International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.10, pp. 1553-1558 ISSN 2078-2365 http://www.ieejournal.com/ Grid and Islanded Operation of a Distribution Generation Inverters in a Microgrid N.Saida Naik, J.Bhavani [email protected], [email protected] Abstract— This paper presents the design of a micro grid. The proposed micro grid consists of a photo voltaic array which represents the main generation unit in the microgrid and proton exchange membrane fuel cell is supplement the variable power generated by the photovoltaic array. a lithium ion battery is included in the microgrid for reduce the burden of the power generated by the microgrid during the peak period. The all those different dg’s units is coordinate to operate the energy management systems during the grid connected operation. The overall system improves the power quality and reliability of the power distribution system that the microgrid is connected to. The control design employs the output regulation (OR) theory. Kalman filters used to extract the harmonic component of the distorted source voltage and load current, and estimate the state observer gain and frequency tracking .The simulation studies verified through different test case. Index Terms— Distributed generation (DG), microgrid, output based controller (ORC), kalman filter. I. INTRODUCTION Now a days using of the power electronics devices poses a power quality problems and the concept of microgrid is useful (helpful) to consumer for reliable and efficient power supply and reduce [1] the per unit cost of the electrical load and reduce the total energy losses and also the interconnection of microgrid to the utility grid with the help of power electronics devices poses power quality problems. The power quality problems like voltage sag/swell, frequency deviation, harmonic supply voltage and load current in the microgrid. To overcome all those power quality problems uses different power conditioning devices. Such as like active power filters [2], uninterruptible power supplies [3], dynamic voltage restorers [4] and unified power quality conditioners [5] are protected their consumers loads and protects the system against the power quality problems, This paper represents the microsource devices are connected to the utility grid through dc to dc converters and voltage source inverters at the point of common coupling (PCC). At point of common coupling different electrical Loads are connected to. The proposed microgrid consists of a photovoltaic array, proton exchange membrane fuel cell and lithium ion storage battery. The photovoltaic array operates main generation unit of the microgrid. During the sunless hours proton exchange membrane fuel cell operates the main generation unit. The lithium ion storage battery is implemented to operate the peak shaving during the grid connected operation and islanded operation. As such modern control theories are used to implement the system. Such controllers’ presents in this paper as output regulation based controller (ORC) [6-7], this controller regulates the dc link voltage of the system. II. SYSTEM DESCRIPTION AND MODELLING The figure1 shows the configuration of microgrid presented in this paper that is operated to operate grid connected and islanded mode of operation. The proposed microgrid consists of 15KVA micro turbine (MT), 5KW_p photovoltaic array. The PV array is connected to grid through dc to dc converter and voltage source inverter (VSI). The microgrid and pv array operates as primary generation units. .20Ah of lithium ion storage battery (SB) and 5KW proton exchange membrane fuel cell (PEMFC). The SB is connected to grid through buck boost converter and VSI. The PEMFC and SB are back up protection of the PV array and will supply the power for any shortage in the generated power to ensure the stable operation of the overall system. When the fault occurs on the upstream of the distribution network the circuit breaker is disconnect the microgrid from utility grid .Then the generation of the main DGs units are able to meet the load demand the system must be stable otherwise PEMFC and SB are supply the power unless it 1553 Saida and Bhavani Grid and Islanded Operation of a Distribution Generation Inverters in a Microgrid International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.10, pp. 1553-1558 ISSN 2078-2365 http://www.ieejournal.com/ cannot meet the load demand shutdown the system completely. Figure3: Operation of the SB and PEMFC stack during islanded operation A. DG inverter modeling (12) Figure1: Overall proposed microgrid system Power balance equation of the system during grid connected mode is Pmt+Ppv+Pb+Pfc=PL (1) Here Pmt and Ppv are power delivered by the MT and PV array. And Pb is the storage battery power subjected to charging and discharging constraints is shown in the figure [2-3]. Pb ≤ Pb,max (2) The figure [4-5] shows the single phase circuit representation of DG inverters during grid connected and islanded operation[10],[14] respectively. The output voltage across the DG inverters is UjVdcj. Where Uj is the control input i.e j=1,2. And Lf,Cf is the filter which protects from the high switching frequency harmonic. Rf is the resistance loss of the DG inverter. The load current iL is the sum of current delivered to the load. iL includes the fundamental and harmonic component therefore iL can be written as iL =iL1+iL2 =iLf+iLh =iLfsin(wt-θLf)+Σ Nh=3,5.iLhsin(hwt+θLh) =iLf,p+iLf,q+iLh (4) Where θLf and θLh are the respective phase angles of the fundamental and harmonic component of the load current iL..The current supplied by the DG inverter is given by IDGj=(iLf,p-ig)+iLf,q+iLh (5) Figure2:Operation of the SB during grid-‐connected operation Pfc is the power delivered by the pemfc and PL is the load power .The storage battery energy constraints is given by SOCmin < SOC ≤ SOCmax Figure4: Equivalent circuit of DG inverter of during grid-‐connected (3) SOC[8-9] of the battery cannot be determined directly, it can be find by different techniques is presented. 1554 Saida and Bhavani Grid and Islanded Operation of a Distribution Generation Inverters in a Microgrid International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.10, pp. 1553-1558 ISSN 2078-2365 http://www.ieejournal.com/ Figure 5: Equivalent circuit of DG inverter of during Islanded connected Where ig is the grid current. With the power electronics devices, the microgrid current img and grid voltage Vg could be distorted. The grid voltage is also fundamental and harmonic components can be written as Vg=Vf+Vh = Vfsinwt+Σ Nh=3,5.Vhsin(hwt-θh) xgj=ij is the state Vj’= Vinj=Vh –Vz – Vt (11) = vDGJ+ i j- iDGj (10) Where i denotes model of the DG inverters j during islanded operation.where j=1,2,3,4 and Aij= i j- =Aijxij+Bij1 ij’+Bij2uj yij=Cijxij+Dij1ij’+Dij2uj (7) Vt and Vz is the voltage drop across the line impedance and voltage drop across the equivalent leakage reactance of the series connected transformer respectively. To derive the state space model of the DG inverter during grid connected and islanded operations, is to simply apply the Kirchhoff’s voltage and current law to the network is shown in the figure6. = is the exogenous input, uj is the control input, with -1≤uj ≤1; and ygj= iDGj is the output. The islanded operation of SB and PEMFC is derived in state space model is obtained (6) Where θh is the harmonic component of the grid voltage. For compensate the harmonic in Vg the series voltage source inverter injects the voltage is given by T uj ; Bij1= Dij1= Bij2= ; Cij= ; Dij2= T = ;xij= is the stete vector; =iLis the exogenous input of the DG inverter j; uj is the T control input , with -1≤uj ≤1 and yij= is the output, which will regulated to track the desired reference. can be derived using a Kalman filter applied to the output T yij= . With III. CONTROL PHILOSOPHY The aim of the controller is to maintain the output of the plant is y=(vmg ig)T it is to track the reference signal r=( vmg* ig*)T , under a periodic disturbance (vmg ig)T . The reference signals vmg* and ig* both are pure sine waves 50Hz frequency without any harmonic distortions. a. Model of the exogenous signal Figure6: Single-‐phase representation of the DG inverter during both grid-‐connected and islanded operations Where ij is the current flowing through Lfj.therefore grid connected DG inverter can be modeled in state space can be written as =Agjxgj+Bgj1 vj’+Bgj2uj ygj=Cgjxgj+Dgj1vj’+Dgj2uj (8) (9) Where g represents the grid connected operation and j represents the operation of the DG inverter (j=1,2)(1=MT,2=PV). Agj= - ; Bgj1= Dgj1= Bgj2= ; Dgj2=0 ; Cgj=1 The exogenous signals vg ,iL ,vmg* ,ig* are periodic signals all those are represented in state space model. For example vg can be expressed in state space model is ξVg=AVg ξVg vg=CVg ξVg (12) (13) iL ,vmg* ,ig* are modeled into state space form =Ãξ (vg iL)T =Ĉw ξ +w (14) (15) r=(vmg* ig*)T= Ĉd ξ (16) Which is called as exogenous system is presented in this paper. 1555 Saida and Bhavani Grid and Islanded Operation of a Distribution Generation Inverters in a Microgrid International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.10, pp. 1553-1558 ISSN 2078-2365 http://www.ieejournal.com/ b. Output based regulation controller (ORC) Subtitling the exogenous equations into the state space model of the plant, the following model is obtained = Ax+ B0ξ + B2u y= Cx + D0 ξ +D2u (17) (18) the control law for the OR is proposed as (19) d ( x − X ξ ) =(A+B2F)(x-X ξ) dt LOAD1 CURRENT(A) Where u is the control signal which generated by the controller used for switching scheme for the plant. x and ξ are the outputs of the exogenous and plant kalman filter(13). XÃ=AX+Bo+B2U (20) =CX+Do+D2U (21) 50 0 -50 0.1 0.15 0.2 0.15 0.2 0.25 TIME(SEC) 0.3 0.35 0.4 0.25 0.3 0.35 0.4 0.3 0.35 0.4 100 DG 1 CURRENT(A) u = U ξ + F(x - X ξ ) 50 0 -50 -100 0.1 TIME(SEC) 50 (22) e=(C+D2F)( x-X ξ) (23) GRID CURRENT(A) : the DG1 (middle) and grid current (bottom) is shown in the figure.8. the below figure.9 shows the grid voltage and current waveform . The total real and reactive power delivered by the load is 20KW and 12.7KVAr during grid connected mode of operation the DG1 inverter and DG2 inverter shares the power is DG1=7.5KW and DG2 is 3KW is shown in the figure.10, reactive power supplied the load is shares the DG1 and DG2 0 -50 0.1 0.15 0.2 0.25 TIME(SEC) Where ‘e’ is the error tracking (y-r). F can be find from the (A+B2F) is Hurwitz and the closed loop system is stable.the model of ORC is shown in figure below. Fig.8:load1current (top),DG1current (middle),gridcurrent(bottom) 80 VOLTAGE(V) CURRENT(A) 60 VOLTAGE(V) CURRENT(A) 40 20 0 -20 -40 -60 -80 0.1 0.15 0.2 0.25 TIME(SEC) 0.3 0.35 0.4 Fig9. voltage and current waveform of grid 15000 IV. SIMULATION RESULTS 10000 REAL POWER(KW) The simulation model of the microgrid is implemented in MATLAB/SIMULINK is shown in the figure. The microgrid consists of two types of loads i.e non liner and linear loads rated of PL1= 15KW, QL1=9.7KVAr and PL2=5KW, QL2=3KVAr are respectively. 5000 0 0 Test case1: Power Quality Improvement With Load Sharing During Grid-Connected Operation x 10 1 1.5 2 2.5 TIME(SEC) 3 3.5 4 4.5 5 x 10 4 2 REACTIVE POWER(KVAR) This case demonstrates the improvement of power quality of the distribution network during grid connected operation and compensate the harmonic injection into the distribution network during grid connected operation. In this mode of operation the storage battery is charge and stores the energy for 0≤t≤0.4sec.the total load current is the sum of the microgrid current and current supplied by the grid current. The waveform of load current iL1 (top), current supplied by 3 0.5 4 1 0 -1 -2 -3 0 0.05 0.1 0.15 0.2 TIME(SEC) 0.25 0.3 0.35 0.4 1556 Saida and Bhavani Grid and Islanded Operation of a Distribution Generation Inverters in a Microgrid International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.10, pp. 1553-1558 ISSN 2078-2365 http://www.ieejournal.com/ 14000 4500 4000 12000 3000 REALPOWER(W) REAL POWER(KW) 3500 10000 8000 6000 2500 2000 1500 4000 1000 2000 0 500 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0 0.1 0.4 0.15 0.2 0.25 TIME(SEC) 0.3 0.35 0.4 3500 3000 Fig.10: power supplied by MT and PV array The remaining power is supplied by the grid is shown in the figure.11. 7.5KW (50% of PL1) and 2KW(20% of PL2). REAL POWER(W) 2500 2000 1500 1000 10000 500 9000 0 0.1 REAL POWER(WATTS) 8000 7000 5000 0.2 0.25 TIME(SEC) 0.3 0.35 0.4 4000 3000 2000 V. CONCLUSION 1000 0 0 0.05 0.1 0.15 0.2 0.25 TIME(SEC) 0.3 0.35 0.4 REACTIVE POWER DELIVERED BY THE GRID 1 0.8 0.6 REACTIVE POWER(KVAR) 0.15 Fig.12 Power delivered by SB and PEMFC 6000 0.4 0.2 0 -0.2 -0.4 -0.6 -0.8 -1 0 0.05 0.1 0.15 0.2 0.25 TIME(SEC) 0.3 0.35 0.4 Fig.11 power supplied by grid Test case 2: load sharing during Islanded operation This test case demonstrates the islanded mode of operation of microgrid. The circuit breaker is initially fully isolated, when ever fault occurs on the upstream network, the circuit breaker disconnect the microgrid from the distribution grid. This test is employed to momentarily provide the sharing of real and reactive power of storage battery SB and PEMFC.during the interval of 0≤t≤0.4sec, at 0.2sec the circuit breaker switch opened, the amount of real power delivered by the SB and PEMFC is shown in the figure.12.at t=0.2 sec the SB is supplies the 3.28KW and PEMFC is supplies the 2.28KW.initially the SB is idle or charge now in islanded mode the SB is supplies the power is shown in the figure.12.the real power is supplied by the MT and PV array [14]is increased This paper presents the design of microgrid is proposed and operation of microgrid during grid connected and islanded mode of operation has been presented with the help of MATLAB/SIMULINK. The proposed system integrates with kalman filter in a control design and kalman filter is estimate the state observer gain and extracts the harmonic compensation in the supply voltage and load current. The control design consists of ORC. The system is tested under different test cases and a validate results are presented in this paper. From these test cases the system improves the power quality and reliability. REFERENCES [1] K. Chen, “The impact of energy efficient equipment on system power quality,” in Proc. IEEE Ind. Appl. Conf., 2000, vol. 5, pp. 3240–3247. [2] L. H. Tey, P. L. So, and Y. C. Chu, “Improvement of power quality using adaptive shunt active filter,” IEEE Trans. Power Del., vol. 20, no. 2,pp. 1558–1568, Apr. 2005. [3] M. Pascal, G. Garcer´a, E. Figueres, and F. G. Esp´ın, “Robust modelfollowing control of parallel UPS single-phase inverters,” IEEE Trans.Ind. Electron., vol. 55, no. 8, pp. 2870–2883, Aug. 2008. [4] D. M. Vilathagamuwa, H. M. Wijekoon, and S. S. Choi, “A novel technique to compensate voltage sags in multiline distribution system–The interline dynamic voltage restorer,” IEEE Trans. Ind. Electron., vol. 54, no. 4, pp. 2249–2261, Aug. 2007. [5] K. H. Kwan, Y. C. Chu, and P. L. So, “Model-based H∞ control of a unified power quality conditioner,” IEEE Trans. Ind. Electron., vol. 56,no. 7, pp. 2493–2502, Jul. 2009. [6] S. Mohana Priya, K. Keerthana,” Regulating Unified Power Quality Conditioner Output Using Kalman Filters”, ICAEM,pp.62-73. 1557 Saida and Bhavani Grid and Islanded Operation of a Distribution Generation Inverters in a Microgrid International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.10, pp. 1553-1558 ISSN 2078-2365 http://www.ieejournal.com/ [7] Z. L. Lin, A. A. Stoorvogel, and A. Saberi, “Output regulation for linear systems subject to input saturation,” Automatica, vol. 32, no. 1, pp. 29–47, Jan. 1996. [8] M. Coleman, C. K. Lee, C. Zhu, and W. G. Hurley, “State-of-charge determination from EMF voltage estimation: Using impedance, terminal voltage, and current for lead-acid and lithium-ion batteries,” IEEE Trans. Ind. Electron., vol. 54, no. 5, pp. 2550–2557, Oct. 2007. [9] J.M.Guerrero, J. Matas, L. Garcíade Vicuña, M. Castilla, and J.Miret, “Decentralized control for parallel operation of distributed generation inverters using resistive output impedance,” IEEE Trans. Ind. Electron., vol. 54, no. 2, pp. 994–1004, Apr. 2007 [10] Paolo Piagi , Member, IEEE, Robert H. Lasseter, Fellow, IEEE,” Autonomous Control of Microgrids” IEEE PES Meeting, Montreal, June 2006. [11] A. Gosh and G. Ledwich, Power Quality Enhancement Using Custom Power Devices. Norwell, MA: Kluwer, 2002, pp. 380–406. [12] K. T. Tan, IEEE, P. L. So, IEEE, Y. C. Chu, IEEE, and M. Z. Q. Chen,” A Flexible AC Distribution System Device for a Microgrid”,Ieee transactions on energy conversion, vol. 28, no. 3, september 2013 [13] J. A. Macias and A. Gomez, “Self-tuning of Kalman filters for harmonic computation,” IEEE Trans. Power Del., vol. 21, no. 1, pp. 501–503, Jan. 2006. [14] Gowtham.D, R.Rajasekar,” Effective Islanding Operation for PV Connected Distributed Generation System with Synchronous Frame Controller”, International Electrical Engineering Journal (IEEJ) Vol. 5 (2014) No.4, pp. 1335-1340 ISSN 2078-2365. 1558 Saida and Bhavani Grid and Islanded Operation of a Distribution Generation Inverters in a Microgrid