* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Download KB009
Ground (electricity) wikipedia , lookup
Electrical ballast wikipedia , lookup
Resistive opto-isolator wikipedia , lookup
Variable-frequency drive wikipedia , lookup
Time-to-digital converter wikipedia , lookup
Current source wikipedia , lookup
Opto-isolator wikipedia , lookup
Mercury-arc valve wikipedia , lookup
Fault tolerance wikipedia , lookup
Electrical substation wikipedia , lookup
Distribution management system wikipedia , lookup
Spark-gap transmitter wikipedia , lookup
Alternating current wikipedia , lookup
Oscilloscope history wikipedia , lookup
Switched-mode power supply wikipedia , lookup
Buck converter wikipedia , lookup
Earthing system wikipedia , lookup
Surge protector wikipedia , lookup
Capacitor discharge ignition wikipedia , lookup
Electrolytic capacitor wikipedia , lookup
Tantalum capacitor wikipedia , lookup
Niobium capacitor wikipedia , lookup
Aluminum electrolytic capacitor wikipedia , lookup
Capacitor plague wikipedia , lookup
Capacitors September 2000 — Greenwood SC General Capacitor Fusing Criteria KILOVAR BRIEFS 9 Introduction The purpose of this issue of Kilovar Briefs is to present the fundamental principles for effective fusing of the Cooper Power Systems all-film capacitor. This criteria can be applied to other types of shunt capacitors; however, the degree of protection may not be as effective. Figure 1. Group Fusing. The basic objectives in selecting capacitor fuses are twofold: 1. The fuse must be capable of withstanding steady state and transient currents in order to avoid spurious fuse operations. 2. The fuse must effectively remove a failed or failing capacitor unit from service without causing further damage or disruption to the system. These objectives are accomplished through two different fusing methods — group fusing and individual fusing. Group Protection is defined as one fuse protecting more than one capacitor. This usually involves one fuse on each phase protecting all the capacitors on that phase (see Figure 1). Group Protection is generally used for protecting pole-mounted distribution capacitor racks. In this type of application, the fuse links are installed in cutouts and mounted on a cross arm above the capacitor rack. Individual Protection is defined as each capacitor in a bank being protected by its own individual fuse (see Figure 2). This type of protection is commonly used in outdoor substation capacitor banks. Fuses are the busmounted type. Withstanding Steady State and Transient Currents The continuous current and the transient current duties determine the minimum acceptable fuse size so as to avoid spurious fuse blowing under normal conditions. The requirements for group fused and individually fused applications are the same for the continuous current duty but differ for the transient duty. September 2000 • Supersedes 3/87 Printed in USA Figure 2. Individual Fusing. The fuse link is chosen to have a minimum rating of at least 135% of rated capacitor current. This overrating is due to these three allowances — 10% for overvoltage conditions, 15% for capacitance tolerance and 10% for harmonics. Fuses can be damaged due to high magnitude, high frequency currents. If possible, it is desirable to minimize spurious fuse operations by selecting an appropriately large fuse link so as to withstand these transient currents. The two sources of system-generated transient current are capacitor bank switching and lightning surges. Switching is typically only a concern when capacitor banks are switched on the same bus; i.e., back-to-back switching. This is seldom the case for pole-mounted group fused capacitors. However, these fuses are subject to high frequency transients due to lightning surges. Low current rated links are especially susceptible to these surges. 1 General Capacitor Fusing Criteria Unlike pole-mounted capacitor racks, individually fused substation capacitor banks are generally not exposed to significantly high magnitude, high frequency lightning surges. Transient currents due to switching are also of no significant concern unless capacitor banks are switched back-to-back. Even in that case if the switchgear is applied within the ANSI standards for inrush current frequency and magnitude, the fuse duty is generally acceptable. The fuse link and capacitor must be able to adequately handle the available fault current. When capacitors are connected grounded wye in a single series group application, a capacity failure (terminal-to-terminal short) will cause system fault current to flow. The capacitor must be able to withstand the fault current until the fuse interrupts the circuit. Additionally, the fuse must be able to successfully interrupt the available fault current. Figure 3. Energy Discharge into Failed Unit and Energy Outrush from Remaining Good Capacitors. When a capacitor unit goes to a complete short, other series groups within the capacitor banks are subject to a 60 Hz overvoltage until the fuse clears. The fuse should clear fast enough so as not to damage the good units due to this overvoltage. In an individually fused application, there is one additional transient consideration. When a capacitor unit fails, i.e., goes to a short circuit, the remaining good capacitors will discharge into the failed capacitor. The fuses on the good capacitors should be able to withstand this high frequency outrush current to avoid multiple fuse operations whenever a single unit fails. See Figure 3. Effectively Removing a Failed or Failing Capacitor Unit In removing a failed or failing capacitor unit from service, it is desired that this occur without causing any further damage or disruption to the system. It is important that the clearing fuse and the capacitor unit be able to withstand the available 60 Hz current and the high frequency energy discharge from the parallel capacitors. In addition, the fuse must clear fast enough to limit the voltage on the remaining healthy capacitors to acceptable levels and to coordinate with an unbalance detection scheme. 2 The maximum clearing TCC curve for the fuse link must coordinate with the tank rupture curve for the capacitor (see Figure 4). This coordination is necessary to ensure that the fuse will clear the circuit prior to tank rupture occurring. The fuse maximum clear TCC must fall to the left of the tank rupture TCC curve at and below the level of available fault current. In the case of high fault currents, the tank rupture curve should be compensated for asymmetry. The fuses and the capacitor must be capable of handling the available parallel stored energy. When a capacitor failure occurs, all of the stored energy of the parallel connected capacitors can discharge through the failed capacitor and its fuse. The total calculated parallel stored energy should not exceed the energy capability or joule rating of the capacitor unit and fuse. Exceeding their ratings would result in probable fuse failure and rupture of the capacitor unit. When a fuse operates in a capacitor bank, an increase in the fundamental frequency voltage occurs on the remaining units in that series group. An unbalance detection scheme is employed to monitor such conditions and to take action as required. The settings of this protection scheme should be coordinated with fuse TCCs so that the fuses will be allowed to clear a failed capacitor unit before the unbalance detection scheme trips the capacitor bank. If the bank is tripped before the fuse operates there will be no visible indication of the cause of the bank tripping. KILOVAR BRIEFS Improper Coordination Proper Coordination 1000 1000 Tank Rupture Tank Rupture 100 (Time) Seconds 100 (Time) Seconds 9 10 1 10 1 Fuse Fuse 0.1 0.1 0.0 0.0 5 50 500 5000 (Current) Amps 5 50000 50 500 5000 (Current) Amps 50000 Figure 4. Tank Rupture Coordination. Summary Group and individual fusing will be dealt with in greater detail in future Kilovar issues, at which time recommendations will be included. A summary of the key criteria in choosing the appropriate fusing for a shunt capacitor application is given in the following table. In comparing the need for slow clearing and fast clearing fuses, it sometimes is not reasonably possible to meet all of these criteria. In those cases, trade offs must be made and some risks taken as to those conditions when the fuses and capacitors may not operate in a desirable manner. TABLE 1 Summary of Shunt Capacitor Fusing Criteria Key Criteria Group Individual Protection Protection Withstanding Steady State and Transient Currents: Continuous Current External Transient Currents — Lightning — Switching Outrush Current Effectively Removing Failed or Failing Capacitor Unit: Fault Current Tank Rupture Curve Coordination Voltage on Good Capacitors Energy Discharge Into Failed Unit Coordinate with Unbalance Detection Scheme X X X X X X X X X X X X Fuse Characteristic Desired Slow Fast Clearing Clearing X X X X X * * * X X * X *This criteria helps to determine whether expulsion or current limiting fuses are required. 3 P.O. Box 1640 Waukesha, WI 53187 http://www.cooperpower.com ©2000 Cooper Industries, Inc. Printed on Recycled Paper