Download S275-10-3 (Discontinued Product)

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Mains electricity wikipedia , lookup

Portable appliance testing wikipedia , lookup

Opto-isolator wikipedia , lookup

Transcript
NOTICE: This bulletin is also applicable to Kyle product
serial numbers beginning with the prefix CP57.
Fault Interrupters
Type CI; Three-Phase
Maintenance Instructions
S275-10-3
Service Information
Serial No. 1000 and above
CONTENTS
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Duty Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Frequency of Maintenance . . . . . . . . . . . . . . . . . . . . 2
Periodic Maintenance Inspection . . . . . . . . . . . . . . . 2
Insulation Level Withstand Tests . . . . . . . . . . . . . . . . 3
Shop Maintenance Procedures . . . . . . . . . . . . . . . . . 3
Leak Testing Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Untanking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Tanking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Interrupter Replacement . . . . . . . . . . . . . . . . . . . . . . 6
Aperseal Cable Seals . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Electronic Trip Control . . . . . . . . . . . . . . . . . . . . . . . . 6
Testing CT Protectlon Board . . . . . . . . . . . . . . . . . . . 8
Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Testing in Place . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Bench Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Operating Procedures . . . . . . . . . . . . . . . . . . . . . . . . 8
Mechanical Operation Check . . . . . . . . . . . . . . . . . . . 8
Electrical Operation Check . . . . . . . . . . . . . . . . . . . . 10
Manual Closing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Manual Tripping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
In-Service Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Initial Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Automatic Operation . . . . . . . . . . . . . . . . . . . . . . . . . 10
Schematic Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . 10
Service Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
RADIATION
WARNING:
Before performing electrical tests on Type CI fault interrupters, refer to Service Information S280-90-1, Vacuum
Interrupters Radiation Warning.
INTRODUCTION
Service Information S275-10-3 provides maintenance instructions for the Type Cl three-phase fault interrupter. Included is a
general description of the interrupter and control, and their operation. A service parts list, keyed to exploded-view drawings of
the interrupter, is included at the back of the manual.
DESCRIPTION
The Type Cl fault interrupter (Figure 1) is an automatic, nonreclosing, three-phase interrupting device that will interrupt currents through 12000 amps symmetrical on systems rated
through 38 kv. A compact, lightweight device, the Type Cl features submersible construction, a stored-energy mechanism,
and dry, solid insulated vacuum interrupters.
Line currents are sensed by 1000:1 ratio encapsulated bushing current transformers on each phase on the interrupter. This
provides a continuous measurement of phase and ground current, which is monitored by the Electronic Trip Control. When
Figure 1.
Type CI fault interrupter, 200 amp version.
87863KMA
the selected minimum-trip current value is exceeded, and after a time
delay, the control sends a trip signal to the interrupter operating mechanism. Control operating power is also obtained from the BCT’s; thus
no external power is required for timing or trip functions. The control is
easily programmed for various minimum trip values and time-current
characteristics on both phase and ground.
The integral galvanized-steel mounting frame with predrilled mounting holes facilitates wall, floor, or ceiling mounting. The electronic control, enclosed in a weatherproof (nonsubmersible) cabinet and connected to the interrupter through two shielded plug-in cables, can be
mounted on either side of the interrupter frame or at a remote location
up to 100 feet away.
High-voltage connections are made to either 200 amp universal
bushing wells or 600 amp bushings depending on the continuous current rating of the unit selected. Both are molded as an integral part of
the solid insulation system, and they interface with industry-standard
200 amp loadbreak and nonloadbreak bushing plug inserts or 600
amp shielded cable connectors.
These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide direction for
meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not
covered sufficiently for the user’s purpose, please contact your Cooper Power Systems sales engineer.
December 1987 • New Issue
1
Interrupter contact opening and closing is through release of
stored-spring energy. Both the opening and closing springs are
charged by a 120 volt ac motor which runs automatically
immediately after each opening operation. A push-pull spring
charging feature permits manual spring charging should motor
power be lost.
In addition to automatic tripping on fault current, the Type Cl
interrupter can be tripped with a remote contact, with the manual operated switch on the control panel, or with the mechanically-linked trip-reset lever, on the front of the mechanism tank.
It can be closed with a remote contact, with the manual control
switch on the panel, or with the mechanically-linked close lever
at the front of the tank.
DUTY CYCLE
Rated Max.
Voltage
15.5kV
27.0kV
38.0kV
Percent of
Interrupter
Rating
Minimum
X/R
15-20
4
88
45-55
90-100
8
15
Total
3
7
14
Total
4
8
15
Total
112
132
232
88
112
32
232
88
112
32
232
15-20
45-55
90-100
15-20
45-55
90-100
Number of
Unit
Operations
Fault Interrupters for AC Systems,” it is recommended that the
following maintenance procedures must be performed yearly, or
at the completion of an equivalent duty cycle.
• However, in the absence of specific operating experience, it
is recommended that an external inspection be made on a
yearly basis. (See “Maintenance Procedure” below.)
Periodic Maintenance Inspection
Each periodic maintenance inspection, done at the completion
of an equivalent duty cycle, should include:
1. Bypass and remove interrupter from service.
2. Inspect external components.
A. Check for broken or cracked interrupters. Replace as
necessary.
B. Check for scratched paint, repaint as needed.
C. Note counter reading and enter in the record log.
3. Perform an insulation level withstand test.
4. Remove tank to expose internal components.
5. Oil fills the cavity around the moving contact operator rod. If
oil or oil residue is observed within the tank, carefully
inspect the base of each interrupter to determine the source
of the leak. If an interrupter is leaking, it should be returned
to the factory for repair.
6. Clean internal components.
CAUTION
Never use volatile solutions, detergents, or water-soluble
cleaners.
7. Check contact erosion of the vacuum interrupters. With the
contacts closed the dimension between the support plate and
boss, see Figure 2, should not exceed 5/8".
MAINTENANCE
Frequency of Maintenance
Because interrupters are applied under widely varying operating and climatic conditions, maintenance intervals are best
determined by the user based on actual operating experience.
To assure proper operation, interrupters must be maintained
when they have operated the equivalent of a complete duty
cycle and before the dielectric strength has deteriorated below
prescribed levels. In the absence of specific operating experience, the following procedures are recommended.
• When Type Cl interrupters are operated under usual service
conditions as defined in ANSI (American National Standards
Institute) C37.60,’`Requirements for overhead, Pad
Mounted, Dry Vault, and Submersible Automatic Circuit
Reclosers and
2
Figure 2.
Measuring erosion of interrupter contacts.
S275-10-3
8. Check circuit components attached to the operating
mechanism.
A. Check condition of wiring to terminal strips and
make sure all connections are tight.
B. Check condition and operation of all microswitches
and trip solenoids.
C. Check condition of current transformers and the
associated wiring, if equipped.
9. Replace tank gasket. Apply quick-set adhesive to position and hold gasket in groove at corners of tank.
10. Check the tightness of all cable connectors and other
fastners.
11. Clean gasket seat and retank the interrupter. Replace
the head bolts and tighten to 10-15 ft-lbs. torque. Apply
clamping force gradually and equally, in rotation, to
each bolt to achieve an evenly distributed gasket sealing pressure. Leak test tank, see procedure page 3.
Insulation Level Withstand Tests
High-potential withstand tests provide information on the dielectric condition of the interrupter. Testing is performed at
75% of the rated low-frequency withstand voltage.
Interrupter
Type
BIL (Kv)
15.5 Kv
27 Kv
38 Kv
95
125
150*
Teat Voltage
(Kvac)
26.3
30
45*
Test Voltage
(Kvdc)
40
58.5*
72*
2. Ground tank and frame.
3. Connect and ground three upper bushings.
4. Connect three lower bushings.
5. Apply proper test voltage to lower bushings.
6. The interrupter should withstand the test voltage for 60
seconds.
7. Reverse the connections: ground lower bushings; apply test
voltage to upper bushings for 60 seconds.
8. The interrupter should withstand the test voltage for 60
seconds.
TEST RESULTS: These high potential withstand tests provide
information on the dielectric condition and integrity of the interrupters.
A. If the interrupter passes the closed-contacts test (Tests 1
and 2) but fails the open-contacts test (Test 3),a deterioration of one or more of the interrupters is likely to be the
cause. Check each interrupter individually to determine the
failed phase or phases, and replace the interrupter(s).
Retest to confirm the repair.
B. If the interrupter fails the closed-contacts tests (Test 1 and
2) the cause is likely to be failed insulation. Replace damaged interrupter and retest.
SHOP MAINTENANCE PROCEDURES
Leak Testing Tank
If the interrupter is installed in an environment where it may be
submerged, it should be leak tested after the tank has been
removed and replaced, to ensure that all seals are fluid tight.
*May be limited by cables or terminations.
CAUTION
WARNING
Proper cable terminators must be used to attach test supply to the interrupter bushing terminals. Use of improper
cable terminators can result in flashovers, damage to
equipment, serious personal injury or death.
TEST 1: Proceed as follows:
1. Manually close interrupter.
2. Ground tank and frame.
3. Connect three upper bushings together.
4. Apply proper test voltage to lower bushings.
5. The interrupter should withstand the test voltage for 60
seconds.
TEST 2: Proceed as follows:
1. Manually close interrupter.
2. Ground tank and frame.
3. Ground Phase A and Phase C.
4. Apply proper test voltage to Phase B.
5. The interrupter should withstand the test voltage for 60
seconds.
TEST 3: Proceed as follows:
1. Manually open interrupter.
Do not pressurize tank assembly to more than 5 psi. Pressures
beyond 5 psi can cause permanent damage to the tank assembly and seals.
1. Remove plug, located on mechanism cover assembly.
2. Attach a gas pressure source (nitrogen or clean dry air) to the
pressure fitting and slowly increase the pressure to between 4
and 4-1/2, psi.
3. Apply liberal amounts of liquid soap solution to all seams, seals
and junctures. Leaks will be evidenced by expanding bubbles.
If any leaks are observed, corrective measures must be taken.
NOTE: Pressure will escape through the control cable. As a result,the
pressure source must be maintained throughout the leak testing.
4. Release pressure, disconnect gas pressure source, and reinstall original plug with fresh sealing tape.
Untanking
The tank assembly is removable to allow access to the mechanism, and for vacuum interrupter removal. If access to the mechanism is required, the tank can be removed while the interrupter
assembly remains in the frame assembly. However,
3
if a vacuum interrupter is to be removed, the interrupter
assembly must be removed from the bail and frame assembly.
NOTE: Removal of the bail and frame assembly(steps 1-4) is only
required if a vacuum interrupter is to be removed, refer to Figure 3.
1. Place blocks under tank to support interrupter assembly
when frame is removed.
2. Remove lower plate.
Figure 3.
Bail and frame assembly removal/installation.
4
3. Remove bail and parking stand assembly.
4. Remove support frames and interrupter support plate.
5. Remove hardware securing trip lever assembly (Figure 4) to
tank. Pull lever assembly out of tank.
6. Pull spring charging handle out and insert a wooden block.
Remove three screws that secure clamping ring, see Figure
5.
S275-10-1
Figure 4.
Trip lever assembly removal/installation.
Figure 5.
Clamping ring removal/installation.
87887KMA
87888KMA
7. Remove set screw, see Figure 6.
8. Remove charging handle assembly, see Figure 7.
WARNING
Use a suitable hoist when lifting interrupter assembly. If
interrrupter assembly only (without frame) is to be lifted,
attach hooks to lifting points located between interrupters
and secure sling to center interrupter. If the sling is not
secured, the assembly will flip which could cause serious
injury or damage to the equipment.
CAUTION
Carefully lift the mechanism assembly from tank. There is
very little clearance between the mechanism assembly
and the tank. If the mechanism binds or catches on the
tank as it is removed, damage to the mechanism can
result.
9. Remove hardware that secures cover assembly to tank
and carefully lift assembly out of tank. Carefully guide the
mechanism assembly through tank opening.
Figure 6.
Set screw removal.
Figure 7.
Charging handle removal.
87891KMA
87890KMA
Tanking
To retank interrupter proceed as follows:
1. Clean the underside of the cover assembly to ensure a good
seal. Install a new tank seal, use quick-set adhesive to position
and secure gasket at corners of tank.
WARNING
Use a suitable hoist when lifting interrupter assembly. If interrupter assembly only (without frame) is to be lifted, attach hooks
to lifting points located between interrupters and secure sling to
center interrupter. If the sling is not secured, the assembly will
flip which could cause serious injury or damage to the equipment.
CAUTION
Carefully lower the mechanism assembly into tank. There is
very little clearance between the mechanism assembly and the
tank. If the mechanism binds or catches on the tank as it is
removed, damage to the mechanism can result.
5
2. Carefully lower interrupter assembly into tank. Guide mechanism into tank to prevent it from catching as it enters.
Install hardware and tighten to 10-15 ft-lbs torque.
3. Install two new o-rings on the trip lever shaft and lubricate it
with a little grease (SWS-290). Install shaft assembly
through tank and engage with mechanism main shaft.
Install hex cap screws and lockwashers (Figure 4).
4. Place a few drops of Loctite 242 on threads of charging
handle extension, install extension and tighten securely.
5. Place a few drops of Loctite 242 on set screw and install,
see Figure 8.
NOTE: The current transformers on the encapsulated interrupter bushings are permanently affixed. ACT cannot be removed without damaging
both the CT and the interrupter.
1. Close interrupter contacts.
2. Remove the bail and frame assembly and untank mechanism. Refer to "Untanking” procedure for instructions.
3. Remove lifting angles mounting support.
4. Remove cotter pin.
5. Remove remaining nut(s), clamps and spacers, if used.
6. Carefully remove interrupter.
7. Clean sealant off surface of cover.
8. Place new o-ring into groove in bottom of new interrupter.
9. Apply a small bead of Dow Corning 732 RTV adhesive/
sealant, or equivalent, around perimeter of o-ring groove.
10. Carefully place interrupter moving contact rod through cover
assembly. Slide moving contact rod into operating rod and
align connecting pin holes.
11. Loosely install spacers, if used, clamps and nut(s).
12. Loosely install lifting angle and mounting support.
13. Tighten all clamp hardware, a little at a time in rotation, to 10
15 ft-lbs torque.
14. Tighten support hardware.
15. Install connecting pin and cotter pin.
16. Install tank,frame and bail assemblies, refer to Tanking pr
cedure for instructions.
Aperseal Cable Seals
When removing or installing aperseal cable seals, the body of
the aperseal must not be rotated.
Figure 8.
Set screw installation.
87889KMA
CAUTION
6. Install clamping ring, secure with screws previously
removed, see Figure 5.
NOTE: If the bail and frame assembly were removed, continue with
the following steps. Refer to Figure 3 for bail and frame assembly
item references.
7. Install support frames and interrupter support plate.
8. Install bail and parking stand assembly.
9. Install lower plate.
Interrupter Replacement
The vacuum interrupters used in the Type Cl interrupter are of
an encapsulated design. If the interrupter or interrupter housing are damaged in any way the entire assembly must be
replaced. To replace an interrupter assembly proceed as follows, refer to Figure 9 for item references:
6
Rotating the body of the aperseal may break the seal between
body and cable. This will provide a path for moisture, or other
contaminants, to enter the interrupter operating mechanism
tank. This will damage the mechanism and may render it inoperative.
To remove or install an aperseal secure the aperseal body with
soft-jawed pliers (to prevent it from rotating), while turning the
nut. When tightening—tighten to 45-55 inch-pounds torque.
Electronic Trip Control
The electronic trip control monitors the current level passing
through the Cl interrupter, by measuring the voltages produced in
the bushing mounted current transformers. If excessive current
levels are present, the control initiates a trip signal.
Repairs to the control are limited to the replacement of damaged components, ie. control circuit board, switches or diodes.
S275-10-3
Figure 9.
Interrupter replacement.
7
Figure 10.
Testing CT protection circuit in place.
Figure 11.
Bench testing CT protection circuit.
TESTING CT PROTECTION BOARD
The CT protection board provides automatic protection for the
bushing mounted CTs. It is located within the mechanism tank,
on the left side of the mechanism frame. When the control is
removed from an in-service interrupter, the CT protection
board will automatically protect the CTs. If the CT protection
board malfunctions, CT(s) can be damaged. The following
tests can be used to verify that the protection board is working
properly.
Test circuits for the CT protection board are shown in
Figures 10 and 11. The board can be tested without removal
of either the mechanism tank or it may also be bench tested.
Test Procedure
TESTING IN PLACE
Assemble and connect the equipment as shown in Figure 10,
which shows the test current being applied to phase A.
1. Manually close the interrupted contacts, refer to manual
closing procedure.
2. Slowly increase the voltage on the variable transformer
while observing the voltage between pins A and D.
3. After approximately 115 volts, the voltage should drop off
even though the voltage from the variable transformer is
increased. If the voltage does not drop off, the CT protection board is not operating properly and must be replaced.
4. Disconnect input power and reconnect to test phase B and
then phase C. Ground can be tested between pins E & F
while the test circuit is connected to any phase.
BENCH TESTING
Assemble and connect the equipment as shown in Figure 11,
which shows the test voltage being applied to phase A.
1. Slowly increase the voltage on the variable transformer
while observing the voltage between the 1000:1 CT leads.
2. After approximately 115 volts, the voltage should drop off
8
even though the voltage from the variable transformer is
increased. If the voltage does not drop off, the CT protection
board is damaged and must be replaced.
3. Disconnect input power and reconnect to test phase B,
phase C and ground.
OPERATING PROCEDURES
The interrupter should not be operated or placed into service
until there is a full understanding of its operating procedures.
Mechanism and control levers and indicators referred to in this
section are identified in Figures 12 and 13.
Mechanical Operation Check
A simple nonelectric test of interrupter operation will assure that
the operator mechanism and the interrupter linkage are functioning properly. The following procedure may be used.
1. Remove control fuse from 120 volt ac fuse block in cabinet
interior to isolate mechanism from electrical system.
2. Check that the interrupter is open. The Contact-Position
Indicator visible from the front of the mechanism tank should
read OPEN.
NOTE: If interrupter is closed move the Trip-Reset handle at the
front of the mechanism tank to TRIP. This will release a latch in the
mechanism and open the interrupter contacts. The Contact-Position
Indicator will then read OPEN.
3. Using the manual closing procedure described in Manual
Closing section, close the interrupter. The Contact-Position
Indicator should read CLOSED.
4. Move the Trip-Reset handle to TRIP. The interrupter contacts
should open and the Contact-Position Indicators should read
OPEN.
Successful completion of the above four steps confirm proper operation of the interrupter operating mechanism.
S275-10-3
Figure 12.
Front of Type CI interrupter mechanism tank.
87857KMA
Figure 13.
Panel of electronic trip control used with Type CI interrupter.
87858KMA
9
Electrical Operation Check
The following procedure may be used to check the electrical
operation of the interrupter.
1. Make sure that the Trip-Reset handle on the mechanism
tank is set on RESET.
2. Apply 120 volt ac power. Upon application of power, the
spring-charging motor will run to charge the closing
springs. The spring-charging motor will stop running when
the springs are fully charged and the spring indicator will
indicate that the springs are charged.
3. To close the interrupter, move Manual Control switch on
control panel to CLOSE. The interrupter should close
immediately. The red indicator lamp on the control panel
should light and the Contact-Position Indicator at the front
of the mechanism tank should read CLOSED.
4. To open the interrupter, move the Manual Control switch to
TRIP. The interrupter should open. The green indicator
lamp on the control panel should light and the ContactPosition Indicator in the mechanism tank should read
OPEN.
Manual Closing
Manual deenergized closing into an energized line,without the
120 volt ac supply, can be accomplished with the Push-Pull
handle located on the left front of the mechanism tank (Figure
12).
1. If the electronic control is connected, make sure the manual
control switch on the control panel has been moved to the
TRIP position and released.
2. Move Trip-Reset handle, right front of mechanism tank to
either the TRIP or RESET position.
3. Pull Push-Pull handle approximately 30 times, or until the
operating spring indicator reads SPRING CHARGED.
4. Move Trip-Reset handle to CLOSE. Interrupter contacts will
close and handle will spring back to the RESET position.
Manual Tripping
A closed interrupter can be manually tripped at the operator
mechanism by moving the Trip-Reset handle at the front of the
tank to TRIP.
This will release a trip latch in the operating mechanism,
allowing the charged opening springs to drive the contacts to
their open position.
The interrupter cannot be closed while the Trip-Reset handle is in the TRIP position.
10
IN-SERVICE OPERATION
Initial Operation
To place the interrupter in operation, proceed as follows:
1. Make sure that the control cables extending from the interrupter are connected to the control and that 120 volt ac power
is supplied to the control.
2. Make sure that the Trip-Reset handle at the front of the interrupter mechanism tank is in the RESET position.
3. Move the Manual Control switch on the electronic control
panel to CLOSE. The interrupter will close. The red indicator
lamp on the control panel will light and the indicator flag in the
mechanism will read CLOSED.
Automatic operation
Once the unit is closed and in service, the electronic control will
automatically trip the interrupter in accordance with the programmed operating characteristics when a phase or ground fault
occurs. While closed, the red indicator lamp on the control panel
will provide a continuous indication of closed contacts. The indicator flag, visible through a viewing port at the front of the mechanism tank, will display CLOSED.
To open the interrupter while it is in service, move the manual
control switch to TRIP. The interrupter will immediately open.
Whether tripped automatically or manually, the green indicator
lamp on the panel and the OPEN position of the mechanism flag
will indicate open contacts.
If the remote control operating feature is being used, operations initiated by the remote trip and close dry contacts will be
identical to those initiated with the Manual Control switch.
Indicator lamp and Contact-Position Indicator displays will also
be the same.
SCHEMATIC DIAGRAMS
Figure 14 shows the schematic wiring diagrams for the Type Cl
interrupter. This drawing reflects a standard unit. Refer to the
wiring diagrams furnished with your interrupter for information on
factory installed accessories.
S275-10-3
Figure 14.
Schematic diagram of Type CI interrupter.
11
SERVICE PARTS LIST
The service parts and hardware listed and illustrated include
only those parts and assemblies usually furnished for repair or
involved in the maintenance procedures described in this manual. Further breakdown of listed assemblies is not recommended.
Dimensions of all common hardware parts have been carefully checked so that they may be locally acquired. The suffix
letter of the 14 character catalog number for common hardware parts codes the plating of the part:
A—No plating; raw material
H—Silver
M—Black oxide
Q—Cadmium + zinc + chromate
Y—Zinc + chromate
Z—Electro zinc + bronze irridite
A hardware kit, Catalog No. KA849R1, contains an assortment of roll pins, cotter pins, retaining rings, stop nuts, etc.—
common hardware parts used in Cooper Power System's interrupters that may not be readily available locally.
To assure correct receipt of any parts order, always include
interrupter type and serial number. Because of Cooper Power
System's continuous improvement policy, there may be
instances where the parts furnished may not look exactly the
same as the parts ordered. However, they will be completely
interchangeable without any rework of the interrupter.
All parts carry the same warranty as any whole item of
switchgear, i.e. against defects in material or workmanship
within a period of one year from date of shipment.
Type CI Interrupter Control Parts
Catalog No.
KA1110ME
KA852ME1
KP4011A12
KP4012A44
KPP140T
KP2069A8
KP2101A14
KP2101A214
KP1118ME
KP1119ME
KCF101EA
KP2056A5
KP2056A28
KP2101A24
KP2101A224
KP1100ME
KP1110ME
KP2075A13
KCF51E*
KCF51E*
KCF110K*
KCF110K*
KCF53EA
KCF53EB
KCF54EA
KCF52EA
KCF52EB
Description
Surge card assembly
Heater assembly
Silicon diode (D2)
Zener diode (D1)
Selector switch assembly (SW1)
Pointer knob
Terminal strip (T2)
Terminal marker (T2)
Winq head stud
Stud retainer
Light socket Sylvania Cat. #30152-0
Red lens, Sylvania Cat. #30170-0
Green lens, Sylvania Cat. #30174-0
Lamp, Sylvania Cat. #120 PSB
Toggle switch SW2)
Control circuit board
Receptacle, 14 pin (R 1)
Receptacle, 10 pin (R2)
Terminal strip (T3)
Terminal marker (T3)
Fuse block (F)
Fuse block end piece
Fuse
Time delay plug (phase)
Time delay plug (ground)
Minimum trip resistor (phase)
Minimum trip resistor (ground)
Phase instantaneous trip accessory
Phase and ground instantaneous trip accessory
Target accessory
Phase and ground inrush restraint accessory
Ground inrush restraint accessory
* Enter value or curve required
12
Tank Assembly (Figure 15)
Item
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
DescrIptlon
Retaining ring
Retaining ring
O-ring gasket
Tank assembly
Capscrew, hex hd,5/16-18 x 3/4,
st stl
Lockwasher, 5/16, med, st sti
Hex nut 5/16-18, st stl
Name plate
Lock nuts
O-ring
Port cover assembly
O-ring
Port cover assembly
Hinge and pointer assembly
O-ring
Lockwasher, 1/4, med, st stl
Capscrew, hex hd,1/4-20 x 1/2,
st stl
Decal
Charging handle
Hex jam nut 3/8-16 st stl
Shroud
Clamp
Screw round hd, #6-32 x 5/16
st sti
Lockwasher, #6, st stl
Bellows
Clamping ring
Shaft extension
Set screw
Guide plate
o-ring
Retaining ring
Spacer
Charging handle assembly
Washer, 3/8, st stl
Capscrew, hex hd, 3/8-16x 1
st stl
Catalog
Number
KP2013A41
KP2013A28
KP2103A18
KNC1095A
Ouan.
Req’d.
1
1
1
1
K730115131075A
K900815031000A
K880215118031A
KPP1026T1
KP2020A22
KP2000A56
KNC142S00A
KP2000A34
KP144VW54
KNC175S
KP2000A26
K900815025000A
22
22
22
1
4
1
1
1
2
1
2
2
K730115125050A
KP1041V4H
KNC1186S
K880715116038A
KNC1209S
KP2251A1
2
1
1
1
1
1
K721515106031 A
K900815006000A
KP2241 A 1
KNC 1208S
KNC1207S
KP2023A8
KNC1206S
KP2006A56
KP2013A41
KP3009A208
KNC232S
K900215037000A
3
3
1
1
1
1
1
1
1
1
1
1
K732415137100A
1
S275-10-3
Figure 15.
Tank assembly.
13
Figure 16.
Bail and frame assembly.
14
S275-10-3
Bail and Frame Assembly (Figure 16)
Item
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Description
Support plate
Lifting lug
Capscrew, hex hd, 3/8-16 x 1
st stl
Grommet strip 13-1/4"
Hex nut, 3/8-16 st stl
Lockwasher, 3/8, med, st stl
Support, right hand
Bracket
Bail and parking stand
"Z"
"U"
Bail adapter
Lower plate
Hex nut, 5/8-11, st stl
Lockwasher, 5/8, med, st stl
Capscrew, hex hd, 5/8-11 x
2-1/2, st stl
Bracket
Capscrew, hex hd, 3/8-16 x
1-1/4, st stl
Support, left hand
Flat washer, 5/8, st stl
Catalog
Number
Quan.
Req’d.
KNC1211S
KNC1126S
1
2
K730115137100A
K999904250454A
K880215116037A
K900815037000A
KNC178S
KNC1124S
14
3
15
15
1
1
KPP159TA
KNC177SB
KNC1129S
KNC1125S
K880215111062A
K900815062000A
1
1
6
1
1
2
K730115162250A
KPP1035T1
2
1
K730115137125A
KNC179S
K900215062000A
1
1
1
15
Figure 17.
Interrupter top cover assembly.
16
S275-10-3
Interrupter and Top Cover Assembly (Figure 17)
Item
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Description
Hex nut,3/8-16, st stl
Lifting angle
Mounting support
Capscrew, hex hd, 1/4-20 x
5/8, st stl
Cable support
Lockwasher, 1/4, med, st stl
Hex nut, 1/4-20, st stl
Interrupter assembly
Current transformer
Cover assembly
Spacer
Clamp
Cotter pin, 1/16 x 1 /2, brass
Connecting pin
Capscrew, hex hd, 3/8-16 x
5/8, st stl
Lockwasher, 3/8, med, st stl
Wire tie
O-ring
Aperseal
Pipe plug
Catalog
Number
Quan.
Req’d.
K880215116037A
KNC1122S
KNC1123S
11
2
1
K730115125062A
KNC 1119S1
K900815025000A
K880215120025A
Consult factory
Consult factory
Consult factory
KP3011A27
KP1252VS
K970525062050A
KNC1087S1
3
1
3
3
3
3
1
2
9
6
3
K730115137062A
K9W815037000A
K994904170004A
KP2000A59
KP2151A1
KP2007A10
2
2
4
3
3
1
17
Figure 18.
Mechanism assembly.
18
S275-10-3
Mechanism Assembly (Figure 18)
Item
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Description
Machine screw, rd hd, #6-32
x 1, stl
Lockwasher, #6, med, stl
Microswitch
Bracket assembly
Machine screw, rd hd, #6-32
x 1-3/4,stl
Bracket assembly
Insulation
Capscrew, hex hd, 1/4-20 x
1/2, stl
Lockwasher, 1/4, med, stl
Solenoid and bracket assembly
Solenoid only
Retaining ring, Type C, WA514
Latch assembly
Spacer
Microswitch
Spring
Counter assembly
Screw, self tapping, rd hd
#6-32 x 3/8 Type F, stl
Bracket
Machine screw, rd hd, #6-32
x 3/8, stl
Bi-stable actuator
Lockwasher, #8, med, stl
Machine screw rd hd
#8-24 x , 1/4, stl
Catalog
Number
Quan.
Req’d.
K721501106100Z
K900801006000Z
KP2181A13
KNC213S
4
12
3
1
K721501106175Z
KNC135S
KNC1070S
6
2
3
K730101125050o
K900801025000Z
KPP163T
KPP1060T
K970915250000A
KNC 133SA
KP3007A 173
KA2181 -8
KRK310F1
KA28C06
2
2
1
1
1
1
2
1
1
1
K751501106037Z
KNC 1170S
2
1
K721501106037Z
KRB296VA
K900801008000Z
2
1
2
K721501108025Z
2
Item
No.
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
Description
Terminal strip
Marker strip
Machine screw, rd hd, #6-32
x 5/8, stl
Mechanism Assembly
Hex nut, #6, stl
Machine screw, rd hd, # 10-24
X 1-1/2,stl
Lockwasher, # 10, med
Motor and gear assembly
CT protection board assembly
Hex nut, #6-32, st stl
Spacer
Lockwasher, #6, med, st stl
Machine screw, rd hd, #6-32
X 1/2,st stl
Machine screw, rd hd, #6-32
x 3/8, stl
Lockwasher, #6, med, stl
Bracket
Lockwasher, #6, int tooth, st stl
Terminal strip
Marker strip
Catalog
Number
Quan.
Req’d.
KP2101A30
KP2101A230
1
1
K721501106062Z
KPP172T
K881001132006Z
2
1
4
K721501110150Z
K900801010000Z
KNC209S
KA 197GV2
K881015132006A
KP3004A 18
K900815006000A
4
4
1
1
3
3
3
K721515106050A
5
K721501106037Z
K900801006000Z
KNC1134S
K901015006000A
KP2101A14
KPP1028T1
2
2
1
2
1
1
19
©2005
Cooper Power Systems or its affiliates.
1045 Hickory Street
Pewaukee, WI 53072 USA
www.cooperpower.com
KDL
6/05