Download The Sure-Lites Lifeway II Three Phase

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Power engineering wikipedia , lookup

History of electric power transmission wikipedia , lookup

Current source wikipedia , lookup

Stray voltage wikipedia , lookup

Electrical substation wikipedia , lookup

Resistive opto-isolator wikipedia , lookup

Three-phase electric power wikipedia , lookup

Pulse-width modulation wikipedia , lookup

Alternating current wikipedia , lookup

Electric battery wikipedia , lookup

Mains electricity wikipedia , lookup

Rectifier wikipedia , lookup

Voltage regulator wikipedia , lookup

Distribution management system wikipedia , lookup

Voltage optimisation wikipedia , lookup

Islanding wikipedia , lookup

Variable-frequency drive wikipedia , lookup

Uninterruptible power supply wikipedia , lookup

Schmitt trigger wikipedia , lookup

Buck converter wikipedia , lookup

Rechargeable battery wikipedia , lookup

Solar micro-inverter wikipedia , lookup

Power inverter wikipedia , lookup

Switched-mode power supply wikipedia , lookup

Opto-isolator wikipedia , lookup

Transcript
COOPER LIGHTING - SURE-LITES ®
DESCRIPTION
The Sure-Lites Lifeway II Three Phase represents the highest performance
in uninterruptible technology while the transistorized inverter is providing
power protection. Ready for virtually any emergency with this stand by
power system. This pulse width modulated inverter has 2 millisecond
transfer time. The AC in to AC out operating efficiency is typically 98%,
well above a typical fast transfer inverter. The internal construction of
each cabinet consists of an AC to DC battery charger, DC to AC inverter.
Type
Catalog #
Project
Date
Comments
Prepared by
S P E C I F I C AT I O N F E AT U R E S
E l e c t ri c a l
H o u s i n g C o n s t ru c t i o n
Wa rra n t y
- Choice of 120/208 VAC
or 277/480 VAC, 60 Hz;
other voltages available,
consult Cooper Lighting
Representative
- Available from 4.8 to 50 kVA
- Three Phase, WYE or DELTA
configurations
- 98% efficiency
- PWM/GBT Technology
- 115% overload capacity
- Sine wave output
- 80db transverse mode
noise attenuation
- 120db common mode
noise attenuation
- Input circuit breaker
- Battery circuit breaker
on 24kVA and up
- Sealed lead calcium
batteries standard
- Output distortion <3%THD
Linear Load
- Solid-State
- Self Testing and SelfDiagnostic with Event,
Test and Alarm Logs (includes
5 minute monthly test and 90
minute annual test)
- RS-232 Communication
- Supports LED and HID Lighting
- Formed Steel Cabinet and
Doors are Finished in a
Durable Powder
- Front Access Doors Allow
Easy Entry for Servicing
- Acoustically Quiet
- Limited Manufacturer's One
(1) Year Warranty On
All Electronics*
- Limited Manufacturer's Two
(2) Year Warranty On All
Electronics with Start-Up
Service*
- Limited Manufacturer's Battery
Warranty: One (1) Year Full Value
Warranty/9 Years Pro Rata
M o d e ls
C3FT004 thru 016
C3FT024 thru 050
C3FT024 thru 050**
Code Compliance
- UL 924 Listed
Application
- HID, Fluorescent and
Incandescent Lighting
- Electronic Equipment
- Manufacturing Equipment
LIFEWAY II
THREE PHASE
SERIES
4 . 8 - 5 0 K VA
HID
F L U O R E S C E NT
I N C A N D E S C E NT
A
H e i g ht
W i d th
D e p th
A
47"
72"
72”
B
30"
44"
48”
C
25"
31"
31”
B
Three Phase, UPS
* Additional Warranty Details Upon Request
**Battery Cabinets
ORDERING INFORMATION
Series
C3FT=Three Phase
KVA Rating
004=4.8
Voltage Input
Voltage Output
120
120
006=6.0
008=8.0
277
010=10.0
012=12.5
Notes: *
C
277
O ff i c e B u i l d i n g s
Industrial Complexes
Military Complexes
S p o rt s C o m p l e x e s
Pr i s o n s
Ra i l wa y
Tr a n s i t
A i r p o rt s
L a r g e 9 11 I n s t a l l a t i o n s
Hospitals
Colleges
See Optional
Features on
back.
016=16.7
024=24.0
033=33.0
040=40.0
050=50.0
Specifications and dimensions subject to change without notice.
Consult your representative for additional options and finishes.
ADX052054 pc
2010-08-19 16:59:52
LIFEWAY II THREE PHASE SERIES
S P E C I F I C AT I O N DATA
Input:
Voltage
Input Power Walk-In
Input Frequency
Synchronizing Slew Rate
Protection
Harmonic Distortion
Power Factor
120/208 or 277/480VAC 3-phase 4-wire +1-% - 15%. (Wye configuration)
Limiting inrush current to less than 125%, 10 times for 1 line cycle
60Hz, +/-3%, 50Hz available upon request
1Hz per second nominal
Input Circuit Breaker
<10%
.5 lag/lead
Output:
Voltage
Static Voltage
Dynamic Voltage
Harmonic Distortion
Output Frequency
Load Power Factor
Inverter Overload
Protection
120/208 or 277/480VAC 3-phase 4-wire. (Wye or Delta configuration)
Load current change +/-4%, battery discharge +/-4%
+/-3% for +/-25% load step change, +/-6% for a 50% load step change, recovery within 3 cycles
<3% THD for linear load
60Hz +/- .05Hz during emergency mode
.5 lag to .5 lead
115% for 5 minutes
Output Circuit Breaker (optional)
Battery:
Type
Charger
Protection
Disconnect
Optional Runtimes
Valve-regulated sealed lead calcium. Contact factory for additional battery types.
Microprocessor controlled for various battery types and temperature compensating (recharge per UL924 spec)
Automatic low-battery disconnect; automatic restart upon utility return.
Fuse-and-Fuse/Circuit Breaker above 24KVA
Extended runtimes available. Consult factory for additional information
Environmental:
Altitude
Operating Temperature
Storage Temperature
Relative Humidity
<10,000 feet (above sea level) without derating
20 to 30 degrees Celsius
-20 to 70 degrees Celsius (electronics only)
<95% (non-condensing)
General:
Design
Generator Input
Control Input
Standy-by UPS. PWM inverter type utilizing IGBT technology with 2ms transfer time.
Compatible with generators
Microprocessor controlled 2 x 20-character display with touch pad controls & functions
5 LED indicators & alarm with ring-back feature
Input & Output Voltage, Battery Voltage, Battery & Output Current, Output VA, Temperature, Inverter Wattage
High/Low Battery Charger Fault, Near Low Battery, Low Battery, Load Reduction Fault, Output Overload,
High/Low AC Input Volts, High Ambient Temperature, Inverter Fault, Output Fault, Optional Circuit Breaker Trip
Metering
Alarms
Communications
Manual Maintenance Bypass
Alarm Contacts
RS-232 port (DB9) Programmable monthly and yearly testing (meets NFPA 101 Life Safety Code requirements)
Standard
Optional Summary Form “C” Contacts
Auto Dialer, Battery Charger Upgrade, Dimming Bypass Relay, Extended Factory Warranty, External Maintenance
Bypass Switch (MBYP), Factory Startup and Training, Fax/Modem, Output Circuit Breakers (OCB), Output Trip
Alarms, Remote Meter Panel, Remote Summary Alarm Panel, Seismic Mounting, Summary Alarm Dry Contact,
Summary Form C Contacts, and Variable Time Delay.
Optional Features:
Physical:
Cabinet
Cooling
Cable Entry
Access
Freestanding NEMA Type 1
Forced Air during emergency mode
Top and side on 4.8KVA - 16.7KVA; side only on 24KVA - 50KVA
Front
UPS Electronics Module
Part #
C3FT004 4.8
C3FT006 6.0
C3FT008 8.0
C3FT010 10.0
C3FT012 12.5
C3FT016 16.7
C3FT024 24.0
C3FT033 33.0
C3FT040 40.0
C3FT050 50.0
Batteries
Power Rating (kVA)
Power Rating (kW)
Efficiency (@ full load)
Audible Noise (dBA @ 1m)1
Heat Loss (BTU)
Cabinet Dimensions
4.8
6.0
8.0
10.0
12.5
16.7
24.0
33.0
40.0
50.0
97
97
97
97
97
97
97
97
97
97
45
45
45
45
45
45
45
45
45
45
326
408
544
680
850
1136
1632
2244
2720
3400
Battery Module
Voltage (VDC)
Current (Amperes)
Run Time (mins)
Cabinet Dimensions
Number of
Batteries
Width Height Depth
Weight
in/cm
in/cm
in/cm
lbs / k g
30/77
30/77
30/77
30/77
30/77
30/77
44/112
44/112
44/112
44/112
47/120
47/120
47/120
47/120
47/120
47/120
72/183
72/183
72/183
72/183
25/64
25/64
25/64
25/64
25/64
25/64
31/79
31/79
31/79
31/79
535/243
535/243
535/243
639/290
639/290
639/290
1250/567
1230/567
1450/658
1450/658
B attery Total Weight
lbs / k g
888/403
1110/504
1480/672
1776/806
2220/1007
2960/1343
4440/2014
6080/2758
7400/3357
9120/4137
12
15
20
24
30
40
60
40
100
60
144
180
240
144
180
240
240
240
240
240
39
39
39
81
81
81
117
160
194
90
90
90
90
90
90
90
90
90
243 90
Number of
Battery Cabinets
Width
Height
Depth
in/cm
in/cm
in/cm
Weight
lbs / k g
30/77
30/77
30/77
30/77
30/77
30/77
48/122
48/122
48/122
48/122
47/120
47/120
47/120
47/120
47/120
47/120
72/183
72/183
72/183
72/183
25/64
25/64
25/64
25/64
25/64
25/64
31/79
31/79
31/79
31/79
210/96
210/96
230/106
420/191
420/191
464/211
700/318
1300/590
1300/590
1400/635
Tot. Sys. Wt.
1
1
1
2
2
2
1
2
2
2
1633/741
1855/842
2247/1020
2835/1286
3279/1488
4063/1843
6390/2899
8630/3915
10150/4604
11980/5434
Specifications and dimensions subject to change without notice.
Sure-Lites • Customer First Center • 1121 Highway 74 South • Peachtree City, GA 30269 • TEL 770.486.4800 • FAX 770.486.4801
ADX052054 pc
2010-08-19 16:59:52