Download Self healing power system by accurate fault location

Survey
yes no Was this document useful for you?
   Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Document related concepts

Electric power system wikipedia , lookup

Telecommunications engineering wikipedia , lookup

Islanding wikipedia , lookup

Power over Ethernet wikipedia , lookup

Alternating current wikipedia , lookup

Mains electricity wikipedia , lookup

Electrification wikipedia , lookup

Distributed control system wikipedia , lookup

Ground (electricity) wikipedia , lookup

Power engineering wikipedia , lookup

Immunity-aware programming wikipedia , lookup

Electrical grid wikipedia , lookup

Amtrak's 25 Hz traction power system wikipedia , lookup

Electrical substation wikipedia , lookup

Earthing system wikipedia , lookup

Fault tolerance wikipedia , lookup

Transcript
Jussi Ahola, ABB Oy
A self healing power system for the accurate fault
location and zone concept
T&D Smart Grids Europe 2012
© ABB Group
May 25, 2017 | Slide 1 1MRS757736
A self-healing power system
Introduction
© ABB Group
May 25, 2017 | Slide 2

Why self-healing?

Needs to improvements

Reliability of the supply

Quality of the power

Operational efficiency

Accurate fault location, including also earth faults, is crucial for fast fault isolation

Fast fault isolation enables fast power restoration  SAIDI improvement

Local automation confines the impact of a network fault to the limited area 
SAIFI improvement

Automation helps in cases when there are many faults happening all over the
network – it saves control centre’s time to handle other faults

Utilize information from different sources and use them to support each other
A self-healing power system
The Zone concept


Divide the network into
zones based on
protection zones and
control zones
Control room
Distributed
generation
Limit the effects of
disturbances to smaller
areas brings less
consumers affected and
revenue lost

Get improved voltage
quality (light substations
and shorter lines)

Get improved use of the
distribution network
investments heals higher
degree of utilization, less
stress on the network and
improved asset
management

Adapts to changes in
the operational
environment which can
be implemented step by
step and grows with the
requirement
Communication
Substation
© ABB Group
May 25, 2017 | Slide 3
Pole mounted
recloser
Pole mounted
switchdisconnector
Disconnector
Station
Recloser station
Switching Station
A self-healing power system
Intelligent Zone concept components
Distribution
Management System
© ABB Group
May 25, 2017 | Slide 4
A self-healing power system
Intelligent Zone concept components
REF615
Bay level
Protection
algorithms for
short circuits and
Distribution
earth fault

Management System
© ABB Group
May 25, 2017 | Slide 5

Disturbance data
recording,
COMTRADE

Enable prediction
of nonpermanent earth
faults

Fully automated
fault localization
A self-healing power system
Intelligent Zone concept components
RER601, REC603
Wireless Gateway
Protection Zone
level

Reclosers enable
automatic isolation
Distribution
 Indicators transmit
Management
System
REC523
Recloser OVR3
SECTOS
Fault Indicator
© ABB Group
May 25, 2017 | Slide 6
the fault status
A self-healing power system
Intelligent Zone concept components
M2M Gateway
Communication
Secure end-to-end
communication
utilising M2M VPN
Distribution
technology and
Management
System
built-in firewall

© ABB Group
May 25, 2017 | Slide 7

Precise, real-time
data acquisition
from your
distribution
network with
standardized
protocols

IEC 60870-5-104
(GPRS)
A self-healing power system
Multiple levels of security
A secure connection pipe
SCADA/DMS
M2M GATEWAY
APN TUNNELING
COMMS EQUIPMENT

M2M gateway physically separates
external and internal IP networks

Integrated firewall blocks unauthorized
access

Secure VPN: strong authentication and
encryption

Private IP address on equipment level: not
visible to public, only through M2M
gateway

GPRS radio signals are crypted with
multiple algorithms

Equipment has in-built firewalls: accepts
traffic only from M2M gateway
A self-healing power system
Intelligent Zone concept components
COM600
Substation level

Grid Automation
Controller
 Generates the
Distribution
fault report System
to DMS
Management
© ABB Group
May 25, 2017 | Slide 9
A self-healing power system
Intelligent Zone concept components
MicroSCADA Pro
DMS 600
Distribution
Management level

DMS analyzes the
fault report
Distribution
 Locates theSystem
fault
Management
on geographical
map
© ABB Group
May 25, 2017 | Slide 10

Network
reconfiguration

Generates
restoration
sequence

Possibility to run
the sequence
automatically
through SCADA

Fault reporting
even for nonpermanent faults
(enable predictive
maintenance)
A self-healing power system
Advanced fault reporting
© ABB Group
May 25, 2017 | Slide 11

Advanced fault report functions on
substation level, contributed by
advanced IEDs is of essential
significance

Advanced station level fault reporting
reduces the amount of non-processed
data sent to operators – control center
can focus on overall coordination
tasks.

The grid automation controller
generates a fault report including the
distance estimation information and
sends it to the DMS
Pilot Case
Fortum Oy, Masala
Where to start

SAIDI > 200min

Fault location and isolation based on ”trial and error”-method - increase also
SAIFI, specially at the end of feeders

Only 15% of fault could be located, overcurrent faults
Target
© ABB Group
May 25, 2017 | Slide 12

Improve the reliability - reduce SAIDI by 50%

Verify the functionality of the concept
Pilot Case
Fortum Oy, Masala
Zone Concept

2 feeders

4 protection zones

20 remote zones
The pilot scope
Disconnectors with fault
indication 4 pcs

© ABB Group
May 25, 2017 | Slide 13

ABB RER601

KOHU + REC523

Overhead reclosers 2 pcs

Total feeder length 100km
Pilot Case
The results and the conclusion
© ABB Group
May 25, 2017 | Slide 14

Improved network reliability

Enhanced power quality

The data quality is improved and quantity decreased,
which is transfered to the control centre

Advanced station level reporting reduces the amount of
non-processed data sent to operators – control center
can focus on overall coordination tasks.

The accuracy of the fault location of the DMS 600 fault
management function is enhanced by adding
information from all system levels of the distribution
network
© ABB Group
May 25, 2017 | Slide 15