BUSSMANN
SERIES
SurgePOD™ HEAVY DUTY
Robust surge protection for critical
commercial and industrial applications
Product description:
Features and benefits:
Eaton’s Bussmann series
SurgePOD™HEAVY DUTY
is ideal for a wide range
of applications. SurgePOD
HEAVY DUTY Surge
Protective Devices (SPDs) are
Type 1 UL® 1449 3rd Edition
Listed for easy specification
and installation on the
loadside or lineside of the
service entrance overcurrent
protective device.
•
Type 1 UL 1449 3rd
Edition Listed SPDs
are easily selected and
installed on the loadside
or lineside of the service
entrance overcurrent
protective device.
•
Voltage and system type
specific models precisely
match and protect
electrical systems and
equipment up to 600Vac.
•
Compact UV resistant
NEMA® 4X enclosure
for indoor or outdoor
installation.
•
easyID™ LED status
indicator provides surge
protection status at a
glance.
®
Bussmann
series SurgePOD
HEAVY DUTY
SPDs feature a
nominal system
voltage range of
120 to 600Vac for
a wide range of
applications.
Designed for critical
commercial and industrial
applications, the SurgePOD
HEAVY DUTY utilizes
patented SurgePOD module
MOV thermal disconnect
technology that eliminates
the need for any additional
overcurrent protection.
Patented Bussmann series
SurgePOD module technology
matches SurgePOD HEAVY
DUTY SPDs to specific voltage
and system types.
Specifications
•
Type 1 SPD for critical commercial and
industrial applications
•
120 to 600Vac
•
200kA SCCR
•
Single-phase, split-phase, Wye,
Delta and Highleg Delta systems
•
Five-year warranty
easyID™
SurgePOD HEAVY DUTY
Color
Black
Markets
Commercial and industrial
Systems types
Single, Split, Delta, Highleg and Wye
Nominal systems voltage
120, 208, 240, 277, 347, 480, 600Vac
Maximum continuous operating AC voltage
Matched to nominal voltage
MCOV[Vc]
150 to 550Vac
Installation
2, 3, 4, 5 connections
N-G protection
Available
Protection from
Serve transient
SCCR
Nominal discharge current (8x20ups) In
200kA
Max. discharge current (8x20ups) Imax
50kA
Response time ta
<25ns
Frequency
50/60Hz
Operating status / fault length
One bi-colored LED— green (good)/red (replace)
Conductor gauge / length
Mounting
10AWG stranded copper/18 inches
Chase nipple/ bracket (bracket customer supplied)
Enclosure rating
NEMA 4X - UL 94-5VA
Degree of protection (installed state)
IP20 (finger-safe)
SPD install location
Indoor/outdoors
Circuit location
Standards / agency information
Operating temperature
Lineside/loadside
20kA
UL 1449 3rd Edition Type 1 Listed SPD— cULus, CSA, RoHS compliant
-40oC to + 85oC
16,000 feet
5 years*
Operating altitude
Product warranty
See data sheet No. 2163 for additional information.
*See Eaton SPD limited warranty statement (3A 1502) for details at Eaton.com/bussmannseries
easyID™ LED status indicator
Standard on the SurgePOD HEAVY DUTY, the easyID™ LED status indicator will always illuminate when the unit is properly installed and
the system or equipment being protected is energized. The following LED colors indicate:
Green LED = good
Circuit is energized
and protected.
Red LED = replace
Circuit is energized
and unprotected.
Unit needs
replacing.
LED is out/unlit* =
• Circuit is mostly
likely deenergized.
• Unit’s leads are
disconnected.
• Unit is damaged.
* Authorized personnel should follow all prescribed lockout/tagout and safety procedures in troubleshooting the cause for the above conditions. Opening the SPD enclosure will void UL and warranty.
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Bussmann Division
114 Old State Road
Ellisville, MO 63021
United States
Eaton.com/bussmannseries
© 2015 Eaton
All Rights Reserved
Printed in USA
Publication No. 3213
September 2015
Eaton, Bussmann, easyID and SurgePOD
HEAVY DUTY are valuable trademarks
of Eaton in the US and other countries.
You are not permitted to use the Eaton
trademarks without prior written consent
of Eaton.
CSA is a registered trademark of the
Canadian Standards Group.
NEMA is a registered trademark of
the National Electrical Manufacturers
Association.
UL is a registered trademark of the
Underwriters Laboratories, Inc.
For Eaton’s Bussmann series
product information,
call 1-855-287-7626 or visit:
Eaton.com/bussmannseries
Follow us on social media to get the
latest product and support information.