30) continuous minutes or more. Section 304.7, Appendix 2: Events Reportable by the Operator of a Generating Unit or an Aggregated Generating Facility: An unplanned evacuation of a control centre of a generating unit or an aggregated generating facility for thirty (30) continuous minutes or more. Section 304.7, Appendix 4: Events Reportable by the ISO: An unplanned evacuation of a control centre of a transmission facility for thirty (30) continuous minutes or more. Page 5 of 7 Public NERC EOP-004-2 Event Type 16 Complete loss of voice communication capability Threshold for reporting Complete loss of voice communication capability affecting a bulk electric system control centre for 30 continuous minutes or more. Equivalent Alberta Requirements Administrative Amendments / Alberta Variances EOP-004-AB-2, Appendix 1: Reportable Events: 10. a complete loss, for thirty (30) continuous minutes or more, of voice communication systems for the control centre of the ISO. Section 304.7, Appendix 1: Events Reportable by the Operator of a Transmission Facility: A complete loss, for thirty (30) continuous minutes or more, of voice communication systems for a control centre of a transmission facility. Section 304.7, Appendix 2: Events Reportable by the Operator of a Generating Unit or an Aggregated Generating Facility: A complete loss, for thirty (30) continuous minutes or more, of voice communication systems for a control centre of a generating unit or an aggregated generating facility. Section 304.7, Appendix 4: Events Reportable by the ISO: A complete loss, for thirty (30) continuous minutes or more, of voice communication systems for a control centre of a transmission facility. 17 Complete loss of monitoring capability Complete loss of monitoring capability affecting a bulk electric system control center for 30 continuous minutes or more such that analysis capability (i.e., State Estimator or Contingency Analysis) is rendered inoperable. EOP-004-AB-2, Appendix 1: Reportable Events: 11. a complete loss of monitoring capability affecting the control centre of the ISO for thirty (30) continuous minutes or more that renders analysis capability, such as state estimator or contingency analysis, inoperable. Section 304.7, Appendix 1: Events Reportable by the Operator of a Transmission Facility: A loss of monitoring or control that significantly affects the ability of the operator of a transmission facility to make operating decisions for thirty (30) continuous minutes or more, including: (i) loss of the ability to remotely monitor or control system elements of the bulk electric system; (ii) loss of communications from supervisory control and data acquisition remote terminal units; Page 6 of 7 Administrative amendment: The AESO provided clarity regarding monitoring capability that affects the bulk electric system. Public NERC EOP-004-2 Event Type Threshold for reporting Equivalent Alberta Requirements Administrative Amendments / Alberta Variances (iii) unavailability of inter control centre protocol links reducing bulk electric system visibility; or (iv) loss of the ability to remotely monitor and control generating units providing regulating reserves. Section 304.7, Appendix 2: Events Reportable by the Operator of a Generating Unit or an Aggregated Generating Facility: A loss of monitoring or control that significantly affects the ability of the operator of a generating unit or the aggregated generating facility to make operating decisions for thirty (30) continuous minutes or more, including: (i) loss of the ability to remotely monitor or control generating units connected to the bulk electric system; (ii) loss of communications from supervisory and data acquisition remote terminal units; (iii) unavailability of inter control centre protocol links reducing visibility of generating units connected to the bulk electric system; or(iv) loss of the ability to remotely monitor and control generating units providing regulating reserves. Section 304.7, Appendix 4: Events Reportable by the ISO: A loss of monitoring or control that significantly affects the ability of the operator of a transmission facility to make operating decisions for thirty (30) continuous minutes or more, including: (i) loss of the ability to remotely monitor or control system elements of the bulk electric system; (ii) loss of communications from supervisory control and data acquisition remote terminal units; (iii) unavailability of inter control centre protocol links reducing bulk electric system visibility; or (iv) loss of the ability to remotely monitor and control generating units providing regulating reserves. Page 7 of 7 Public